C Note! LGI16... Burner Controls. Building Technologies

Similar documents
LGA... Gas Burner Controls. Building Technologies Division

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

Flame Safeguards LFE10. Building Technologies HVAC Products

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

Oil Burner Controls LOA3... Building Technologies HVAC Products

RAR... Photocell Detectors. Building Technologies Division

Oil Burner Controls LOA3... Building Technologies Division

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44...

UV Flame Supervision System

LAE10 LFE10. Use. Series 02

Infrared Flame Detectors

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies HVAC Products

Flame detector. The QRA4.U is for use with the following types of burner control:

Blue-flame Detectors

Flame detector. The QRA4.U is for use with the following types of burner control:

Burner controls. Building Technologies HVAC Products

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division

Flame detector. Building Technologies Division Infrastructure & Cities Sector

Infrared Flame Detectors

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

Basic unit with integrated air-fuel ratio control for forced draft burners

QRA10... QRA53... QRA55...

QRA10... QRA53... QRA55...

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

QRA10... QRA53... QRA55...

Basic unit with integrated fuel-air ratio control for forced draft burners LMV Building Technologies Division

QRA10... QRA53... QRA55...

Use. Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation.

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

Burner Controls. Building Technologies HVAC Products

Use. The burner controls are certified to EN 230 and EN 298.

Burner Management System

EUROBOX SERIES TYPES CM... SM... MM...

Basic Unit with integrated Fuel / Air Ratio Control for Forced Draft Burners LMV Building Technologies

EUROFLAT SERIES TYPES C... S... M...

EUROBOX SERIES TYPES CM...N SM...N MM...N

Gas Burner Controls. Building Technologies HVAC Products

Burner Management System

Burner Management System

LFL Series Burner Flame Safeguard Control

Program module for burner control LME71.000

MICROFLAT SERIES TYPES C.../U T X

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR..

Forced draught gas burner

Heating Element. Building Technologies HVAC Products

Building Technologies Division

Building Technologies

Gas burner automatic safety control MMI / 811.1

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners

MMG Gas burner safety control

LC3000 Level Controller Installation and Maintenance Instructions

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

UV Scanner. Model Specification. Introduction. 854 Instruction Manual

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

Forced draught gas burner

Product Range Overview

UV - flame detector dual fuel burners for intermittent burner operations

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

MBCE-110/230UV Flame Sensor Module

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Eclipse 90 UV Scanner Model A Version 1

QFM21... Duct sensors. Symaro. for relative humidity and temperature

for relative humidity and temperature with calibration certificates

MMI (40-34) Gas burner safty control

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY

Eclipse Self-Check UV Scanner

Thermal Reset Limit Thermostats Electromechanical TW according to DIN EN 14597

Building Technologies Division

Rules for Classification and Construction Additional Rules and Guidelines

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

UV - flame detector KLC 10 for oil -, gas- and dual fuel burners for intermittent burner operations

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

Advanced Ultraviolet Burner Controller

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

Operating Manual MS220KA and MSR220KA

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING

CATALOGUE PRODUITS - CSA - CSI - CSM - CSS - CSS2 - P16 - P19 - P20 - P25 - UV DETECTOR

DKO 974/976 DKO 974 N/976 N. Oil Burner Safety Control

Operating Manual MS220DA

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

AS/NZS :2003 Luminaires - Part 1: General requirements and tests

LME75... Burner controls. Building Technologies

Frost Protection Thermostat

for relative humidity and temperature

Old documentation - Only for your information! Product is not available anymore!

AUR300C, AUR350C. Advanced Ultraviolet Burner Controller

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

RE-PR3-E-27 3-Phase Panel Mount 27kW

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

British Gas 330+ High Efficiency Condensing Boiler. Instructions for Use. To b e l e f t w i t h t h e u s e r. British Gas Service Tel:

Transcription:

7 786 Burner Controls LGI16... Burner controls For use on industrial furnaces For burners in continuous operation Without fan control and air pressure supervision Flame supervision - with QR53... / QR55, flame detector - with ionizations probe With self-supervising flame signal amplifier Quick startup 1-stage operation with interrupted pilot burner or 2-stage operation Common or separate ionization probe and ignition electrode (single- or double-electrode operation) utomatic restart (repetition) or lockout after loss of flame during operation Indication of program sequence Remote reset facility Programming mechanism in plastic housing, plugs into the base The LGI16... and this Data Sheet are intended for use by OEMs which integrate the burner controls in their products. C Note! Do not use for new designs.

Use Supervision and control of oil or gas burners for use on industrial furnaces that operate continuously for longer periods of time (>24 hours) without controlled shutdown. Flame supervision - QR53... / QR55... flame detector - Ionization probe - QR53... / QR55... flame detector and ionization probe together, e.g. with burner with ignition burner, refer also to Data Sheet N7712 Warning notes To avoid injury to persons, damage to property or the environment, the following warning notes must be observed! Do not open, interfere with or modify the unit! ll activities (mounting, installation and service work, etc.) must be performed by qualified staff Before making any wiring changes in the connection area, completely isolate the plant from mains supply (all-polar disconnection). Ensure that the plant cannot be inadvertently switched on again and that it is indeed dead. If not disconnected, there is a risk of electric shock hazard Ensure protection against electric shock hazard by providing adequate protection for the burner control s terminals Each time work has been carried out (mounting, installation and service work, etc.), heck to ensure that wiring is in an orderly state and make the safety checks as described in «Commissioning notes». Press the lockout reset button / operation button only manually (applying a force of no more than 10 N), without using any tools or pointed objects Do not press the lockout reset button on the unit or the remote reset button (input 21) for more than 10 seconds, since this would damage the lockout relay inside the unit Fall or shock can adversely affect the safety functions. Such units must not be put into operation, even if they do not exhibit any damage Mounting notes Ensure that the relevant national safety regulations are complied with 2/14

Installation notes lways run the high-voltage ignition cables separately while observing the greatest possible distances to the unit and to other cables Do not mix up live and neutral conductors Install switches, fuses and earthing, in compliance with local regulations Make certain that the maximum permissible current rating of the connection terminals will not be exceeded Caution! Observe the polarity Burner controls LGI16... are not able to detect wrong polarity of live and neutral conductors When used in connection with UV detector QR53... / QR55..., terminal 22 must be earthed For repetitive operation, remove wire link «J» between terminals 8 and 11 in base GM15 Warning! Danger - high voltage In single-electrode operation, measurement of the ionization current is not possible. During the ignition times, the ionization current path carries high voltage. Electrical connection of flame detectors It is important to achieve practically disturbance-free signal transmission: Never run the detector cable together with other cables Line capacitance reduces the magnitude of the flame signal Use a separate cable Observe the permissible length of the detector cables (refer to «Technical data») It is not permitted to connect 2 flame detectors QR53... / QR55... in parallel When using the QR53... / QR55..., earthing of terminal 22 is mandatory The ionization probe does not offer protection against electric shock hazard Locate the ignition electrode and ionization probe such that the ignition spark cannot arc over to the ionization probe (risk of electrical overloads) and that it cannot adversely affect the supervision of ionization Supervision with ionization probe and QR53 / QR55... flame detector is possible but, for safety reasons, both must not be active at the same time, with the exception of the second safety time «t9». t the end of the second safety time, one of the detected flames must extinguish, e.g. by shutting down the pilot gas valve connected to terminal 17 For cable lengths, refer to «Technical data», section «Detector and flame supervision» Insulation resistance Must be a minimum of 50 MW between ionization probe and ground Soiled detector holders reduce the insulation resistance, thus supporting creepage currents Earth the burner in compliance with the relevant regulations; earthing the boiler alone does not suffice 3/14

Commissioning notes When commissioning the plant or when doing maintenance work, make the following safety checks: Safety check nticipated response a) Burner startup with flame detector darkened Lockout at the end of safety time (TS) b) Burner startup with flame detector exposed to extraneous light c) Burner operation with simulated loss of flame; for that purpose, darken the flame detector during operation Lockout after no more than 40 seconds Restart followed by lockout at the end of safety time (TS) if wire link (J) (terminals 8...11) is removed, otherwise immediate lockout Standards and certificates pplied directives: Low-voltage directive 2014/35/EU Electromagnetic compatibility EMC (immunity) *) 2014/30/EU *) The compliance with EMC emission requirements must be checked after the burner control is installed in equipment C Note! These devices may only be used as replacements within the EU and EFT countries. Compliance with the regulations of the earlier, now withdrawn directives is verified by the adherence to the following standards: utomatic burner control systems for oil burners DIN EN 230:2005 utomatic burner control systems for burners and DIN EN 298:2004 appliances burning gaseous or liquid fuels utomatic electrical controls for household and similar use Part 2-5: Particular requirements for automatic electrical burner control systems DIN EN 60730-2-5:2005 EC Conformity mark (Eurasian Conformity mark) ISO 9001:2015 ISO 14001:2015 OHSS 18001:2007 China RoHS Hazardous substances table: http://www.siemens.com/download?6v10883536 4/14

Life cycle Burner control have a designed lifetime* of 250,000 burner startup cycles which, under normal operating conditions in heating mode, correspond to approx. 10 years of usage (starting from the production date given on the type field). This lifetime is based on the endurance tests in the standard EN 230 / EN 298. summary of the conditions has been published by the European Control Manufacturers ssociation (fecor) (www.afecor.org). The designed lifetime is based on use of the burner controls according to the manufacturer s Data Sheet. fter reaching the designed lifetime in terms of the number of burner startup cycles, or the respective time of usage, the burner control is to be replaced by authorized personnel. * The designed lifetime is not the warranty time specified in the Terms of Delivery Disposal notes The unit contains electrical and electronic components and must not be disposed of together with household waste. Local and currently valid legislation must be observed. 5/14

Mechanical design LGI16... Housing Ordering Plug-in design Exchangeable unit fuse (including spare fuse) Impact-proof plastic housing Synchronous drive motor Lockout relay with electric, remote reset facility Self-supervising electronic flame signal amplifier with flame relay Program indication in the viewing window by means of disk on the spindle of the sequence switch (refer to «Control and function diagram» Lockout warning lamp in the viewing window Reset after lockout by slightly pressing on the viewing window Printed circuit board with electronic components Programming mechanism with fixed settings Made of impact-proof and heat-resistance black plastic Lockout reset button with viewing window; located behind it: Lockout warning lamp Lockout indicator - coupled to the spindle of the sequence switch - visible in the transparent lockout reset button - uses easy-to-remember symbols to indicate the type of fault and the point in time lockout occurred Burner control, without plug-in base Plug-in base is not included in standard delivery, must be ordered as a separate item! rticle no. Type Mains voltage BPZ:LGI16.05327 LGI16.05327 230 V~ BPZLGI16.05317 LGI16.05317 100...110 V~ ccessories for medium-capacity burner controls Refer to Data Sheet N7230 rticle no. Type Thread type BPZ:GM15 GM15 Plug-in base with Pg11 thread for cable entry glands BPZ:GM15.1 GM15.1 Plug-in base with M16 thread for cable entry glands Flame detector UV detector QR53 / QR55 Refer to Data Sheet N7712 Ionizations probe Supplied by the burner manufacturer 6/14

Technical data General unit data Mains voltage C 230 V 15%/10% C 100 V 15%...C 110 V 10% Mains frequency 50...60 Hz ±6% Unit fuse, built-in T6,3H250, DIN EN 60 127 (5 x 20 mm) External primary fuse Max. 16, slow Weight pprox. 1,000 g Power consumption pprox. C 3.5 V Perm. mounting position Optional Degree of protection IP40, when fitted, with the exception of the connection area (terminal base) Safety class II Perm. input current at terminal 1 Max. 5 (peaks of 20 / 20 ms) Perm. current load on control terminals Max. 4 (peaks of 20 / 20 ms) Required switching capacity of the switching devices connected to terminals 4 and 5 Depending on the loads connected to terminals 16...19 Min. 1, C 250 V Detector and flame supervision QR5x.C... QR5x.E... QR5x.D... QR5x.G... Ionization probe Operating voltage C 280 V ¹) ±10 % C 280 V ¹) ±10 % C 245 V ¹) ±10 % Detector current required Min. DC 35 µ Min. DC 120 µ Min. DC 12 µ Detector current possible Max. DC 50 µ Max. DC 270 µ Max. DC 100 µ Short-circuit current --- --- Ca. C 300 µ Length of detector cable, laid separately ²) ²) Max. 60 m Mounting position Optional Optional --- 1) lternating current, measured with no detector current at C 110V / C 230 V mains voltage. Internal resistance of measuring instrument: 10 MW. Shutter drive of UV detector QR53... / QR55 operates on mains voltage 2) Detector cable laid at a distance of at least 50 mm from other mains carrying cables: s a multicore cable: max. 50 m With 5 single wires: max. 70 m Detector cable laid directly adjacent to other mains carrying cables: With shielded 3-core control cable connected to pins 3, 4 and 5 of the QR53... / QR55 ; for the mains connection (pins 1 and 2), a normal mains cable can be used max. 15 m With 3 screened 3-core coaxial cables (93 W; 45 pf/m) connected to pins 3, 4 and 5 of the QR53... / QR55 ; for the mains connection (pins 1 and 2), a normal mains cable can be used max. 60 m If possible, connect cable shielding at both ends of the cable 7/14

Technical data (cont'd) Environmental conditions Storage DIN EN 60721-3-1 Climatic conditions class 1K3 Mechanical conditions class 1M2 Temperature range -20...60 C Humidity <95 % r.h. Transport DIN EN 60 721-3-2 Climatic conditions class 2K2 Mechanical conditions class 2M2 Temperature range -40...60 C Humidity <95 % r.h. Operation DIN EN 60 721-3-3 Climatic conditions class 3K5 Mechanical conditions class 3M2 Temperature range -20...60 C Humidity <95 % r.h. Installation altitude Max. 2,000 m above sea level Caution! Condensation, formation of ice and ingress of water are not permitted! Detector current measurement LGI16... / QR53... / QR55... 22 With QR5x.C... DC 35...50 µ 7785v04/1008 22 With QR5x.D... DC 120...270 µ 7785v01/1008 470 µf/25 V 470 µf/25 V With QR5x.E... With QR5x.G... 22 DC 35...50 µ 7785v04/1008 22 DC 120...270 µ 7785v01/1008 470 µf/25 V 470 µf/25 V 8/14

Detector current measurement (cont'd) LGI16... / ionization probe The measuring device must be connected between terminal 24 and the detector electrode (pole to terminal 24). With ionization 24 DC 12...100 µ ION 7785v03/1008 Burner control LGI16... base Terminals in the control panel 2 Mains cable 3 x 1.5 mm Burner Terminals in the burner compartment QR5... Single-wire coaxial cable (e.g. RG62) Shielding Cable GM19 Max. 60 m Legend QR5... ION mmeter UV flame detector Ionization probe 9/14

Function Program sequence When power is supplied to the burner control and the control loop (terminals 4 and 5) is closed, the LGI16 will start the program sequence as shown in «Control and function program», the most important program steps being the following: Waiting time No external function Internal flame simulation test Release of ignition Release of pilot gas valve Establishment of pilot flame during the first safety time (TS) Release of gas valve stage 1 Release of gas valve stage 1 Establishment of pilot flame during the first safety time (TS) Release of gas valve stage 2 Establishment of main flame during the second safety time (t9) Burner operation The burner control maintains its operating position and continuously checks the presence of flame Shutdown when the control loop between terminals 4 and 5 opens. The signal to the gas valves will immediately be cut off. During the time home run (t20), the programming mechanism returns to its start position Control program in the event of fault Flame signal on startup causes the burner control to initiate lockout No flame signal at the end of the first or second safety time causes the burner control to initiate lockout Loss of flame during operation Wire link «J», between terminals 8...11 in the base Wire link fitted: burner control will initiate lockout Without wire link: burner control will automatically execute a restart (repetition) Base GM15 is supplied with wire link «J» fitted. In the event of lockout, the signals to the gas valves will be cut off in less than one second and the burner control locked. Resetting is always to be made manually by pressing lockout reset button «EK1» or «EK2». In the case of repetition, the signals to the gas valves will also be cut off in less than one second. Then, the programming mechanism will automatically return to its start position (home run) to make a new start. Common ignition probe and ionization electrode (Single-electrode operation, ionization probe, connected to terminal 7) In the period between the ignition time (tz) and the end of the first safety time (TS), the secondary side of the ignition transformer is switched from earthing to the flame signal amplifier. 10/14

Control and function diagram P S F tz TS tw 7786f01/0305 t4 t3 B S C D 1 2 21 3 4 5 16 17 18 19 11 8 7 22 23 15 J GP SB 1 1 R 22 H 5 3 4 1 W 4) 2 EK2 Z I BV1 BV2 M Si 3) L FEZ Z L ZBV BV1 N QR5... 2) t9 t5 t20 1 2 22 24 ION Legend Caution! Do not press lockout reset button (EK...) for more than 10 seconds! Valid for expanding flame burner Valid for interrupted pilot burner F P S Flame signal amplifier Programming mechanism Indication of program sequence in viewing window TS Ignition safety time 5 s ¹ ) tw Waiting time 4.5 s ¹ ) tz Ignition time 2.5 s ¹ ) t3 Preignition time 2.5 s ¹ ) t4 Interval between start of release of the valve connected to terminal 17 or 18 and release of the valve connected 7,4 s ¹ ) to terminal 19 t5 Interval up to the self-shutdown of the programming mechanism in the operating position t9 Transition time from pilot burner to main burner second safety time (2. safety time (t9) plus safety time in operation) 3.5 s ¹ ) t20 Home run time until the startup position after a controlled shutdown is reached 15 s ¹ ) 1) Data valid at 50 Hz, at 60 Hz, the times are 20 % shorter 2) When used in connection with QR53... / QR55, terminal 22 must be earthed 3) Connection with separate ignition electrode and ionization probe (double-electrode operation) 4) Connection with common ignition electrode and ionization probe (single-electrode operation) Control signals of burner control at nominal voltage Required input signal Terminal connected to earth 11/14

Connection diagram and internal diagram SB 7786a01/0305 LGI16... 1 br1 a b ar1 4 S III a b GPmin. I a b 22 24 1 M 3) ION 15 23 UV QR5... 2) 2 W 5 4 3 R 22 15 23 24 5 8 J 11 EK1 L1 fr1 a b a b IV a XI a b XII XIII a b R a VI NTC a b br2 M IX II X E BR a b a b fr2 fr3 FR VIII a b VII b a b a ar3 ar4 M SM a V b V 3 21 2 16 17 18 19 7 L N Si H L EK2 1 3) Z ZBV BV1 BV2 BV1 4) Z I FEZ 22 Caution! Do not press lockout reset button (EK...) for more than 10 seconds! Legend Valid for expanding flame burner Valid for interrupted pilot burner 2) When used in connection with QR53... / QR55, terminal 22 must be earthed 3) Connection with separate ignition electrode and ionization probe (double-electrode operation) 4) Connection with common ignition electrode and ionization probe (single-electrode operation) 12/14

Legend B B C C C D D L R S BR BV... EK... ION FEZ FR GP H J L1 M NTC QR5... R SB Si SM UV V W Z ZBV ZI Start of program; control loop between terminals 4 and 5 closed Startup program Burner operation Controlled shutdown; control loop between terminals 4 and 5 open Home run of programming mechanism Ready for restart Remote indication of lockout (alarm) Main relay (load relay) with contacts (ar) Unit fuse Lockout relay with contacts (br) Fuel valve Lockout reset button Ionization probe Ignition electrode and ionization probe Flame relay with contacts (fr) Gas pressure switch, minimum gas pressure switch Main switch Wire link between terminals 8 and 11 in the base of the LGI16..., in the event of loss of flame during operation: Wire link fitted: Lockout Without wire link: utomatic restart (repetition) Lockout warning lamp on the burner control Fan motor Resistor with negative temperature coefficient Flame detector Temperature or pressure controller Manual reset safety limiter External fuse Synchronous motor of programming mechanism UV radiation Flame signal amplifier Limit thermostat or pressure switch Ignition transformer for double-electrode operation Pilot gas valve Ignition transformer for single-electrode operation Control signals delivered by the burner control Permissible input signals Terminal grounded 13/14

Dimensions Dimensions in mm LGI16... 108,5 1,5 27,5 27,5 7,5 103 37 123 Plug-in base GM15 / GM15.1 7786m04/0305 103 Ó 2018 Siemens G, Berliner Ring 23, D-76437 Rastatt Subject to change! 14/14