Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

Similar documents
UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

Displacement Ventilation

DESCRIPTION OF TECHNOLOGY

Underfloor Air Distribution:

RADIANT COOLING RESEARCH SCOPING STUDY

design brief This design brief provides an introduction into the design and application of DV. It addresses the following issues:

7. MECHANICAL SYSTEM DESIGN

HVAC 101. H V A C S y s t e m s

IDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions

Space Air Diffusion II

HVAC DISTRIBUTION and DELIVERY SYSTEMS

ASHRAE JOURNAL ON REHEAT

Temperature Control and Zoning of UFAD Systems

UNDERFLOOR PRODUCTS E3

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Making UFAD Systems Work BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE

Jim Aswegan Chief Engineer

High-Performance VAV Systems

POTENTIAL AND LIMITATIONS FOR HYDRONIC RADIANT SLABS USING WATERSIDE FREE COOLING AND DEDICATED OUTSIDE AIR SYSTEMS

UFAD Underfloor air distribution system

Better Air Dispersion for. Underfloor. Plenums

Summary Comparison of Simulation Program Features

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Air Conditioning Clinic

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

FORM EG2 (502) FlexSys Configured Packaged Rooftop Air Conditioning Units

Engineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.

CEE 243. Week 2 HVAC systems at Y2E2

4. OVERVIEW OF MECHANICAL SYSTEM

APPLICATION GUIDE BEAMS

BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

CHAPTER 4. HVAC DELIVERY SYSTEMS

A REASONABLE ALTERNATIVE TO CHILLED BEAMS Dan Int-Hout Chief Engineer

HVAC Mandatory Provisions Part II, Page 1

DESIGNING MODULAR VAV SYSTEMS

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

Chilled Ceilings / Beams Working Principles & Applications

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I.

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

photo by PFC Price Fan Column

Yan Xue 1 and Qingyan Chen 2,1* Abstract

ApacheHVAC User Guide Part F: Loads Analysis and Reporting Tools

Inffusers. idl20 (2 WAY) ids60 (4 WAY)

Residential ventilation concepts based on the idea of displacement airflow distribution

Pharmaceutical Facility Design

2009 IECC Commercial Mechanical Requirements

CONSTRUCTION AND ENERGY COSTS FOR RADIANT VS. VAV SYSTEMS

HVAC Controls Upgrades: Requirement Details ( )

Underfloor Air Distribution in a Commercial High Rise: The New York Times Headquarters

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

Duct Design and Installation

Chilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

Technical Assignment 3 11/15/04. Executive Summary

ApacheHVAC User Guide. IES Virtual Environment 6.4

Dehumidifying with Dedicated Outdoor Air

August 15, 2013 Page 1 of 19

Halton Vario Design Guide

Appendix 13. Categories of Cooling and Heating systems

IRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE

Agenda and Objectives

IAQ Building Education and Assessment Model (I-BEAM)

RADIANT COOLING SYSTEMS OPPORTUNITIES FOR RADIANT COOLING IN NORTH AMERICAN CONSTRUCTION DALE HANSCOMB, REHAU Sales Manager Building Technology

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

The School District of Philadelphia Administration Headquarters Shell and Core Renovations 440 North Broad Street Philadelphia, PA

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

ApacheHVAC in VE 2012

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

Displacement Ventilation in Classrooms

Selected Laboratory Energy Efficiency Measures

Underfloor Air Conditioning in North America David Arnold Troup Bywaters + Anders/ Director and Regional Chair ASHRAE Region at Large

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2

maximize displacement ventilation Opportunities

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

EarthWise System Seminar

HVAC Controls Upgrades: Requirement Details ( )

4-Pipe VAV vs. Active Chilled Beams for Labs

Why Doesn t My HVAC System Work?

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me!

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks

Intermediate framed denotes standard framing 16 inches on center with headers insulated with a minimum of R-10 insulation.

SUPPORTING DOCUMENT RESIDENTIAL ENERGY CODE WORKSHEET (2015) EFFECTIVE JANUARY 1, 2017

ApacheHVAC User Guide Part B: Equipment, Loops, Components, and Controls

NEW AR-L AR-C AND HIGH-CAPACITY LINEAR COOLING PANELS. Higher energy efficiency. Increased thermal comfort

Welcome. High Performance Mechanicals for Houses That Work. Energy Design Conference - Duluth, MN. February 21 st, 2018

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS

The School District of Philadelphia Administration Headquarters

Transcription:

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems CBE Timothy Moore CENTER FOR THE BUILT ENVIRONMENT SimBuild August 2006

Published methodologies for UFAD and DV

Load splits or Plume Factors UFAD and TDV differences in stratification height and gradient based upon Loads and T Airflow rate Coupling with radiant systems Cooling vs. Dead-band vs. Heating modes Radiant and conductive heat transfer to UFAD plenum Radiant exchange (with all view factors accounted for) plus convective heat transfer in radiant cooling applications

UFAD and TDV differences in stratification per T

Cooling Load splits for UFAD and TDV Apportioning internal loads to return plenum is a good idea, but methods proposed in EDR document need refinement or replacement Assigning occupants to plenum zone w/o fixing OA per zone results in reduction of ventilation rate and related loads One overall split may be adequate for component loads, but needs to vary with system mode (cooling, heating, or dead-band) Differentiation based on system type & configuration (table ) Evolving UFAD version of equest/doe-2 comes closer Cooling, heating, and dead-band plume factors for UFAD or DV Ability to model UFAD supply plenum (including thermal decay) Plume factors can be used for some radiant cooling applications to apportion load to chiller/cooling tower and not airside systems

Cooling Load splits for UFAD and TDV Perimeter loads not adequately addressed in EDR guidelines are included in equest-ufad development Existing method would need additional glazing in RA plenum zone Proportionate U-Factors and SHGC adjustment in both added and actual to maintain same loads (but would need to leave T vis in actual glazing unchanged for daylighting) equest-ufad single plume factor for each zone effectively incl. this Need guidance on splits for different diffuser types, blinds, etc. Need guidance re: TDV limitations and variable load splits Not typically recommended for perimeter zones with high loads Maintaining comfort avoiding excessive stratification - requires high airflow or added sensible load removal (e.g., radiant cooling) High airflows = high fan energy & reduced load split (plume factor) Diffuser size limits capacity for high airflows

Stratification change with airflow rate Test results for airflow rate with constant load, swirl diffusers, interior zone Height, ft 11 10 9 8 7 6 5 4 3 2 1.0 cfm/sq. ft 0.6 cfm/sq. ft 0.3 cfm/sq. ft ASHRAE Std.55-2004 5 F T 1 0 Still satisfies vertical temperature difference (5 F) with 40% less air 69 70 71 72 73 74 75 76 77 78 79 80 81 82 Room Temperature, F

Cooling Fan energy Fan power reduction for lower static Essential to provide for reduced static pressure set point: e.g., 0.5-1.0 iwc less than OH for some UFAD designs Depends on reduction of ductwork plus air-side load fraction Allow for static pressure reset with load in VAV systems 80% % Fan Power Savings (Relative to Overhead VAV System) 60% 40% 20% Underfloor VAV Low Volume: 90% CFM, 75% FSP Underfloor VAV High Volume: 120% CFM 75% FSP 0% -20% 50% 60% 70% 80% 90% 100% % of Design Load

Cooling - Zone equipment Zone equipment needs to be adequately represented Series fan-powered-boxes Perimeter heating by FPB drawing from occupied space vs. plenum Cooling-only boxes for modulating diffuser systems Fan coils or radiant systems for TDV Return Air Plenum No U/A diffusers in perimeter zones Raised Access Floor Return Air Grille T Heating Coil Glazing Fan Coil w/ ECM motor Flex Duct

Cooling Economizer Not accounting for thermal decay in UFAD plenum will lead to overestimate of economizer savings Savings for Oakland with AHU supply air temperature (SAT) : 65 F = 83% 60 F = 31% Must account for thermal decay in plenum affect on SAT Decay depends on airflow and plenum configuration Economizer operation also limited in some radiant applications High-capacity panel system +DOAS dehumidification may limit economizer hours in off-design conditions Hours 300 250 200 150 100 50 0 33 37 39 41 43 45 47 San Francisco Outdoor Temperature Distribution (Dry Bulb temperatures betweeen 8am and 8pm) 49 51 53 55 100% Economizer Load Reduction? 2217 Hours 54 Hours 57 59 61 63 65 67 69 71 73 75 Outdoor Dry Bulb Temperature [F]?? 77 79 81 83 85 87 89 91 93 95

Heating TDV Separate heating system typically required Baseboards, radiant, or fan coils in perimeter Fan coils ok for interior, but switch to mixed Becomes well-mixed space in heating operation UFAD Need heating options for heating-only fan coils or baseboards Becomes well-mixed space in heating operation

Load-Split Plume Factors Proliferation In addition to Cooling, heating, and deadband Case UFAD Core zone, high-throw vs. low-throw diffuser % load to Space UFAD Perimeter, blinds open, high-throw vs. low-throw diffuser UFAD Perimeter, blinds closed UFAD Atrium (two-or-more-story, fully glazed atrium) UFAD with Radiant chilled ceiling (high- T panels vs. low- T overhead slab) TDV Core zone TDV Perimeter (low loads or loads reduced by radiant cooling, or similar) TDV Atrium (two-story fully glazed atrium with chilled slab) 10 9 3.0 2.7 10 9 Peak solar load Height [ft] 8 7 6 5 4 2.4 2.1 1.8 1.5 1.2 Height [m] Height [ft] 8 7 6 5 4 Blinds open, 8 Linear bar grilles, vanes at 90 1.6 cfm/sf Blinds closed, 8 Linear bar grilles, vanes at 90 1.0 cfm/sf 3 0.9 3 2 0.6 2 1 0.3 1 0 0.0 68 70 72 74 76 78 80 Room Temperature [ F] INT_8-2 INT_8-3 INT_8-4 INT_8-5 INT_8-6 INT_8-7 0 68 70 72 74 76 78 80 82 84 Room Temperature [ F]

Typical Distribution of Room Cooling Load Heat transfer into SA plenum: UFAD with hung ceiling RA plenum Heat gain into space 100% (internal and perimeter loads) Through slab 24% Through raised floor (mostly radiation from ceiling) 11% Airside Extraction 65% Total into supply plenum ~35% (+/- 5% per airflow rate) Removed from airside (still seen as coil load to maintain SAT at diffuser)

Potential for thermal decay in UFAD plenum Initial thermal conditions in UFAD plenum (before implementing spread diffusers on stub ducts) --- Flack+Kurtz CFD modeling

Stacked thermal zones simulation approach A commonly used and often recommended approach to modeling stratified environments with geometrically based thermal model + linked inter-zonal bulk airflow model Atria, UFAD, TDV, radiant cooling (radiant designs where downsized airside system leads to thermal stratification)

Stacked thermal zones simulation approach Separate RA plenum (if included) and SA plenum zone for UFAD is straightforward Zones linked only by holes or air barriers can be used to represent occupied and stratified sub-zones Loads with appropriate radiant and convective splits can be places in relevant sub-zones Added sub-division of stratified zone improves representation of thermal stratification, but exacerbates fundamental limitation

Stacked thermal zones simulation approach 76 76 74 74 Temperature ( F) 72 70 68 Temperature ( F) 72 70 68 Stacked zones do permit approximation of stratified environments using linked bulk airflow models, however 66 66 64 64 62 62 60 00:00 06:00 60 07 08 09 10 Air temperature: 0 Return Air Plenum (ufad - energy pw 3 strat z + occ bot zx - with stub duct.aps) Air temperature: 3 lower Stratified zone (ufad - energy pw 3 strat z + occ bot zx - with stub duct.aps) Air temperature: 6 UFAD Plenum (ufad - energy pw 3 strat z + occ bot zx - with stub duct.aps) Air temperature: 0 Return Air Plenum (ufad - energy pw 3 strat z + occ bot z - with stub duct.aps) Air temperature: 3 lower Stratified zone (ufad - energy pw 3 strat z + occ bot z - with stub duct.aps) Air temperature: 6 UFAD Plenum (ufad - energy pw 3 strat z + occ bot z - with stub duct.aps) Air temperature: 7 Stub Duct to UFAD Pln (ufad - energy pw 3 strat z + occ bot z - with stub duct.aps)

Direct-bean solar and LW IR reaching floor Simple shoe-box model used to test effect of stacked zones in geometrically based simulation tools (such as EnergyPlus, iesve, etc.) While there is full accounting for solar radiation and radiant heat transfer between surfaces in a single zone, stacked zones present view-factor issues

Limitations of stacked thermal zones approach Floor Surface Temperature Floor Surface Temperature and Incident and Incident Solar Solar Flux FluxReaching the Floor relative to single zone model 2 zones, 4 spaces Solar Flux temp Temperature (F) solar flux (Btu/hr-ft^2) 1 zone, 4 spaces 2 zones, 2 spaces 1 zone, 2 spaces 1 zone, 1 space 0% 20% 40% 60% 80% 100% 120%

Possible simulation tool solutions Appropriate dynamic simulation of stratified environments, or those with significant buoyancy-driven thermal convection, where radiant heat transfer is also significant, may be accomplished by: Adding capability for appropriate accounting of solar gains and radiant exchange between surfaces across inter-zonal adjacencies so that inter-zonal airflow models can be employed (i.e., across sub zones) OR Including appropriate multi-node airflow models applicable within a single zone (wherein radiant exchange is properly accounted for by the geometrically based thermal model of that zone) Must either be adaptable to or adjustable for various configurations, or provided in versions for each (e.g., for radiant cooling, DV, UFAD, atria, etc. and various combinations thereof). EnergyPlus UFAD and DV airflow models point to potential paths, but there is much work yet to be done here.