CFP-2401B/CFP-2402B. Fire Alarm Control Panel. Installation, Maintenance and Operating Instruction Manual.

Similar documents
CMP-2401B/CMP-2402B. Fire Alarm Control Panel. Installation, Maintenance and Operating Instruction Manual

Instruction Manual. CMP-12/24 Fire Alarm Control Panel. 12 Clintonville Road, Northford, CT DOCUMENT /11/96 REV: D1

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

FCPS-24F/FCPS-24FE. Field Charger/Power Supply D P/N 50079:D ECN Installation, Operation and Application Manual

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

The RPT-485W/RPT-485WF

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual

Conventional Fire Alarm Control Panel

SILENT KNIGHT. Model SK-2/E & SK-4/E. Installation and Operations Manual. Fire Alarm Control Panel. Part Number Rev. A ECN /08/05

The System 5000 Operating Manual

HP101U Conventional Fire Alarm Control Panel Installation And Operation Manual

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

FCPS-24/FCPS-24E. Field Charger/Power Supply. Installation, Operation and Application Manual.

Fire Alarm Control Panels MS-2 & MS-4 MS-2E & MS-4E. Instruction Manual. Document /6/2014 Rev: G3 P/N 51512:G3 ECN

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

The MS-4412B/MS-4424B(E) FIRE ALARM CONTROL PANELS

Fire Alarm Control Panel MS-2410B & MS-2410BE

CFP-2410B. Programming, Installation, Maintenance and Operating Manual. Conventional Fire Alarm Control Panel.

PN: 51883:D ECN Field Charger/Power Supply FCPS-24FS6 FCPS-24FS8. Document # /14/05 Revision: D

TECHNICAL DATA OBSOLETE

4100U City and Relay Cards Installation Instructions

The MS-4424 FIRE ALARM CONTROL PANEL

Annunciator Modules. for Fire Lite Fire Alarm Control Panels. Document # /30/95 Revision:

PN:51264:A2 ECN Remote Fire Annunciator FDU-80. Document /14/00 Rev: A.

ECC-50DA/E ECC-125DA/E ECC-50BDA/E. Distributed Audio Amplifiers. Installation Manual C. Document LS FL-E 1/30/2014 Rev:

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

30.45 Electric Release PDRP-2001

Field Charger/Power Supply FCPS-24S6 FCPS-24S8. Document # /06/03 Revision: C1 PN: 51977:C1 ECN

CHG-120 Battery Charger Instruction Manual. Document /06/2002 Rev: B1 PN 50641: B1 ECN

Booster Power Supply Manual

AFP-100 Intelligent Fire Panel

PN: 53049:A1 ECN Agent Release Control System MRP-2002 MRP-2002E. Document # /01/08 Revision: A1

MR-2602 Two Zone Fire Alarm Control Panel

The MC-1. Master Clock System

Supplement to the AM2020/AFP1010 Voice Alarm Multiplex Manual Number 15889, Revision F1, dated 12/11/97

EXTINGUISHING AGENT RELEASE MODULE

AGENT RELEASE CONTROL PANEL AC POWER ZONE 1 SYSTEM ALARM RELEASE ZONE 2 SUPERVISORY TROUBLE CIRCUIT TROUBLE ABORT SILENCED POWER TROUBLE

PN: 51604:A ECN Voice Evacuation Control Panel FIRE COMMAND 25/50X & FIRE COMMAND 25/50XE. Document # /17/02 Rev.

HPFF8(E)/HPFF8CM(E) NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

MS-5012 Control Communicator

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

Lamp Driver Module LDM-32F

PRE-ACTION/DELUGE CONTROL PANEL MRP-2001 MRP-2001E MRP-2001C. Instruction Manual. Document /15/2010 Rev: D P/N 53040:D ECN

INSTALLATION INSTRUCTIONS MODEL PA-250 AND PA-500 BOOSTER AMPLIFIER

Digital Alarm Communicator/Transmitter. Document # /07/00 Rev. P/N 50921:C ECN

12 Clintonville Road, Northford, CT Technical Manual MS-9200 DOCUMENT # /28/97 REV: B P/N 50428:B1 ECN

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel

Installation Guide for models:

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

/9308 External Battery Chargers Installation Instructions

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

ECC-50/100C. Emergency Command Center

Digital Alarm Communicator/Transmitter 411UD. Document # /07/00 Rev. P/N 50759:C ECN

Document /2/2011 Rev: D1 P/N 53192:D1 ECN

Electric Release Panel Wiring Tips

PN: 52626:A1 ECN Fire Alarm Control Panels MS-5UD & MS-10UD Series. Document # /11/07 Revision: A1

Specification/ Data Sheet

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

FA-102T. Fire Alarm Control Panel. Installation and Operation Manual. LT-514 Rev.7 December 2009 A.C. ON SIGNAL SILENCED

The ACM-8R Annunciator Control Module

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

Remote NAC Power Supply D7038

Installation, Operating and Maintenance Manual

Installation Guide for models:

CZ-6A Six Zone Interface Module

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

The PDRP-1002/PDRP-1002E Agent Release Control System

RE 102 RE Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

December Scorpio. Fire Control Panel. Installation, Operation & Maintenance Manual. P/N UL Listing File No. S2422.

Model 17A00 Expansion Enclosure

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

Series. Access Power Controllers. Installation Guide

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

RELEASE DEVICE CONTROLS

The ADT SLC Signaling Line Circuit Manual

Model SK Installation and Operations Manual. Fire Control / Communicator. Document Rev: P P/N :P ECN:

ANNUNCIATOR FIXED MODULE

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

Fire Alarm Control Panels. MS-5UD Series MS-10UD Series. Manual. Document /7/2014 Rev: C4 P/N 52626:C4 ECN

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Doc. No Part No Rev. U * T*

RE 2554 RE Automatic Fire Alarm Control Panel (Protective premises Unit) Installation, Commissioning & Operating User Manual

RAM-208. Remote Multiplex Annunciator Panel. Wiring & Installation Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

PSN-1000 & PSN 1000(E) Installation Manual

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

SC-6 Six Supervised Control Module

Beacon 800 Gas Monitor Operator s Manual

Transcription:

24 Viceroy Road Concord, Ontario L4K2L9 Phone (905) 660-7210 FAX (905) 660-7204 CFP-2401B/CFP-2402B Fire Alarm Control Panel Installation, Maintenance and Operating Instruction Manual Document #51100 11/5/98 Rev. P/N 51100:A ECN 98-489A 1998 Notifier

Installation Precautions - Adherence to the following will aid in problem-free installation with long-term relia WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood. CAUTION - System Reacceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72-1993 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49 O C/ 32-120 O F and at a relative humidity of 85% RH (non-condensing) at 30 O C/86 O F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal room temperature of 15-27 O C/ 60-80 O F. Verify that wire sizes are adequate for all initiating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Fire Alarm System Limitations An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices and a fire alarm control with remote notification capability can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors - both ionization and photoelectric types, have sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling and /or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. FCC Warning Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer and printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation. While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplies with each device. System inspection and testing should be scheduled monthly or as required by National and/or local fire codes. Adequate written records of all inspections should be kept. WARNING: This equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications, It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense. Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.

Table of Contents CHAPTER 1: Product Description...7 1.1: Product Features...7 FIGURE 1-1: CFP-2401B/CFP-2402B...8 1.2: Specifications...9 1.3: Controls, Indicators and Operation...10 1.3.1: Front Panel Slide Switches...10 FIGURE 1-2: CFP-2401B/CFP-2402B Control Switches...10 1.3.2: LED Indicators...11 FIGURE 1-3: LED Indicators (CFP-2402B Illustrated)...11 1.3.3: Local Sounder...12 1.3.4: Normal Standby Operation...12 1.3.5: Alarm Condition...12 1.3.6: Trouble Condition...12 1.4: Circuits...13 1.5: Components...13 1.6: Optional Modules and Accessories...14 CHAPTER 2: Installation...15 2.1: Mounting Options...15 FIGURE 2-1: CFP-2401B/CFP-2402B Mounting...15 2.2: Backbox Mounting...15 FIGURE 2-2: Cabinet Dimensions and Knockout Locations...16 FIGURE 2-3: FACP Backbox...17 2.3: Operating Power...18 FIGURE 2-4: Operating Power Connections...18 2.4: Input Circuits...19 FIGURE 2-5: CFP-2402B Style B Initiating Device Circuit Connections...19 2.5: Output Circuits...20 FIGURE 2-6: Auxiliary Power Connection...20 FIGURE 2-7: Notification Appliance Circuit Connections...20 FIGURE 2-8: Relay Terminals...21 2.6: UL Power-limited Wiring Requirements...21 FIGURE 2-9: Typical Wiring Diagram for UL Power-limited Requirements...21 2.7: Installation of Optional Module...22 2.7.1: 4XTM Transmitter Module...22 FIGURE 2-10: 4XTM Module Connections...22 2.7.2: RTB - Remote Trouble Buzzer...23 FIGURE 2-11: RTB Remote Trouble Buzzer Connection...23 CHAPTER 3: Programming Options...24 3.1: Earth Ground Fault Detection...24 FIGURE 3-1: Ground Fault Detection Circuit...24 3.2: Optional 4XTM Transmitter Module Placement Supervision...24 FIGURE 3-2: 4XTM Module Placement Supervision...24 CHAPTER 4: Periodic Testing and Maintenance...25 CHAPTER 5: Battery Calculations...26 TABLE 5-1: Battery Calculations...26 5.1: The Main Power Supply...27 TABLE 5-2: Load in Standby...27 TABLE 5-3: Load in Alarm...28 Document 51100 Rev. A 11/5/98 P/N: 51100:A 3

Notes 4 Document #51100 Rev.A 11/5/98 P/N 51100:A

This control panel has been designed to comply with standards set forth by the following regulatory agencies: Underwriters Laboratories Standard UL 864 NFPA 72 National Fire Alarm Code CAN/ULC - S527M Standard for Control Units for Fire Alarm Systems Before proceeding, the installer should be familiar with the following documents. NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards: NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module). Underwriters Laboratories Canada Documents: CAN/ULC - S524M Standard for Installation of Fire Alarm Systems CAN/ULC - S527-M87 Standard for Control Units for Fire Alarm Systems Other: Applicable Local and State Building Codes C22.1 Canadian Electrical Code, Part I C22.2 No. 0, General Requirements - Canadian Electrical Code, Part II C22.2 No. 0.4, Bonding and Grounding of Electrical Equipment (Protective Grounding) - Canadian C282, Emergency Electrical Power Supply for Buildings - Canadian Requirements of the Local Authority Having Jurisdiction (LAHJ) Notifier Documents Notifier Device Compatibility Document Document #15378 Document #51100 Rev. A 11/5/98 P/N 51100:A 5

CFP-2401B/CFP-2402B Main Circuit Board + + + Connections to Remote Trouble Buzzer CFP-2402B Only GND AC TBL BUZ +24V REG RES ALARM NC C NO TROUBLE NC C NO SIGNAL OUTPUT + - INITIAT ZONE 1 + - INITIAT ZONE 2 + - TB1 TB2 GND AC TBL BUZ +24V REG RES NC ALARM C NO TROUBLE NC C NO SIGNAL OUTPUT + - IN ITIAT ZONE 1 + - IN ITIAT ZONE 2 + - TB1 TB2 SW1 SYSTEM RESET System Reset SW2 SW3 SIG SILENCE ZONE 1 SIG SILENCE ZONE 2 Signal Silence Zone 1 Signal Silence Zone 2 (CFP-2402B Only) Transformer J5 CUT IF 4X OPTION BOARD IS PRESENT SW4 TBL SILENCE Trouble Silence R14 NEUTRAL F2 J4 CUT TO DISABLE EARTH FAULT R72 Cut if Option Board is Present R14 F2 AC Power Fuse 2 Amp 3AG Slow Blow EARTH HOT TB3 J3 BATTERY J1 J4 Cut to Disable Earth Fault R72 NEUTRAL EARTH J3 Battery (7.0 AH, 12VDC) Option Module Connectors 2402LAYO.CDR HOT TB3 J1 6 Document #51100 Rev.A 11/5/98 P/N 51100:A

Product Description CHAPTER 1 Product Description The CFP-2401B is a one zone FACP (Fire Alarm Control Panel) and the CFP-2402B is a two zone FACP. This manual will use the term FACP to refer to both the CFP-2401B and CFP-2402B where features are identical. These control panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings. The FACPs use conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices and other normally-open contact devices. Outputs include one NAC (Notification Appliance Circuit) and 24 volt resettable power. The FACP also supervises all wiring, AC voltage and battery level. Activation of a compatible smoke detector or any normally open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED and sound the piezo at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate a supplementary control function. 1.1 Product Features Style B (Class B) Initiating Device Circuit (IDC) CFP-2401B - one IDC CFP-2402B - two IDCs One NFPA Style Y (Class B) Notification Appliance Circuit (NAC) Form-C Alarm Relay Form-C Trouble Relay Control switches Reset Trouble Silence Signal Silence - Zone One Signal Silence - Zone Two (CFP-2402B only) LED Indicators AC Power Zone Alarm and Trouble Bell Trouble Option Module Trouble System Trouble Zone Silence Ground Fault Battery Trouble Piezo Sounder for alarm and trouble signal Dress Panel coverplate 24 volt operation Small backbox size Low AC voltage sense Silence Inhibit Notification Appliance Circuit Automatic Battery Float Charger Battery Deep Discharge Protection Optional Remote Trouble Buzzer Document #51100 Rev. A 11/5/98 P/N 51100:A 7

Product Features FIGURE 1-1:CFP-2401B/CFP-2402B +24 Volt Resettable Power Trouble Relay Input Zones (2 on CFP-2402B only) Remote Trouble Buzzer Alarm Relay Notification Appliance Circuit Cut if Option Module is Installed Transformer GND AC TBLBUZ+24V REG RES ALARM TROUBLE SIGNAL IN IT IAT IN IT IAT OUTPUTZONE 1 ZONE 2 NC C NO NC C NO - + - + - + System Reset * TB1 TB2 SW1 SW2 SW3 SIG SILENCE SYSTEM RESET ZONE 1 SIG SILENCE ZONE 2 Signal Silence Zone 1* Signal Silence Zone 2 * (CFP- 2402B) J5 CAUTION! HIGH VOLTAG E F2 R14 CUT IF 4X OPTION BOARD IS PRESENT J4 SW4 CUT TO DISABLE EARTH FAULT TBL SILE NCE Trouble Silence * Cut to Disable Earth Fault NEUTRALEARTH HOT R72 Option Module Connectors TB3 J3 BATTERY J1 2401INBX.CDR Holds up to two 7 AH Batteries * Note that all switches are illustrated in the normal position. 8 Document #51100 Rev.A 11/5/98 P/N 51100:A

Specifications 1.2 Specifications AC Power - TB3 120 VAC, 60 Hz, 0.5 amps Fuse F2-2 Amp, 3AG Slow Blow Wire size: minimum #14 AWG (2.0 mm 2 ) with 600V insulation Battery (lead acid only) - J3 Maximum Charging Circuit: Normal Flat Charge - 27.6V @ 0.8 amp Maximum Charger Capacity: 7.0 Amp Hour battery which can be housed in the FACP cabinet Battery Deep Discharge Protection: In order to protect the battery, the deep discharge circuit disconnects the battery from the FACP when the battery voltage drops below 15 VDC. The FACP will restart and the battery will begin recharging only after primary AC power is restored. Initiating Device Circuit(s) - TB2 Zone 1 - TB2 Terminals Initiating Zone 1 (-) & (+) Zone 2 - TB2 Terminals Initiating Zone 2 (-) & (+) (CFP-2402B only) Power-limited circuitry Operation: NFPA Style B (Class B) Normal Operating Voltage: Nominal 24 VDC, ripple 2.0 V P-P Alarm Current: 20 ma minimum Short Circuit Current: 40 ma maximum Maximum Loop Resistance: 100 ohms per side (200 ohms total zone resistance) End-of-Line Resistor: 3.9K ohm, ½ watt Detector Loop Current is sufficient to ensure operation of two alarmed detectors per zone Standby Current: 9 ma (includes ELR and 3 ma maximum detector current) Smoke Detector Identifier A Refer to Notifier Device Compatibility Document for listed compatible devices Notification Appliance Circuit - TB2, Terminals Signal Output (-) and Signal Output (+) Operation: NFPA Style Y (Class B) Power-limited circuitry Normal Operating Voltage: Nominal 24 VDC Current Limit: via PTC Maximum signaling current: 1.25 amps End-of-Line Resistor: 3.9K ohm, ½ watt Refer to Notifier Device Compatibility Document for listed compatible devices Two Form-C Relays - Terminals Alarm (NC, C, NO) and Trouble (NC, C, NO) Relay contact ratings: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive) Resettable Power - TB1, Terminals Ground and +24V Resettable Operating Voltage: Nominal 24 VDC Up to 85 ma is available for powering 4-wire smoke detectors Power-limited circuitry Refer to Notifier Device Compatibility Document for compatible listed devices Document #51100 Rev. A 11/5/98 P/N 51100:A 9

Controls, Indicators and Operation 1.3 Controls, Indicators and Operation 1.3.1 Front Panel Slide Switches FIGURE 1-2:CFP-2401B/CFP-2402B Control Switches SIGNAL INIT IAT INIT IAT OUTPUT ZONE 1 ZONE 2 + + + - - - TB2 SW1 SYSTEM RESET System Reset SW2 SIG SILENCE ZONE 1 Signal Silence Zone 1 SW3 SIG SILENCE ZONE 2 Signal Silence Zone 2 (CFP-2402B only) CUT IF 4X OPTION BOARD IS PRESENT SW4 TBL SILENCE Trouble Silence R14 2402SWTC.CDR All switches are illustrated in their normal position. The function of each switch is listed below. System Reset The function of this nonlatching switch is: 1. to reset the FACP and the smoke detectors provided the alarm condition has been cleared and 60 seconds has elapsed since the first alarm 2. LED test Signal Silence - Zone 1 Placing the switch in the Silence position will silence the Notification Appliance Circuit if 60 seconds has elapsed since the first alarm. A trouble condition is indicated while the switch is in the Silence position. If an alarm occurs on the silenced zone, the alarm LED will indicate the alarm condition and the alarm relay will transfer. Signal Silence - Zone 2 (CFP-2402B only) Placing the switch in the Silence position will silence the Notification Appliance Circuit if 60 seconds has elapsed since the first alarm. A trouble condition is indicated while the switch is in the Silence position. If an alarm occurs on the silenced zone, the alarm LED will indicate the alarm condition and the alarm relay will transfer. Trouble Silence This latching, two-position switch, will silence the piezo sounder. The trouble LED will continue to indicate a trouble condition. An intermittent tone will sound when the trouble is cleared to indicate that this switch should be returned to its normal position. 10 Document #51100 Rev.A 11/5/98 P/N 51100:A

Controls, Indicators and Operation 1.3.2 LED Indicators FIGURE 1-3:LED Indicators (CFP-2402B Illustrated) 2401DISP.CDR The LED indicators for the CFP-2401B/CFP-2402B are labeled in English and French. The purpose of each indicator is listed below: AC Power (Alimentation) - green LED The green LED is on when the FACP is operating from normal AC power. The LED turns off to indicate a below normal AC voltage (brownout) or complete loss of AC power. The System Trouble LED will also turn on. Option Trouble (Trouble Option) - yellow LED This yellow LED turns on to indicate the removal of the optional supervised 4XTM Transmitter Module or a trouble with the module. Zone 1 Alarm (Alarme Zone 1) - red LED This red LED turns on to indicate an alarm condition, even if the Zone Silence switch is in the Silence position. Zone 2 Alarm (Alarme Zone 2) - red LED (CFP-2402B only) This red LED turns on to indicate an alarm condition, even if the Zone Silence switch is in the Silence position. Zone 1 Trouble (Trouble Zone 1) - yellow LED This yellow LED turns on to indicate a trouble condition, such as an open in the field wiring, on the IDC (Initiating Device Circuit) zone 1. Zone 2 Trouble (Trouble Zone 2) - yellow LED (CFP-2402B only) This yellow LED turns on to indicate a trouble condition, such as an open in the field wiring on the IDC (Initiating Device Circuit) zone 2. Zone Silence (M.S. Silence Zone) - yellow LED This yellow LED turns on to indicate that the Notification Appliance Circuit has been silenced. Bell Trouble (Trouble Cloche) - yellow LED This yellow LED turns on to indicate a trouble condition, such as an open or short in the field wiring, on the Notification Appliance Circuit. Battery Trouble (Trouble Piles) - yellow LED This yellow LED turns on to indicate a low battery/no battery condition or battery charger fault. Document #51100 Rev. A 11/5/98 P/N 51100:A 11

Controls, Indicators and Operation System Trouble (Trouble Systeme) - yellow LED This yellow LED turns on for all faults or abnormal operating conditions. Ground Fault (Faute M.A.L.T.) - yellow LED This yellow LED turns on to indicate a ground fault condition (low impedance to ground) on any field wiring or battery connections. 1.3.3 Local Sounder A piezo sounder provides distinct signals for alarm and trouble conditions: Alarm - steady Trouble - pulse 1.3.4 Normal Standby Operation Normal standby operation indicates that there are no alarms or trouble conditions present on the FACP and that the IDC zone(s) have not been Silenced. In Normal Operation: All switches must be in their normal positions. Refer to Figure 1-1, CFP-2401B/CFP-2402B, on page 8. The green AC power LED is on steady The red alarm LED(s) are off All yellow trouble LEDs are off 1.3.5 Alarm Condition Alarm condition indicates that an IDC (input) zone has detected an alarm (active smoke detector, pull station activation, etc.). In Alarm Operation: The zone alarm LED will turn on The notification appliances are activated The optional 4XTM Transmitter Module is activated Piezo sounder turns on steady The alarm relay will transfer 1.3.6 Trouble Condition Trouble condition indicates that one or more faults have been detected by the FACP. Contact the local service representative for immediate correction of the fault since FACP operation may be impaired. A Trouble condition will cause the following: The yellow System Trouble LED will light steady Additional trouble LEDs may turn on The piezo sounder will pulse 12 Document #51100 Rev.A 11/5/98 P/N 51100:A

GND AC TBL BUZ +24V ALARM TROUBLE SIG NAL IN IT IA T IN IT IA T REG OUTPUT ZONE 1 ZONE 2 RES NC NO NC NO + + + C U T IF 4X OPTION BO ARD IS PRESENT BATTE RY CUT TO DISABLE EARTH FAULT Circuits 1.4 Circuits Input Circuits The CFP-2401B has one IDC (Initiating Device Circuit) and the CFP-2402B has two IDCs. Input circuit(s) provide Style B (Class B) configuration and accept 2-wire smoke detectors and normally-open contact devices. Output Circuits 24 Volt Resettable Power Output 85 ma 24 Volt Battery Charger (up to two 7 AH batteries) Notification Appliance Circuit One Style Y (Class B) Notification Appliance Circuit @ 1.25 amps maximum Relays Two dry Form-C relays for system alarm and system trouble are provided standard. Contacts are rated 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive). Battery Charger The battery charger will charge up to two 7 AH batteries. The FACP cabinet holds a maximum of two 7 AH batteries. 1.5 Components Main Circuit Board The main circuit board contains power supply, alarm and trouble relays, control switches, LED indicators, option jumpers, wiring interface connectors and other primary components. The option module plugs in and is mounted to the main circuit board. The main circuit board is delivered premounted in the cabinet. NEUTR AL EARTH HOT TB1 J5 F2 C C - - - TB2 R14 J4 SW1 SW2 SW3 SW4 R72 SYSTEM RESET SIG SILENCE ZONE 1 SIG SILENCE ZONE 2 T BL SILENCE 2402BORD.CDR Cabinet The cabinet measures 14.5" (36.83 cm) high X 12.5" (31.75 cm) wide X 2.875" (7.303 cm) deep and provides space for two batteries (up to 7.0 Amp Hours each). Also supplied is a blue dress panel which mounts inside the cabinet. Dress Panel A blue dress panel, which is required for Canadian installations, is provided with the cabinet. The dress panel restricts access to the system wiring while allowing access to the control switches. Transformer Assembly One transformer is provided standard with the panel. The transformer plugs into connector J5 on the main circuit board. TB3 J3 J1 CF2401DR.CDR DP-2401.CDR Batteries The cabinet provides space for two 7 Amp Hour batteries which must be ordered separately. 2401XFOR.CDR 2401BATT.CDR Document #51100 Rev. A 11/5/98 P/N 51100:A 13

Optional Modules and Accessories 1.6 Optional Modules and Accessories 4XTM Transmitter Module The 4XTM Transmitter Module provides supervised outputs for local energy municipal box and alarm and trouble reverse polarity transmitters. It includes a disable switch and disable trouble LED on the module. A jumper option on the module allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. Remote Trouble Buzzer One Remote Trouble Buzzer can be connected to the FACP using four wires. The remote unit includes an AC LED, System Trouble LED and piezo sounder which are controlled by the control panel. It mounts to a singlegang electrical box. 14 Document #51100 Rev.A 11/5/98 P/N 51100:A

Installation CHAPTER 2 Installation 2.1 Mounting Options FIGURE 2-1:CFP-2401B/CFP-2402B Mounting The cabinet may be either semi-flush or surface mounted. The door is removable during the installation period by opening and lifting the door off the hinges. The cabinet mounts using two key slots and two additional 0.250 (0.635 cm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom. Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the required conductors into the box. Note that there are no knockouts on the left (hinged) side of the cabinet. All wiring should be in accordance with the National and/or Local codes for fire alarm systems. CF2401DR.CDR 2.2 Backbox Mounting 1. Open the door. 2. Remove the main PC board assembly by unscrewing the four screws in the corners of the board. Set the board aside in a safe, clean place. Avoid static discharge which may damage the board. 3. Mark and predrill holes for the top two keyhole mounting bolts using the dimensions illustrated in Figure 2-2. 4. Install two upper fasteners in the wall with the screw heads protruding. 5. Using the upper keyholes, mount the backbox over the two screws. 6. Mark and drill the lower two holes. 7. Mount the backbox, install the remaining fasteners and tighten. 8. When the location is dry and free of construction dust, reinstall the main PC board. Document #51100 Rev. A 11/5/98 P/N 51100:A 15

Backbox Mounting Draw wires through the respective knockout locations. FIGURE 2-2:Cabinet Dimensions and Knockout Locations Top 10.12 (25.75 cm) 8.12 (20.63 cm) 6.12 (15.55 cm) 4.12 (10.47 cm) 1.125 (2.858 cm) 1.43 (3.63 cm) 2.875 (7.303 cm) (7.62 cm) 3.0 12.5 (31.75 cm) 6.5 (16.51 cm) 0.875 (2.223 cm) (3.63 cm) 1.43 1.1 (2.794 cm) 1.50 (3.81 cm) 1.75 (4.45 cm) 16.625" (42.228 cm) 12.625" (32.068 cm) 14.625 (37.148 cm) 17.625" (44.768 cm) 14.5 (36.83 cm) 1.75 (4.45 cm) 3.50 (8.89 cm) TR-3-R Trim Ring Right Side 5024JRBB.CDR Bottom 16 Document #51100 Rev.A 11/5/98 P/N 51100:A

Backbox Mounting FIGURE 2-3:FACP Backbox To p Depth=2.875" (7.303 cm) Door=12.714" (32.294 cm) Backbox=12.5 (31.75 cm) Depth=3" (7.62 cm) Door=14.714" (37.374 cm) Backbox=14.5" (36.83 cm) Bottom Right side 2401CABB.CDR Document #51100 Rev. A 11/5/98 P/N 51100:A 17

Operating Power! 2.3 Operating Power WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting modules, interconnecting cables or wiring while this unit is energized. Primary Power Source (AC) and Earth Ground Connections AC power connections are made inside the control panel cabinet. The AC input circuit is limited by fuse F2 (2 amp, 3AG Slow Blow). The primary power source for the FACP is 120 VAC, 60 Hz, 0.5 amps. Run a pair of wires (with ground conductor) from the protected premises main breaker box to TB3 of the main circuit board. As per the National and Canadian Electric Code, use 14 AWG (2.00 mm 2, 1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other equipment may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect devices. A separate Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm 2 )] to the grounding stud on the backbox. Do not use conduit for the Earth Ground connection since this does not provide reliable protection.! Secondary Power Source (Batteries) Observe polarity when connecting the battery. Connect the battery cable to J3 on the main circuit board using the plug-in connector and cable provided. The battery charger is current-limited and capable of recharging sealed lead acid type batteries. The charger shuts off when the system is in alarm. See Battery Calculations for calculation of the correct battery rating. WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention. FIGURE 2-4:Operating Power Connections Grounding Stud GND AC TBLBUZ+24V REG RES ALARM TROUBLE SIGNAL IN IT IAT IN IT IAT 2 NC NO C NO NC C - - + - OUTPUTZONE 1 ZONE + + TB1 TB2 SW1 SYSTEM RESET SW2 SIG SILENCE ZONE 1 SW3 SIG SILENCE ZONE 2 Earth J5 CAUTION! HIGH VOLTAGE F2 R14 CU T IF 4X OPTION BOARD IS PRESENT SW4 T BL SILE NCE J4 CUT TO DISABLE EARTH FA ULT NEUTRALEARTH HOT R72 TB3 J3 BATTERY J1 AC Hot Neutral 2402ACBX.CDR 18 Document #51100 Rev.A 11/5/98 P/N 51100:A

Input Circuits 2.4 Input Circuits The CFP-2401B has one IDC (Initiating Device Circuit) and the CFP-2402B has two IDCs. The maximum total loop resistance limit for each input circuit is 200 ohms. The field wiring is supervised for opens, shorts and ground faults. All conditions are visually and audibly annunciated. The zone(s) is a Style B (Class B) Initiating Device Circuit designed to accept any normally-open contact devices and conventional 2-wire or 4-wire, 24 VDC smoke detectors. Resettable power is provided via TB1 Terminals 24V Resettable (+) and Ground (-). Remove the End-of Line resistor from the FACP and install it on the IDC wiring after the last device in the circuit. Refer to the Notifier Device Compatibility Document for a list of compatible smoke detectors and the maximum number of 2-wire detectors per circuit. It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on the same zone. FIGURE 2-5:CFP-2402B Style B Initiating Device Circuit Connections Style B (Class B) Initiating Device Circuit (supervised and power-limited). 3.9K ohm, ½ watt UL listed compatible 2-wire smoke detector Manual Pull Station Heat Detector Dummy load unused circuit TB1 GND AC TBL BUZ NC C NO NC C NO + + + REMOTE +24 VDC RESET + - - - ALARM TROUBLE SIGNAL INITIATING OUTPUT ZONE 1 INITIATING ZONE 2 TB2 2402IDC.CDR Document #51100 Rev. A 11/5/98 P/N 51100:A 19

Output Circuits 2.5 Output Circuits DC Power Output Connections FIGURE 2-6:Auxiliary Power Connection 4-Wire Smoke Detector Power (85 ma) 24 VDC filtered, resettable power for 4-wire smoke detectors can be obtained from TB1 Terminals 24V Resettable (+) and Ground (-) TB1 - - - GND AC TBL BUZ + NC C NO NC C NO + + + REMOTE +24 VDC RESET ALARM TROUBLE SIGNAL OUTPUT INITIATING ZONE 1 INITIATING ZONE 2 TB2 2402TERM.CDR Notification Appliance Circuit The FACP provides one supervised Notification Appliance Circuit as Style Y (Class B). The circuit is capable of 1.25 amps of current. Observe polarity when connecting polarized devices to the NAC. Remove the End-of-Line resistor from the FACP and install it on the Notification Appliance Circuit wiring after the last device. Refer to the Notifier Device Compatibility Document for a listing of compatible notification appliances. FIGURE 2-7:Notification Appliance Circuit Connections Style Y (Class B) Notification Appliance Circuit (supervised). 3.9 K ohm, ½ watt Polarized Bell + Note: Notification Appliance polarities shown in alarm state Polarized Horn + Polarized Horn + Note: Terminal polarity shown in alarm state TB1 GND AC TBL BUZ + NC C NO NC C NO - + - + - + REMOTE +24 VDC RESET ALARM TROUBLE SIGNAL OUTPUT INITIATING ZONE1 INITIATING ZONE2 TB2 2402NAC.CDR 20 Document #51100 Rev.A 11/5/98 P/N 51100:A

UL Power-limited Wiring Requirements Standard Relays The FACP provides two Form-C relays rated for 2.0 amps @ 30 VDC (resistive) and 2.0 amps @ 30 VAC (resistive). FIGURE 2-8:Relay Terminals Relay connections may be power-limited or nonpower-limited, provided that a minimum of 0.25" is maintained between conductors of power-limited and nonpower-limited circuits. ALARM TROUBLE TB1 GND AC TBL BUZ + NC C NO NC C NO - + - + - + TB2 SIGNAL OUTPUT INITIATING ZONE 1 INITIATING ZONE 2 M2401REL.CDR 2.6 UL Power-limited Wiring Requirements Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the FACP is illustrated below. FIGURE 2-9:Typical Wiring Diagram for UL Power-limited Requirements Grounding Stud Power-limited Circuit Nonpower-limited Circuit Power-limited Circuit GND AC TBLBUZ+24V ALARM TROUBLE SIGNAL IN IT IAT IN IT IAT REG OUTPUTZONE 1 ZONE 2 RES NC C NO NC C NO - + - + - + TB1 TB2 SW1 SYSTEM RESET SW2 SIG SILENCE ZONE 1 SW3 SIG SILENCE ZONE 2 J5 CAUTION! HIGH VOLTAG E F2 R14 CUT IF 4X OPTION BOARD IS PRESENT J4 SW4 CUT TO DISABLE EARTH FAU LT T BL SILE NCE Power-limited Circuit NEUTRALEARTH HOT R72 AC Power TB3 J3 BATTERY J1 2401PWRL..CDR Document #51100 Rev. A 11/5/98 P/N 51100:A 21

Installation of Optional Module 2.7 Installation of Optional Module CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring. 2.7.1 4XTM Transmitter Module Push the disconnect switch to the down position to prevent accidental activation of the municipal box during testing of the control panel. The Disconnect LED will remain illuminated while the municipal box is disconnected. The System Trouble LED will indicate disconnected and/or open circuit conditions on the municipal box. During trouble conditions, it is possible to obtain the circuit condition on the alarm reverse polarity output. If this operation is desired, cut the TBL jumper on the 4XTM module. FIGURE 2-10:4XTM Module Connections TROUBLE SIGNAL IN IT IAT IN IT IAT OUTPUT ZONE 1 ZONE 2 NO + + + NC C - - - TB2 SW1 SYSTEM RESET 2402BRD2.CDR SW2 SIG SILENCE ZONE 1 Cut R14 for 4XTM module placement supervision SW3 SW4 SIG SILENCE ZONE 2 TBL SILENCE 4XTM Module CUT IF 4X OPTION BOARD IS PRESENT Polarities are shown for module activation R14 TBL Jumper J4 CUT TO DISABLE EARTH FAULT 1 (+) Remote Alarm (power-limited)* 2 (-) 3 (+) Remote Trouble (power-limited)* 4 (-) 5 no connection 6 (+) Municipal Box (nonpower-limited)* 7 (-) Install 4XTM Module by plugging into connector J6 and J7 on CFP-2401B/02B main board R72 * Wiring from these terminals can exit the protected premises. Disconnect Switch Disconnect LED J3 BATTERY J1 4XTM.CDR 22 Document #51100 Rev.A 11/5/98 P/N 51100:A

Installation of Optional Module 2.7.2 RTB - Remote Trouble Buzzer The RTB is a Remote Trouble Buzzer which provides a green AC Power LED and a yellow Trouble LED along with a piezo sounder, all of which mimic the condition of the control panel. The RTB can be mounted remotely in a single-gang electrical box. Four wires are required to connect the RTB to the CFP-2401B/CFP-2402B control panel as illustrated in Figure 2-11. FIGURE 2-11:RTB Remote Trouble Buzzer Connection RTB Remote Trouble Buzzer Ground Trouble LED RTBBUZZ.CDR AC Power LED Buzzer CFP-2401B/CFP-2402B TB1 GND AC TBL BUZ +24V ALARM TROUBLE SIGNAL INIT IAT INIT IAT REG OUTPUT ZONE 1 ZONE 2 RES NC NO NC NO + + + C C - - - TB2 J5 F2 2402RTB.CDR Document #51100 Rev. A 11/5/98 P/N 51100:A 23

Programming Options CHAPTER 3 Programming Options This chapter describes the programming options available by cutting resistors on the FACP main circuit board. Options should be selected (resistors cut if necessary) prior to applying power to the control panel. 3.1 Earth Ground Fault Detection The FACP is factory configured to automatically detect ground fault conditions. A ground fault occurs when a low resistance is detected between an FACP circuit and earth ground. This condition will cause the System Trouble LED and Ground Fault LED to turn on and the piezo sounder to pulse. The Ground Fault Detection circuit can be disabled by cutting resistor R72 on the main circuit board. Refer to the local codes and consult the local Authority Having Jurisdiction before disabling the Ground Fault Detection circuit. FIGURE 3-1:Ground Fault Detection Circuit J4 CUT TO DISABLE EARTH FAULT NEUTRAL EARTH HOT R72 R72 Cut to Disable Ground Fault Detection TB3 J3 BATTERY J1 2402BRD3.CDR 3.2 Optional 4XTM Transmitter Module Placement Supervision The 4XTM module can be used to connect the FACP to a City Box or Reverse Polarity Remote Station. To supervise placement and operation of the module, cut resistor R14. Refer to the local codes and consult the local Authority Having Jurisdiction before installing the 4XTM Transmitter Module. FIGURE 3-2:4XTM Module Placement Supervision J5 R14 CUT IF 4X OPTION BOARD IS PRESENT SW4 TBL SILENCE 2402BRD4.CDR R14 Cut to Supervise Placement of 4XTM Module when installed 24 Document #51100 Rev.A 11/5/98 P/N 51100:A

Periodic Testing and Maintenance CHAPTER 4 Periodic Testing and Maintenance To ensure proper and reliable operation, it is recommended that system inspection and testing be scheduled monthly or as required by national and/or local fire codes. Testing should be done by a qualified service representative if a malfunction is encountered. Before Testing: 1. Notify the fire department and/or central alarm receiving station if an alarm condition will be transmitted. 2. Notify the facility personnel of a test so that alarm sounding devices are ignored during the test period. 3. When necessary, activation of notification appliances can be prevented by using the Signal Silence switch to silence the zone. Testing: 1. Activate a zone via an alarm initiating device and check that active notification appliances sound and the alarm LED lights. Reset the system and repeat the procedure for each zone*. 2. Momentarily activate the following switches (one at a time) and check for a trouble signal: Reset (all LEDs should illuminate for Lamp Test) Signal Silence 3. Depress the Trouble Silence switch and check for an intermittent audible signal. Return the Trouble Silence switch to the normal position. 4. Momentarily open the following circuits one at a time and check for a trouble signal: Notification Appliance (bell) Circuit Initiating Device Circuit Zone 1 Initiating Device Circuit Zone 2 (CFP-2402B only) 5. If new batteries were installed, wait 48 hours before completing this step. Remove AC power, activate a zone and check that: The Alarm LED lights All active notification appliances sound Measure battery voltage while the notification appliances are sounding. Replace any battery with terminal voltage less than 85% of rating. Reapply AC power and press the Reset switch*. 6. Return all switches to their normal positions. Notify the fire department, central station and/or building personnel that testing is completed. *Note that the Reset and Signal Silence switches will not operate for one minute following activation of an alarm. Document #51100 Rev. A 11/5/98 P/N 51100:A 25

Battery Calculations CHAPTER 5 Battery Calculations Use the Total Standby and Alarm Load Currents calculated in Table 5-2 and Table 5-3 for the following battery calculation. TABLE 5-1: Battery Calculations Standby Load Current (amps) [ ] X Required Standby Time in Hours (24 or 60 Hours) [ ] = Alarm Load Current (amps) [ ] X Required Alarm Time in Hours (i.e. 5 minutes = 0.084 10 minutes = 0.167) [ ] = Add Standby and Alarm Load for Required Ampere Hour Battery = Multiply by the Derating Factor of 1.2 X1.2 Total Ampere Hours (AH) Required = Note: 1. 7 Ampere Hour battery can be located in the backbox. 26 Document #51100 Rev.A 11/5/98 P/N 51100:A

The Main Power Supply 5.1 The Main Power Supply The FACP provides filtered power for operating the fire alarm control panel, external devices and the standby battery. The power for operating external devices is limited. Use Table 5-2 (standby or nonalarm) and Table 5-3 (alarm) to determine if external loading is within the capabilities of the power supply. For 4-wire smoke detectors, be sure to power them from TB1 Terminals (+24V Resettable) and (-Ground). TABLE 5-2: Load in Standby Device Type # of Devices Current (amps) Total Current (amps) Main Circuit Board 1 X 0.075 = 0.075 4XTM (1 max.) X 0.005 = Remote Trouble Unit (1 max.) X 0.020 = 2-wire Detector Heads [ ] X [ ] 1 = 4-wire Detector Heads [ ] X [ ] 1 = Power Supervision Relays 2 [ ] X [ ] = Additional Current Draw from TB1 (nonalarm) 3 = Sum Column for Standby Load = amps 1. Refer to the Device Compatibility Document for 2-wire smoke detector standby current. 2. Must use compatible listed Power Supervision Relay. 3. The total standby current must include the resettable power from TB1. Caution must be taken to ensure that current drawn from this output during alarm does not exceed maximum ratings specified (see Table 5-3 ) Document #51100 Rev. A 11/5/98 P/N 51100:A 27

The Main Power Supply TABLE 5-3: Load in Alarm Device Type # of Devices Current (amps) Total Current (amps) Main Circuit Board 1 X 0.125 1 = 4XTM (1 max.) X 0.045 = Remote Trouble Unit (1 max.) X 0.050 = 4-wire Detector Heads 2 [ ] X [ ] = Power Supervision Relays 3 [ ] X [ ] = Notification Appliances 4 [ ] X [ ] = Additional Current Draw from TB1 (nonalarm) 2 = Sum Column for Alarm Load = amps 1. The current shown represents the CFP-2401B control panel in alarm. If both zones of the CFP-2402B control panel are in alarm, the current draw increases to 0.175 amps. 2. Current limitations of terminals: TB1, Terminals Ground and +24V Resettable = 0.085 amps, filtered, 24 VDC +/-5%, ripple @ 10mV RMS. 3. Must use compatible listed Power Supervision Relay 4. Enter current draw of each device. Current limitation of TB2 Notification Appliance Circuit is 1.25 amps. 28 Document #51100 Rev.A 11/5/98 P/N 51100:A

Index Numerics 4XTMF see Transmitter Module A Alarm 12 B Backbox 17 Battery 13 Alarm 28 Calculations 26 Charger 13 see also Power - Battery Standby 27 Trouble 11 C Cabinet 13 Dimensions 16 Knockouts 16 see also Backbox D Description 7 Discharge Protection 9 Dress Panel 13 E Earth Ground 18 Fault Detection 24 F Form-C Relays See also Relays G Ground Fault see also Earth Ground - Fault Detection I Indicators 11 AC Power 11 Battery Trouble 11 Bell Trouble 11 Ground Fault 12 Option Trouble 11 System Trouble 12 see also Trouble Zone Alarm 11 see also Alarm Zone Silence 11 Zone Trouble 11 Initiating Device Circuit Current Alarm 9 Short Circuit 9 Standby 9 End-of-Line Resistor 9 Style Y 9 Voltage 9 Input Circuits 13, 19 L LED see Indicators M Maintenance 25 Mounting 15 N Notification Appliance Circuit 9, 13, 20 Current 9 End-of-Line Resistor 9 Style Y 9 Voltage 9 O Operational Power 18 Primary 18 see Battery Output Circuits 20 Resettable Power 13 see Battery - Charger P Piezo see Sounder Power AC 9 AC fuse 9 see also Operational Power - Primary Battery 9 Charger Capacity 9 charging circuit 9 Deep Discharge Protection 9 Programming 24 R Relays 9, 13, 21 Contact Rating 9 Remote Trouble Buzzer 14, 23 Resettable Power Current 9 voltage 9 Resistor, End-of-Line Initiating Device Circuit 9 Notification Appliance Circuit 9 RTB see Remote Trouble Buzzer S Sounder Alarm 12 Trouble 12 Standby 12 Style B 7 Style Y 7 Switches 10 Reset 10 Signal Silence 10 Trouble Silence 10 T Testing 25 Transformer Assembly 13 Transmitter Module 14, 22 Placement Supervision 24 Trouble 12 U UL Power-limited Wiring 21 Document #51100 Rev. A 11/5/98 P/N 51100:A 29

Notes 30 Document #51100 Rev.A 11/5/98 P/N 51100:A

Notes Document #51100 Rev.A 11/5/98 P/N 51100:A 31

Limited Warranty Notifier warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of Notifier is to repair or replace, at is option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service. For products not under Notifier manufacturing date-stamp control, the warranty is eighteen (18) months from date of original purchase by Notifier distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. This warranty is void if the product is altered, repaired or serviced by anyone other than Notifier or its authorized distributors or if there is a failure to maintain the products and systems in which they operate in proper and workable manner. In case of defect, secure a Return Material Authorization form from our customer service department. Return product, transportation prepaid, to Notifier, 24 Viceroy Road, Concord, Ontario L4K2L9. This writing constitutes the only warranty made by Notifier with respect to its products. Notifier does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that Notifier is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse, abuse, accident or similar incident. Notifier GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MERCHANTABIL- ITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIR- CUMSTANCES SHALL Notifier BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE Notifier PRODUCTS. FURTHERMORE, Notifier SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS. This warranty replaces all previous warranties and is the only warranty made by Notifier. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. Notifier is a registered trademark. 24 Viceroy Road, Concord, Ontario L4K2L9 Phone: (905) 660-7210 FAX: (905) 660-7204