THE EFFECTS OF HUMIDITY, COMPRESSOR OPERATION TIME AND AMBIENT TEMPERATURE ON FROST FORMATION IN AN INDUSTRIAL FRIDGE *

Similar documents
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Experimental Study of Initial Process of Frost on Heat Exchanger Surface of Refrigerated Transport Vehicle

Global Journal of Engineering Science and Research Management

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Theoritical Analysis For Miniature Vapor Compression Cycle Performance Using Microchannel And Finned Tube Condenser

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

2. HEAT EXCHANGERS MESA

Frost Growth Detection Using Capacitive Sensor

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

An Experimental Study on Drying of Pistacia Terebinthus in a Fixed Bed Dryer

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Development and Application of Micro Channel Heat Exchanger for Heat Pump

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

A Statistical Analysis of a Liquid Desiccant Dehumidifier/Regenerator in an Air Conditioning System

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Effect of domestic storage and cooking conditions on the risk distribution in ready to cook meat products

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Thermal Performance of a Loop Thermosyphon

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Research Article / Araştırma Makalesi EXPERIMENTAL INVESTIGATION OF R600A REFRIGERANT FLOW INSIDE ADIABATIC CAPILLARY TUBE

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Influence of temperature and drying air velocity on the kinetics of convective drying in the food industry

MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

Refrigerant Mass and Oil Migration During Start-up Transient

Experimental Study on Frost Height of Round Plate Fin-Tube Heat Exchangers for Mobile Heat Pumps

Heat transfer and heating rate of food stuffs in commercial shop ovens

Real Time Upright Freezer Evaporator Performance Under Frosted Conditions

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Shortcut Model for Predicting Refrigeration Cycle Performance

Experimental Study on Thermal Behavior of a Stainless Steel-Di Water Flat Plate Heat Pipe

Development of Small-diameter Tube Heat Exchanger: Circuit Design and Performance Simulation

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

ENSC 388: Engineering Thermodynamics and Heat Transfer

Induction heating with the ring effect for injection molding plates

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Numerical study of heat pipe application in heat recovery systems

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

The Experimental Research on Grain Storage Heat and Moisture Transfer Siyu Chen 1,2, Wenfu Wu 1,Yan Xu 1,Chunshan Liu 2, Yaqiu Zhang 1, a

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

SIMULATION OF A NEW TYPE GAS-FIRED AIR-COOLED AIR-CONDITIONER. Lin Wang, Xing Xu, Aihua Ma, Yonghui Guo and Xiwen Zhou

The correct citation for this paper is:

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

A New Approach for Modeling of Hot Air-microwave Thin Layer Drying of Soybean

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

中国科技论文在线 Energy Conversion and Management 52 (2011)

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Investigation of Metal and Metal Oxide nanocoating on Fins in HPHE with Silver Water NanoFluid

Thin-layer drying of some Sri Lankan paddy varieties under low humid conditions

Development of Bionic Air Cooler Used in High Temperature Coal Mine

Natural Convection Heat Transfer Augmentation from Heat Sinks using Perforated Fins: A Review

Experimental Study on the Effects of Compression Parameters on Molding Quality of Dried Fish Floss

Analysis of Pullout Resistance of Soil-Nailing in Lateritic Soil

Influences of temperature of vapour-condenser and pressure in the vacuum chamber on the cooling rate during vacuum cooling

THE BEHAVIOR OF LEWIS NUMBER IN FINNED TUBE COOLING COILS UNDER HIGHLY MOIST INLET AIR CONDITIONS

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

PERFORMANCE IMPROVEMENT OF SPLIT AIR CONDITIONER USING EVAPORATIVE COOLING METHOD IN THE CLIMATIC CONDITION OF GUWAHATI, ASSAM

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

DESIGN AND ANLYSIS OF MODIFIED HYBRID SOLAR SYSTEM USING NANO FLUIDS

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

Heat Exchanger Joule-Thomson Transient Cryogenic Refrigeration. Iranian Journal of Chemical Engineering Vol. 14, No. 3 (Summer 2017), IAChE

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

Cassava Chip Drying by Using a Small-Scale Hot-Air Microwave Oven

COP-Based Performance Evaluation of Domestic Refrigerators using Accelerated Flow Evaporators

Measurement of internal pressure and thermal performance in a closed-loop oscillating heat-pipe with check valves (CLOHP/CV)

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Experimental study on the characteristics of longitudinal fin air-heating vaporizers in different seasons

Performance of the Variable Refrigerant Volume Air-Conditioning System. with Heat Recovery

Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers

Transcription:

IJST, Transactions of Mechanical Engineering, Vol. 39, No. M1 +, pp 197-203 Printed in The Islamic Republic of Iran, 2015 Shiraz University THE EFFECTS OF HUMIDITY, COMPRESSOR OPERATION TIME AND AMBIENT TEMPERATURE ON FROST FORMATION IN AN INDUSTRIAL FRIDGE * A. R. TAHAVVOR ** AND S. HOSSEINI Dept. of Mechanical Eng., College of Engineering, Shiraz Branch, Islamic Azad University, Shiraz, I. R. of Iran Email: tahavvor@iaushiraz.ac.ir Abstract Fridges are used in various industries, and heat exchanger is one of the main components of these systems; therefore, efficiency analysis of these systems is very important. In many fridges, frost over the heat exchanger tubes or pipes affects the system operation and reduces heat transfer between the refrigerant and ambient, so defrosting systems are usually used to enhance heat transfer. Designing defrosting systems requires sufficient information about frost formation processes. Therefore, the objective of this study is experimental investigation of frost formation over a heat exchanger pipe in a pilot fridge. To do this, some steps are considered. For distinct cases, experiments are done to collect database for frost parameters under desired conditions. Then, based on experimental measurements some correlations are proposed for practical applications of frost growth and defrosting process over heat exchanger tubes. Keywords Frost formation, fridge, defrost, compressor operation time, humidity 1. INTRODUCTION Processes involving heat and mass transfer from humid air to a cold surface, with simultaneous deposition of frost, are of great importance in a variety of industrial equipment. Frost will form on a surface placed in moist air when the temperature of the surface is below the dew point of air and freezing point of water. The frost formation is influenced by many factors. In addition, fridges are commonly used in various industries and usually frost is formed over heat exchanger tubes. Frost over heat exchanger tubes and pipes influences the system operation and reduces heat transfer between the refrigerant and the ambient. Design and operation of any defrosting system requires sufficient information about frost formation process. According to [1], frost density changes greatly with time, and the crystal growth period and layer growth period are distinguished remarkably. They denote that at transition time, density of frost reaches a specified value that depends on the cold surface temperature, which is the end of early-stage period. Many researchers presented numerical and experimental models to predict frosting process over a circular cylinder subjected to humid air cross [2-6]. Review of literature shows that frost studies for forced convection are extensive. Regarding free convection, [7] carried out some experiments about free convection frost growth over vertical cylinders. Tokura et al. [8] reported experimental results of deposited mass and presented dimensionless correlations for frost thickness, conductivity and density. Tanda and Fessa [9] and [10] experimentally investigated the free convection frost growth in vertical channels and offered some correlations for frost properties such as thickness, density and mass. Chen and Oosthuizen [11] carried out some experiments about frost formation on a cooled horizontal cylinder with two cylinders of different diameters, but during most of the experiments, cylinder surface temperature was Received by the editors July 27, 2014; Accepted November 10, 2014. Corresponding author

198 A. Tahavvor and S. Hosseini not constant. In addition [12] performed some experiments for frost deposition rate on a horizontal cylinder during free convection. Tahavvor and Yaghoubi [13] developed a numerical model to simulate the early-stage of frost formation in natural convection and a correlation is proposed to predict transition time as a function of all relevant parameters. In addition, they carried out several experiments about frost formation. These experiments were performed on a cold horizontal cylinder under natural convection condition and several correlations were proposed for frost properties as a function of all relevant parameters [14, 15]. In another experimental study, researchers investigated the effect of airflow, humidity, refrigerant temperature and fin types on heat transfer rate [16]. They reported that frost formation rate increased when humidity and airflow increased and refrigerant temperature decreased. Iragorry and Tao [17] determined the frost surface temperature using an infrared thermometer and developed an efficient defrosting system according to their measurements. Liu [18] and [19] experimentally studied the effect of surface paint on frost formation. El Cheikh and Jacobi [20] developed a mathematical model for frost growth and densification on flat surfaces. Frost formation in micro-scale is also studied by some researchers [21, 22]. In addition, [23] experimentally studied the frost formation on a fin-and-tube heat exchanger by natural convection. Yao et al. [24] investigated the effect of flat fins over heat exchanger tubes on frost formation. They have tested the exchangers with one and multi rows of tubes. Guo et al. [25] experimentally studied the effect of air source heat pump system and its performance on frost formation. Recently, according to the experimental measurements, Tahavvor et al. [26] presented the fractal-based model to predict frost layer density and thickness. Nevertheless, from a review of the literature it can be seen that few reports are available about experimental study of frost formation on horizontal cylinders under natural convection in industrial applications such as industrial fridges. Therefore, in this study the aim is experimental investigation of frost formation over heat exchanger pipes in a pilot industrial fridge. To do this, some steps are considered. First, for some distinct cases, experiments are carried out to achieve database for frost parameters under desired conditions. Finally, based on the experimental measurements new correlations are proposed for frost properties in practical applications. a) Experimental apparatus 2. EXPERIMENTS In this study, test room is a 5 m 4 m 3 m industrial fridge (in Asalooyeh in the southwest of Iran). Equipment in this fridge allows the user to control ambient temperature and humidity. Test fridge contains both air-cooling unit and humidifier. These units work until the desired temperature and relative humidity are reached. Capacity of the cooling unit compressor is about 42000 BTU H -1 and R22 is used as a refrigerant. Minimum reachable temperature of this fridge is -20 C. Devices used in experimental procedure are listed below: Digital thermometer Temperature sensors Digital psychrometer Humidity sensors Scaled container Each device is calibrated to provide excellent sensitivity and stability. b) Experiments procedure Before each measurement, all surfaces were cleaned of frost and dried and the following steps were followed: IJST, Transactions of Mechanical Engineering, Volume 39, Number M1 + May 2015

The effects of humidity, compressor operation time and 199 Desired temperature and humidity are set and the humidifier and cooling unit are turned on. When the fridge reaches the desired temperature and humidity, data acquisition systems are turned on and the programs for collecting the experimental data are loaded and run. Defrost system is turned on. Water from the defrost stage is collected into the scaled container to measure the amount of defrosted water. Several experiments under various conditions (Table 1) are done according to the described procedure. In the experiments, initial temperature range is between 22~24 C and humidity of the fridge varies between 28~31 % respectively. These initial conditions depend on the atmospheric conditions of Asalooyeh in October and November. Compressor operating time is working time of compressor until it reaches the desired temperature. In addition, some tests are done to investigate the effect of ambient or initial fridge temperature on frost formation. To achieve this aim, fridge temperature and relative humidity are set to -13 C and 90% respectively. Measurements are done for a range of ambient temperature in four periods of a day. Conditions and results of these experiments are listed in Table 2. Also, in all tests, defrost time is set to 40 minutes to defrost all the frost. 3. RESULTS AND DISCUSSIONS Experimental measurements for each test are presented in the last two columns of Table 1 and Table 2. One of the important parameters of energy consumption and cost is compressor operation time. Compressor operating time is the working time of compressor until the desired temperature is reached. Experimental measurements contain compressor operation time (COT) and volume of defrosted water. Table 1. Experiments conditions and measurements Fridge Temp. ( C) Fridge RH (%) COT (min) Defrosted water (cc) -7 88 245 335-7 90 237 340-7 92 230 345-7 96 222 375-9 65 300 220-9 75 280 310-9 85 270 360-9 88 260 360-9 95 260 380-11 92 250 365-11 95 245 460-11 96 230 470-13 90 513 375-13 92 500 405-13 95 415 475-13 96 405 585-15 65 515 270-15 75 505 290-15 85 432 340-15 95 426 480-17 65 660 365-17 75 628 380-17 85 615 405-17 88 611 430 May 2015 IJST, Transactions of Mechanical Engineering, Volume 39, Number M1 +

200 A. Tahavvor and S. Hosseini Table 2. Experiments conditions and measurements Ambient Temperature ( C) COT (min) Defrosted water (cc) 6 ~ 8 425 310 13 ~ 15 478 350 15 ~ 17 460 335 17 ~ 19 513 375 Figure 1 shows the COT vs. thermostat temperature for different relative humidities. From Fig. 1, it is observed that in constant relative humidity condition, when thermostat temperature decreases, COT increases. In addition, it reveals that in constant temperature condition, increasing relative humidity causes reduction in COT. According to this figure increasing relative humidity from 65% to 96% decreases the COT around 10%, relative to thermostat temperature. Therefore, relative humidity has no considerable effect on compressor operation time. In RH higher than 92% for thermostat temperature of -13 C, COT jumps suddenly due to uncontrollable ambient conditions variations. According to the gathered data, the following correlation is proposed for the relation between thermostat temperature, COT and relative humidity. COT = a + b(rh) + c(rh)² + d(t) + e(t)² + f(t)³ + g(t) 4 + h(t) 5 (1) where T and RH are the thermostat temperature and relative humidity, respectively. Coefficients of Eq. (1) are presented in Table 3. Figure 2 illustrates the correlation between Eq. (1) and the experimental measurements. As can be seen in this figure (and from Table 4) very good agreement exists between experimental data and correlated surface (Eq. (1)). Figure 3 shows the volume of defrosted water vs. thermostat temperature for different relative humidities. From this figure it is observed that, similar to COT in constant relative humidity, when thermostat temperature is reduced, the amount of defrosted water is increased. In addition, it is shown that in constant temperature, increasing relative humidity from 65% to 96% increases the defrosted water around 50~60%. Therefore, opposite to the COT, relative humidity has a considerable effect on the volume of defrosted water. The following correlation proposed a relationship between thermostat temperature, relative humidity and volume of defrosted water (V). V = a + b/(rh) + c(t) + d/(rh)² + e(t)² + f(t)/(rh) + g/(rh)³ + h(t)³ + i(t)²/(rh) + j(t)/(rh)² (2) Coefficients of Eq. (2) are listed in Table 3. Figure 4 illustrates the correlation between Eq. (2) and the experimental measurements. Same as Fig. 2 very good agreement exists between experimental measurements and correlated surface (Eq. (2)). Figure 5 shows variation of defrosted water vs. thermostat temperature. This figure shows that decreasing the thermostat temperature increased the amount of defrosted water. Figure 6 shows the COT vs. relative humidity. From this figure, it is observed that increasing relative humidity decreases COT. The effect of ambient temperature is presented in Fig. 7. This figure shows that when the ambient temperature increases, the amount of defrosted water increases. The relationship between ambient temperature and volume of defrosted water is proposed as follows: V = a + b(ta) + c(ta)² (3) where Ta is the mean ambient temperature. Equations (1)-(3) are determined from regression techniques based on least square method. This method recommends various forms for experimental data. Finally, the equation with the best correlation to the original data is selected for each variable. It should be noted that various forms of the equations are due to various types of independent variables. IJST, Transactions of Mechanical Engineering, Volume 39, Number M1 + May 2015

The effects of humidity, compressor operation time and 201 The R-square values from regression procedure of each correlation are listed in Table 4. Table 3. Coefficients of correlations Coefficient Equation (1) Equation (2) Equation (3) a -62447.36 7409.08 364.40 b 20.72-2205125 -12.86 c -0.14-751.18 0.75 d -28608.14 198159861 - e -5139.79-24.68 - f -449.70 74718.92 - g -19.18-5648521391 - h -0.32-0.51 - i - 645.23 - j - -2257423.65 - a) Uncertainty analysis During experiments, errors may be generated from various sources and uncertainty of each quantity should be determined. Table 4 summarizes accuracies for all processes and uncertainties for the correlations (1) to (3). Process Table 4. Accuracy of measurements and uncertainties for correlations Accuracy Digital thermometer 1 % Temperature sensors 0.2 % Digital psychrometer 3 % Humidity sensors 1 % Ambient temperature 3 % Volume of defrosted water 2.5 % Parameter r-square Uncertainty Equation 1 COT 0.96 11.8 % Equation 2 Volume of defrosted water 0.97 14.2 % Equation 3 Volume of defrosted water 0.999997 14.2 % 4. CONCLUSION In this study, frost formation in an industrial fridge is investigated experimentally. Main results of the study are: In constant relative humidity condition, as the thermostat temperature reduced, COT increased about 9%. In constant temperature condition, when the relative humidity increased, COT decreased. In constant relative humidity, as the thermostat temperature reduces, amount of defrost water increases. In constant temperature, increasing relative humidity increases the defrosted water. decreasing thermostat temperature increases amount of defrosted water Increasing relative humidity decreases COT. When ambient temperature increases, the amount of defrost water increases Acknowledgment: The authors duly acknowledge Mr. S. Khanalizade for preparing the test environment and his support. May 2015 IJST, Transactions of Mechanical Engineering, Volume 39, Number M1 +

202 A. Tahavvor and S. Hosseini REFERENCES 1. Hayashi, Y., Aoki, A., Adachi, S. & Hori, K. (1977). Study of frost properties correlating with frost formation types. J. Heat Trans., Vol. 99, pp. 239-245. 2. Raju, S. P. & Sherif, S. A. (1993). Frost formation and heat transfer on circular cylinders in cross-flow. Int. J. Refrigeration, Vol. 16, No. 6, pp. 390-402. 3. Ismail, K.A.R., Salinas, C.S. & Goncalves, M. M. (1997). Frost growth around a cylinder in a wet air stream. Int. J. Refrigeration, Vol. 20, No. 2, pp. 106 119. 4. Sengupta, S., Sherif, S.A. & Wong, K.V. (1998). Empirical heat transfer and frost thickness correlations during frost deposition on a cylinder in cross-flow in the transient regime. Int. J. Energy Research, Vol. 22, pp. 615-624. 5. Lee, Y. B. & Ro, S. T. (2001). An experimental study of frost formation on a horizontal cylinder under cross flow. Int. J. Refrigeration, Vol. 24, pp. 468-474. 6. Lee, Y. B. & Ro, S. T. (2005). Analysis of the frost growth on a flat plate by simple models of saturation and supersaturation. Exp. Thermal Fluid Sci., Vol. 29, pp. 685 696. 7. Cremers, C. J. & Mehra, V. K. (1982). Frost formation on vertical cylinders in free convection. J. Heat Trans., Vol. 104, No. 1, pp. 3-7. 8. Tokura, I., Saito, H. & Kishinami, K. (1983). Study on properties and growth rate of frost layers on cold surfaces. J. Heat Trans., Vol. 105.4, pp. 895-901. 9. Tanda, G. & Fossa, M. (2010). Frost formation in vertical channels under natural convection. Int. J. Multiphase Flow, Vol. 36, No. 3, pp. 210-220. 10. Tanda, G. & Fossa, M. (2006). Free convection frost growth in a narrow vertical channel. Int. J. Heat Mass Trans., Vol. 49, No. 11, pp. 1946-1957. 11. Chen, J. & Oosthuizen, P. H. (1994). Frost formation on a horizontal cylinder with free convection. Master Thesis, Queen s University, Kingston, Canada. 12. Yaghoubi, M. & Khoshnazar, H. (2010). Experimental study of frost formation on a horizontal cylinder. AiAA/ASME Joint Thermophysics and Heat Transfer Conference, Chicago, USA. 13. Tahavvor, A. R. & Yaghoubi, M. (2009). Analysis of early-stage frost formation in natural convection over a horizontal cylinder. Int. J. Refrigeration, Vol. 32, pp. 1343-1349. 14. Tahavvor, A. R. & Yaghoubi, M. (2010). Experimental and numerical study of frost formation by natural convection over a cold horizontal circular cylinder. Int. J. Refrigeration, Vol. 33, No. 7, pp. 1444-1458. 15. Tahavvor, A. R. & Yaghoubi, M. (2011). Prediction of frost deposition on a horizontal circular cylinder under natural convection using artificial neural networks. Int. J. Refrigeration. Vol. 34, No. 2, pp. 560-566. 16. Yan, W. M., Li, H. Y., Wu, Y. J., Lin, J. Y. & Chang, W. R. (2003). Performance of finned tube heat exchangers operating under frosting conditions. Int. J Heat Mass Trans., Vol. 46, No. 5, pp. 871-877. 17. Iragorry, J. & Tao, Y. X. (2005). Frost temperature relations for defrosting sensing system. J. Heat Trans., Vol. 127, No. 3, pp. 344-351. 18. Liu, Z., Gou, Wang, J. & Cheng, S. (2008). Frost formation on a super-hydrophobic surface under natural convection conditions. Int. J. Heat Mass Trans., Vol. 51, No. 25, pp. 5975-5982. 19. Liu, Z., Wang, H., Zhang, X., Meng, S. & Ma, C. (2006). An experimental study on minimizing frost deposition on a cold surface under natural convection conditions by use of a novel anti-frosting paint. Part I. Anti-frosting performance and comparison with the uncoated metallic surface. Int. J. Refrigeration, Vol. 29, No. 2, pp. 229-236. 20. El Cheikh, A., & Jacobi, A. (2014). A mathematical model for frost growth and densification on flat surfaces. Int. J. Heat Mass Transfer, Vol. 77, pp. 604-611. IJST, Transactions of Mechanical Engineering, Volume 39, Number M1 + May 2015

The effects of humidity, compressor operation time and 203 21. Inada, T., Tomita, H. & Koyama, T. (2014). Ice nucleation in water droplets on glass surfaces: From micro-to macro-scale. Int. J. Refrigeration, Vol. 40, pp. 294-301. 22. Moallem, E., Hong, T., Cremaschi, L. & Fisher, D. E. (2013). Experimental investigation of adverse effect of frost formation on microchannel evaporators, part 1: Effect of fin geometry and environmental effects. Int. J. Refrigeration, Vol. 36, No. 6, pp. 1762-1775. 23. Amini, M., Pishevar, A. R. & Yaghoubi, M. (2014). Experimental study of frost formation on a fin-and-tube heat exchanger by natural convection. Int. J. Refrigeration, Vol. 46, 37-49. 24. Yao, Y., Jiang, Y., Deng, S. & Ma, Z. (2004). A study on the performance of the airside heat exchanger under frosting in an air source heat pump water heater/chiller unit. Int. J. Heat Mass Trans., Vol. 47, No. 17, pp. 3745-3756. 25. Guo, X. M., Chen, Y. G., Wang, W. H. & Chen, C. Z. (2008). Experimental study on frost growth and dynamic performance of air source heat pump system. Appl. Thermal Eng., Vol. 28, No. 17, pp. 2267-2278. 26. Tahavvor, A.R., Zakeri, E. & Moezi, S. A. (2014). Modeling of frost growth on a horizontal circular cylinder under natural convection using fractal geometry analysis. Iranian Journal of Science Technology, Transactions of Mechanical Engineering, Vol. 38, No. M1, pp. 1-8. May 2015 IJST, Transactions of Mechanical Engineering, Volume 39, Number M1 +