Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Similar documents
[Jhansi, 5(10): October 2018] ISSN DOI /zenodo Impact Factor

Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Waghmare Tushar Ramrao, D.S.Nakate

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

Enhancement of COP in Vapour Compression Refrigeration System

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Global Journal of Engineering Science and Research Management

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

[Vali*, 5(2): February, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

VCR SYSTEM USING R-600a/ POE OIL/MINERAL OIL/NANO-SiO 2 AS WORKING FLUID: AN EXPERIMENTAL INVESTIGATION

Week 9. Refrigeration Cycles I. GENESYS Laboratory

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Optimum Length of a Condenser for Domestic Vapor Compression refrigeration System

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Performance Assessment of Water Cooled Condenser Refrigeration System

Experimental Study of Modified Refrigerator Cum Air Conditioning and Water Cooler System

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

Theoritical Analysis For Miniature Vapor Compression Cycle Performance Using Microchannel And Finned Tube Condenser

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Performance Enhancement of Mini Refrigerator with Phase Change Materials

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

II. OBJECTIVE OF RESEARCH

Performance investigation of Air-conditioning system using ejector as expansion device

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

Sarthak Thakar, 2 R.P.Prajapati 1

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

PERFORMANCE OF REFRIGERATOR USING R-600A AS REFRIGERANT

Numerical Simulation of Window Air Conditioner

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Chapter 9. Refrigeration and Liquefaction

Design & Fabrication of Hybrid Cooler

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

STUDY OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING DOUBLE PIPE HEAT EXCHANGER

DEEPAK PALIWAL, S.P.S.RAJPUT

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Design and Development of Water Cooled Condenser for Domestic Refrigerator

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Design and Experimental Studies on Modified Solar Dryer

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

To Improve Cop of Domestic Refrigerator with the Help of Water Cooling Condenser

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

An experimental study of the effect of evaporator temperature on the compressor work of a simple vapour compression refrigeration system

A Review of Different Types of Combine Cooling System

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

PERFORMANCE ENHANCEMENT OF AIR CONDITIONER *

International Journal of Informative & Futuristic Research ISSN (Online):

Experimental Investigation on Domestic Refrigerator by Shell and Tube Heat Exchanger after the Condenser Using Sub Colling of Refregaring Fluid

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Performance Study on A Window Type Air Conditioner Condenser Using Alternative Refrigerant R407C

Cost-Effective COP Enhancement of a Domestic Air Cooled Refrigerator using R-134a Refrigerant

ADVANCES in NATURAL and APPLIED SCIENCES

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Performance Study of Triple Concentric Pipe Heat Exchanger

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Transcription:

Enhancement of COP by Using Spiral and Microchannel instead of conventional of VCR System 1 P.G. Lohote, 2 Dr.K.P. Kolhe. 1 P.G. Student, 2 Professor. 1,2 Department of Mechanical Engineering, JSPM s, Imperial College of Engineering & Research, Wagholi, Pune, INDIA. Abstract Most of the household refrigerators work on the Vapour compression refrigeration system which are holding high coefficient of performance. The system is assembled with the components like compressor, condenser, expansion valve and evaporator etc. The system performance is governed by each individual component being the part of that system and liable to take system performance up or down ultimately. The research article elaborates work about COP enhancement of domestic refrigerator by making alternative arrangement for condenser. The use of spiral and micro channel condenser raises COP of refrigerator to the value that was never before, the geometry, enhanced surface area of such micro channels are found adding positive results in the enhancement of COP value and work is elaborate through research work drafted in the paper. The results obtained through spiral and micro channel condenser installation are compared with conventional refrigerator and found worth appreciate. The COP enhancement through spiral and micro channel type condenser installation has noted down increased by 5.06% and 13.82% respectively. The base value considered in the comparison is COP of domestic refrigerator with regular condenser system inbuilt. Keywords: COP, Micro channel, Vapor compression refrigeration. 1. INTRODUCTION Most of the domestic and commercial refrigerators are operates on Vapor-Compression cycle and run for normal COP value which holds the scope of improvement with alteration made in components assembled in system. Figure 1 shows the schematic diagram of components for typical vapor-compression refrigeration system. In the thermodynamics cycle, a circulating refrigerant such as Freon enters the compressor in vaporized form [1]. Fig. 1 Architecture of VCR System [1] From point 1 to point 2, the vapor is compressed at constant entropy and exit compressor as a vapor which holding very high temperature. From point 2 to point 3 and further to point 4, the vapor travels through condenser which cools the vapor until it starts condensing, and then condenses the vapor into a liquid by removing additional heat at constant pressure and temperature. In between points 4 and 5, the liquid refrigerant goes through expansion valve/throttle valve, where its pressure decreases abruptly, causing flash evaporation and autorefrigeration of less than half of the liquid. It further results in forming mixture of liquid and vapor at the lower temperature and pressure as shown at point 5[7]. The cold liquid-vapor mixture then travels through the Evaporator coil and get vaporized by cooling the warm air, being blown by fan across the Evaporator coils or tubes. The resulting refrigerant vapor returns back to the compressor inlet at point 1 to complete the thermodynamic cycle and so on. The discussion taken place is centric about idle vapor-compression refrigeration cycle, and does not account real-time effects like frictional pressure drop in the system, thermodynamic irreversibility during compression of the refrigerant vapor, and non-ideal gas behavior which come occurred all of them or in the set of few leading to deviate refrigerator performance from idle one and impact of which can be viewed in terms down value of COP [7]. JETIR1607007 Journal of Emerging Technologies and Innovative Research (JETIR) www.jetir.org 31

Fig. 2 Idle Vapor-Compression Refrigeration cycle [7] In vapor compression refrigerating system basically there are following types of heat exchangers used. One, which absorbs the heat by means of evaporator Second, which removed absorbed heat from refrigerant and added heat of compression and condenses it back to liquid [4] It comes to attract an attention about condenser performance which leading to increase COP of overall refrigerator system. And thus project work is shaped, replacement of domestic refrigerator provided with regular condenser by spiral and micro channel type condenser to study percentage of enhancement come occurred in COP as an outcome [2][6]. 2. EXPERIMENTAL WORK The condenser is one of most important component of Vapor compression refrigeration system which contributes lot in the overall system performance. Effectiveness of its working through rigged control taken over various performances affecting attributes correlate to it, delivers the worth accepted results at minimum possible cost expenditure. As function of is dissipating the heat absorbed by refrigerant during the process of evaporation and compression. The refrigerant COP is the function of its operating temperature, the current work undertakes modification of condenser geometry and thus through effective temperature regulation maintained, system COP would be high. The project work is centric about, installation of spiral and micro channel shape base condenser to the refrigerator holding 165 Liters capacity. The refrigerator with spiral and micro channel shape condenser, put in to the service is shown below, Fig. 3 VCR installed with Spiral condenser and Microchannel condenser JETIR1607007 Journal of Emerging Technologies and Innovative Research (JETIR) www.jetir.org 32

Table 1 Specifications of the condenser Parameters Existing Spiral Micro channel Diameter of 6.35 mm 6.35 mm 0.9 mm coil Spacing 42 mm 45 mm 42 mm No. of Turns 8 5 8 Length of coil 5320 mm 5320 mm 5320 mm Height 595 mm 595 mm 595 mm 3. EXPERIMENTAL PROCEDURE The following procedure is intended to build an experimental set up for Vapor compression refrigeration system. Domestic refrigerator working on Vapor compression cycle and holding capacity (165 Liter). Pressure and temperature sensors are fixed at the point of compressor entry and exit too. Additional temperature sensor is fixed at the evaporator. System flushing is executed through pressurized Nitrogen gas. Conventional condenser replaced by Spiral and micro channel shape base condenser. R-600 refrigerant is charged in to VCR system Switch ON the refrigerator system and observations are noted from Pressure gauge and control panel for respective temperature readings. The performance of the existing system, Spiral system and micro channel condenser system is investigated with respect to set of observations in terms of Temperature and pressure readings obtained. COP discussed system is investigated with the help of P-H chart The results are tabulated for Existing, Spiral and micro channel condenser based system 4. RESULTS AND DISCUSSIONS OF THE STUDY: The replacement of conventional refrigerator system by spiral and micro channel shape condenser shows enhanced work capability every time added with worth appreciate result and thus following discussion can be added to work further on the system its performance to improve beyond its current working capacity. The discussion in the context can be added as follows, Optimization head Result improvement found Scope of further improvement geometry COP found increased with With alteration made in condenser geometry altered to geometry the space compactness Microchannel and spiral type can be considered to reduce further. Pitch of coil Surface area Heat rejection to surrounding found increased with respect to increased pitch value Heat rejection found maximum with respect to increased surface area Pitch of coil reduced further to support compactness in the structure without compromising rate of heat rejection and thus ultimately refrigerator COP Beyond one limit, surface area added adverse effect and thus its value supposed to so maintain, without affecting COP, the rate of heat rejection to surrounding will address as smooth as required. Table 2 Result table obtained with respect to observation noted down and calculations performed Parameters Existing Spiral Microchannel COP 2.17 2.28 2.41 Net refrigeration Effect 160 183 205 Mass Flow rate to obtain 1TR 1.31 1.14 1.02 Compressor work (KJ/Kg) 73.73 80 85 Heat rejected in condenser KJ/Kg 260 263 290 Compression pressure ratio 11.86 12.11 12.75 4.1 Effect of type of condenser on the COP Fig 5 shows the effect of type of condenser on the COP. From the figure it has been observed that domestic refrigerator gives better performance when Microchannel condenser is used. JETIR1607007 Journal of Emerging Technologies and Innovative Research (JETIR) www.jetir.org 33

Fig. 5 Effect studied between type of condenser and respective COP obtained 4.2 Effect of type of condenser on the Mass Flow rate From figure 6 it was observed that when we use microchannel instead of using existing and spiral condenser there is a considerable reduction in mass flow rate of refrigerant per TR. Fig. 6 Type of condenser recommended in to operation vs. Mass Flow rate to achieve 1TR 4.3 Effect of type of condenser on the rate of Heat rejection to surrounding Above figure shows the heat rejection rate for the different types of condenser. It is seen that Microchannel condenser has maximum heat rejection of 290 KJ/Kg than other two types. Fig. 7 Effect studied between type of condenser in service and rate of heat rejection to surrounding JETIR1607007 Journal of Emerging Technologies and Innovative Research (JETIR) www.jetir.org 34

5. CONCLUSION OF THE STUDY The current work is centric about performance study of spiral and micro channel shaped condenser used in refrigerator holding 165 liters capacity. The data obtained from fabricated experimental set up used in analyzing performance of spiral and micro channel shaped condenser used as a part of vapor compression system. With introduction made for spiral and micro channel shape condensers, COP value found increased by 5.06 % and 13.82 % respectively over the conventional refrigeration system. When spiral condenser is replaced by micro channel there is increase in refrigeration effect and compressor work by 12.02 % and 6.25 % respectively with increase in rate of heat rejection considerably. The summarized observations made has verified the performance of Micro channel shape base condenser and so the refrigeration System has better performance over conventional refrigeration system supported with regular shape condenser. REFERENCES [1] B. Santosh Kumar. (2015), Experimental Investigation of Vapour compression system with Spiral shaped condenser, IJRME,02, pp.11-14. [2] Pravin lohote and Kolhe K.P. (2016) Review on Performance analysis of Vapour Compression Refrigeration System by using Microchannel heat exchanger JETIR 3(4)pp 202-206. [3] Pawankumar, Kolhe K.P, and C. K. Datta Study of effect of pulse process parameters on GTAW process on AA aluminum alloy 7039. International Journal of Engineering and technology in India. ISSN-0976-1268 2010, 1 (2), Pp.61-67. [4] Francisco julio do Nascimento (2013) An experimental study on flow boiling heat transfer of R134 A in microchannel based heat sink, Science direct,45, pp.117-127. [5] Seunghyun Lee (2016), Investigation of flow boiling in the large microchannel heat exchanger in a refrigeration loop in space application, Science direct, 97 pp.110-129. [6] Huize li (2015) An experimentally validated model for microchannel heat exchanger incorporating lubricant heat effect, Science Direct, 59, pp.259-268. [7] R.S.Andhare (2016),Heat transfer and pressure drop characteristics of a flat plate manifold microchannel heat exchanger in counter flow configuration. Science Direct,96, pp178-189. [8] Abdul Kareem R.Abed (2014),Experimental study on the effect of Capillary tube geometry on the performance of Vapour Compression refrigeration System,Diyala Journal of Engineering science,07,pp 47-60 [9] R.Hussainvali,(2015),An experimental investigation and performance evaluation of vapor compression refrigeration system with Helical type condenser by using R134 A and R140A refrigerant, IJERST,4,pp.192-201. [10] Jala Chandramauli, (2015), Design, application and experimental analysis of vapour compression refrigeration system with Ellipse shaped evaporator coil, IJIRSET,4. pp.7775-7782. [11] Jaeseon Lee (2009), Low temperature 2 Phase microchannel cooling for high heat flux for thermal management of defense electronics, IEEE,32, pp.453-465 [12] Ashish Wankhade and Kolhe K. P. (2015) Design and Analysis of Hydraulic Oil Cooler By Application of Heat Pipe. International Journal of Science Engineering and Technology Research 4(9) Pp.3189-3194. JETIR1607007 Journal of Emerging Technologies and Innovative Research (JETIR) www.jetir.org 35