Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Similar documents
Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Purdue e-pubs. Purdue University

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

A study of Transient Performance of A Cascade Heat Pump System

Performance of CO2 Cycles with a Two-Stage Compressor

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Scroll Compressor for Mobile HVAC/R Application

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

ABSTRACT. Title of Document: EXPERIMENTAL EVALUATION OF A. Laeun Kwon, Master of Science, Dr. Yunho Hwang, Mechanical Engineering

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

EN aquatech.piovan.com

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Low GWP Refrigerants for Air Conditioning Applications

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Experimental Study on the Performance of Twisted Capillary Tube

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

High Efficiency R-134a Compressor for Domestic Refrigerator

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

INFLUENCE OF REFRIGERANT CHARGE AND AIR INLET TEMPERATURES ON THE PERFORMANCE OF AN AUTOMOTIVE AIR CONDITIONING SYSTEM

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

THE COOLING CAPACITY AND PRESSURE DROP IN A HYBRID CLOSED CIRCUIT COOLING TOWER

Low Global Warming Refrigerants For Commercial Refrigeration Systems

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Study on a novel variable capacity technology and control strategy for refrigerated shipping container unit

ACMVTECH HIGH EFFICIENCY UNITARY AHU

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Air-Cooled Heat Exchanger Performance for R410A

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

System Modeling of Gas Engine Driven Heat Pump

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Air Cooled Packaged Systems AIRAH Back to Basics

Customers. The core of our innovation. Feeding&Conveying Drying Dosing Temperature Control Refrigeration. Granulation

Variable refrigerant flow (VRF) systems

EXPERIMENTAL INVESTIGATION ON VARIABLE SPEED OPERATION OF AIR CONDITIONING

PERFORMANCE EVALUATION OF CO 2 HEAT PUMP HEATING SYSTEM ABSTRACT 1. INTRODUCTION

THE PERFORMANCE OF COMPACT POLYMER HEAT EXCHANGER USING SPECIALIZED TEST FACILITY

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

Exploring the Performance Characteristics of CO2 Cycles in a Breadboard-Type Test Facility

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

DEEPAK PALIWAL, S.P.S.RAJPUT

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Transcription:

urdue University urdue e-ubs International Refrigeration and Air onditioning onference School of Mechanical Engineering 2008 erformance haracteristic and Optimization of a Simultaneous eating and ooling Multi eat ump oon Kang Korea University Youngju Joo Korea University yenjoon Jung Korea University Yongchan Kim Korea University Follow this and additional works at: http://docs.lib.purdue.edu/iracc Kang, oon; Joo, Youngju; Jung, yenjoon; and Kim, Yongchan, "erformance haracteristic and Optimization of a Simultaneous eating and ooling Multi eat ump" (2008). International Refrigeration and Air onditioning onference. aper 980. http://docs.lib.purdue.edu/iracc/980 his document has been made available through urdue e-ubs, a service of the urdue University Libraries. lease contact epubs@purdue.edu for additional information. omplete proceedings may be acquired in print and on D-ROM directly from the Ray W. errick Laboratories at https://engineering.purdue.edu/ errick/events/orderlit.html

2254, age 1 erformance haracteristic and Optimization of a Simultaneous eating and ooling Multi eat ump oon Kang 1, Youngju Joo 2, yenjoon Jung 3, Yongchan Kim 1 * 1 Department of Mechanical Engineering, Korea University Anam-Dong, Sungbuk-Gu, Seoul, Korea +82-2-32904022, khlabkang@empal.com 2 Graduate School of Mechanical Engineering, Korea University Anam-Dong, Sungbuk-Gu, Seoul, Korea +82-2-9215946, yjjoo@korea.ac.kr 3 Graduate School of Mechanical Engineering, Korea University Anam-Dong, Sungbuk-Gu, Seoul, Korea +82-2-9215946, haiba@korea.ac.kr 1 *Department of Mechanical Engineering, Korea University Anam-Dong, Sungbuk-Gu, Seoul, Korea +82-2-32903366, yongckim@korea.ac.kr ABSRA In this study, a simultaneous heating and cooling multi heat pump having four indoor units and an outdoor unit was designed and constructed. he working of the system was R-410A. he operating characteristics and performances of the heat pump system were measured at five operation modes: cooling-only, cooling-main, heating-only, heatingmain and entire heat recovery operation. o improve the system efficiency and reliability, the system in the heat recovery operation was optimized by varying the compressor rotation speed and EEV opening. In the simultaneous heating and cooling operation, the system O increased by using the heat recovery operation with the optimization of control parameters. 1. INRODUION ooling period in buildings is increasing due to the widespread use of office equipment with high heat flux and the development of architectural engineering technologies. Even in the winter season, both cooling and heating are required in buildings such as office buildings, hotels, hospitals, and convention centers, where cooling load exists in the winter season. Although multi heat pumps are being used more because of their advantages in energy conservation and space saving, conventional multi heat pumps can not satisfy all the needs of various customers because they do not have the function of the simultaneous heating and cooling. herefore, air-conditioner industry is working hard to develop the simultaneous heating and cooling heat pump and increase the system O. revious studies on multi heat pumps concentrated on the improvement of the system performance in the heatingonly and cooling-only operations. owever, studies on the simultaneous heating and cooling heat pump are very limited in literature. herefore, in this study, the state-of art technologies on the simultaneous heating and cooling heat pump were investigated experimentally. he technologies used in the development of multi heat pumps mainly focused on compressor capacity control, refrigerant flow rate control, and alternative refrigerants. he control of the compressor speed in multi heat pumps has been widely adopted to modulate the compressor capacity. In the early stage of compressor development, alternating current (A) inverter technology for compressor speed control was widely used (Aprea et al., 2006). owever, recently, direct current (D) inverter technology is increasingly used International Refrigeration and Air onditioning onference at urdue, July 14-17, 2008

S 2254, age 2 because of its energy saving efficiency and high control accuracy. he control of the refrigerant flow rate was remarkably improved by using electronic expansion valve (EEV) (Qifang et al., 2007; ark et al., 2007), which can precisely control the refrigerant flow rate according to the variations of operating conditions. he compressor inverter and EEV are essential components in the development of multi heat pumps (hoi and Kim, 2003; ark et al., 2001) In this study, a conventional multi heat pump having two operation modes of cooling-only and heating-only was redesigned and reconstructed for the simultaneous heating and cooling operation, with the adoption of EEVs and a variable speed compressor. he operating characteristics and performances of the simultaneous heating and cooling heat pump with R-410A were measured and analyzed at five operation modes: cooling-only, heating-only, coolingmain, heating-main, and entire heat recovery operations. he simultaneous heating and cooling operation was also optimized experimentally by varying control parameters such as the compressor rotation speed and EEV opening, and the optimum control methods were suggested to improve system O. 2. EXERIMENAL SEU AND ES ROEDURE Fig. 1 shows the schematic diagram of the simultaneous heating and cooling multi heat pump. It was designed to obtain cooling capacity of 8.0 kw and O of 3.2 in the cooling-only operation mode listed in able 1. Four indoor units were connected to one outdoor unit, and the designed capacity of each indoor unit was 2.0 kw. A hermetic rotary compressor having a blushless direct current (BLD) motor was adopted for the optimum control of compressor speed. Its cooling capacity and power consumption were 8.0 kw and 2.5 kw, respectively, at the compressor speed of 3,500 rpm and the ARI test condition, where evaporation and condensation temperatures were 7.2 o and 54.4 o, respectively. An EEV, consisting of a stepping motor and a needle valve, was adopted for the optimum control of refrigerant flow rate, and its orifice diameters were 1.4 mm for the indoor unit and 1.8 mm for the outdoor unit, with control resolution of 500 steps. he EEV was fully-closed at 0 step and fully-opened at 500 steps. he heat exchangers for the indoor and outdoor units consisted of micro-fin tubes and slit-fins. he indoor heat exchanger had an evaporation capacity of 2.2 kw at the evaporation temperature of 7.2 o and the air flow rate of 6.0 m 3 /min. he outdoor heat exchanger had the condensation capacity of 11.34 kw at the condensation temperature of 54.4 o and air flow rate of 37.5 m 3 /min. As shown in able 2, the simultaneous heating and cooling heat pump has five operation modes: heating-only, cooling-only, heating-main, cooling-main, and entire heat recovery operations. In the heating-only or cooling-only operation mode, all the indoor units operate at the same mode. In the heating-main operation mode, the number of cooling-operation indoor units is more than that of heating-operation indoor units, and vice versa in the cooling- m Disc. gas line MU IDU (No.1) V V Disc. gas bypass line Flow meter IDU (No.2) EEV(1) 4-way valve EEV (5) ODU eat exchanger Suct. gas line IDU (No.3) EEV(2) EEV(3) Oil Seperator Flow meter m Liquid line Suct. gas line IDU (No.4) EEV(4) ompressor : For heating Accumulator : For cooling Figure 1: Schematic diagram of the experimental setup International Refrigeration and Air onditioning onference at urdue, July 14-17, 2008

2254, age 3 able 1: Experimental conditions Operating mode IDU for cooling IDU for heating ODU ooling-only 27.0 o / 47.0% R -- 35.0 o / 40.4% R ooling-main 27.0 o / 47.0% R 20.0 o / 59.0% R 35.0 o / 40.4% R Entire-heat recovery 27.0 o / 47.0% R 20.0 o / 59.0% R 7.0 o / 86.9% R eating-main 27.0 o / 47.0% R 20.0 o / 59.0% R 7.0 o / 86.9% R eating-only -- 20.0 o / 59.0% R 7.0 o / 86.9% R able 2: Operating status of indoor units with operation modes Operation mode IDU (no.1) IDU (no.2) IDU (no.3) IDU (no.4) ooling-only ooling ooling ooling ooling ooling-main ooling ooling ooling eating Entire heat recovery ooling ooling eating eating eating-main ooling eating eating eating eating-only eating eating eating eating main operation mode. In these operation modes, the total or partial heat absorbed by cooling-operation indoor unit is reused for heating; this is referred to as heat recovery operation. In the entire heat recovery operation mode, the number of cooling-operation indoor units is matched with that of heating-operation indoor units without refrigerant flow to the outdoor heat exchanger, and all the heat absorbed by cooling-operation indoor units is reused for heating. For the individual heating and cooling operations of indoor units, a mode changing unit (MU) was installed between the outdoor unit and indoor units. It consisted of header pipes, branch pipes and solenoid valves, and on/off operations of the solenoid valves were determined according to the operation modes of indoor units. he three connection pipes of discharge-gas, suction-gas and liquid pipes were installed between the MU and the outdoor unit, whereas the conventional multi heat pump had only two connection pipes of gas and liquid pipes between the indoor units and the outdoor unit. he performance of the simultaneous heating and cooling multi heat pump was measured in an air-enthalpy type calorimeter. he measurement devices for air flow rate, temperature and humidity were attached to each indoor unit to measure individual performance of each indoor unit. A resistance temperature detector (t 100 ) was used to measure dry and wet air temperatures, and its accuracy was 0.15 o. he air flow rate of the indoor unit was measured by using the nozzle method. he nozzle diameter was 76.2 mm, and the measurement range was between 4.2-9.7 standard m 3 /min (SMM). he pressure difference across the nozzle was measured by using an electronic differential pressure transducer with an accuracy of 0.25%. he power consumption of the heat pump was measured by using an electronic power meter with an accuracy of 0.2%. he operating status of the indoor units according to operation mode is shown in able 2. he temperature and humidity conditions for the indoor and outdoor rooms in each operation mode are shown in able 1. he air flow rate and capacity of each indoor unit were calculated based on ISO/DIS 15042. 3. RESULS AND DISUSSION In the cooling-only operation at the compressor rotation speed of 3,500 rpm, the optimum system O was observed at the refrigerant charge of 3,900g and the EEV opening of 110 steps in the indoor units. When the operation mode changed from the cooling-only to cooling-main, the evaporation pressure decreased due to the decrease in the number of cooling-operation indoor unit. he condensation pressure also decreased because the heating-operation indoor unit worked as a condenser in the cooling-main operation. he total and average cooling capacities in the cooling-only operation were 8,248.9 W and 2,062.2 W, respectively. he total capacity in the cooling-main operation was 8,120.9 W, which was 1.6% lower than the value in the cooling-only operation. he average cooling capacity in the cooling-main operation was 2,276.3 W, which was 10.4% higher than the value in the cooling-only operation. owever, the heating capacity in the cooling-main operation was 1,291.9 W, which was much lower than the designed capacity of 2.0 kw, because the bypassed refrigerant flow rate to the heatingoperation indoor unit was very low, only 15.4% of the total flow rate. he O in the cooling-main operation was International Refrigeration and Air onditioning onference at urdue, July 14-17, 2008

2254, age 4 3.461, which was 10.8% higher than the value in the cooling-only operation due to the heat recovery operation in the cooling-main operation. In the cooling-main operation, the bypassed refrigerant flow rate to the heating-operation indoor unit had to be controlled optimally to improve the heating capacity and system efficiency. he bypassed flow rate was increased by decreasing the EEV opening of the outdoor unit. he bypass flow ratio R bp was defined as the ratio of the bypass flow rate to the total flow rate. As the bypassed flow rate increased from 15.4% to 38.0%, the flow rate to the heating-operation indoor unit was increased by 84.3%. owever, at the bypassed flow rate of 38.0%, the total flow rate was decreased by 25.3% over the value at the bypass flow rate of 15.4%, due to the generation of uncondensed refrigerant at the exit of the heating-operation indoor unit. Fig. 2 shows the variations of average cooling and heating capacities with the bypassed flow ratio to the heating-operation indoor unit. With the increase of the bypassed flow ratio, the heating capacity increased until the bypass flow ratio of 31%, while the average cooling capacity decreased from the bypass flow ratio of 31% with the rapid decrease of the total flow rate. At the bypassed flow ratio of 27%, the average cooling and heating capacities were 2,283.6 W and 2,070.1 W, respectively, satisfying the designed capacity of 2.0 kw. With the optimization of refrigerant flow rate to the heating-operation indoor unit, the O in the cooling-main operation was 3.807 which increased by 21.8% over the value in the cooling-only operation. he operating characteristics in the heating-only operation were measured at the refrigerant charge amount of 3,900 g and the compressor speed of 3,500 rpm, maintaining the EEV openings of the indoor and outdoor units at 500 and 320 steps, respectively. he operating characteristics in the heating-main operation were also measured at the same conditions as the heating-only operation, except that the EEV opening of the cooling-operation indoor unit was changed to 110 steps. In the heating-main operation, the evaporation pressure increased due to the cooling operation of an indoor unit. Simultaneously, the condensation pressure also increased due to the decrease in the number of heating-operation indoor unit. he total flow rate in the heating-main operation was increased by 11.2% over the value in the heating-only operation due to the increase of compressor suction pressure. he average flow rate to the heating-operation indoor unit in the heating-main operation increased by 48.4% over the value in the heating-only operation, while the flow rate to the cooling-operation indoor unit decreased by 43.6% from the average flow rate to the heating-operation indoor unit. In the heating-main operation, the imbalance in refrigerant distribution resulted in lower cooling capacity. he average heating capacity in the heating-main operation was 2,662.1 W, which was 34.0% higher than the value of 1,986.7 W in the heating-only operation. he cooling capacity was 1,761.5 W, which was 33.8% lower than the average heating capacity in the heating-main operation. 2.4 Average capacity (kw) 2.2 2.0 1.8 1.6 1.4 ooling capacity eating capacity 1.2 15 20 25 30 35 40 R bp (%) Figure 2: Variations of average cooling and heating capacities with bypassed flow ratio in cooling-main operation International Refrigeration and Air onditioning onference at urdue, July 14-17, 2008

2254, age 5 3.0 3.0 Average capacity (kw) 2.5 2.0 1.5 R S = 2.5 100% R S = 80% R S = 70% qc qh 2.0 1.5 1.0 0 20 40 60 80 100 EEV opening of ODU (%) 1.0 0 20 40 60 80 100 EEV opening of IDU c (%) Figure 3: Variations of average cooling and heating capacities with EEV openings in heating-main operation In the heating-main operation, the cooling capacity can be increased by increasing the refrigerant flow rate to the cooling-operation indoor unit. o increase the flow rate to the cooling-operation indoor unit, two methods were considered in this study: (a) decreasing the EEV opening of the outdoor unit and (b) increasing the EEV opening in the cooling-operation indoor unit. An experiment by adopting the first method was performed: the EEV opening of the outdoor unit was decreased from 320 steps (64% of full opening), and the EEV opening in the cooling-operation indoor unit was maintained at 110 steps (22% of full opening). he flow rate to the cooling-operation indoor unit was increased by decreasing the EEV opening in the outdoor unit, even though the total flow rate was decreased. he experiment with the adoption of the second method was conducted by increasing the EEV opening from 110 steps, while the EEV opening in the outdoor unit was maintained at 320 steps. As the EEV opening in the coolingoperation indoor unit increased, the flow rate to the cooling-operation indoor unit increased with the slight increase in the total flow rate. Fig. 3 shows the variations of average cooling and heating capacities with the EEV opening and compressor speed in the heating-main operation. As the EEV opening in the outdoor unit decreased from 64% to 20% at the compressor speed of 3,500 rpm, the cooling capacity increased from 1,761.5 W to 2,889.2 W, showing an increase of 64.0% due to the decrease of the superheat region in the evaporator. he average heating capacity increased from 2,662.1 W to 2,869.1 W, showing an increase of 7.8% due to the increase of the condensation pressure. owever, the condensation pressure increased significantly with the decrease of the EEV opening in the outdoor unit. As the EEV opening in the cooling-operation indoor unit increased from 22% to 80% at the compressor speed of 3,500 rpm, the cooling capacity increased from 1,761.5 W to 2,723.2 W, showing the increase of 54.6%, while the average heating capacity showed no difference with a constant condensation pressure. he cooling capacity remained constant beyond the EEV opening of 60%, because the superheat region did not exist beyond the EEV opening of 60%. he compressor speed was optimized to increase the system O. he compressor speed ratio R cs was defined as the ratio of the actual compressor speed to the reference value of 3,500 rpm. From the experiments with the variations of the EEV opening in the outdoor unit and the compressor speed, the average heating and cooling capacities were 2,025.7 W and 2,041.5 W, respectively, at the EEV opening of 30% and the compressor speed ratio of 70%. From the experiments with the variations of the EEV opening in the cooling-operation indoor unit and the compressor speed, the average heating and cooling capacities were 2,067.8 W and 2,102.3 W, respectively, at the EEV opening of 40% and the compressor speed ratio of 80%. o improve the system efficiency in the heating-main International Refrigeration and Air onditioning onference at urdue, July 14-17, 2008

2254, age 6 operation, the method decreasing the EEV opening in the outdoor unit with the modulation of the compressor speed is recommended, while the condensation pressure should be monitored and restricted not to increase over a limit. In the entire heat recovery operation, the EEV openings in the cooling-operation indoor units were set to 110 steps and those in the heating-operation indoor units were set to 500 steps (full opening) with the refrigerant charge amount of 3,900 g. In the preliminary tests at the compressor speed of 3,500 rpm, the condensation pressure increased up to 4,500 ka, resulting in an abnormally-high compression ratio. It was impossible to maintain continuous operation at the compressor speed of 3,500 rpm due to the possibility of compressor malfunction, even though the average cooling and heating capacities were higher than the values in the other operation modes. For the reliability and efficiency of the system, therefore, the compressor speed should be controlled at an optimum value. Fig. 4 shows the variations of average capacity and power consumption with compressor speed in the entire heat recovery operation mode. he average cooling capacity at the compressor speed ratio of 50% was 2,367.1 W, which was 14.8% higher than the value in the cooling-only operation. he average heating capacity at the compressor speed ratio of 50% was 2,232.6 W, which was 12.4% higher than the value in the heating-only operation. he power consumption at the compressor speed ratio of 50% was 1,196.6 W, which was 45.3% and 49.6% lower than the values in the cooling-only and heating-only operations, respectively. For the entire heat recovery operation mode, the average capacity of each indoor unit satisfied the designed capacity of 2.0 kw at the compressor speed ratio of 50%, resulting in lower power consumption. Fig. 5 shows the variation of O with the compressor rotation speed in the entire heat recovery operation mode. he O at the compressor speed ratio of 50% was 7.688, which was 246.0% and 233.3% higher than the values in the cooling-only and heating-only operations, respectively. his was due to lower power consumption with the decrease of compressor speed. he variation of O in the entire heat recovery operation mode was higher than the values in the cooling-only and heating-only operations. herefore, in the entire heat recovery operation mode, the control resolution on the compressor speed must be considered to minimize the variation of the system efficiency. he test results showed that the system efficiency of the simultaneous heating and cooling heat pump was improved by using the heat recovery operation with the optimization of the compressor speed. Average capacity (kw) 4 3 2 1 Average capacity ower consumption Entire-heat recovery mode ooling capacity eating capacity ooling-only mode eating-only mode 0 0 20 40 60 80 100 120 140 ompressor speed ratio, R S (%) 8 6 4 2 ower consumption (kw) Figure 4: Variations of average capacity and power consumption with compressor speed in entire-heat recovery operation International Refrigeration and Air onditioning onference at urdue, July 14-17, 2008

2254, age 7 12.0 10.0 Entire-heat recovery mode ooling-only mode eating-only mode O 8.0 6.0 4.0 2.0 20 40 60 80 100 120 140 ompressor speed ratio, R S (%) Figure 5: Variation of O with compressor speed in entire-heat recovery operation 5. ONLUSIONS For the simultaneous heating and cooling operations of each indoor unit, the multi heat pump having four indoor units and one outdoor unit was redesigned and reconstructed with the adoption of EEVs and a variable speed compressor. he operating characteristics and performance of the simultaneous heating and cooling heat pump were measured and analyzed in five operation modes: cooling-only, heating-only, cooling-main, heating-main and entire heat recovery operations. he heat recovery operation was optimized by varying the control parameters such as the compressor speed and the EEV opening. With the optimization of the bypassed flow rate to the heating-operation indoor unit, the O in the cooling-main operation increased by 21.8% over the value in the cooling-only operation due to heat recovery. In the heating-main operation, the method decreasing the EEV opening in the outdoor unit showed higher system O than the method increasing the EEV opening in the cooling-operation indoor unit. he O in the heating-main operation was 53.5% higher than the value in the heating-only operation. For the entire heat recovery operation, the average capacity of each indoor unit satisfied the designed capacity at the compressor speed ratio of 50%, resulting in lower power consumption and thus yielding the O of 7.688, which was 246.0% and 233.3% higher than the values in the cooling-only and heating-only operations, respectively. From the experimental results, in the simultaneous heating and cooling operation, the system O increased by using the heat recovery operation with the optimization of control parameters. NOMENLAURE O IDU ODU rpm R R coefficient of performance indoor unit outdoor unit rotation per minute ratio relative humidity Subscripts International Refrigeration and Air onditioning onference at urdue, July 14-17, 2008

2254, age 8 c cs bp h cooling compressor speed bypass heating REFERENES Aprea,., Mastrullo, R., Reno,., 2006, Experimental analysis of the scroll compressor performances varying its speed, Applied hermal Engineering, Vol. 26: pp. 983-992. ASRAE Guideline 2, 1986, Engineering Analysis of Experimental Data, ASRAE, Atlanta, GA, USA. hoi, J.M., Kim, Y.., 2003, apacity modulation of an inveter-driven multi-air conditioner using electronic expansion valves. Energy, Vol. 28: pp. 141-155. ISO/DIS 15042, 2005, Multiple Split-System Air-onditioners and Air-to-Air eat umps - esting and Rating for erformance. ISO, Geneva, Switzerland. Kim, M.., Bullard,.W., 2001, Dynamic characteristics of a R-410A split air-conditioning system, International Journal of Refrigeration, Vol. 24: pp. 652-659. ark,.s., ho,.y., Lee, Y.., Kim, Y.., 2007, Mass flow characteristics and empirical modeling of R22 and R410A flowing through electronic expansion valves, International Journal of Refrigeration, Vol. 30, pp. 1401-1407. ark, Y.., Kim, Y.., Min, M.K., 2001, erformance analysis on a multi-type inverter air conditioner, Energy onversion and Management, Vol. 24, pp. 1607-1621. Qifang, Y., Jiangping,., Zhijiu,., 2007, Experimental investigation of R407 and R410A flow through electronic expansion valve, Energy onversion and Management, Vol. 48, pp.1624-1630. AKNOWLEDGEMEN his work was supported by a grant (2006-E-M11--05-0-000) from the Korea Energy Management orporation. International Refrigeration and Air onditioning onference at urdue, July 14-17, 2008