FLEXIBLE LIGHT COMMERCIAL UNIT TECHNICAL GUIDE CHAMPION PLUS SINGLE PACKAGE GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 3 AND 4 NOMINAL TON GENERAL

Similar documents
FLEXIBLE LIGHT COMMERCIAL UNIT TECHNICAL GUIDE AFFINITY SERIES SINGLE PACKAGE GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 3 THROUGH 5 NOMINAL TON GENERAL

R-410A LUXAIRE ACCLIMATE DYX MODELS 2-4 TON 60 Hertz

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

SUNLINE 2000 SINGLE PACKAGE AIR-COOLED AIR CONDITIONERS DESCRIPTION FEATURES

DESCRIPTION TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS D(HE, HG) 036, 048 & YTG-A-0506

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

PGF SERIES 7-1/2 Ton. Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION

RGE 13 A T - 1 A

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE AIR CONDITIONERS ELECTRIC/ELECTRIC, AIR-COOLED. MODELS: D1EB036 thru Thru 5 Ton (10 SEER)

Weathermaster Series 48HJ004, 005, 006, 007, 008, 009, 012 & 014 COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

13 GEP A L P - 1 A

PGB SERIES 3thru5Ton 10 SEER CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

HEAT EXCHANGER Aluminized serpentine clamshell heat exchanger provides corrosion resistance for longer life and efficient heat transfer.

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

48TF GAS HEATING/ ELECTRIC COOLING UNITS

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

Supersedes: N2Y (498) N2Y (799) MODELS B1HH018 THRU THRU 5 TON (12 SEER)

48TM GAS HEATING/ELECTRIC COOLING UNITS

Commercial High-Efficiency Condensing Units

PAR5. Product Specifications

PRODUCT SPECIFICATIONS 2YCC3048A1120A /1/ /

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

SKYPAK II Heating & Cooling Self Contained Packages

RHEEM PACKAGE GAS/ELECTRIC

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

2YCC3060A1120A /1/ / YCC3060A1096A /1/ /

4YCC3048A3096A /3/ /

TECHNICAL GUIDE STELLAR 2000 TM MODELS: E*FD018 THRU E*FD060 1 Ø E*FD036 THRU E*FD060 3 Ø SPLIT-SYSTEM HEAT PUMPS Rev A (0500)

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

MODELS B1PA024, 030 AND 036

SKYPAK II, 3 Ton Series, gives you a

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

PACKAGE AIR CONDITIONER

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat

HEATING & COOLING SUBMITTAL The DuraPac Series Unit 559F/579F180, 216, 240, , 18, 20, and 25 NOMINAL TONS

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

48SS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

PRODUCT SPECIFICATIONS 2YCC3036A1096A /1/ /

SPLIT-SYSTEM CONDENSING UNITS. "HRC" Series SEER. Models H*RC018 thru H*RC060 Nominal Capacity: 18 thru 60 MBH DESCRIPTION FEATURES

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

48PGD/E/F/L/M/N PG20-28

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

SPLIT SYSTEM HEAT PUMPS "ERC" Series

SKYPAK II, 3 Ton Series, gives you a

TECHNICAL SPECIFICATIONS

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

SPLIT SYSTEM HEAT PUMPS 14 SEER

50TM COMBINATION HEATING/COOLING UNITS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

SPLIT-SYSTEM CONDENSING UNITS. HRC Series TECHNICAL SPECIFICATIONS

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

SPECIFICATIONS 4YCC3060A-SPEC-1A SINGLE PACKAGED GAS HEATING ELECTRIC COOLING 4YCC3060A1096/120B TAG:

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

4YCC3036A1075B /1/ / YCC3036A1064B /1/ /

SUBMITTAL. Project. CLU Swenson Center. Date 01/07/2010. Mechanical Contractor. West Coast Air Conditioning. Mechanical Engineer

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

TECHNICAL SPECIFICATIONS

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

P8SE Series. 14 SEER, Single Phase Packaged Air Conditioner TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 3, 4, 5 Ton Units

PAJ3. Product Specifications

48GS HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING/ ELECTRIC COOLING UNITS

DCG Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

Ruud Commercial Achiever Series Package Gas Electric Unit

TECHNICAL GUIDE MODELS: P*DH GAS-FIRED CONDENSING / HIGH EFFICIENCY DOWNFLOW / HORIZONTAL FURNACES 91 AFUE DESCRIPTION WARRANTY FEATURES

Rooftop Units 60HZ. PACKAGED HEAT PUMPS 13HPP / rhp13 PRODUCT SPECIFICATIONS 13 HPP 36 A P - 1 A RHP 13 A 36 T - 1 A MODEL NUMBER IDENTIFICATION

50TM TFF COMBINATION HEATING/COOLING UNITS

TECHNICAL GUIDE STELLAR 2000 TM MODELS: H*DB012 THRU H*DB076 (1 Ø & 3 Ø) SPLIT-SYSTEM AIR CONDITIONERS A TG2Y (02/00) DESCRIPTION

Submittal Summary Page

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

Advance Release September 2009

DCG Commercial. Submittal Data Form

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

Submittal. Date: January 8, Customer P.O. Number: Customer Project Number: CARROLLTON, TX 75006

48GS(N) STANDARD EFFICIENCY 48GX(N) HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING ELECTRIC COOLING UNITS

DCC Commercial. Submittal Data Form. 7½ - 12½ Ton Packaged Air Conditioners Up to 11.3 EER Cooling Capacity: 88, ,000 BTU/h

RG7D 1-Stage Heat Series

Product Data. Fig. 1 - Unit 50VR -A

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

KG6TE Series. High Efficiency / Direct Vent or Non Direct Vent 2-Stage Condensing Gas Furnace with Variable Speed Blower TECHNICAL SPECIFICATIONS

DCC Series. Submittal Data Form 15- & 20-TON, THREE-PHASE PACKAGED AIR CONDITIONERS UP TO 11 EER

Commercial High-Efficiency Condensing Units

15 SEER, PACKAGE AIR CONDITIONING UNITS, 2-5 TONS Single Phase, 208/230 V, 60 Hz COOLING

TECHNICAL SPECIFICATIONS

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

Model 655A Sizes

KG6RC Series TECHNICAL SPECIFICATIONS FEATURES AND BENEFITS

2220 SE Ninth Avenue 2113 Delta Waters Road Portland OR Medford OR

MACH N-407 Heat Pump Air-Cooled Chiller

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

EER PACKAGE AIR CONDITIONER, 6.9 to 14.4 kw, 2 4 TONS 3 Phase, Standard CFM / Ls EER

Supersedes: A-0202 MODELS B1HA018 THRU THRU 5 TON (10 SEER)

Transcription:

TECHNICAL GUIDE CHAMPION PLUS SINGLE PACKAGE GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 3 AND 4 NOMINAL TON D1NP036 and 048 13 SEER FLEXIBLE LIGHT COMMERCIAL UNIT GENERAL YORK s Champion package units are designed to handle applications ranging from residential to light commercial and any in between. The Champion is a unit that gives you the flexibility and choices you need in today s market. FEATURING COOLING/GAS HEATING UNITS (NATURAL GAS OR PROPANE) LOW PROFILE QUIET OPERATION COMMON FOOTPRINT OPTIONAL FACTORY INSTALLED ECONOMIZERS OPTIONAL SLIDE IN MOTORIZED DAMPERS OPTIONAL SLIDE IN ECONOMIZERS OPTIONAL PROPANE CONVERSION KIT OPTIONAL HIGH ALTITUDE GAS OR PROPANE KIT OPTIONAL NOx KIT MODULAR ELECTRICAL CONNECTIONS FOR EASE OF INSTALLATION FULL PERIMETER BASE RAILS TROUBLE FREE UTILITY CONNECTIONS 1 OR2 THROWAWAYFILTERS 5 YEAR LIMITED WARRANTY ON COMPRESSOR 10 YEAR LIMITED WARRANT ON GAS-FIRED HEAT EXCHANGERS 1 YEAR LIMITED WARRANTY ON ALL REPLACE- MENT PARTS FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

TABLE OF CONTENTS DESCRIPTION...3 STANDARDFEATURES/BENEFITS...3 FIELD-INSTALLED ACCESSORIES....4 TYPICALWIRINGDIAGRAMNOTES...22 LIST OF FIGURES Fig# Description Pg# 1 UNITCOMPONENTLOCATION...5 2 FIELD WIRING DIAGRAM CONTROL WIRING.... 12 3 POWERWIRINGFIELDDIAGRAM...13 4 UNITDIMENSIONS-FRONT...14 5 UNITDIMENSIONS-FRONT&BOTTOM...15 6 UNITDIMENSIONS-BACK&BOTTOM...15 7 TYPICAL SLAB ON GROUND INSTALLATION.... 16 8 TYPICAL ROOF CURB INSTALLATION......... 16 9 TYPICAL DUCT APPLICATIONS............... 17 10 UNITCENTEROFGRAVITY...17 11 ROOF CURB DIMENSIONS................... 18 12 ROOF CURB CROSS SECTION............... 18 13 TYPICAL WIRING DIAGRAM (208/230-1-60 POWERSUPPLY)...19 14 TYPICAL WIRING DIAGRAM (208/230-3-60 POWERSUPPLY)...20 LIST OF FIGURES (CONT.) Fig# Description Pg# 15 TYPICAL WIRING DIAGRAM (460-3-60 POWER SUPPLY)...21 16 TYPICALWIRINGDIAGRAMLEGEND...22 LIST OF TABLES Tbl# Description Pg# 1 PHYSICALDATA...6 2 RATINGSCOOLING/GASHEATING...7 3 DNP036 COOLING CAPACITIES - 3 TON......... 8 4 DNP048 COOLING CAPACITIES - 4 TON......... 9 5 SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230VOLTS...10 6 BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208/230VOLTS...11 7 ADDITONAL STATIC PRESSURE RESISTANCE - 3TON(DNP036)...12 8 ADDITIONAL STATIC PRESSURE RESISTANCE - 4TON(DNP048)...12 9 ELECTRICALDATA...13 10 UNITDIMENSIONSFRONT...14 11 UNITMINIMUMCLEARANCES...14 12 UNIT WEIGHTS AND CENTER OF GRAVITY..... 17 2 Unitary Products Group

DESCRIPTION These packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation. The gas-fired heaters have aluminized steel tubular heat exchangers and hot surface to pilot ignition. They are available in natural gas with field conversion to propane. STANDARD FEATURES/BENEFITS OPERATING EFFICIENCY - All units provide high operating efficiencies and have a minimum AFUE of 80% and SEER of 13.0. All efficiencies exceed legislated minimum levels. ON SITE FLEXIBILITY - All model sizes share a common, compact design cabinet in a single footprint. The installer has the flexibility of setting one curb and placing the proper tonnage unit on that curb after the internal load has been determined. Field convertible duct connections from side shot to down shot allows the installer to have greater flexibility and needs to carry less inventory. LOWER INSTALLATION COST - Installation time and costs are reduced by easy power and control wiring connections. The small base dimension means less space is required on the ground or roof, plus, the installer can fit this unit between the wheel wells of full size pick-up truck. All models are well under 500 pounds. All units are completely wired, charged with R-22 and tested prior to shipment. Unique test stations using a new state of the art computerized process system are used to insure product quality. Refrigerant charge, and component part numbers are verified via computers at assembly. Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas system safeties are monitored and recorded by the system to insure unit performance. Equal size, side supply and return duct connections allows easy hook-up of ducts to match low crawl spaces without transition pieces. UTILITY CONNECTIONS MADE EASY - Gas and electric utility knockouts are provided through the bottom as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. A field supplied and field installed electrical disconnect switch must be installed. CONVERTIBLE AIRFLOW DESIGN - The bottom duct openings are covered when they leave the factory ready to be used for a side supply / side return application. If a bottom supply / bottom return application is desired, you simply remove the two panels from the bottom of the unit and place them in the side supply / side return duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory. CONDENSATE PAN - A non-corrosive, long-lasting, watertight pan is positioned below the evaporator coil to collect and drain all condensate. Less collection of stagnate condensate will build-up. The condensate pan conforms to ASHRAE 62-89 standards (Ventilation for Acceptable Indoor Air Quality). CONDENSATE DRAIN - The heavy duty, inch NPTI copper connection is more tolerable during installation and is more durable over time. The connection is rigidly mounted to assure proper fit and leak tight seal. DURABLE FINISH - With a heavy duty cabinet made of powder-painted, galvanized steel the neutral color blends into surrounding areas. The powered paint, provides a better paint to steel bond, which resists corrosion and rust creep. The special primer formulas and glossy earth tone finish insure less fading when exposed to sunlight and offers a more attractive on site appearance. This paint finish meets ASTM-B117 standards for 750 hours salt spray rating. The highest in the industry. FULL PERIMETER BASE RAILS - The easily removable base rails provide a solid foundation for the entire unit and protects the unit during shipment. The rails provide fork lift access from all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On applications when the unit is placed on a pad, the base will keep the unit off the pad to deter corrosion. On applications where height is limited, the inch high base rails may be removed on location. MORE ATTRACTIVE APPEARANCE - A single piece Water Shed top cover containing a top discharge condenser fan arrangement requires less square footage on installation and provides a wider variety of installations. The one piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance. The cabinet panels have a non-fibrous insulation that does not add insulation fibers into conditioned area. TOP DISCHARGE - The top discharge condenser fan does not disrupt neighboring areas or does this dry-out vegetation surrounding the unit. The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications. CONDENSER COIL GRILLE - A multi-piece totally enclosed, rigidly mounted condenser coil grille provides protection from objects and personal after installation and provides protection during transit and installation. LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up and away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds. The unique formed base pan also aids in sound alterations with it's Super-Structure design. This design strategically places embossments in the pan for optimum strength and rigidity. Unitary Products Group 3

FAN SYSTEM - All models operate over a wide range of design conditions with a constant CFM, electrically commutated (ECM) fan motor. These units easily match all types of applications and provides greater on site flexibility to match comfort requirement. These models have 2 cooling speeds and a single heating speed. The cooling speed is factory set and can be field adjusted to a second speed. The heating speed is factory set to maintain mid point rise at the units heating input. It cannot be field adjusted. This allows maximum comfort conditions. SIMPLE CONTROL CIRCUIT - A low voltage printed circuit board contains a diagnostic indicator light and a low voltage terminal strip. An additional set of pin connectors is also provided to simplify the field interface of external controls. Maten-lock plug connectors are used. The electrical control box is not located in the compressor compartment. The controls are mounted on a Control-Tilt control panel to allow the access cover to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded. PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the compressor if undesirable operating conditions occur. EXCLUSIVE COIL DESIGN - Grooved copper tubes and enhanced aluminum fin construction improves heat transfer for maximum efficiency and durability. HEAT EXCHANGERS - Are corrosion-resistant, aluminizedsteel tubular construction to provide long-life, trouble-free operation. The unique blow-through design also assures that condensate does not collect in humid areas when in the cooling cycle. This adds to longer heat exchanger life and higher long term efficiencies. POST PURGE INDUCED DRAFT COMBUSTION - Exhausts combustion products from the heat exchanger upon completion of the heating cycle to prolong the heat exchanger life. SELF DIAGNOSTIC FAN CONTROL MODULE - Due to this self diagnostic control, less on site time is required to trouble shoot these units. HOT SURFACE TO PILOT IGNITION - Provides faster heat delivery. This ignition is highly reliable, durable and eliminates nuisance lockouts. Also assures starts in damp conditions. MULTI PORT IN-SHOT BURNERS - No field adjustment is required to mix the air and gas. These burners are constructed of high-grade corrosion-resistant, aluminized-steel. LOW MAINTENANCE - Long life, permanently lubricated condenser and evaporator fan motor bearings need no annual maintenance adding greater reliability to the unit. Blower assembly can be easily cleaned by the unique Slip- Track slide-out blower assembly. SECURED SERVICE ACCESS PORTS - Protected, externally mounted, re-usable service access ports are provided on both the high and low lines for ease of evacuating and charging the system. No final field mounting required. EASY SERVICE ACCESS - A large, single panel covers the electrical and gas controls makes servicing easy. The blower compartment has an additional large panel with a built-in handle tab. Removing this panel will allow the blower assembly to slide-out for easy removal for maintenance and ease of trouble shooting. REPLACEMENT PARTS - The installer has no need to carry an inventory of unique parts or needs special training to replace any of the components parts for these units. All are easily obtained from Source 1 or other part houses. SYSTEM INTEGRATION - Each unit has the internal ability to integrate an electronic air cleaner or humidifier to work in conjunction with the base unit. FIELD-INSTALLED ACCESSORIES LOW NOX KIT - Kit includes all the necessary hardware and instructions to field convert units to reduce emissions to less than 40 nanogram per Joule. California requirement on single phase models only. PROPANE CONVERSION KIT - Kit includes burner orifices, gas valve conversion and installation instructions necessary to field convert unit from natural gas to propane. HIGH ALTITUDE CONVERSION KIT (Natural Gas/Propane) - Kit includes all necessary labels and instructions necessary to field alter units with natural gas/propane. Burner orifices must be obtained from Source 1 Parts. Propane Conversion Kit must be obtained separately. ECONOMIZER DOWN DISCHARGE / SUPPLY KIT - Modulating integrated economizer provides simultaneous operation between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy are also available. A built-in barometric relief of 25% is provided. SINGLE ENTHALPY SENSOR - Sensor replaces dry bulb sensor standard in economizer kit. Provides improved economizer operation by sensing the dry bulb temperature from outdoors plus the enthalpy content of the outdoor air. DUAL ENTHALPY SENSOR - Additional sensor to single enthalpy sensor. Sensor senses both the return air temperature dry bulb and humidity in conjunction with the single enthalpy to determine the most economical mix. Single Enthalpy sensor also required. UPGRADE SAFETY PACKAGE - Contains screw in type High pressure, Low Pressure/Loss of Charge switch, freeze protection switch and lockout relay. Switches are placed onto 4 Unitary Products Group

existing scharder ports located in the unit by furnished adapters. When abnormal conditions are sensed through the pressure switches, the unit will lock out preventing any further operation until reset or problem is corrected. Package agency approved. HAIL GUARD KIT - Kit contains protected grilles made of expanded aluminum grilles with full perimeter inch frame. Sloped hoods are also included to assure maximum protection. ANTI SHORT CYCLE TIMER - Automatically prevents the compressor from restarting for 5 minutes after cycled off.not required if Thermostat 2ET07700224 and 2ET04700224 are used. FILTER / FRAME KIT (Single Phase only) - Kit contains the necessary hardware to field install return air filters into the base unit. Pre-cut filter racks and appropriate cleanable standard size filters are shipped in one kit. The filter rack is suitable for either 1" or 2" filters. (1" filter is supplied) This kit is available for single phase horizontal or vertical duct application only. Standard in all 3 Phase models. MOTORIZED FRESH AIR DAMPER - Designed for duct mounted side supply/return and unit mounted down supply/ return applications. Damper capable of providing 0% through 50% of outdoor air (field supplied). Closes on power loss, includes hood and screen assembly. RECTANGLE TO ROUND ADAPTERS - Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit over current duct openings on the base unit. Transition is from side square duct opening to 14" round duct opening. ROOF CURBS - NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also provides seal strip to assure a water tight seal. 8 and 14 inch high roof curbs are available. MANUAL OUTDOOR DAMPER - Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications. Includes hood and screen assembly. WALL THERMOSTAT - The units are designed to operate with 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat / single stage cool thermostats - with or without the economizer. LOW AMBIENT KIT - Kit provides necessary hardware to convert unit to operate in cooling cycle down to 0º F. Standard unit operation 45º F. TRANSFORMER KIT - Kit provides necessary hardware to provide single phase models from factory furnished 40 VA transformer capability to 75 VA transformer capability. DIRECT DRIVE CONDENSER FAN MOTOR BLOW-THROUGH DESIGN WITH RELIABLE ALUMINIZED STEEL TUBULAR HEAT EXCHANGERS HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN EVAPORATOR COIL LONG LASTING POWDER PAINT FINISH EARTH TONE COLOR HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN CONDENSER COIL DECORATIVE PROTECTIVE COIL GAURD REAR AND BOTTOM RETURN AIR AND SUPPLY AIR DUCT OPENINGS HIGH EFFICIENCY COMPRESSOR RIGIDLY MOUNTED HEAVY GAUGE REMOVABLE BASE RAILS ECM DIRECT DRIVE BLOWER MOTOR WITH SLIDE-OUT BLOWER ASSEMBLY FIGURE 1: UNIT COMPONENT LOCATION POWER VENTER MOTOR HOT SURFACE PILOT ASSEMBLY HIGH GRADE ALUMINIZED IN-SHOT BURNERS LOW VOLTAGE TERMINAL BLOCK SELF-DIAGNOSTIC CONTROLS WITH "COMFORT-MATCH" SPEED CONTROL AUTOMATIC GAS VALVE (1/2" - 14 NPTI) HIGH VOLTAGE TERMINAL BLOCK Unitary Products Group 5

TABLE 1: PHYSICAL DATA EVAPORATOR BLOWER EVAPORATOR COIL CONDENSER FAN MODEL DNP 036 048 CENTRIFUGAL BLOWER (Dia. x W. in.) 11 x 10 12 x 11 FAN MOTOR HP (ECM) 3/4 1 ROWS DEEP 3 3 FINS PER INCH 13 16 FACE AREA (Sq. Ft.) 3.5 4.5 PROPELLER DIA. (in.) 22 22 FAN MOTOR HP 1/4 1/3 NOM. CFM TOTAL 2,400 3,000 ROWS DEEP 2 2 CONDENSER COIL FINS PER INCH 20 20 FACE AREA (Sq. Ft.) 11.7 14.7 CHARGE REFRIGERANT 22 (lbs./oz.) 6 / 12 8 / 4 FILTER FACE AREA (Sq. Ft.) Size (Nominal) 2.6/20x20 FURNACE SECTION 3.3/20x12 (2 Reqd.) NATURAL GAS BURNER ORIFICE NO. (Drill Size) 43 40 PROPANE BURNER ORIFICE NO. (Drill Size) 55 53 GAS CONNECTION SIZE 1/2 NPTI 1/2 NPTI COMPRESSOR HERMETIC TYPE, (Qty. = 1) Scroll Scroll 6 Unitary Products Group

TABLE 2: RATINGS COOLING/GAS HEATING MODEL DNP NET COOLING CAPACITY 1 SOUND RATING MBH SEER 3 (dbels) 2 INPUT (MBH) OUTPUT (MBH) GAS HEAT CAPACITY / EFFICIENCIES AFUE 4 (%) NUMBER OF BURNERS TEMP. RISE ( F) RANGE 036N03606 37.4 13.65 81 45 36 80.4 2 25-55 036N03625 37.4 13.65 81 45 36 80.4 2 25-55 036N03646 37.4 13.65 81 45 36 80.4 2 25-55 036N05606 37.4 13.65 81 70 56 80.2 3 25-55 036N05625 37.4 13.65 81 70 56 80.2 3 25-55 036N05646 37.4 13.65 81 70 56 80.2 3 25-55 036N07206 37.4 13.65 81 90 72 80.1 4 30-60 036N07225 37.4 13.65 81 90 72 80.1 4 30-60 036N07246 37.4 13.65 81 90 72 80.1 4 30-60 048N06506 48.0 13.20 84 80 64 80.8 3 25-55 048N06525 48.0 13.20 84 80 64 80.8 3 25-55 048N06546 48.0 13.20 84 80 64 80.8 3 25-55 048N09006 48.0 13.20 84 108 86 80.6 4 35-65 048N09025 48.0 13.20 84 108 86 80.6 4 35-65 048N09046 48.0 13.20 84 108 86 80.6 4 35-65 048N11006 48.0 13.20 84 135 107 80.5 5 45-75 048N11025 48.0 13.20 84 135 107 80.5 5 45-75 048N11046 48.0 13.20 84 135 107 80.5 5 45-75 1. Net Cooling Capacity = ARI 210 standard rating conditions. 2. (dbels) = ARI 270-95 3. Seasonal Energy Efficiency Ration - the total cooling output in BTU s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. 4. AFUE = Annual Fuel Utilization Efficiency. Unitary Products Group 7

TABLE 3: DNP036 COOLING CAPACITIES - 3 TON 85 F 95 F 105 F 115 F 125 F TEMPERATURE OF AIR ON CONDENSER COIL Sensible Capacity MBH 1 Sensible Capacity MBH 1 Sensible Capacity MBH 1 Sensible Capacity MBH 1 Sensible Capacity MBH 1 NET CAP. MBH TOTAL POWER INPUT kw Entering Dry Bulb F NET CAP. MBH TOTAL POWER INPUT kw Entering Dry Bulb F NET CAP. MBH TOTAL POWER INPUT kw Entering Dry Bulb F NET CAP. MBH TOTAL POWER INPUT kw Entering Dry Bulb F NET CAP. MBH TOTAL POWER INPUT kw Entering Dry Bulb F AIR ON EVAPORATOR COIL 1,200 CFM 1,350 CFM WB F WB F 72 67 62 57 72 67 62 57 43.3 39.9 37.4 36.7 44 40.5 38 37.2 2.93 2.89 2.9 2.88 3.08 3.05 3.06 3.04 86 29.5 35.8 37.4 36.7 31.8 38.4 38 37.2 83 26 32.3 37.4 36.7 27.8 34.4 38 37.2 80 22.5 28.8 34.8 35.6 23.8 30.4 36.7 36.7 77 19 25.3 31.3 32.1 19.9 26.4 32.7 32.7 74 15.5 21.8 27.8 28.6 15.9 22.5 28.7 28.7 71-18.3 24.3 25.1-18.5 24.7 24.7 68-14.8 20.8 21.6-14.5 20.7 20.7 41.4 37.1 35.7 35.3 42.5 38 36.6 36.2 3.22 3.27 3.18 3.15 3.32 3.37 3.28 3.25 86 28.5 34.8 35.7 35.3 31 36.9 36.6 36.2 83 25 31.3 35.7 35.3 27 33.7 36.6 36.2 80 21.5 27.8 33.5 33.9 23 29.7 25.5 35.5 77 18 24.3 30 30.4 19 25.7 31.5 31.5 74 14.5 20.8 26.5 26.9 15 21.7 17.6 27.5 71-17.3 23 23.4-17.7 23.6 23.5 68-13.8 19.5 19.9-13.8 19.6 19.5 38.5 34.8 33.9 33.6 39.6 35.8 34.8 34.5 3.61 3.61 3.5 3.48 3.73 3.72 3.61 3.59 86 27.6 33.6 33.9 33.6 29.9 35.1 34.8 34.5 83 24.1 30.1 33.9 33.6 26 32.4 34.8 34.5 80 20.6 26.6 32 32.2 22 28.4 33.9 33.8 77 17.1 23.1 28.5 28.7 18 24.4 29.9 29.8 74 13.6 19.6 25 25.2 14 20.5 25.9 25.8 71-16.1 21.5 21.7-16.5 21.9 21.8 68-12.6 18 18.2-12.5 18 17.9 35.6 32.6 32.2 31.9 36.7 33.5 33.1 32.8 4.01 3.95 3.82 3.8 4.14 4.07 3.93 3.92 86 26.6 32.4 32.2 31.9 28.9 33.4 33.1 32.8 83 23.1 28.9 32.2 31.9 24.9 31.1 33.1 32.8 80 19.6 25.4 30.6 30.6 21 27.1 32.3 32.1 77 16.1 21.9 27.1 27.1 17 23.2 28.3 28.1 74 12.6 18.4 23.6 23.6 13 19.2 24.3 24.1 71-14.9 20.1 20.1-15.2 20.3 20.2 68-11.4 16.6 16.6-11.2 16.3 16.2 32.8 30.2 30.4 30.1 33.7 31.2 31.3 30 4.4 4.3 4.1 4.1 4.5 4.4 4.3 4.2 86 25.6 31.2 30.4 30.1 27.9 31.6 31.3 31 83 22.1 27.7 30.4 30.1 23.9 29.9 31.3 31 80 18.6 24.2 19.1 28.9 19.9 25.9 30.6 30.4 77 15.1 20.7 25.6 25.4 15.9 21.9 26.6 26.4 74 11.6 17.2 22.1 21.9 12 17.9 22.7 22.5 71-13.7 18.6 18.4-13.9 18.7 18.5 68-10.2 15.1 14.9-9.9 14.7 14.5 1. These capacities are net capacities (the indoor fan heat is deducted). ALL SENSIBLE CAPACITY 8 Unitary Products Group

TABLE 4: DNP048 COOLING CAPACITIES - 4 TON 85 F 95 F 105 F 115 F 125 F TEMPERATURE OF AIR ON CONDENSER COIL Sensible Capacity MBH 1 Sensible Capacity MBH 1 Sensible Capacity MBH 1 Sensible Capacity MBH 1 Sensible Capacity MBH 1 NET CAP. MBH TOTAL POWER INPUT kw Entering Dry Bulb F NET CAP. MBH TOTAL POWER INPUT kw Entering Dry Bulb F NET CAP. MBH TOTAL POWER INPUT kw Entering Dry Bulb F NET CAP. MBH TOTAL POWER INPUT kw Entering Dry Bulb F NET CAP. MBH TOTAL POWER INPUT kw Entering Dry Bulb F AIRONEVAPORATORCOIL 1,400 CFM 1,600 CFM WB F WB F 72 67 62 57 72 67 62 57 54.0 49.2 45.6 45.9 55.2 50.4 46.6 46.9 3.69 3.66 3.62 3.57 3.85 3.83 3.79 3.73 86 35.8 43.7 45.6 45.9 39.1 47.7 46.6 46.9 83 31.7 39.6 44.6 45.3 34.5 43 46.6 46.9 80 27.7 35.6 42.4 43.6 29.8 38.3 45.7 46.9 77 23.6 31.6 38.4 39.5 25.1 33.7 41 42.3 74 19.6 27.5 34.3 35.5 20.5 29 36.3 37.6 71-23.5 30.3 31.4-24.3 31.7 32.9 68-19.4 26.2 27.4-19.7 27 28.3 51.8 46.8 43.8 44.0 51.9 46.9 43.9 44.2 4.07 4.04 4.01 3.99 4.21 4.18 4.15 4.12 86 35.4 42.9 43.8 44.0 38.4 46.4 43.9 44.2 83 31.4 38.9 42.8 43.2 33.8 41.7 43.9 44.2 80 27.4 34.9 40.9 41.5 29.1 37.1 43.5 44.2 77 23.3 30.8 36.8 37.5 24.4 32.4 38.8 39.5 74 19.3 26.8 32.8 33.4 19.8 27.7 34.1 34.8 71-22.7 28.7 29.4-23.1 29.5 30.2 68-18.7 24.7 25.4-18.4 24.8 25.5 48.7 44.3 41.4 41.7 49.2 44.7 41.8 42.1 4.49 4.45 4.38 4.34 4.63 4.59 4.51 4.48 86 34.1 41.3 41.4 41.7 37.1 4.44 41.8 42.1 83 30.0 37.7 40.7 41.1 32.4 40.6 41.8 42.1 80 26.0 33.6 38.9 39.4 27.8 35.9 41.6 42.1 77 22.0 29.6 34.9 35.3 23.1 31.3 36.9 37.4 74 17.8 25.6 30.8 31.3 18.4 26.6 32.3 32.7 71-21.5 26.8 27.3-21.9 27.6 28.1 68-17.5 22.8 23.2-17.3 22.9 23.4 45.7 41.8 39.1 39.4 46.4 42.5 39.7 40 4.91 4.86 4.74 4.70 5.05 5 4.87 4.83 86 32.7 39.7 39.1 39.4 35.8 42.5 39.7 40 83 28.7 36.5 38.7 38.9 31.1 39.5 39.7 40 80 24.6 32.4 37.0 37.2 26.4 34.8 39.7 40 77 20.6 28.4 32.9 33.2 21.8 30.1 35 35.3 74 16.6 24.4 28.9 29.1 17.1 25.5 30.4 30.6 71-20.3 24.9 25.1-20.8 25.7 26 68-16.3 20.8 21.1-16.2 21 21.3 42.7 39.3 36.8 37.0 43.6 40.2 37.6 37.9 4.3 5.3 5.1 5.0 5.5 5.4 5.2 5.2 86 31.4 38.0 36.8 37.0 34.5 40.5 37.6 37.9 83 27.3 35.3 36.7 36.8 29.8 38.4 37.6 37.9 80 23.3 31.2 35.1 35.1 25.1 33.7 37.6 37.9 77 19.2 27.2 31.0 31.0 20.5 29 33.2 33.2 74 15.2 23.1 27.0 27.0 15.8 24.4 28.5 28.5 71-19.1 22.9 23.0-19.7 23.8 23.9 68-15.1 18.9 18.9-15 19.2 19.2 1. These capacities are net capacities (the indoor fan heat is deducted). ALL SENSIBLE CAPACITY Unitary Products Group 9

TABLE 5: SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS 1 MODEL # DNP MODE (COOLING / HEATING) CFM EXTERNAL STATIC PRESSURE - IWG.20.30.40.50.60.70.80.90 1.0 WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS 036 COOLING 1200 354 396 436 511 548 599 641 677 721 036 COOLING (FIELD SETTING) 1350 442 503 563 606 648 685 721 774 826 036 036 036 HEATING (2 TUBE) HEATING (3 TUBE) HEATING (4 TUBE) 700 1250 1350 207 383 442 231 432 503 254 478 563 298 543 606 320 581 648 349 628 685 048 COOLING 1400 427 476 525 599 673 716 759 812 865 048 COOLING (FIELD SETTING) 1600 476 532 587 687 786 872 958 994 1030 048 048 048 HEATING (3 TUBE) HEATING (4 TUBE) HEATING (5 TUBE) 1525 1600 1600 458 476 476 511 532 532 564 587 587 654 687 687 744 786 786 814 872 872 1. Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 7 and 8. 10 Unitary Products Group

TABLE 6: BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS 1 MODEL # DNP MODE (COOLING / HEATING) CFM EXTERNAL STATIC PRESSURE - IWG.20.30.40.50.60.70.80.90 1.0 WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS 036 COOLING 1200 354 396 436 511 548 599 641 677 721 036 COOLING (FIELD SETTING) 1350 442 503 563 606 648 685 721 774 826 036 036 036 HEATING (2 TUBE) HEATING (3 TUBE) HEATING (4 TUBE) 700 1250 1350 207 383 442 231 432 503 254 478 563 298 543 606 320 581 648 349 628 685 048 COOLING 1400 427 476 525 599 673 716 759 812 865 048 COOLING (FIELD SETTING) 1600 476 532 587 687 786 872 958 994 1030 048 048 048 HEATING (3 TUBE) HEATING (4 TUBE) HEATING (5 TUBE) 1525 1600 1600 458 476 476 511 532 532 564 587 587 654 687 687 744 786 786 814 872 872 1. Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 7 and 8. Unitary Products Group 11

TABLE 7: ADDITONAL STATIC PRESSURE RESISTANCE - 3 TON (DNP036) 1 RESISTANCE, IWG DESCRIPTION CFM 500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600 WET EVAPORATOR COIL.01.01.01.02.03.04.05.06.07.08.09.09 ECONOMIZER 2.00.00.00.01.01.01.01.02.03.04.05.06 FILTER FRAME KIT.01.02.04.06.08.10.13.16.17.18.19.20 1. Deduct these resistance values from the available external static pressure shown in Tables 5 and 6. 2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation. TABLE 8: ADDITIONAL STATIC PRESSURE RESISTANCE - 4 TON (DNP048) 1 RESISTANCE, IWG DESCRIPTION CFM 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000 WET EVAPORATOR COIL.02.03.04.05.06.07.07.08.09.09 ECONOMIZER 2.02.02.02.03.03.04.04.04.05.05 FILTER FRAME KIT.04.04.05.05.06.07.08.09.10.11 1. 2. Deduct these resistance values from the available external static pressure shown in Tables 5 and 6. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation. 6 0-4 5 6 ) 6 7 16 6-4 1 ) 5 6 4 12 6-0 - ) 6 ) 6 1+ 12 ) 6 4 5 0 7, * - 5-6 ) 6! # ) 2 5 4 ), - 5 E E K M EHA I E A B & ) 9 / M EHA I D K @ > A K I A @ B H= BEA @ E I J= A @ " L JM EHA 4 / 4 / 9 ; 9 ; " 8 6 6 4 ) 5 4-4 + + 2 4 / 4 ) ) * - 6 0-4 5 6 ) 6 ; FIGURE 2 : FIELD WIRING DIAGRAM CONTROL WIRING 12 Unitary Products Group

+ 6 ) + 6 4 + 6 ) + 6 4 / 4 7, 7 / 4 - - 4 6 - - + 6 4 1+ ), ) 6 ) 6 ) * - 5 6 5 1-6 0 -, 15 + - + 6 1-, 5 7 2 2 1-,, 15 + - + 6 5 1 / - 2 0 ) 5-2 9-4 5 7 2 2 ; / 4 7, 7 / 4 - - 4 6 - - + 6 4 1+ ), ) 6 ) 6 ) * - 5 6 5 1-6 0 -, 15 + - + 6 1-, 5 7 2 2 1-,, 15 + - + 6 6 0 4 - - 2 0 ) 5-2 9-4 5 7 2 2 ; FIGURE 3 : POWER WIRING FIELD DIAGRAM TABLE 9: ELECTRICAL DATA Model DNP POWER SUPPLY VOLTAGE LIMITATIONS 1 MIN. MAX. COMPRESSOR RLA LRA COND. FAN MOTOR FLA SUPPLY AIR BLOWER MOTOR FLA MINIMUM CIRCUIT AMPACITY MAX. FUSE SIZE AMPS 2 MAX. HACR BREAKER SIZE AMPS UNIT POWER FACTOR 036 208/230-1-60 187 253 17.2 88 1.1 6.8 29.4 45 45 0.96 036 208/230-3-60 187 253 11.4 77 1.1 6.8 22.2 30 30 0.96 036 460-3-60 414 504 5.7 39 0.6 6.8 14.8 20 20 0.96 048 208/230-1-60 187 253 23.4 126 1.9 9.1 39.5 60 60 0.96 048 208/230-3-60 187 253 13 93 1.9 9.1 26.5 35 35 0.96 048 460-3-60 414 504 6.4 46.5 1.0 9.1 18.4 25 25 0.96 TRANSFORMER SIZE (VA) 40 75 75 40 75 75 1. Rated in accordance with ARI Standard 110, utilization range "A". 2. Dual element, time delay type. Unitary Products Group 13

8-6 ) 14 7 6-6 0, * 9-4 5-4 8 1+ - ) + + - 5 5 + 2 ) 4 6-6 2 ) - / ) 5 5 7 2 2 ; ", 1) 0-2 6 1 + - + 6 1 +, - 5-4 + 1 7 16 +, - 5 ) 6 - + - + 6 1! " 2 6 1 6 4 ) 2 4 - + -, -, )! & 0 1/ 0 8 6 ) / - +! &, 1) + 7 6 *!! " 0 1/ 0 8 6 ) / - + % &, 1) + 7 6 / ) 5 5 7 2 2 ; ", 1) + 7 6 2 6 1 + - + 6 1 4-4 1/ - 4 ) 6 + - + 6 1 5 + * 7 5 6 1 ) 14 1-6 7 8-4 5 4 6 9 8 6 ) / - +! &, 1) + 7 6 : % & 0 - " % " 8-4 )!! #! & # &! " " ' & / ) 5 - - + 6 4 1+ + 6 4 5-4 8 1+ - ) + + - 5 5 8-4 ) + 2 ) 4 6-6 2 ) - All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. FIGURE 4: UNIT DIMENSIONS - FRONT TABLE 10: UNIT DIMENSIONS FRONT UNIT SIZE DIMENSION A B 036 33-1/2 18-1/4 048 41-1/2 23-1/8 TABLE 11: UNIT MINIMUM CLEARANCES 12 CLEARANCES FRONT 36 BACK 0 LEFT SIDE (Filter-Access) 24 RIGHT SIDE 12 BELOW UNIT 3 0 ABOVE UNIT 4 36 (For Condenser Air Discharge) 1. A 1 clearance must be provided between any combustible material and the supply air ductwork. 2. The products of combustion must not be allowed to accumulate within a confined space and recirculate. 3. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material. 4. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet. 14 Unitary Products Group

HIGH VOLTAGE CONN. 1 3/32" DIA. KNOCKOUT 87/8 11 7/8 19 1/4 FRONT GAS SUPPLY 1 5/8" DIA. KNOCKOUT (1/2" NPTI CONNECTION) LOW VOLTAGE CONN. 7/8" DIA. KNOCKOUT 45/8 CONDENSATE DRAIN 3/4"' NPTI 26 3/4 6 FIGURE 5: UNIT DIMENSIONS - FRONT & BOTTOM 5 1, - 5 7 2 2 ; ) 14 2-1 / " +, - 5-4 + 1 &! & * 6 6 5 7 2 2 ; ) 14 2-1 / " * ) +!! & 5 1, - 4-6 7 4 ) 14 2-1 / " "! #! " ' ' $ #!! "! " # * 6 6 4-6 7 4 ) 14 2-1 / FIGURE 6: UNIT DIMENSIONS - BACK & BOTTOM Unitary Products Group 15

1-, 5 7 2 2 1-,, 15 + - + 6 5 9 16 + 0 + ) 6 -, 6 4 - ) 4 7 16 6 2 9-4 5 7 2 2 ; + 6 4 9 14 1 / 6 1, 4 6 0-4 5 6 ) 6 4-6 7 4 ) 14, 7 + 6 5 7 2 2 ; ) 14, 7 + 6 6 / ) 5 5 7 2 2 ; 1 - ) 7 ) / ) 5 5 0 7 6 8 ) 8 - FIGURE 7: TYPICAL SLAB ON GROUND INSTALLATION ) 7 ) / ) 5 5 0 7 6 8 ) 8-1-, 5 7 2 2 1-,, 15 + - + 6 5 9 16 + 0 7 6 -, 7 16 6 2 9-4 5 7 2 2 ; 6 / ) 5 5 7 2 2 ; 1 - FIGURE 8: + 6 4 9 14 1 / 6 1, 4 6 0-4 5 6 ) 6 TYPICAL ROOF CURB INSTALLATION 4-6 7 4 ) 14, 7 + 6 5 7 2 2 ; ) 14, 7 + 6 16 Unitary Products Group

4 + 7 4 * 1 5 6 ) ) 6 1 4 - ) 4, 7 + 6 4 + 7 4 * 1 5 6 ) ) 6 1 * 6 6, 7 + 6 5 ) * / 4 7, 1 5 6 ) ) 6 1 FIGURE 9: TYPICAL DUCT APPLICATIONS TABLE 12: UNIT WEIGHTS AND CENTER OF GRAVITY UNIT SIZE SHIPPING WEIGHT (lbs.) OPERATING WEIGHT (lbs.) CORNER WEIGHTS (location, lbs.) A B C D 036 400 395 100 96 98 101 048 475 470 133 130 102 104 ECONIMIZER (lbs.) 40 ROOF CURB (lbs.) 8-70 14-75 "D" FRONT OF UNIT CENTER OF GRAVITY "A" "C" 49 1/8 "B" 25 25 47 1/4 FIGURE 10: UNIT CENTER OF GRAVITY Unitary Products Group 17

4 - + -, -,, 7 + 6 5 1 - % : $! " "! "! " % # & % " " # & "! "! 2-1 / 4 4-6 7 4 ) 14, 7 + 6 2-1 / 4 5 7 2 2 ; ) 14, 7 + 6 " 4 - + -, -,, 7 + 6 5 1 - % & : FIGURE 11: ROOF CURB DIMENSIONS 1 1. 8 Roof curb also available! " : 9 1, - / ) 5-6 1 / 4 + 7 4 * 4 ) - ), ), 7 + 6 5 7 2 2 4 6 5 7 4 ) + - 5 7 16 * ) 5-7 16 * ) 5-4 ) 1 9, ) 1-4 & 1 ) * 8-1 15 0 -, 4 + 7 6-4 ) 5 0 1 / " + ) 6 5 6 4 12 + 7 4 * 4 ) - 1 5 7 ) 6 1 ), 4 1 / ) 6-4 1) 1 5 7 ) 6 1 4, - + 6 ), 4 1 / ) 6-4 1) FIGURE 12: ROOF CURB CROSS SECTION 18 Unitary Products Group

FIGURE 13: TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPLY) Unitary Products Group 19

FIGURE 14: TYPICAL WIRING DIAGRAM (208/230-3-60 POWER SUPPLY) 20 Unitary Products Group

FIGURE 15: TYPICAL WIRING DIAGRAM (460-3-60 POWER SUPPLY) Unitary Products Group 21

TYPICAL WIRING DIAGRAM NOTES (SEE FIGURES 13, 14, 15 AND 16) 1. All field wiring to be accomplished following city, local and/or national codes in effect at time of installation of this unit. 2. Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation if any of the wire as supplied with this unit must be removed it must be replaced with type 105 C, 600V wire or equivalent clearly renumbered for identification. Verify proper operation after servicing. 3. Motors are inherently protected 4. See unit nameplate for maximum fuse size and minimum circuit ampacity. 5. Select indoor blower cooling speed from unit wiring diagram Table 1. Heating speed is preset at the factory. 6. If both LR and ASCT are present, wire 801/BL and 805/ BL are connected to ASCT-3 if LR only is present wire 801/BL and 805/BL are connected to M1 coil. If ASCT only is present wire 202/Y is connected to ASCT-3. If neither LR or ASCT are present, Wire 202/Y is connect to M1 coil. 7. Shunt contact also used with crankcase heater. (Optional). CAUTION Open all disconnects before servicing this unit. ALS ASCT COMPR EAC FS HP HSP HUM LP LR LS M1 M2 PS RC1/RC2 RS T1 T2 TB2 LEGEND : AUXILLARY LIMIT SWITCH ANTI-SHORT CYCLE TIMER (OPTIONAL ACCESSORY) COMPRESSOR ELECTRIC AIR CLEANER RELAY OUTPUT ON CONTROL BOARD, 24-1-60, 18VA MAX. FREEZESTAT SWITCH (OPTIONAL ACCESSORY) OPEN @ 25 0 F HIGH PRESSURE SWITCH (OPTIONAL ACCESSORY) OPENS @ 380 PSIG HOT SURFACE TO PILOT HUMIDIFER RELAY OUTPUT ON CONTROL BOARD, 24-1-60, 18VA MAX. LOW PRESSURE SWITCH (OPTIONAL ACCESSORY) OPEN @ 7 PSIG LOCK OUT RELAY (OPTIONAL ACCESSORY) LIMIT SWITCH CONTACTOR, COMPR. & O.D.FAN CONTACTOR, DRAFT INDUCER MOTOR PRESSURE SWITCH MAKES @.193 IWC NOM. (.33 IWC MAX.) COMPR. START & OUTDOOR FAN RUN CAPACITOR ROLL OUT SWITCH TRANSFORMER, 24V, 40VA TRANSFORMER, 480/240 VOLT TERMINAL BLOCK, 24V, I.D. MOTOR "SPEED" CONNECTION IDENTIFIED TERMINAL ON CAPACITOR ROOM THERMOSTAT 24V CONNECTIONS TB1 ON CONTROL BOARD FACTORY WIRING AND DEVICES OPTIONAL WIRING AND DEVICES FIELD WIRING DNP LEGEND WIRING DIA. FIGURE 16: TYPICAL WIRING DIAGRAM LEGEND 22 Unitary Products Group

Unitary Products Group 23

Subject to change without notice. Printed in U.S.A. Copyright by Unitary Products Group 2002. All rights reserved. Supersedes: Nothing 036-21366-001-A-0302 Unitary 5005 Norman Products York OK Group Drive 73069