TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

Similar documents
TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Low Global Warming Refrigerants For Commercial Refrigeration Systems

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

GWP Alternative Refrigerants

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Low GWP Refrigerants for Air Conditioning Applications

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a

January 16 th, 2014 New York City

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Report No CRT-414

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

Evaluation of HCFC Alternative Refrigerants

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research

Steady and Cyclic Performance Testing of Packaged R-410A Units

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

System Modeling of Gas Engine Driven Heat Pump

Transcritical CO2 Bottle Cooler Development

R32 Compressor for Air conditioning and Refrigeration applications in China

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

Study of R161 Refrigerant for Residential Airconditioning

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Purdue e-pubs. Purdue University

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Performance Measurement of R32 Vapor Injection Heat Pump System

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

Application Engineering

Summary of Research Activities. Eckhard A. Groll Professor of Mechanical Engineering

The Refrigeration Cycle

*Corresponding author;

AIR CONDITIONER PERFORMANCE RATING

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration

R-404A Alternative with Low Compressor Discharge Temperature

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

System Considerations for Refrigerant Blends with Temperature Glide

AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP)

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Superheat charging curves for technicians

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

The Refrigeration Cycle

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Product Data. Fig. 1 - Unit 50VR -A

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

Implications of GHP Fan Control Strategies on Humidity Control in Commercial Applications

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Effect of magnetic field on the performance of new refrigerant mixtures

SERVICE ASSISTANT OVERVIEW FDSI Online Training

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

recooler HP EQKR HEAT PUMP

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

On Balance: Heat Rejection Control a Packaged Solution

R4H4. Product Specifications

Air Cooled Packaged Systems AIRAH Back to Basics

R4H4. Product Specifications

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

INVERTER SCROLL. LG Electronics Distributed by. Copyright 2017 LG Electronics. All rights reserved.

2016 Annual Conference

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Pressure Enthalpy Charts

Refrigeration/Troubleshooting Manual

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

Improved R134A Mobile Air Conditioning Systems

How to Cut Chiller Energy Costs by 30%

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Transcription:

Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #63 System Soft-optimization Tests of Refrigerant R-32, DR-5A, and DR-55 in a R-410A 4-ton Unitary Rooftop Heat Pump-Heating Mode Performance Ken Schultz Marcos Perez-Blanco Steve Kujak Ingersoll Rand 3600 Pammel Creek Road La Crosse, WI 54601 January 18, 2016 This report has been made available to the public as part of the author company s participation in the AHRI s Low-GWP AREP.

Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 2 of 12 INTRODUCTION This report documents tests performed on a 4 RT (14 kw) rooftop heat pump, to evaluate the performance of lower GWP refrigerants as alternatives to R410A in unitary air-conditioning and heat pump equipment. Compositions and GWPs are listed below in Table 1. The unit was run at the rating conditions specified in AHRI Standard 210/240 for heating mode performance. Tests were run using R410A (baseline), DR-55, R32, and DR-5A with performance of the three alternatives compared to the baseline R410A. The tests were performed in controlled ambient chambers at Ingersoll Rand/Trane s La Crosse Development Laboratory in La Crosse, Wisconsin, from late-may through early-august 2015. Table 1. Refrigerants tested, with compositions and global warming potentials (GWPs). Name composition (%wt) GWP (AR4) GWP (AR5) R410A 50% R32 / 50% R125 2088 1924 DR-55 67% R32 / 7% R125 / 26% R1234yf 698 675 R32 100% R32 675 677 DR-5A 68.9% R32 / 31.1% R1234yf 466 466 The thermodynamic properties of R410A and R32 are based on NIST s REFPROP v8.1. 1 The thermodynamic properties of DR-55 and DR-5A are based on REFPROP v9.1 using mixing parameters for the R32/R1234yf and R125/R1234yf pairs provided Chemours (formerly DuPont). DETAILS OF TEST SETUP Description of Baseline System A Precedent model WSC048E3ROA1J rooftop unit, manufactured by Trane, was chosen for refrigerant testing purposes. The unit is rated at a net heating capacity of 44,000 BTU/hr (12.9 kw) heating capacity and 3.40 COP, with a catalog refrigerant charge of 9.0 lbm (4.1 kg) of R410A. The unit is driven by an Alliance model SXA044B2BPA fixed speed scroll compressor with a displacement of 0.00148 ft³/rev (2.56 in³/rev or 0.0419 L/rev) lubricated with Emkarate RL32H POE oil. The compressor runs at 3500 RPM at 60 Hz input frequency for a displacement of 311 ft³/hr (8.82 m³/hr). The indoor and outdoor heat exchangers are of aluminum-fin/copper-tube construction with fixed speed fans. Description of Modifications to System The original factory-installed fixed TXVs for cooling and heating were both replaced with adjustable TXVs of the same size. Additionally the compressor was fitted with a variable frequency drive (VFD, Trane TR200 P5K5), which allowed the compressor speed (volumetric capacity) to be varied so that all the refrigerants could be tested at the same thermodynamic capacity. Measure- 1 The descriptions of R410A and R32 have not changed from REFPROP v8.1 to the current v9.1. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 3 of 12 ment of input power was made upstream of the VFD, however, the efficiency of the AFD is essentially constant (cataloged at 0.97) over the range of power and speed tested, so it has no effect on the comparisons between refrigerants. Description of Tests Conducted The method of test was consistent with Appendix M of AHRI Standard 210/240 with Addenda 1 and 2 (2008/2012), with operating conditions generally held within tighter tolerances. The indoor (ID) airflow rate was fixed at the catalog value of 1600 scfm for all tests. Figure 1 shows a diagram of the Precedent unit. In this diagram, the reversing valve is in the heating mode position. The points in the cycle at which measurements such as pressure and temperature were taken are indicated on the diagram. The accuracies of the various instrument types are listed in Table 2. Table 2. Instrumentation accuracies. measurement accuracy thermocouples (uncalibrated) ±1 RTD sensors (calibrated) ±0.1 air-side pressure differences (calibrated) Rosemount 1151DP3S12 (30 inh 2 O full scale) ±0.075% of span pressure transducers (calibrated) Honeywell DS-750 (750 psi full scale) ±0.1% full scale refrigerant turbine meter (calibrated) Flow Technology FT4-8NE00-LEAH4 ±0.5% of reading electrical power (calibrated) YEW WT230 (6 kw full scale) ± (0.1% of reading + 0.1% of range) The reported heating capacities were calculated from airside flow rate and temperature (dry bulb and wet bulb) measurements. For confirmation, capacity was also calculated from refrigerant side flow rate and enthalpy measurements around the indoor coil, providing a check on energy balance. Internal property codes, consistent with ASHRAE and NIST REFPROP descriptions, were used for calculation of air and refrigerant thermodynamic properties. Tests were carried out at the rating points called out in AHRI Standard 210/240 for heating performance, listed in Table 3. The H2 conditions produce frosting on the outdoor evaporator coil, resulting in cyclic heat/defrost operation. The capacity and efficiency values reported here are integrated averages over a number of heat/defrost cycles acquired after several heat/defrost cycles had occurred and periodic steady-state had been established. Although the H3 conditions also result in frosting of the outdoor coil, the build-up rate is slow enough to allow essentially steady-state behavior. Performance at the H3 conditions was determined by averaging capacity and power consumption for 30 minute period following the termination of a defrost cycle. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 4 of 12 Table 3. Conditions for the H1, H2, and H3 heating mode rating tests. test indoor Tdb indoor Twb outdoor Tdb outdoor Twb H1 70 / 21.1 C 60 / 15.6 C 47 / 8.3 C 43 / 6.1 C H2 70 / 21.1 C 60 / 15.6 C 35 / 1.7 C 33 / 0.6 C H3 70 / 21.1 C 60 / 15.6 C 17 / 8.3 C 15 / 9.4 C Refrigerant charge and compressor speed were taken from the A cooling condition as described in the previous report 2 and summarized in Table 4. A charge sweep run with R410A in heating mode at the H1 conditions showed a peak in COP at the same 9.0 lbm (4.1 kg) charge determined from the cooling mode tests. The heating mode TXV was adjusted at the H1 conditions with each alternative refrigerant to deliver the same compressor suction superheat as obtained with R410A (~10/5.6 C). RESULTS Table 4 shows the refrigerant charge, TXV setting, and compressor speed used for each refrigerant. Also shown is the heating mode capacity and COP measured at the H1 rating point. Air-side capacities relative to the average of the R410A test points are shown in Figure 2. Capacity was very repeatable within ±1.5% for each refrigerant at the H1 point. Unit capacity was very similar with all refrigerants being within 2.5% of R410A. COP data are shown in Figure 3. COP was also very repeatable at the H1 point, generally within ±0.5% to ±1% for each refrigerant. DR-55 and DR-5A provided COPs ~1.5% better than R410A; R32 s COP was ~3% higher. Table 4. Refrigerant charge, TXV position, and compressor speed selected for each refrigerant, along with the average capacity and COP obtained at the H1 point for each. Refrig # of Charge TXV AFD wrt wrt CAP COP runs (lbm) (turns) (Hz) R410A R410A R410A 5 9.0 0 60 46,500 3.535 DR-55 3 8.2 1 CW 60 45,340 2.5% 3.587 +1.5% R32 4 7.25 1 CW 55 45,370 2.4% 3.647 +3.2% DR-5A 2 8.2 1½ CW 61 45,740 1.6% 3.579 +1.3% CW is clockwise (in/closed), CAP is Air-side Capacity in BTU/hr. The air-side heating capacities and COPs (as integrated averages over a number of heating/defrost cycles) taken under the H2 conditions are shown in Figure 4 and Figure 5, respectively. Significant variability in performance was observed during the H2 tests, especially with R410A. This can be attributed to several potential causes, one being variability in the frost build process and the (in)ability of the facility to hold chamber conditions perfectly as the unit switches between operating modes. 2 TEST REPORT #56, SOFT-OPTIMIZED SYSTEM TEST OF R410A, DR-55, R32, AND DR-5A IN A 4-TON UNITARY ROOFTOP HEAT PUMP, Schultz, Perez-Blanco, and Kujak, submitted to AHRI Low GWP AREP 29-Sep-2015. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 5 of 12 Under the H2 defrost conditions, DR-55 provided about 10% additional capacity over R410A and R32 15% to 20% more capacity along with significantly higher efficiencies. Figure 6 shows time traces of heat pump status and compressor power draw during operating under H2 conditions for each refrigerant. As shown in Figure 7, the fraction of time spent in defrost mode with R32 was shorter than for the other refrigerants. The defrost period for R32 ranged from 2.5 to 3 minutes while being 5 to 10 minutes for the other refrigerants. Heating periods ranged from 35 to 50 minutes for all refrigerants. The differences in defrost periods appear to be driven by differences in controls response. Defrost mode is supposed to terminate when the outdoor coil sensor (attached to the inlet to the bottom circuit) reading (OCT) is a specified offset above the outdoor air temperature. With R32 in the unit, defrost periods terminated when OCT was slightly above the setpoint. With R410A and DR-5A, the OCT reading was 20d to 30d beyond the setpoint before defrost ended. With DR-55, the OCT reading was 10d to 20d higher than the setpoint when defrost stopped. Although this phenomenon was generally repeatable, it is not understood how or why the controls response should be dependent on the refrigerant present. 3 Given the similarities in properties of these four refrigerants, it would be expected that similar levels of performance should be obtained if defrost occurred at common initiation and termination temperatures. (This also suggests that the level of performance obtained with R32 should be approachable with the other refrigerants.) Heating capacities and COPs relative to R410A at the H3 conditions are shown in Figure 11. At this colder outdoor condition, all refrigerants produced slightly lower capacities, ranging from R32 being 1% lower to DR-55 being 4% lower than R410A. COPs were equal to 1% lower with DR-5A and DR-55 and up by 4% with R32. The compressor discharge temperatures (CDTs) measured are shown in Figure 9 for the H1 tests and in Figure 10 for the H3 tests. R32 ran about 20d higher than the baseline R410A. DR-5A ran about 10d to 14d higher and DR-55 ran only 8d higher. Similar results were obtained during the heating segments of the H2 tests. All CDTs were well below the maximum operating temperature limit of 250. Heating mode cyclic degradation coefficients (C Dh ), calculated from the H1C (cyclic) tests with each refrigerant, are shown in Figure 11, along with percent differences relative to R410A. All the C Dh values are quite small, so the differences between them are of little significance. SUMMARY Performance tests have been run on a standard production rooftop unit of nominal 44,000 BTU/hr heating capacity and 3.40 COP with R410A, serving as the baseline, and alternative refrigerants DR-55, R32, and DR-5A. No alterations were made to the unit other than replacing the fixed TXVs with adjustable TXVs to allow keeping the superheats with the low GWP refrigerants consistent with the R410A baseline, and installing a VFD on the compressor to match the baseline capacity. 3 The OCT values used here are readings from a thermocouple attached to the OCT sensor well. The OCT thermocouple readings closely matched readings from another thermocouple attached to the same circuit approximately 3 inches upstream. Although there might have been an offset between the OCT sensor and thermocouple readings, it would be expected to be a fixed value not dependent on the refrigerant being used. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 6 of 12 At the H1 and H3 (continuous run) heating points, all three alternative refrigerants showed a small (1% to 4%) decrease in capacity. All three alternatives showed small improvements in COP at the H1 point (1% to 2%). DR-55 showed a small decrease (~1%) at the H3 point while R32 showed a small increase (~4%). At the H2 cyclic defrost test condition, there was a modest increase in capacity with DR-55 (~10%) and a significant increase (~20%) with R32. There was a large improvement in COP at the H2 condition when running with DR-55 (10% to 15%) and R32 (~25%). This was driven mainly by the shorter defrost periods with DR-55 and especially so with R32. This appears to have been driven by the controller tripping the end of defrost at quite different temperatures between the refrigerants. It is unclear at this time why this happened. It is expected that differences in performance under frosting conditions between the refrigerants would be much smaller with consistent trip points. Compressor discharge temperatures (CDTs) were slightly higher when running with DR-55 and DR-5A, typically 5 d to 10 d (3 Cd to 6 Cd). As expected, the highest discharge temperatures were measured with R32, being roughly 20 d higher than with R410A. Figure 1. Precedent unit test setup indicating measurement locations. Heating mode flow directions are shown. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 7 of 12 Figure 2. Air-side heating capacity at the H1 conditions relative to the average of the R410A baseline points. Figure 3. Heating COP at the H1 conditions relative to the average of the R410A baseline points. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 8 of 12 Figure 4. Air-side heating capacity (as an integrated average over a number of heating/defrost cycles) at the H2 conditions relative to the average of the R410A baseline points. Note the order of runs, starting with R410A, progressing with DR-55, R32, and DR-5A through Run 127. Additional runs were then collected with R410A, R32, and DR-55 (in that order). Figure 5. Heating COP (as an integrated average over a number of heating/defrost cycles) at the H2 conditions relative to the average of the R410A baseline points. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 9 of 12 R410A R32 DR-55 DR-5A Figure 6. Traces with time (in minutes) of compressor power (in kw on left axis) and heat pump status (right axis, 0 = defrost mode, 500 = heating mode) while operating at the H2 conditions. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 10 of 12 Figure 7. Fraction of time that unit spent in heating mode (bottom segment of the columns) and defrost mode (upper segment of the columns) during H2 tests. Figure 8. Performance under H3 conditions. Left) Air-side capacity relative to R410A. Right) Heating COP relative to R410A. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 11 of 12 Figure 9. Compressor discharge temperatures measured during operation at the H1 test conditions. Figure 10. Compressor discharge temperatures measured during operation at the H3 test conditions. Figure 11. Left: Cyclic degradation coefficients determined by the H1C test. Right: Percent difference of cyclic degradation coefficients relative to R410A. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 12 of 12 DATA TABLES Tables of data recorded for the H1 and H3 test points from selected runs for each refrigerant follow. Note: The value for the compressor/unit lubricant charge is unknown (not listed on any of the unit labels nor in the catalog). The standard production lubricant charged was used for both the cooling and heating tests. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H1 Basic Information Alternative Refrigerant DR 55 Run #70 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #12 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz 60 60 Hz 1.00 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge 4.08 3.72 kg 9.0 8.2 lbm 0.91 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 47 Air Wet Bulb 6.1 C 43 EB = Qrefrig/Qair 1 2.2 0.8 % 2.2 0.8 % Air side Capacity 13.65 13.29 kw 46,590 45,640 Btu/hr 0.980 Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input 3.865 3.709 kw 3.865 3.709 kw 0.960 Power to Compressor 3.016 2.855 kw 3.016 2.855 kw 0.947 COP or EER (total) 3.53 3.58 [] 3.53 3.61 [] 1.021 COP or EER (compressor only) 4.53 4.66 [] 4.53 4.66 [] 1.028 Refrigerant Mass Flow Rate 239 158 kg/hr 527 432 lbm/hr 0.820 Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H1 Baseline Refrig: R410A Run #12 Alternate Refrig: DR 55 Run #70 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure 99.12 99.19 kpa 14.38 14.39 psia 1.001 Evaporator (fin &tube coil) fluid flow rate air 45.02 45.27 L/hr 1590 1599 scfm 1.005 entering DBT 21.1 21.1 C 70.1 70.1 0.0d entering WBT 14.7 14.3 C 58.5 57.8 0.7d entering DPT 10.4 9.6 C 50.7 49.4 1.4d leaving DBT 36.1 35.7 C 97.0 96.3 0.7d leaving WBT 19.9 19.5 C 67.8 67.1 0.7d leaving DPT 10.7 10.0 C 51.3 50.1 1.2d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT 8.3 8.4 C 47.0 47.1 +0.1d entering DPT 10.4 9.7 C 50.8 49.4 1.4d entering w 0.00804 0.00763 kgw/kgda 0.00804 0.00763 lbmw/lbmda 0.00040 Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction 4.6 775 5.3 747 40.2 112.4 41.5 108.3 discharge 64.7 2307 68.6 2192 148.4 334.6 155.5 317.9 suction SH 5.5 5.3 9.9 9.5 Condenser (refrig to air fin & tube coil) inlet 61.2 2267 64.2 2158 142.2 328.9 147.6 313.0 outlet 34.1 5435 33.6 5436 93.4 788.3 92.5 788.4 outlet subcooling 3.2 3.1 5.8 5.6 Expansion Device (TXV) inlet 32.3 2206 31.6 2118 90.1 320.0 88.9 307.2 inlet subcooling 3.8 4.4 6.9 7.9 Evaporator (refrig to air fin & tube coil) inlet (header) 2.0 861 1.4 812 35.7 124.8 34.5 117.7 outlet 2.5 778 3.0 747 36.5 112.8 37.4 108.4 outlet superheat 3.3 2.9 5.9 5.3 Refrigerant Reversing Valve LP inlet 2.7 778 3.3 747 36.9 112.8 37.9 108.4 LP outlet 4.8 775 5.5 747 40.6 112.4 41.8 108.3 HP inlet 63.4 2307 66.9 2192 146.1 334.6 152.5 317.9 HP outlet 60.2 2206 63.2 2118 140.3 320.0 145.8 307.2

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H3 Basic Information Alternative Refrigerant DR 55 Run #145 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #29 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz 60 60 Hz 1.00 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge 4.08 3.72 kg 9.0 8.2 lbm 0.91 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 17 Air Wet Bulb 9.4 C 15 EB = Qrefrig/Qair 1 16.1 11.1 % 16.1 11.1 % Air side Capacity 13.65 13.29 kw 25,270 24,230 Btu/hr 0.959 Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input 3.498 3.383 kw 3.498 3.383 kw 0.967 Power to Compressor 2.616 2.501 kw 2.616 2.501 kw 0.956 COP or EER (total) 3.90 3.93 [] 2.12 2.10 [] 0.992 COP or EER (compressor only) 5.22 5.32 [] 5.22 5.32 [] 1.018 Refrigerant Mass Flow Rate 239 158 kg/hr 295 238 lbm/hr 0.809 Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H3 Baseline Refrig: R410A Run #29 Alternate Refrig: DR 55 Run #145 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure 99.07 99.24 kpa 14.37 14.39 psia 1.002 Evaporator (fin &tube coil) fluid flow rate air 45.56 45.41 L/hr 1609 1604 scfm 0.997 entering DBT 21.2 21.2 C 70.1 70.2 +0.1d entering WBT 13.1 13.5 C 55.7 56.3 +0.7d entering DPT 6.9 7.8 C 44.5 46.0 +1.5d leaving DBT 29.2 28.9 C 84.6 84.1 0.5d leaving WBT 16.1 16.3 C 61.0 61.4 +0.4d leaving DPT 6.8 7.7 C 44.3 45.9 +1.6d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT 8.7 8.6 C 16.3 16.5 +0.3d entering DPT 7.0 7.8 C 44.6 46.1 +1.5d entering w 0.00635 0.00671 kgw/kgda 0.00635 0.00671 lbmw/lbmda +0.00036 Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction 8.6 449 5.3 747 16.4 65.2 41.5 108.3 discharge 67.0 1933 68.6 2192 152.6 280.4 155.5 317.9 suction SH 8.2 5.3 14.7 9.5 Condenser (refrig to air fin & tube coil) inlet 59.3 1916 64.2 2158 138.7 277.8 147.6 313.0 outlet 28.5 5436 33.6 5436 83.4 788.4 92.5 788.4 outlet subcooling 2.0 3.1 3.6 5.6 Expansion Device (TXV) inlet 25.6 1898 31.6 2118 78.1 275.3 88.9 307.2 inlet subcooling 4.6 4.4 8.3 7.9 Evaporator (refrig to air fin & tube coil) inlet (header) 14.2 497 1.4 812 6.4 72.0 34.5 117.7 outlet 11.9 449 3.0 747 10.6 65.1 37.4 108.4 outlet superheat 4.9 2.9 8.9 5.3 Refrigerant Reversing Valve LP inlet 11.4 449 3.3 747 11.6 65.1 37.9 108.4 LP outlet 8.0 449 5.5 747 17.6 65.2 41.8 108.3 HP inlet 64.8 1933 66.9 2192 148.6 280.4 152.5 317.9 HP outlet 58.1 1898 63.2 2118 136.5 275.3 145.8 307.2

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H1 Basic Information Alternative Refrigerant R32 Run #102 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #12 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz 60 55 Hz 0.92 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge 4.08 3.29 kg 9.0 7.3 lbm 0.81 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 47 Air Wet Bulb 6.1 C 43 EB = Qrefrig/Qair 1 2.2 2.3 % 2.2 2.3 % Air side Capacity 13.65 13.29 kw 46,590 45,360 Btu/hr 0.974 Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input 3.865 3.653 kw 3.865 3.653 kw 0.945 Power to Compressor 3.016 2.802 kw 3.016 2.802 kw 0.929 COP or EER (total) 3.53 3.64 [] 3.53 3.64 [] 1.030 COP or EER (compressor only) 4.53 4.74 [] 4.53 4.74 [] 1.048 Refrigerant Mass Flow Rate 239 158 kg/hr 527 348 lbm/hr 0.659 Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H1 Baseline Refrig: R410A Run #12 Alternate Refrig: R32 Run #102 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure 99.12 98.90 kpa 14.38 14.34 psia 0.998 Evaporator (fin &tube coil) fluid flow rate air 45.02 45.31 L/hr 1590 1600 scfm 1.006 entering DBT 21.1 21.2 C 70.1 70.1 +0.0d entering WBT 14.7 14.4 C 58.5 57.9 0.6d entering DPT 10.4 9.7 C 50.7 49.5 1.2d leaving DBT 36.1 35.6 C 97.0 96.1 0.9d leaving WBT 19.9 19.7 C 67.8 67.5 0.4d leaving DPT 10.7 10.6 C 51.3 51.1 0.2d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT 8.3 8.3 C 47.0 47.0 0.0d entering DPT 10.4 9.8 C 50.8 49.6 1.2d entering w 0.00804 0.00769 kgw/kgda 0.00804 0.00769 lbmw/lbmda 0.00034 Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction 4.6 775 5.3 808 40.2 112.4 41.5 117.2 discharge 64.7 2307 76.7 2303 148.4 334.6 170.1 334.0 suction SH 5.5 5.5 9.9 9.9 Condenser (refrig to air fin & tube coil) inlet 61.2 2267 70.8 2277 142.2 328.9 159.4 330.2 outlet 34.1 5435 34.4 5433 93.4 788.3 93.9 788.0 outlet subcooling 3.2 2.2 5.8 3.9 Expansion Device (TXV) inlet 32.3 2206 32.2 2251 90.1 320.0 89.9 326.4 inlet subcooling 3.8 3.9 6.9 7.1 Evaporator (refrig to air fin & tube coil) inlet (header) 2.0 861 1.3 852 35.7 124.8 34.3 123.6 outlet 2.5 778 2.8 808 36.5 112.8 37.1 117.2 outlet superheat 3.3 3.0 5.9 5.5 Refrigerant Reversing Valve LP inlet 2.7 778 3.1 808 36.9 112.8 37.6 117.2 LP outlet 4.8 775 5.5 808 40.6 112.4 41.9 117.2 HP inlet 63.4 2307 74.7 2303 146.1 334.6 166.4 334.0 HP outlet 60.2 2206 69.9 2251 140.3 320.0 157.8 326.4

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H3 Basic Information Alternative Refrigerant R32 Run #100 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #29 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz 60 55 Hz 0.92 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge 4.08 3.29 kg 9.0 7.3 lbm 0.81 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 17 Air Wet Bulb 9.4 C 15 EB = Qrefrig/Qair 1 16.1 16.0 % 16.1 16.0 % Air side Capacity 13.65 13.29 kw 25,270 25,010 Btu/hr 0.990 Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input 3.498 3.326 kw 3.498 3.326 kw 0.951 Power to Compressor 2.616 2.444 kw 2.616 2.444 kw 0.935 COP or EER (total) 3.90 4.00 [] 2.12 2.20 [] 1.041 COP or EER (compressor only) 5.22 5.44 [] 5.22 5.44 [] 1.042 Refrigerant Mass Flow Rate 239 158 kg/hr 295 204 lbm/hr 0.693 Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H3 Baseline Refrig: R410A Run #29 Alternate Refrig: R32 Run #100 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure 99.07 99.16 kpa 14.37 14.38 psia 1.001 Evaporator (fin &tube coil) fluid flow rate air 45.56 45.28 L/hr 1609 1599 scfm 0.994 entering DBT 21.2 21.2 C 70.1 70.1 +0.0d entering WBT 13.1 13.5 C 55.7 56.2 +0.6d entering DPT 6.9 7.7 C 44.5 45.8 +1.3d leaving DBT 29.2 29.2 C 84.6 84.5 0.1d leaving WBT 16.1 16.4 C 61.0 61.6 +0.6d leaving DPT 6.8 7.8 C 44.3 46.0 +1.7d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT 8.7 8.7 C 16.3 16.3 +0.1d entering DPT 7.0 7.7 C 44.6 45.9 +1.3d entering w 0.00635 0.00667 kgw/kgda 0.00635 0.00667 lbmw/lbmda +0.00032 Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction 8.6 449 5.3 808 16.4 65.2 41.5 117.2 discharge 67.0 1933 76.7 2303 152.6 280.4 170.1 334.0 suction SH 8.2 5.5 14.7 9.9 Condenser (refrig to air fin & tube coil) inlet 59.3 1916 70.8 2277 138.7 277.8 159.4 330.2 outlet 28.5 5436 34.4 5433 83.4 788.4 93.9 788.0 outlet subcooling 2.0 2.2 3.6 3.9 Expansion Device (TXV) inlet 25.6 1898 32.2 2251 78.1 275.3 89.9 326.4 inlet subcooling 4.6 3.9 8.3 7.1 Evaporator (refrig to air fin & tube coil) inlet (header) 14.2 497 1.3 852 6.4 72.0 34.3 123.6 outlet 11.9 449 2.8 808 10.6 65.1 37.1 117.2 outlet superheat 4.9 3.0 8.9 5.5 Refrigerant Reversing Valve LP inlet 11.4 449 3.1 808 11.6 65.1 37.6 117.2 LP outlet 8.0 449 5.5 808 17.6 65.2 41.9 117.2 HP inlet 64.8 1933 74.7 2303 148.6 280.4 166.4 334.0 HP outlet 58.1 1898 69.9 2251 136.5 275.3 157.8 326.4

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H1 Basic Information Alternative Refrigerant DR 5A Run #125 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #12 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz 60 61 Hz 1.02 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge 4.08 3.72 kg 9.0 8.2 lbm 0.91 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 47 Air Wet Bulb 6.1 C 43 EB = Qrefrig/Qair 1 2.2 0.1 % 2.2 0.1 % Air side Capacity 13.65 13.29 kw 46,590 45,800 Btu/hr 0.983 Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input 3.865 3.740 kw 3.865 3.740 kw 0.968 Power to Compressor 3.016 3.299 kw 3.016 3.299 kw 1.094 COP or EER (total) 3.53 3.55 [] 3.53 3.59 [] 1.016 COP or EER (compressor only) 4.53 4.03 [] 4.53 4.03 [] 0.890 Refrigerant Mass Flow Rate 239 158 kg/hr 527 421 lbm/hr 0.798 Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H1 Baseline Refrig: R410A Run #12 Alternate Refrig: DR 5A Run #125 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure 99.12 99.27 kpa 14.38 14.40 psia 1.002 Evaporator (fin &tube coil) fluid flow rate air 45.02 45.39 L/hr 1590 1603 scfm 1.008 entering DBT 21.1 21.1 C 70.1 70.1 +0.0d entering WBT 14.7 14.3 C 58.5 57.7 0.8d entering DPT 10.4 9.5 C 50.7 49.1 1.6d leaving DBT 36.1 35.8 C 97.0 96.4 0.6d leaving WBT 19.9 19.6 C 67.8 67.3 0.6d leaving DPT 10.7 10.2 C 51.3 50.4 0.9d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT 8.3 8.4 C 47.0 47.1 +0.1d entering DPT 10.4 9.6 C 50.8 49.2 1.6d entering w 0.00804 0.00756 kgw/kgda 0.00804 0.00756 lbmw/lbmda 0.00048 Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction 4.6 775 5.4 731 40.2 112.4 41.6 106.0 discharge 64.7 2307 69.9 2178 148.4 334.6 157.9 315.9 suction SH 5.5 5.5 9.9 9.9 Condenser (refrig to air fin & tube coil) inlet 61.2 2267 65.3 2146 142.2 328.9 149.6 311.2 outlet 34.1 5435 33.4 5434 93.4 788.3 92.2 788.2 outlet subcooling 3.2 3.4 5.8 6.2 Expansion Device (TXV) inlet 32.3 2206 31.3 2106 90.1 320.0 88.3 305.5 inlet subcooling 3.8 4.8 6.9 8.7 Evaporator (refrig to air fin & tube coil) inlet (header) 2.0 861 1.0 795 35.7 124.8 33.8 115.4 outlet 2.5 778 3.1 731 36.5 112.8 37.6 106.1 outlet superheat 3.3 3.2 5.9 5.8 Refrigerant Reversing Valve LP inlet 2.7 778 3.3 731 36.9 112.8 37.9 106.1 LP outlet 4.8 775 5.6 731 40.6 112.4 42.0 106.0 HP inlet 63.4 2307 68.1 2178 146.1 334.6 154.7 315.9 HP outlet 60.2 2206 64.3 2106 140.3 320.0 147.8 305.5

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H3 Basic Information Alternative Refrigerant DR 5A Run #128 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #29 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz 60 61 Hz 1.02 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge 4.08 3.72 kg 9.0 8.2 lbm 0.91 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 17 Air Wet Bulb 9.4 C 15 EB = Qrefrig/Qair 1 16.1 11.0 % 16.1 11.0 % Air side Capacity 13.65 13.29 kw 25,270 24,530 Btu/hr 0.971 Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input 3.498 3.403 kw 3.498 3.403 kw 0.973 Power to Compressor 2.616 2.527 kw 2.616 2.527 kw 0.966 COP or EER (total) 3.90 3.91 [] 2.12 2.11 [] 0.998 COP or EER (compressor only) 5.22 5.26 [] 5.22 5.26 [] 1.008 Refrigerant Mass Flow Rate 239 158 kg/hr 295 230 lbm/hr 0.780 Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H3 Baseline Refrig: R410A Run #29 Alternate Refrig: DR 5A Run #128 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure 99.07 98.97 kpa 14.37 14.35 psia 0.999 Evaporator (fin &tube coil) fluid flow rate air 45.56 45.36 L/hr 1609 1602 scfm 0.996 entering DBT 21.2 21.2 C 70.1 70.2 +0.1d entering WBT 13.1 11.6 C 55.7 52.9 2.8d entering DPT 6.9 2.8 C 44.5 37.1 7.4d leaving DBT 29.2 29.1 C 84.6 84.3 0.2d leaving WBT 16.1 14.8 C 61.0 58.7 2.3d leaving DPT 6.8 3.4 C 44.3 38.1 6.2d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT 8.7 8.5 C 16.3 16.7 +0.5d entering DPT 7.0 2.9 C 44.6 37.2 7.3d entering w 0.00635 0.00477 kgw/kgda 0.00635 0.00477 lbmw/lbmda 0.00158 Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction 8.6 449 5.4 731 16.4 65.2 41.6 106.0 discharge 67.0 1933 69.9 2178 152.6 280.4 157.9 315.9 suction SH 8.2 5.5 14.7 9.9 Condenser (refrig to air fin & tube coil) inlet 59.3 1916 65.3 2146 138.7 277.8 149.6 311.2 outlet 28.5 5436 33.4 5434 83.4 788.4 92.2 788.2 outlet subcooling 2.0 3.4 3.6 6.2 Expansion Device (TXV) inlet 25.6 1898 31.3 2106 78.1 275.3 88.3 305.5 inlet subcooling 4.6 4.8 8.3 8.7 Evaporator (refrig to air fin & tube coil) inlet (header) 14.2 497 1.0 795 6.4 72.0 33.8 115.4 outlet 11.9 449 3.1 731 10.6 65.1 37.6 106.1 outlet superheat 4.9 3.2 8.9 5.8 Refrigerant Reversing Valve LP inlet 11.4 449 3.3 731 11.6 65.1 37.9 106.1 LP outlet 8.0 449 5.6 731 17.6 65.2 42.0 106.0 HP inlet 64.8 1933 68.1 2178 148.6 280.4 154.7 315.9 HP outlet 58.1 1898 64.3 2106 136.5 275.3 147.8 305.5