Seasonal Performance and Exergy Analysis of Multi-Function Heat Pump Units

Similar documents
Swiss Heat Pump Research Highlights II Advanced Heat Pumps in Switzerland Prof. Dr. Beat Wellig

IWT-TETRA: ZON-WARM. Solar Thermal and Heat Pump Systems. Domestic Hot Water production. Jan Verheyen. Warmtepomp Symposium 11/09/2013

CEN standardization work on refrigerating systems, especially standard EN 378

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

This document is a preview generated by EVS

Applications of Thermodynamics: Heat Pumps and Refrigerators

This document is a preview generated by EVS

Adsolair 56/58. Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system

EXHAUST AIR HEAT PUMPS EVALUATED FOR NORDIC CIRCUMSTANCES

PERFORMANCE MONITORING OF A HIGH-TEMPERATURE AIR-TO-WATER HEAT PUMP WITH INJECTION CYCLE INSTALLED IN A LOW-INSULATED SINGLE-FAMILY HOUSE IN BELGIUM

Chapter 9. Refrigeration and Liquefaction

A Notification under Article 12 of Regulation (EU) No 1025/2012 1

Draft COMMUNICATION FROM THE COMMISSION

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

ANALYSIS OF AN AIR SOURCE HEAT PUMP SYSTEM WITH SPEED CONTROLLED COMPRESSOR AND VAPOR INJECTION

Final report Annex 32 part 2

Update Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South

This document is a preview generated by EVS

Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation.

The products covered by the Regulation can be classified as follows:

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

Task 4: R&D Overview Switzerland

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Modelling the Performance of a Diffusion Absorption Refrigeration System

Shortcut Model for Predicting Refrigeration Cycle Performance

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

WP2 European Product Analysis, Task 2.1 Determining energy efficiency criteria, D 2.1 Periodic Criteria Papers (first set)

Kawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

European Parliament and of the Council with regard to energy labelling of residential ventilation units. (Text with EEA relevance) (2016/C 416/06)

Technical Note. EHPA Quality Label Model Range Definition Version

The importance of hot water system design in the Passivhaus

A WET-VAPOUR INJECTION AND VARIABLE SPEED SCROLL COMPRESSOR AIR TO WATER HEAT PUMP MODEL AND ITS FIELD TEST VALIDATION

This document is a preview generated by EVS

COMMISSION REGULATION (EU) No /.. of

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Desiccant Cooling with Solar Energy

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Performance of the Low-energy House in Sisimiut

REVERSIBLE R744 (CO 2 ) HEAT PUMPS APPLIED IN PUBLIC TRAINS

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Standard hydraulic circuits for small-scale heat pump plant

Systems engineering Slide 1

HVAC product labelling and certification

This document is a preview generated by EVS

ETA ACCU 90% HIGHEST EFFICIENCY AIR HANDLING UNIT

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters

The natural ombination

Certified Passive House Component For cool, temperate climates, valid until 31 December 2017

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Adconair 76. Comfort air conditioning unit with counterflow plate heat exchanger. AIR VOLUME FLOW: 2,600 23,600 m³/h

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

High Efficiency Heat Pump for Domestic Hot Water Generation

PRODUCT DATA SHEETS HEAT PUMPS

THE HEAT PUMP CHOICE OF PROFESSIONALS

COMMISSION DELEGATED REGULATION (EU) /... of XXX. on the classification of the frost resistance performance for clay tiles under EN 1304

Heat Consumption Assessment of the Domestic Hot Water Systems in the Apartment Buildings

ME 354 THERMODYNAMICS LAB THE REFRIGERATION CYCLE

National foreword. Compliance with a British Standard cannot confer immunity from legal obligations.

Air conditioning. EcoCond EcoCond+

ErP. ErP READY. The Eco-Design Directive ErP for refrigerator systems and heat pumps. READY

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Available online at ScienceDirect. Energy Procedia 91 (2016 ) 35 41

COMMISSION DELEGATED REGULATION (EU) /... of

Saving resources by going evaporative: how evaporative cooling technologies and water cooled chillers can significantly reduce energy

1/2011. Das TGA-Online Portal. Organ des Organ des. adwkuihdfwu. Assessment

ECOFOREST GEOTERMIA. ecogeo. Ground/Air Source Heat Pumps.

your comfort. our world. Altherma Flex Type Renewable heat pump system for every environment

Compendium DES July 2016, CARN

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

R E P O R T D I N E N

EHPA Testing Regulation

Quality Heat Exchangers

Zehnder ComfoAir 550. Ventilation unit

A study of Transient Performance of A Cascade Heat Pump System

ScienceDirect. Influence of hydraulics and control of thermal storage in solar assisted heat pump combisystems

This document is a preview generated by EVS

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

DOMESTIC LINE DUPLEX EASY

September 11, 2012 Ministry of Economy, Trade and Industry

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

c Dr. Md. Zahurul Haq (BUET) Refrigeration Cycles ME 6101 (2013) 2 / 25 T270 COP R = Q L

BUSINESS PLAN CEN/TC 162 PROTECTIVE CLOTHING INCLUDING HAND AND ARM PROTECTION AND LIFEJACKETS EXECUTIVE SUMMARY

Oxyvap Evaporative Cooling Applications

According to the following European Regulations which come into force:

Feasible Working Domains Decision Support for Heat Pump Projects

Refrigeration Cycles. Refrigerators, Air-conditioners & Heat Pumps. Refrigeration Capacity/Performance. Dr. Md. Zahurul Haq

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

DRAFT ECODESIGN REGULATION FOR ENER LOT21 PRODUCTS

Sub-Critical Operation of the CO2 Expander/ Compressor

T270 COP R = Q L. c Dr. Md. Zahurul Haq (BUET) Refrigeration Cycles ME 6101 (2017) 2 / 23 T354

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

Daikin VRV Systems Plugin VE2012 User Guide

Potential and Simulation of Open-Cycle Solar-Assisted Climatisation-Plants in Single-Family-Houses

Transcription:

Seasonal Performance and Exergy Analysis of Multi-Function Heat Pump Units Ralf Dott, Thomas Afjei and Carsten Wemhöner Institute of Energy in Building, University of Applied Sciences Northwestern Switzerland, Muttenz, Switzerland Corresponding email: ralf.dott@fhnw.ch SUMMARY Overall energy rating of buildings including installed HVAC systems gets more important due to climate protection as demonstrated in building energy certificates presently introduced in the EU. Multifunctional system layouts for combined space heating, domestic hot water and ventilation, however, are often not covered by current product test standards and calculation methods. In this project consistent testing and calculation of multifunctional ventilation compact units with heat pumps has been elaborated based on present standard testing and calculation approaches. Different comparisons of calculated and field-monitored overall seasonal performance factor accomplished in Annex 28 show deviations in the range of ±6%. Results are currently implemented in the respective testing and calculation CEN standards in the frame of the EU Directive on the Energy Performance of Buildings (EPBD) and related product testing. Concerning component optimisation exergy analyses are a useful means, since different loss mechanisms can be quantified on a uniform basis. INTRODUCTION Due to reduced energy needs in modern highly-insulated and -tight buildings, multifunctional system configurations have been introduced in the markets to cover different building energy needs for space heating (SH), domestic hot water (DHW) and ventilation with one unit. However, a system assessment requires standard test procedure and calculation methods, which are presently incomplete or missing for innovative multifunctional system layouts. The assessment is needed for different purposes, on the one hand for the holistic energy rating in the frame of the building energy certificate as currently introduced in the EU based on the Directive on the Energy Performance of Buildings (EPBD). On the other hand, transparent labelling concerning energy consumption/costs and environmental impact is needed to convince consumers to apply environmentally sound technologies. METHODS IEA HPP Annex 28 has been accomplished in 2003-2005 as co-normative research project in the frame of the Heat Pump Program (HPP) of the International Energy Agency (IEA). The nine countries AT, CA, CH, DE, FR, JP, NO, SE and US participated in the project. The scope and objective of Annex 28 were the development of

comprehensive test procedures for combined operating heat pumps for SH and DHW with minimum testing requirements subsequent transparent and easy-to-use calculation methods for the SPF of combined operating heat pumps as recommendations to standardisation organisations. Thereby, two types of combined operating heat pump systems have to be differentiated alternate combined operation, where the heat pump is switched between SH- and DHW operation, and simultaneous systems, where SH and DHW energy is produced at the same time. Since ventilation compact units with exhaust heat pumps have become a standard heating system in ultra-low energy dwellings, they have been included in the scope, as well. The accomplished work in Annex 28 comprises the testing of the systems according to existing and extended standards, calculation of the systems and field monitoring for the validation of the calculation results and to gain experience with the functionality for system optimisation. Since test procedures for the SH-only, DHW-only and ventilation system already are in use, existing standards for the single operation modes have been extended to cover highly-integrated system configurations, as shown in Figure 1 and 3. RESULTS Results presented here refer to the Swiss national project in the IEA HPP Annex 28 [7] dedicated to the testing and calculation of heat pump compact units and field testing. Test procedure for heat pump compact units The testing of ventilation compact units with heat pump comprises Assessment of -tightness (testing for internal and external leakage) Testing ventilation Thermodynamic tests Acoustic tests Filter bypass leakage (optional) Operation/Maintenance/Safety (optional) Hygienic investigations (optional) The following description refers to the thermodynamic testing as developed at HLKS of HTA Lucerne, the national Swiss test centre for residential ventilation systems. No European test standard for compact units exists, yet, but only test standards for the ventilation part and test standards for heat pumps for SH and DHW. The test procedure is based on the testing of German Institute of Building Technology (DIBt) and guidelines of the German Passive House Institute (PHI). However, the heat pump has been considered as core component of the compact unit and test points have been chosen based on the European heat pump test standards EN 14511 [2] for space heating mode and EN 255-3 [3] for DHW mode. Since the operation conditions for the heat pump depend on the heat recovery a combined testing of the heat pump and the ventilation system is advantageous. Consequently, testing of the three basic operation modes deliver the respective characteristics of the component: ventilation-only operation (characteristic: temperature change coefficient, fan power) combined ventilation and heat pump in SH operation (COP, heating capacity SH) combined ventilation and heat pump in DHW operation (COP, heating capacity DHW)

exhaust outdoor return supply exhaust outdoor return supply exhaust outdoor return supply Heat recovery Heat recovery Heat recovery Domestic hot water storage Domestic hot water storage Domestic hot water storage Figure 1. Operation modes for thermodynamic testing of compact units with internal circuit (left: ventilation only, middle: ventilation and SH, right: ventilation and DHW) Figure 1 shows the different operation modes on the example of a heat pump compact unit with an internal circuit. The active circuit is depicted bold. The component characteristic depends on the temperatures and the volume flow rates, thus test points of EN 14511 have to be tested for different volume flow rates to be determined. To characterise the ventilation part including heat recovery unit, the temperature change coefficient and the electrothermal amplification factor are being determined. Calculation method The calculation of compact unit with heat pump is based on a temperature class approach (bin method) inline with the proposal for combined operating heat pump systems. Input data of the calculation method are the energy needs of the SH and DHW distribution system, test points of the unit according to the above test method, heating degree hours of the site, the system configuration and control details (e.g. heating curve, balance point). The cumulative annual frequency of the outside temperature is divided into temperature classes (bins). In the centre of each bin, an operating point is evaluated, where the operation characteristic is known, i.e. at conditions defined in the heat pump testing standard. The operating point is considered to characterise the heat pump operation of the whole bin. The areas of each bin correspond to heating degree hours, which are proportional to the energy need in the bin. Thus, a weighting of COP values at the operating conditions with the energy fraction of the bin and a subsequent summation of all bins delivers the seasonal performance. Electrical back-up heaters and recovered heat by a ventilation heat recovery only, if not already taken into account in the building energy calculation - can also be considered by an evaluation of the respective area in the cumulative frequency diagram. For the domestic hot water operation, a similar calculation is performed based on standardised testing results of DHW-testing, e.g. for Europe according to EN 255-3 [3]. The overall seasonal performance can be calculated by weighting of respective operation modes, i.e. space heating-only, domestic hot water-only and combined operation.

Figure 2. Principle of the bin method for multifunctional system for SH, DHW and ventilation with heat recovery unit (alternate mode) (OP - operating point, BU back-up, SH heat pump SH mode, W heat pump DHW mode, HR heat recovery unit) Field monitoring Calculation results have been compared to field testing results of a compact unit with source heat pumps installed in a single family low energy house according to the Swiss MINERGIE standard. Figure 3 left shows the dwelling and a sketch of the principle system variant of system layouts of ventilation compact units with heat pump. In the investigated pilot plant, the compact unit works with a ventilation heat recovery and floor heating distribution system. A ground-to- heat exchanger and solar collector are not installed. Figure 3. MINERGIE dwelling for field testing and principle system layout of compact units The evaluation period of the field testing is April, 26 th 2004 to April, 25 th 2005. Figure 4 shows the annual electrical energy consumption of the different components of the compact unit (left) and heat energy consumption (right) for the different building needs. 75% of the electrical energy consumption is used as driving energy for the heat pump compressor, while 20% is used by auxiliaries and only 5% by the electrical back-up heater. Concerning the heat energy consumption, the remarkably low DHW heat energy consumption of only 9% explains the high fraction of SH energy of 83% despite the layout as low energy house.

Figure 4. Annual electrical (left) and heat energy consumption (right) of the compact unit Figure 5 presents the system boundaries used for the evaluation of performance characteristic number for the assessment of a ventilation compact unit with -source heat pump. The same numbers have been calculated with the calculation method. Figure 5. System boundaries for the assessment of the monitored compact unit The SPF-HP comprises the system boundary according to the European heat pump testing. The Generator SPF (SPF-G) is the ratio of the produced energy of all generators (heat pump, back-up) to the respective electrical energy input and is well suited for the comparison to other heat generators like boilers. The System SPF (SPF-S) is related to the energy need and is calculated as ratio between the used energy (incl. the recovered ventilation energy) and the total electrical energy input to the entire system (incl. auxiliaries and electrical input to the ventilation). Results of the overall SPF for the system boundaries are depicted in Table 1. Table 1. Monitoring and calculation overall SPF results for a ventilation compact unit with -source heat pump installed in a low-energy house acc. to Swiss MINERGIE standard. Monitoring (Reference) Calculation Difference SPF-HP 3.66 3.54-3.3% SPF-G 3.42 3.42 0.0 % SPF-S 3.06 2.96-3.2% Exergy analysis Exergy is defined as the fraction of the energy that can be arbitrarily converted in each of the different energy forms. In all natural processes, exergy is converted to anergy, e.g. by irreversible heat transfer due to finite temperature differences or pressure drop due to friction, which corresponds to an exergy loss. Therefore, the exergy content is a measure of the thermodynamic quality of an energy flow or a process. An exergetic consideration has been applied to characterise the impact of the temperature requirements of different source and sink systems used in compact units (cf. Figure 3 right) on the performance of a ventilation compact unit.

Pure heating distribution systems have the limitation that the maximum temperature is restricted to about 50 C. Moreover, to avoid excessive exergy input to the fans, common designs limit the volume flow to the hygienic necessary. Thus, heating systems can only be applied in ultra low energy dwellings due to the limited heat capacity of the and require high supply temperature up to the limit of about 50 C in colder winter periods. Floor heating systems, on the other hand, have a large surface for the heat emission in the room, whereby supply temperatures below 30 C can be realised. However, additional exergy input for the circulation pump to transport the heat transfer medium is required. The exergy comparison has been accomplished for an ultra-low energy house under the simplifying assumptions of adiabatic components, negligence of defrosting operation and a constant internal exergetic efficiency of the refrigerant process of ζ=0.5 (exergy losses of compression, refrigerant pipe, heat exchanger friction, expansion) to focus on the exergy losses linked to the source/ sink system periphery. Table 2 shows the boundary conditions used. Table 2. Boundary conditions and resulting source and sink temperature (HR heat recovery) Building Ambient temperature [ C]/Indoor design temperature [ C] -4 / 20 Heat load for the heat pump at ambient temperature [W] 1200 Ventilation system Volume flow rate ventilation system [m 3 /h] 110 Temperature change coefficient (considered the same for supply and return path) [-] 0.8 Pressure drop HR, condenser and evaporator [Pa] / channels (each supply/return [Pa] 80 / 40 Constant fan power [W]/ Pressure drop dependent fan power [W/Pa] 10/ 0.12 Heat pump Pinch point condenser heating [K]/floor heating [K]/Pinch point evaporator both[k] 5 / 2 / 5 Required supply temperature / floor heating at ambient conditions [ C] 48 / 29 Condensation temperature / Evaporation temperature of the heating system [ C] 48 / -21 Condensation temperature / Evaporation temperature of the floor heating system [ C] 30/ -23 Pump power of the circulation pump [W] 40 Since the COP of the heat pump can be expressed by the equation cond ς, (1) cond Tevap ) COP = COPC = ς (T where COP C denotes the Carnot COP, ζ the constant internal exergetic efficiency, T cond the thermodynamic condensation and T evap the thermodynamic evaporation temperature, the COP is proportional to the Carnot COP and thus to the respective temperature levels. Resulting exergy losses of the heating are 14% higher than of the floor heating system despite the exergy input to the circulation pump and the evaporation temperature decrease due to the higher anergy extraction in the evaporator in case of the floor heating system, cf. Table 2. Figure 6 depicts the range of temperature levels in the common components of the compact unit with common source and sink systems. The bold red arrows follow the way of the heat transfer media through the compact unit. Starting at ambient conditions the heat recovery unit raises the exhaust temperature above ambient level, while in the evaporator it is cooled down by the refrigerant. The evaporation temperature level can be increased by a mix with an additional outdoor flow or by a preheating of the in a ground-to- heat exchanger, which is often installed in order to avoid frosting of the heat recovery heat exchanger. The heat pump makes the main temperature lift from the source temperature level to the required distribution temperature level, and in the emission system the temperature level is reduced first to the room temperature, and then by the heat losses of the room to the ambient level. T

Figure 6. Temperature levels in the single components for compact unit (GAHX ground-to- heat exchanger, HRU Heat recovery unit, TABS Thermally activated building structures, COP Coefficient of performance) The temperature levels and corresponding exergy losses depend on the design of the heat exchangers, since larger heat exchanger surfaces reduce the heat transfer resistance and lead to lower temperature differences for the heat transfer. On the other hand, the temperature levels are also defined by the capacity of the source and the sink heat transfer medium. By the choice of hygienic necessary ventilation as heating medium, for instance, high temperature spreads are required based to the limited heat transport capacity due to restricted volume flow rate and the heat capacity of the. The theoretical minimum required temperature lift for a reversible heat transfer is defined by ambient and indoor temperature (reversible Carnot COP). All limitations of the heat transfer system periphery thus have to be compensated by additional exergy input to the heat pump compressor due to the elevated temperature lift. On the sink side the maximum spread is seen between an heating and TABS emission system, on the source side between a system with only ventilation exhaust and a preheating of a higher outside flow. The general advantage of exergy analysis is, that the different loss mechanisms, e.g. due to heat transfer or pressure drop, can be quantified on the same basis as exergy loss. However, an exergy consideration gives only the technical viewpoint, and economical consideration may result in a different assessment. Last but not least environmental and comfort issues have to be considered, as well. DISCUSSION Simplification in the calculation approach The calculation method implies the assumption of the redistribution of the energy according to heating degree hours which are only dependent on the outdoor temperature. The impact of solar and internal gains on the energy redistribution can be approximated by an adjustment of the heating limit based on the quantity of used gains as depicted in Figure 2. Moreover, controller impact cannot be considered in detail, since often, details are not known. Therefore, controller impact is taken into account by standard settings depending on the system layout, e.g. for the running time of auxiliaries.

Implementation of results Results of IEA HPP Annex 28 for the heat pump calculation method has been implemented in the European draft standard pren 15316-4.2 [4] used in the EPBD [1]. As national implementation of the EPBD, Germany has introduced the method on a monthly basis in DIN V 18599 [5]. A working group committed to testing of ventilation compact units with heat pump is presently in constitution as a joint working group of the Technical Committees CEN/TC 113 (heat pump testing) and CEN/TC 156 (ventilation systems). This gives the perspective of uniform testing of heat pump and ventilation part of compact units with heat pump. Component and system optimisation Exergy analyses are well suited for a component and process optimisation, since the impact of different loss mechanisms can be quantified on the uniform basis of exergy losses. The exergy analysis of the compact unit shows that any increase of temperature lift by the layout of the source and sink system has to be supplied as additional exergy to the heat pump. Therefore, system layout guaranteeing high source temperature and low sink temperature level lead to a significant reduction of the exergy losses and thus reduces the electrical energy input. Information on IEA HPP Annex 28 Further information on IEA HPP Annex 28 can be found on the Annex 28 website http://www.annex28.net. The final report of IEA HPP Annex 28 [6] is available at the IEA Heat Pump Centre. It can be ordered on http://www.heatpumpcentre.org, category Publications/ Reports. ACKNOWLEDGEMENT The Swiss national project [7] and the IEA HPP Annex 28 [6] have been funded by the Swiss Federal Office of Energy (SFOE). REFERENCES [1] Directive 2002/91/EC of the European Parliament and of the Council of 16 December 2002 on the Energy performance of Buildings, Official Journal of the European Communities, L1/65- L1/71, 4.1.2003, Brussels [2] EN 14511:2004 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling, CEN, 2004, Brussels [3] EN 255:1997: Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors - Heating mode, Part 3: Testing and requirements for marking for sanitary hot water units, CEN, 1997, Brussels [4] pren 15316-4.2. Heating systems in buildings Methods for the calculation of system energy requirements and system efficiencies Part 4.2 Heat pump systems, CEN, 2006, Brussels [5] DIN V 18599 Energetische Bewertung von Gebäuden - Berechnung des Nutz-, End- und Primärenergiebedarfs für Heizung, Kühlung, Lüftung, Trinkwarmwasser und Beleuchtung, DIN, Berlin [6] Wemhoener, C, Afjei, Th., 2006. Test procedure and seasonal performance calculation of residential heat pumps with combined space and domestic hot water heating, Final report IEA HPP Annex 28, Muttenz [7] Afjei, Th., Wemhoener, C., Dott, R., et al., 2007. Calculation method for the seasonal performance of heat pump compact units and validation, Final report SFOE research project, Muttenz.