STUDYING THE PERFORMANCE OF A COUNTER-FLOW, VERTICAL EVAPORATIVE HUMIDIFIER

Similar documents
ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

Two Stage Indirect/Direct Evaporative Cooling

Psychrometrics. Outline. Psychrometrics. What is psychrometrics? Psychrometrics in daily life and food industry Psychrometric chart

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

EXPERIMENTAL STUDY OF AIR FLOW RATE EFFECTS ON HUMIDIFICATION PARAMETERS WITH PREHEATING AND DEHUMIDIFICATION PROCESS CHANGING

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Optimizing Electric Humidifier Operation with an Air Side Economizer

Chapter 14, Problem 27.

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Theoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

Review on Waste Heat Recovery Techniques in Air Conditioning Application

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Heat pump and energy recovery systems

Modified Air Cooler with Split Cooling Unit

R07. Answer any FIVE Questions All Questions carry equal marks *****

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Dynamic performance of a novel dew point air conditioning for the UK buildings

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

THE COOLING CAPACITY AND PRESSURE DROP IN A HYBRID CLOSED CIRCUIT COOLING TOWER

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Greenhouse Temperature Management

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Heat Recovery Units. Heat Recovery 1

PERFORMANCE OF A MODEL IN-LINE VORTEX SEPARATOR. Keng-Choon Lee Geothermal Institute, The University of Auckland, Private Bag 92019, Auckland, New

Performance investigation of Air-conditioning system using ejector as expansion device

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER

International Journal of Advance Research in Engineering, Science & Technology SOLAR HUMIDIFIER

*Corresponding author;

ANALYSIS OF DESICCANT COOLING SYSTEM

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

DRYING YELLOW-POPLAR IN A SOLAR-DEHUMIDIFIER KILN WITH HEAT STORAGE AND HEAT RECOVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS

Performance Measurement of R32 Vapor Injection Heat Pump System

Purdue e-pubs. Purdue University

2. CURRICULUM. Sl. No.

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Temperature. In the HVAC area, we talk about two kinds of temperatures.

HVAC (Heating, Ventilating, and Air Conditioning)

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Experimental study of air evaporative cooling process using microporous membranes

Optimisation of cooling coil performance during operation stage for improved humidity control

LAB EQUIPMENT DETAILS

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

Active desiccant integration with packaged rooftop HVAC equipment

OPTIMIZING PERFORMANCE IN SPRAY OPERATIONS

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Air Conditioning Clinic

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina


Effects of Volute Tongue Clearance and Rotational Speed on Performance of Centrifugal Blower Nitin S. Jadhav *, S. R. Patil

Comfort and health-indoor air quality

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Transcription:

Journal of Engineering Sciences, Assiut University, Vol. 34, No. 3, pp. 719-732, May 2006 STUDYING THE PERFORMANCE OF A COUNTER-FLOW, VERTICAL EVAPORATIVE HUMIDIFIER Maher A. Mohamed ; Mohamed R. Diab ; Ramadan Bassiouny and Hussein M. Maghrabie Department of Mechanical Power Engineering and Energy ; Faculty of Engineering, Minia University, Minia, Egypt (Received November 3, 2005 Accepted April 22, 2006) ABSTRACT The evaporative humidifier is an energy efficient unit that can be an alternative to other costly cooling systems; depending on climate conditions and building load characteristics. Heat and mass transfer processes occur inside the humidifier as a result of air contact with water spray. The present experimental study aims at investigating some common parameters that have a direct or indirect effect on the evaporative humidifier performance. Among these parameters are: the number of spray nozzles, nozzle arrangements, water-air mass flow rate ratio, and packing material specifications such as: location, z, thickness t, and number of trays. The results showed that the water-air mass flow rate ratio has a significant effect on the humidifier performance. The results also indicated that an increase in the humidifier saturation efficiency, ε, was noticed as the number of spray nozzles increased for the same water flow rate. However, when keeping the water spray supply pressure constant, a decrease in the saturation efficiency was recorded as the number of spray nozzles increased. Furthermore, placing a packing material inside the humidifier results in enhancing the efficiency due to increasing the mass transfer surface area and air residence time. INTRODUCTION Humidity is a major concern for researchers in the air conditioning field due to its important role in many industrial applications and its impact on human comfort. Typical industrial applications of air conditioning are in laboratories, printing plants, the manufacturing of precision parts, textiles, steel, pharmaceuticals, and photographic products. Very recent micro-scale technologies are very sensitive to surrounding environment humidity variation. The application of this technology is obvious in many fields such as communication, data collection, control systems, and office hardware (copier machines, phone systems, computers, and fax machines) [1]. People feel more comfortable when relative humidity (RH) lies between 35-55 % under normal temperature condition. Too low RH results in people discomfort due to dry nose, throat, lips, and skin. High level of humidity causes difficult in breathing, skin itching, a 719

720 Maher A. Mohamed, et al m mr n P T t z NZ NOMENCLATURE mass flow rate, kg/s water-air mass flow rate ratio (m w /m a ) number of packing material trays pressure, kpa. temperature, o C packing material thickness, m tray vertical location, m number of spray nozzles Subscripts a db dis dp i e max wb w air dry-bulb discharge dew-point inlet exit maximum wet-bulb Water Greek symbols Ti,db - Te,db ε saturation efficiency, ( ) % T - T i,db dp and feeling of temperature rise. Feeling of temperature rise means that a person feels warm because of the very low rate of sweat evaporation from the skin surface. So there is a necessity for adjusting air humidity either through air humidification or dehumidification. Air humidification can be attained when water vapor is added to the air increasing the air moisture content. This process can be achieved through evaporative humidifier, steam vaporizer, water atomizer, and air washer. Direct evaporative unit (evaporative humidifier) cools air by direct contact with water, either by an extended wetted surfaces material or with a series of sprays. Indirect evaporative units cool air in a heat exchanger, which transfers heat either to a secondary air stream that has been evaporatively cooled (air to air) or to water that has been evaporatively cooled [2]. In the evaporative humidifier, the moisture is transmitted into the air while flowing through a moistened absorbent material, such as a belt, wicks, or filter. In addition, the wetted material works as filters that help removing incoming pollutants [3]. In all evaporative humidifiers, water vaporizes and the minerals in the water remain in the equipment. This type of coolers is ideal because it can provide high relative humidity at lower temperatures. The evaporative cooler consumes only one fourth of the electrical energy required to operate a mechanical air conditioner or heat pump [4]. The evaporative cooler operates efficiently in hot and dry weathers. However, it has some disadvantages such as, the temperature control in space is not adequate, and the supply air to the humidifier should be from outside The maximum possible mass flow rate ratio of the water spray and air, mr max, for different operating conditions is presented in [5]. This ratio is required to obtain the maximum saturation efficiency. The authors showed that for lower values of dimensionless temperature ratios, defined as the ratio between the difference between the inlet and exit water temperatures to the difference between the inlet water temperature and inlet air wet-bulb temperature, the maximum mass flow rate ratio was

STUDYING THE PERFORMANCE OF A COUNTER-FLOW. 721 very high. The results showed that for temperature ratio up to 0.1, the value of the maximum mass flow rate ratio is very high. However, for values greater than 0.4, the required maximum mass flow rate ratio decreased rapidly. An analytical and experimental study was carried out on the mixing process between air and water droplets in a vertical unit with no internal packing material. The results showed that at any height, all sprayed droplets were not at the same temperature. The arrangement of spray nozzles has a direct effect on the humidifier performance. Hence, care is required in determining the layout of the nozzles to insure as little as possible of the water spray migration to the wall allowing almost one percent of the total water flow to be carried up to the eliminator [6]. The shape effect of the packing material on the heat transfer was marginal [7]. It was noticed that placing packing material into the airflow passage yields about a three-time increase in the wall to air heat transfer rate compared to that of an empty duct [7]. Surfaces of the packing material with reduced dynamic contact angles would increase the performance in terms of cooling effectiveness in the direct evaporative cooling system. However, only those surfaces with significant wicking capacity could increase this performance depending on water flow rate. The increase is significant for certain value of water mass flow rate and then the increase is symptomatic to a high value [8]. Previous available published literatures interested in water droplets-air interaction process revealed the shortage of having a thorough and comprehensive study about the evaporative humidifier performance. Most of the previous work has tackled this interaction process from the cooling tower point of view analysis. Theoretically, both cooling tower and humidifier are devices with an air-water interaction process. However, the function of the cooling tower is to cool water, as a working fluid, on the expense of rejecting its sensible and latent heat to the air. But the humidifier aims at substituting the high sensible load in the air by a latent load from water droplets evaporation, resulting in air temperature decrease. Some researchers have studied the enthalpy and moisture content variation; others have considered the water spray and packing material effect on the evaporative humidifier performance. The effect of mass flow ratio on air dry-bulb temperature and moisture content change has been studied as well. Some others have considered the spray water pressure, and droplet size on heat and mass transfer process. It is important for the HVAC engineer as well as the designer to have a thorough insight into the different parameters that could affect the performance of the humidifier. EXPERIMENTAL SET-UP Figure 1 shows a general layout of the experimental set-up. The experimental set-up mainly includes: a blower, an air pre-heater, a spray humidifier, and duct system equipped with the appropriate measurements. The blower is a radial type with a constant speed of 2890 rpm and a maximum air delivery of 0.1m 3 /s. It is driven by a single phase AC electric motor of 1.1 kw (1.5hp). The air pre-heater consists of an electric coil shaped inside a copper tube. Its total power is 3000 W. The shape insures having two planes normal to the air flow and one plane parallel to the flow.

722 Maher A. Mohamed, et al ` Fig. 1: Layout of the experimental set-up.

STUDYING THE PERFORMANCE OF A COUNTER-FLOW. 723 The spray humidifier consists of a transparent chamber, a bank of spray nozzles, water tank equipped with thermostatic water heaters, centrifugal water pump, and eliminators. The transparent chamber is made of glass walls mounted in an alumetal frame. The dimensions of this chamber are 0.5 0.5 0.5 m 3. A number of packing material trays can be variably mounted inside the chamber. The trays can be easily moved up and down through vertical slots in two side walls of the transparent chamber to adjust the interspaces between the trays. The spray nozzle (or nozzles) connected to the pump discharge pipe is (are) installed at the upper section of the humidifier above the upper tray. The pump is a centrifugal type of 0.6 kw (0.75hp) with a constant speed of 2800 rpm. It is driven by a single-phase AC 220 V electric motor. It provides a manometeric head of 44 to 12 m with a corresponding discharge of 10 to 40 l /min. A fine deck packing material made of recycled plastic with certain configurations was used inside the spray humidifier. This deck is manufactured from PVC sheets arranged all together to form a corrugated shape. The porosity of this packing material measured in the present study was 97%. The surface area per unit volume was 1.922 m 2 /m 3 based on calculation. The air supply duct was made of 0.001m thick galvanized steel sheets and coated with anti-rust paint. The aspect ratio of this duct is one (0.25 0.25 m 2 ). A belllike-shape inlet section was connected to the blower suction side through a circular duct 0.15 m in diameter and 0.4 m in length. To reduce the duct heat loss (or gain) with its surrounding, a blanket of glass wool of thickness 0.03 m was wrapped around the duct walls and humidifier s side walls. Dry and wet-bulb temperature measurements were carried out along the duct before and after each unit of the system using type K-thermocouples. Air temperature and velocity patterns at a cross-section of a non-circular duct are non-uniform. Therefore, an average dry-bulb temperature across the duct was obtained by placing and parallel connecting four junctions of thermocouples at different four places in the duct cross-section area. In measuring wet-bulb temperatures, the thermocouples were placed downstream of the dry-bulb thermocouples to avoid the effect of evaporated water from the wetted wick around the junction. Thermocouples used to measure wet bulb temperatures were installed in places where a proper air velocity over the wetted junction is guaranteed. The wet-bulb thermocouples were placed in the downstream of the dry-bulb thermocouple to avoid the effect of vaporization on recording the dry-bulb temperature. Inside the humidifier the air dry-bulb temperature distributions were measured, in addition to the inlet and exit dry and wet bulb temperatures to locate the process of air humidification on the psychrometric chart. There was a configuration for measuring the wet-bulb temperature. A small plastic bottle, filled with water and raised at a certain distance above the junction, is connected to a small plastic tube that is connected to a small copper tube through which a cotton wick containing the junction was inserted. The small copper tube with the junction extended outside is placed inside the supply duct and downstream of the dry-bulb junction. All necessary properties of air can be directly known from the psychometric chart based on determining these two independent properties, the dry and wet-bulb temperatures.

724 Maher A. Mohamed, et al The supply airflow rate was measured using a standard airflow nozzle (0.038 m throat diameter). The nozzle was constructed and installed in accordance with ASHRAE standards. Because the duct is not circular, four static pressure tabs were placed, at a standard distance, upstream and downstream of the nozzle plate. The pressure drop was measured using a water manometer having one side connected to a manifold of the four static pressure tabs in the upstream and the other side similarly connected downstream. The velocity of air passing through the nozzle was calculated based on the measured pressure drop across the nozzle panel. The Experimental Procedure The test rig is left to run for approximately 45 minutes before recording any measurement. The outdoor air conditions (Tdb, Twb) were measured and located on the psychrometric chart. At the same time, inlet and exit conditions to the humidifier (Tdb, Twb) and airflow rate were measured. The spray water temperature was controlled using two heaters equipped with adjusted thermostats. A gauge pressure indicator on the pump discharge tube was used to measure the pump discharge pressure before water flowing to the spray nozzle (s). Three meshed-trays, equipped with nine thermocouple junctions each, were placed inside the humidifier at different vertical distance to measure the air temperature distribution. These junctions were shielded using plastic tubes to isolate the junctions from the falling water droplets. A by-pass valve is mounted at the pump discharge line. This valve is used to control the water discharge pressure. This pressure allows a certain flow rate to pass to the nozzles. Having a constant discharge pressure and changing the number of nozzles results in having a more fine droplets and larger cone angle in the case of single nozzle than in the case of four nozzles. However, a constant water flow rate for all number of nozzles results in having a larger contact area in the case of the four nozzles than in the case of the single nozzle. RESULTS AND DISCUSSION Figure 2 shows the effect of inlet air temperature variation on the evaporation rate for three different water-air mass flow rate ratios (mr). The evaporation rate is defined as the difference between exit and inlet moisture content multiplied by the air flow rate. The figure illustrates that there is a similar trend for the dependence of evaporation rate on the air dry-bulb temperature. There is almost a linear increase in the evaporation rate as the air inlet dry-bulb temperature increased. A quantitative increase in the evaporation for the higher mass ratio was noticed compared to the lower mass ratio. This would indicate that, for the same inlet air flow, increasing the mass ratio leads to an increase in the water spray contact area and accordingly this enhances the mass transfer process. The saturation efficiency is defined as the ratio of the actual evaporation rate to the maximum possible evaporation rate. This efficiency, as shown in Figure 3, was slightly affected by the air inlet temperature compared to the mass ratio variation effect. The slight change is due to the relative relation of the evaporation rate to the maximum possible evaporation in calculating the saturation efficiency.

STUDYING THE PERFORMANCE OF A COUNTER-FLOW. 725 90 Evaporation Rate, g/min 70 50 30 10 mr =2.5 mr =1.5 mr =1.0 No Pad T w, i =25 o C, NZ=2, m a =0.075 kg/s 30 35 40 45 50 55 Air Inlet Dry-bulb Temperature, o C Figure 2: Effect of air inlet dry-bulb temperature on the evaporation rate for different mass-ratios. 100 90 Saturation Efficiency, % 80 70 60 50 40 mr =2.5 mr =1.5 mr =1.0 No Pad,T w, i =25 o C, NZ=2, m a =0.075kg/s 30 35 40 45 50 55 Air Inlet Dry-bulb Temperature, o C Figure 3: Effect of air inlet dry-bulb temperature on the saturation efficiency for different mass-ratios.

726 Maher A. Mohamed, et al The effect of varying the number of spray nozzles on the evaporation rate and humidifier saturation efficiency is shown in Figures 4 and 5, respectively. When keeping the nozzle discharge pressure constant, increasing the number of nozzles leads to a decrease in the water spray flow rate, and accordingly a decrease in the spray cone angle and contact area. This illustrates the decrease in both evaporation rate and saturation efficiency as nozzle number increased. On the other hand, when keeping the flow rate of the water spray constant, increasing the number of spray nozzles leads to an improvement in the evaporation rate, as shown in Figures 6 and 7. This could be attributed to the increase in the water spray discharge pressure from NZ=1 to NZ=4, which yields more fine drops that shortly evaporate when come into contact with the air stream. In another detailed scenario, a by-pass valve is mounted at the pump discharge line. This valve is used to control the water discharge pressure. This pressure allows a certain flow rate to pass to the nozzles. Having a constant discharge pressure and changing the number of nozzles results in having a more fine droplets and larger cone angle in the case of the single nozzle than in the case of the four nozzles. This leads to a better evaporation rate for the single nozzle compared to the four nozzles. However, a constant water flow rate for all number of nozzles results in having a larger contact area in the case of the four nozzles than in the case of the single nozzle. 120 100 Evaporation Rate, g/min 80 60 40 20 NZ =1 NZ =2 NZ =4 No Pad,Tw,i=25 o C, ma=.012 kg/s,pdis=3 bar 30 35 40 45 50 55 Air Inlet Dry-bulb Temperature, o C Figure 4: Effect of number of spray nozzles on the evaporation rate for constant nozzle discharge pressure.

STUDYING THE PERFORMANCE OF A COUNTER-FLOW. 727 95 85 Saturation Efficiency, % 75 65 55 45 NZ =1 NZ =2 NZ =4 No Pad, T w,i = 25 o C, m a =0.12 kg/s, P dis = 3 bar. 30 35 40 45 50 55 Air Inlet Dry-bulb Temperature, o C Figure 5: Effect of number of spray nozzles on the saturation efficiency for constant nozzle discharge pressure. 150 Evapration Rate, g/min 130 110 90 70 50 NZ =4 NZ =2 NZ =1 No Pad, T w,i = 30 o C, m w = 0.019 kg/s 30 35 40 45 50 Air Inlet Dry-bulb Temperature, o C Figure 6: Effect of number of spray nozzles on the evaporation rate for constant water flow rate.

728 Maher A. Mohamed, et al 95 Saturation Efficiency, % 85 75 65 55 45 NZ =4 NZ =2 NZ =1 No Pad, T w,i = 30 o C, m w = 0.019 kg/s 30 35 40 45 50 Air Inlet Dry-bulb Temperature, o C Figure 7: Effect of number of spray nozzles on the saturation efficiency for constant water flow rate. Figure 8 indicates the effect of how close or far the packing bed from the spray nozzle on the saturation efficiency. The objective of this figure is to see the effect of pad location. This might help reaching acceptable saturation efficiency over a certain height. Hence, this would optimize the humidifier height. As shown from the figure, having the packing bed close to the spray nozzle would cause the spray cone to early disperse and splash resulting in minimizing the evaporation rate. However, moving the packing bed some distance downward from the spray nozzle improves the evaporation rate and saturation efficiency. In addition, the effect of varying the number of packing trays or beds on the saturation efficiency is shown in Fig. (9). Increasing the number of trays resulted in improving the humidifier efficiency, on the expenses of the air pressure drop that adds a resistance on the air handling unit. This increase in the number of trays would increase the contact area and air retardation time. However, an optimization should be achieved according to the height of the humidifier to choose the proper number of trays. The packing tray or bed thickness was thought to affect the evaporation rate. Therefore, a comparison between 0.05 m thick, and 0.1 m thick, as used in industry with the case of no packing is shown in Figure (10). The figure illustrates a noticed improvement in the evaporation rate as the packing thickness increases. This could be attributed to increasing the residence time for the air while passing through a wetted volume. It can be noticed from the figure that doubling the thickness resulted in nearly 20% increase in the evaporation rate at the lower air inlet temperature. This percentage decreased to almost 8% as the air gets hotter approaching the water spray temperature.

STUDYING THE PERFORMANCE OF A COUNTER-FLOW. 729 72 Saturation Efficiency, % 69 66 63 60 Z=0.8 m Z=0.5 m Z=0.3 m Tw, i =35 o C, NZ =4, mr =1.5, t =0.05 m 30 35 40 45 50 55 Air Inlet Dry-bulb Temperature, 0 C Figure 8: Effect of packing material location on the saturation efficiency for different inlet air temperatures. 90 z 85 Saturation Efficiency, % 80 75 70 65 60 n=1 Pad n=2 Pads n=3 Pads Tw, i =35 o C, NZ = 4, mr =1.5, t =0.05 m 30 35 40 45 50 55 Air Inlet Dry-bulb Temperatutre, o C Figure 9: Effect of number of pad trays on the saturation efficiency for different inlet air temperatures.

730 Maher A. Mohamed, et al Evaporation Rate, g/min 300 260 220 180 140 100 mr =1.5, NZ=4 Tw, i= 25 C Tw, i= 45 C Tw, i= 65 C (C) 60 20 300 mr =1.5, NZ=4 (B) Evaporation Rate, g/min 260 220 180 140 100 Tw, i= 25 C Tw, i= 45 C Tw, i= 65 C 60 20 300 mr =1.5, NZ=4 (A) Evaporation Rate, g/min 260 220 180 140 100 60 Tw, i= 25 C Tw, i= 45 C Tw, i= 65 C 20 30 35 40 45 50 55 Air Inlet Dry-bulb Temperature, o C Figure 10: Effect of packing material thickness on the evaporation rate at different temperatures for the same mass ratio and number of nozzles for: (A) No-Pad (B) 0.05 m-pad (C) 0.1 m Pad.

STUDYING THE PERFORMANCE OF A COUNTER-FLOW. 731 CONCLUSIONS The present study has focused on investigating some of the parameters that are expected to affect the evaporative humidifier performance. Some significant conclusions are drawn out from the analysis of the results as follows: 1. Increasing the water spray flow rate and its temperature significantly affect the humidifier performance compared with preheating the inlet air temperature. 2. The humidifier saturation efficiency is increased as the number of spray nozzles increased for the same water flow rate. However, when keeping the water supply pressure constant, a reverse effect was noticed when increasing the number of spray nozzles. 3. Increasing the tray thickness or the number of packing trays resulted in improving the humidifier performance. However, placing a tray close to the spray nozzle would lead to spray splash and disperse causing a decrease in the evaporation rate, and accordingly the saturation efficiency. REFERENCES [1] Arora, S. C., and Domkundwar. S. 1992, Refrigeration and Air Conditioning, 3 rd edition, Chapter 24 pp.24.17-24.30. [2] ASHRAE Handbook of Fundamentals, 1998, American Society of Heating, Refrigerating, and Air Conditioning Engineers, Atlanta, chapter 19, pp 1-20 [3] Pacscod, D., 1979, A Heat Exchanger for Energy Saving in an Air Conditioning Plant, ASHRAE Transactions, 85(2), pp. 238-251. [4] Jameel-ur-Rehman Khan, and Syed M. Zubair, 2001, An Improved Design and Rating Analyses of Counter Flow Wet Cooling Towers, Journal of Heat Transfer, Trans. ASME, Vol. 123,, pp. 770-778. [5] Kau, F. W. and Alexander, D., 1976, Heat Transfer Characteristics of Pours Media chapter 7, pp 84-97. [6] Ciofalo, M., Stasiek, J. and Collins, M. W., 1996, Investigation of Flow and Heat Transfer in Corrugated Passage, II Numerical Simulation, International Journal. of Heat Mass Transfer, Vol. 39/1,, pp. 165-192. [7] ASHRAE Handbook of System and Equipment, 1999, American Society of Heating, Refrigerating, and Air Conditioning Engineers, Inc, New Handbook, Chapter 22. [8] Tibin, A. W., and Robert, L. R., 1996, Surface Wettability Effect on an Indirect Evaporative Cooling System, ASHRAE Transaction, Vol 102, No 1, pp. 427-432.

732 Maher A. Mohamed, et al درا أداء ط ي رأ ذو ن )%# ا#ط& ا%$#ي و"ة! ءة وا أن ن ادي %# أ/#ى ط 2% #وف ا*/ 0 و/.- ا, + ا%*(. 8 7 0 ت ا 2 ل ا,#ارة وا دا/ ا#ط&!*0= >"ك ا:اء #زاز اء. #0BC :ف ارا A ا= 0%# ا, 0 إ( +,- )? ا)ا< ا أن ن : 7( أداء ا#ط&. < 0 ھGه ا)ا<: 7 د أاق ا#زاز 0#& <%D# #0E أو <%D# ااق K% A #ن اء إ( ا:اء و<اO ت <اد ا, N <L): <M دا/ ا#ط& $: و 7 د ر+ف <اد ا, N. اء إ( ا:اء : #0BC ذو د> 7( أداء ا#ط&. A #ن K% أن أظ:#ت ا*. Q! أوT,L ا*. Q أن ھ*ك,K +! ءة ا#ط& ا 0(%N #ا S دة 7 د أاق ا#زاز أ/ Gا + ا> 7 %ر B %ت! A #ن اء. و 7* ا, ظ 7( B %ت VWL رزاز اء "U *- +! ءة ا#ط& ا 0(%N <X زدة 7 د ااق. 7 ]وة 7( ذ Z و Yد <اد "N دا/ ا#ط& \دى إ(,K + ا ءة 0= زدة <K" ا 2 ل ا وز< Aن ا:اء.