"Microbox" DC Models MBOX 125/2DC MBOX 125/2DC204

Similar documents
"Microbox" Continuous Mechanical Extract Ventilation Units. Installation, Operating and Maintenance Instructions

ELEGANCE IPX4 IPX7. Low Carbon Fan with EC Motor Installation and Operating Instructions. 6 models:

ELIX 1003 IPX4. Energy Efficient Centrifugal Fan with EC Motor Installation and Operating Instructions

WHHR Midi & Midi Lite

"WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use

Residential Carbon Friendly Ventilation SAP Q Eligible. ventilation

WHHR125DC - Aera. Whole House Mechanical Ventilation with Heat Recovery - MVHR

G Installation manual Solitude - dmev unit

Apartment Ventilation. "Microbox" Continuous Mechanical Extract Units

SPECIFICATION casing manufactured from aludip steel in white low energy DC external motor aluminium plate heat exchanger

Installation manual Mori HR

Centrif Duo & Centrif Duo Plus

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit

Lo-Carbon Quadra Centrifugal Fan

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS.

FAITH (dmev) 230V / 24V DC SELV Flush Mounted Domestic Continuous Extract Fans

Purge Ventilation Unit. Product Manual. ventilation systems TP625

isense & isense-ht 230V Flush Mounted Domestic Continuous Extract Fans

Titon HRV1 Q Plus HRV1.5 Q Plus HRV2 Q Plus Heat Recovery Ventilation Units

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

EXTRACTOR HOOD. Please read all the instructions carefully before starting the installation. 230 / 240V 50Hz

Lo-Carbon Quadra SELV

INTEGRA PLUS ABC. 230V~ 50Hz. Stock Ref. N. Installation and Wiring Instructions IPX2

HOTLINE:

Titon CME1 Q Plus Mechanical Extract Ventilation Unit

Xcell 270 Longlife DC wholehouse heat recovery unit

Lo-Carbon MULTIVENT MVDC-MS & MVDC-MS H VENTILATION SYSTEMS V~50Hz. Installation and Wiring Instructions IP22. Stock Ref.

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL

AXIAL FAN User s manual. Quiet-dMEV 100 DC.

User and maintenance manual

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS

airooncentre.co.uk irconcentre.co.uk Xpelair Low Energy Wall/Window Fan Range GX6 EC2 GXC6 EC2 Quick Order Hotline or

ISCG90SS _03 ISCG90SS

LV100 Standard LV100PC Pull Cord LV100T Timer LV100H Humidistat LV100HP Humidistat and Pull Cord LV100PIR

Lo-Carbon SELV Tempra

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance

Installation & Operating Instructions

Internal/External Wall/Window Fan Range GX6. Installation and maintenance instructions Retain for future use

CG60/ 70/ 80/ 90/ 100 SS/BK

CENTRIFUGAL FANS user's manual. model VENTS VK.

Installation and Wiring Instructions

Domestic AC Fans 230V Installation and Operating Guide. eco. 230V AC Base Models: icon eco icon icon icon

Simply Silent Contour 4 (100mm) Axial Extraction Fan

100cm Chimney Hood GB IE

MEV SPIDER INSTALLATION GUIDE FOR ENGINEER / INSTALLER

EKF. EC kitchen extract fan range. Installation and Wiring Instructions. Stock Ref. N EKF355E1 EKF400E1 EKF450E1 EKF450E3 EKF500E3 EKF560E3

USER S MANUAL. VKP Series INLINE FAN

Lo-Carbon Quadra Centrifugal Fan

9 inch and 12 inch Axial Fans Models MV230P, MV230AR and MV300AR Instructions for installation, maintenance and safe use.

HR200WK Through the wall Heat Recovery Ventilator

nergybulbs.co.uk Domestic AC Fans 230V Installation and Operating Guide Quick Order Hotline or

Mobile Air Conditioner Instruction Manual Model TC-N9KM

Box60/ 70/ 90. Box60_70_90 v8

Integra. Integra Plus EC MVHR. Installation & Commissioning. Stock Ref. N EC Integra Plus EC PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.

VA 150 A, VA 150 P WINDOW EXTRACT FAN. Installation and Wiring Instructions V/1/50Hz

ART cm Island Curved Glass

Silhouette Installation and Wiring Instructions

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300

User Manual for your GEH6017 & GEH9017 Cooker Hood

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600

Instruction Manual JLCHDD601/JLCHDD901 60cm/90cm Cooker hood

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

Cooker Hood CHIM60 CHIM70 CHIM90 CHIM101 CHIM110. Installation & User s instructions

Xpelair Simply Silent TM Contour Fan

irconcentre.co.uk airooncentre.co.uk

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

Trimbox Mixed Flow Fans. Product Manual. ventilation systems TP220T TP221T TP222T TP223T

Decentralised Mechanical Extract Ventilation 2 Speed Axial Extract Fan with Humidity Enabler Installation Guide

Model: Kair Whole House Ventilator Model Number: KHRVWH2000

AXIAL FANS USER S MANUAL

Smart Smart IR. Service instruction SALES DATE MANUFACTURED ON (DATE): APPROVAL MARK SOLD. model (check applicable) is recognized as serviceable

MRXBOXAB-ECO-LP1 100% Typical Installation. (including opposite handed versions)

Xpelair Simply Silent DX150

INSTALLATION AND USER S MANUAL COOKER HOOD RS-600/A-S

Vent-Axia Svara Multifunctional app controlled fan. Important Information 2 Installation and Wiring Instructions 3-11 Accessories 12 Pin Code 12

PROZONE INSTALLATION AND OPERATING INSTRUCTIONS FOR UK-PR ISS-B

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

GEH9026G Cooker Hood

HEAT RECOVERY VENTILATOR

Installation and Maintenance. Opus OK / Genie NKF1 Kitchen Extract Unit. Contents IMPORTANT WARNING IMPORTANT! Introduction WARNING!

Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System Installation Instructions

Xpelair Simply Silent DX100B

IF IN DOUBT, INSTALLATION SHOULD BE MADE BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH CURRENT WIRING REGULATIONS.

British Gas 330+ High Efficiency Condensing Boiler. Instructions for Use. To b e l e f t w i t h t h e u s e r. British Gas Service Tel:

Whole Room Dryer WRD, WRD/110

Heat Recovery Ventilation Units. LED Status Indicator. Product Manual. ventilation systems. auralite compatible HRV units

FLUEBOOST. flueboost 350 gas fire model

USER S MANUAL. Centrifugal inline fan. VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125. VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315

CAN60 / CAN60SV _01 CAN60_CAN60SV. WARNING: Read the instructions before using the appliance.

Calm. Service Instructions

EVG Extractors. Manual for Installation, Use and Maintenance

JLBIHD624 60cm Cooker Hood

IXL Eco Ventflo. User Guide. Model: (200mm) - Extraction Rate: 340m 3 /h Model: (250mm) - Extraction Rate: 490m 3 /h

USER MANUAL. ICON60H Version 00. Vertical Glass Hood

INSTALLATION INSTRUCTIONS USER GUIDE

3gb53231b.fm5 Page 12 Friday, April 11, :21 PM

Installation, operation and Maintenance Manual

FF820 Freestanding Full Height Larder Fridge Manual for Installation, Use and Maintenance

Local air conditioner

Transcription:

"Microbox" DC Models MBOX 125/2DC MBOX 125/2DC204 Continuous Mechanical Extract Ventilation Unit with Low Energy DC Motor - for domestic and commercial use Installation, Operating and Maintenance Instructions

Page 2 "MICrOBOX" - COntInUOUs MEChanICaL EXtraCt UnIt InstaLLatIOn and OpEratIng InstrUCtIOns PLEASE READ THE FOLLOWING INSTRUCTIONS VERY CAREFULLY BEFORE USING THE PRODUCT. THE MANUFACTURER WILL NOT BE HELD RESPONSIBLE AND DECLINES ANY AND ALL LIABILITY FOR DAMAGE CAUSED TO PERSONS OR PROPERTY DUE TO IMPROPER USE WITH REFERENCE TO THE PRECAUTIONS OUTLINED IN THIS MANUAL. this ManUaL MUst always BE readily available. MBOX125/2DC: 5"/125mm spigot, for dwellings up to 270m 2, max capacity 404m 3 /hr MBOX125/2DC204: 204 x 60mm spigot, for dwellings up to 270m 2, max capacity 404m 3 /hr attention : this symbol indicates that care must be taken in installing this product in order to avoid (potentially lethal) injury both to installer and user. this instruction MUst be followed for installation. 1. Do not use this product for any purpose other than that for which it was designed and as shown in this leaflet. 2. Remove all packaging and check that your fan has not been damaged in transit. If in doubt, contact your supplier. 3. Do not leave packaging within the reach of children or unskilled people. Dispose of hazardous waste (poly styrene, plastic, polypropylene, etc.) responsibly. 4. If the product is dropped or badly knocked, contact your supplier, dealer or manufacturer to ensure that it is operating properly. 5. Using any electrical equipment requires compliance with basic safety rules: - the product must not come into contact with liquid of any sort - the product must not be operated by children or other unskilled people. 6. The product should only be connected to the mains electricity supply or electrical outlet if: - your electrical voltage and frequency correspond to those shown on the rating label. - the capacity of your electricity supply is sufficiently powerful to operate the product at its maximum power If this is not the case, contact professionally qualified personnel. 7. Before carrying out any maintenance or cleaning operation, the product must be switched off and disconnect ed from the main power supply.. 8. If a fault, malfunction or anomaly of any type occurs, the product should be made inoperative (by turning off the switch and by disconnecting it from the mains electricity supply) and qualified personnel contacted imme diately. Always request original spare parts to carry out any repairs. 9. If the product needs to be removed, turn off the main network circuit-breaker and then disconnect the appli ance from that network. 10. The unit should be installed in a safe location as far away as possible from children and/or unskilled people. 11. The electricity system to which the product is connected must comply with the current standards. 12. In order to comply with Construction (Design & Management) regulations, sufficient access for safe maintenance or removal following installation, MUst be provided for this product. WarnIng : this symbol indicates that care must be taken to avoid damaging your product when following these instructions 1. This product is professionally manufactured and complies with the current standards regarding electrical equipment 2. This product conforms with the EEC directive EMC 89/336 concerning the suppression of radio interference and electromagnetic compatibility. 3. This product must not be used in an ambient temperature greater than 40 C (104 F). 4. Do not leave the product exposed to the weather (rain, sun, snow, etc.). 5. Possible product applications are indicated in this leaflet. 6. Do not place the unit or any part of it in water or liquids, except as indicated in the cleaning and maintenance section. 7. When cleaning or performing routine maintenance, check the condition of the appliance. 8. To avoid the risk of fire, do not use the product in the presence of inflammable substances or vapours such as alcohol, insecticides, gasoline, etc. 9. The air or fumes being extracted must be clean and free from greasy particles, soot, chemicals and corrosive agents, inflammable or explosive mixes (if these substances are treated, conctact an authorised dealer for information on a specific range of explosion-proof products). 10. The device must be installed by professionally qualified personnel.

Page 3 11. The product must be connected to the electricity supply by means of a triple-pole switch with a minimum contact opening distance greater than 3 mm. 12. To ensure optimum operation, do not block the air intake and exit vents. 13. The room where the device is located must be adequately ventilated to ensure correct operation (UNI CIG 7129). 14. If the fan is sited in a room containing a fuel burning appliance, the installer must ensure that air replacement is adequate both for the fan and the fuel burning appliance. 15. The unit should not be used as an activator for water heaters, stoves, etc. 16. Any ducting used must be free from blockages 17. Where ducting is installed in an unheated space, all of the ducts should be insulated. Where ducting is installed in a heated space, only the cold ducts should be insulated. i.e. the supply duct from outside and the ex tract duct from the unit to the outside. 18. Your fan must not be exhausted into a duct which is already used for any other purpose (see Approved Document F1 2006 for guidance) 19. THIS APPLIANCE IS PROVIDED WITH THERMAL OVERLOAD PROTECTION. IF THIS IS ACTIVATED, THE FAN MUST BE DISCONNECTED FROM THE MAINS ELECTRICITY SUPPLY. THIS WILL ALLOW THE OVERLOAD DEVICE TO RE-SET. AFTER A BRIEF PERIOD, THE FAN CAN BE RE-STARTED. IF THE FAULT PERSISTS, CONSULT VECTAIRE FOR FURTHER ADVICE. OpEratIOn 1. The Microbox is suitable for ceiling or wall installation. 2. If one of the spigots is not connected to ducting a safety grille MUst be fitted to that spigot, so that it is impossible for any moving part to be touched. 3. This fan runs continuously at a preset trickle speed and has an independently switched boost speed. The trickle & boost speeds are selectable during the installation by adjusting the trimmers in the controller (see wiring diagrams). Electrical Connection WarnIng: these appliances must be earthed and all wiring must conform to current IEE regulations and all applicable standards and Building regulations. The unit is suitable for 230V, 50Hz Single phase supply fused at 3A. The unit is supplied with a mains rated 4 core flexible cord (black, brown, grey and green/yellow) A fused spur box, or triple pole switch having a minimum contact separation of 3mm must be used for isolation. Boost controls must not be located within 1 metre of a cooker or where they may be affected by excessive heat or moisture Boost controls should be clearly identified and conveniently located. The boost switch wiring cable access is via a 12mm cable gland. The boost speed can be triggered by a switched live connection from a variety of external devices including: - PIRFF (passive infra red)* - DRH240 (dynamic remote humidistat)* - THM (thermostat)* - a light switch (if more than one light switch is used, each one must be a double pole switch) - a remote switch/pull cord (*PIRFF, DRH240 and THM may have integral over-run timer which controls the length of time that the fan will continue to operate at its boost speed after the boost has been switched off)

Page 4 C CLEanIng and MaIntEnanCE 1. Before carrying out any maintenance or cleaning operations the mains electrical supply MUst be disconnected. 2. CLEANING AND MAINTENANCE SHOULD BE CARRIED OUT BY A QUALIFIED PERSON 3. Before attempting to remove the motor impeller assembly disconnect the cable by removing the terminal block inside the control box. 4. Loosen the screws (Fig.8) without taking them off. 5. Rotate slightly and remove the motor-impeller assembly (Fig. 8). 6. Clean the motor-impeller assembly either with a dry brush or a dry cloth. 7. Electrical parts cannot be cleaned. 8. Reassemble in the reverse order to above (Fig 9). trouble shooting problem possible CaUsE how to solve the problem The product is not working No power check to see that the electrical connection has been properly made and that there is an electricity supply coming to the fan The fan blade is not turning Blade obstructed check to see there is nothing blocking it DIMEnsIOns - MBOX125/2DC DIMEnsIOns - MBOX125/2DC204 InstaLLatIOn

Page 5 1 2 3 4 5 6 7 8 9

Page 6 WIrIng and COMMIssIOnIng DIagraMs Vectaire Ltd, Lincoln Road, Cressex Business Park, High Wycombe, Buckinghamshire, HP12 3RH Tel: +44 (0)1494 522333. Fax: +44 (0)1494 522337. Email: sales@vectaire.co.uk MBOX125/2DC/MBOX125/2DC204 July 2012