RVL47. Heating Controller. Installations Instructions. Installation

Similar documents
RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

G a

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

RVL470. Heating Controller. Use. Functions. Series B

Operating Instructions

Operating Instructions

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

RVP310. Heating Controller. Building Technologies HVAC Products

RVL481. Heating Controller. including d.h.w. heating

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail)

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

RVL480. Heating Controller

Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482

Heating and D.h.w. Controller RVL482 Basic Documentation

Use. Functions. Key function. Other functions

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

RVL479. Heating Controller. for use with a partner unit

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

QAA Room Unit for Boiler Control with OpenTherm Interface Basic Documentation. Siemens Building Technologies Landis & Staefa Division

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

District heating controller

RVA Heating Circuit or Primary Controller Basic Documentation. Siemens Building Technologies Landis & Staefa Division

District heating controller

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation

RVA Cascade Controller for modulating gas-fired Boilers Basic Documentation

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

REA22 Room Temperature Controller

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

Room Units and Sensors for Use in Heating Plants. Siemens Building Technologies HVAC Products SIGMAGYR. Type summary

PRELIMINARY EDITION

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controller User Manual. Building Technologies HVAC Products

RVS46.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros 2 Zone controller User Manual. Building Technologies HVAC Products

RVS13... RVS53... AVS75... AVS37... QAA75... QAA78... QAA55... Albatros2 Boiler controllers User Manual. Building Technologies HVAC Products

District Heating Controller

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controllers User manual. Building Technologies HVAC Products

QAW70. Room Unit. Building Technologies. for use with heating controllers

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Albatros2 Boiler Controllers User Manual RVS13.. RVS53.. Siemens Schweiz AG HVAC Products. Edition 1.0 Controller series A CE1P2383en

ProCon Boiler Controller Commissioning Quick Reference Guide

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000

Room Unit for Boiler Control QAA User manual. Building Technologies. With OpenTherm Interface

Heating Controller SDC. District Heating Controller DHC 43 OPERATING INSTRUCTIONS

Self-learning Room Temperature Controller

Local Process Bus LPB

Installation, service and operating instruction Cetetherm Midi Compact SR144 DHWC

For the owner and the heating engineer. Operating and Installation Manual VRC 400. Programmable weather compensator with separat HW time control

Type UCG/UDG. English...1 Français...7 Español Up button. OK button. Down button

1. COMMISSIONING OF THE BOILER en DESCRIPTION FUNCTION BUTTON DESCRIPTION SYMBOL DISPLAY

Safety & Installation Instructions

Room Unit. Building Technologies SYNERGYR

Service Instructions for use by heating contractor

Condensing Boiler RS100 Controller Training Program

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

Digital Thermostat Models: VS30W and VS30B

INSTRUCTION FOR THE USER THC V E OIL BLU

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

Semi flush-mount room thermostats

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...

INSTRUCTION MANUAL REMOTE CONTROL DEVICE EASYREMOTE

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

SD2. Differential Controller. Operating and Installation Instructions F2 72.3

Modulating clock thermostat

Heating Controller SDC Remote Heating Controller DHC

1/8. Field settings table [6.8.2] =... ID66F3. Applicable indoor units *HYHBH05AAV3 *HYHBH08AAV3 *HYHBX08AAV3. Notes - 4P E

Heating Controller SDC Remote Heating Controller DHC

Operating instructions THETA control unit for heating contractors. ROTEX control unit: - THETA 23R - THETA RS - THETA HEM1

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

Room thermostats with LCD for wall mounting

Quickheat 30 weather compensated boiler control

Heating Controller SDC Remote Heating Controller DHC

Room thermostat with Auto Timer, independent DHW

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*

Weather compensated flow temperature control of heating and boiler systems

R. Room temperature controller with solar control FR 120. Operating instructions for the user (2012/02)

Lago SD3. Differential Controller with Speed Control. Operating and Installation Instructions

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

user s instructions MH-water heater

User Instructions For TopTronic RS-30

Field settings table [6.8.2] =... ID66F2. Applicable units *BLQ05CAV3 *DLQ05CAV3 *BLQ07CAV3 *DLQ07CAV3. Notes (*1) *B* (*2) *D* 1/8

Operating instruction. Remote control station WCM-FS /

1/8. Field settings table. Applicable indoor units *HYHBH05AAV3 *HYHBH08AAV3 *HYHBX08AAV3. Notes - 4P C

Self-learning Room Temperature Controller

LAE10 LFE10. Use. Series 02

USER MANUAL Comfort System4 TM

Contents. Box contents: JGSTAT2B (Black) Fixing screws (White) Icons used in this manual:

prestige Control Application Supplement - ACVMax

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

Operating Instructions

V. DIFFERENTIAL THERMOSTAT

Installation and Operating Manual. Merlin 5064 V3. System Manager

Operating instructions

Control Application. Supplement - ACVMax

Installation Guide. ECL Comfort 210, application A Table of Contents

Transcription:

Heating Controller Installations Instructions Installation Place of installation - In a dry room, e.g. the boiler room - Mounting choices: - In a control panel (on the inner wall or on a DIN mounting rail) - On a panel - In the control panel front - In the sloping front of a control desk Permissible ambient temperature: 0...50 C Electrical installation - Local regulations for electrical installations must be complied with - Cable tension relief must be provided - The cables from the controller to the actuator and the pump carry mains voltage - The cables to the detectors should not be run parallel to mains carrying cable (e.g. power supply for the pump) Permissible cable lengths - For all detectors: Copper cable 0.6 mm dia 20 m max. Copper cable 1.0 mm 2 80 m max. Copper cable 1.5 mm 2 120 m max. - For the room units: Copper cable 0.6 mm dia 25 m max. Copper cable from 0.8 mm dia 50 m max. - For the data bus: 1.5...2.5 mm 2 according to Landis & Staefa specification Installation and wiring Wall mounting 1. Separate base from the controller 2. Hold base against the wall. Marking «TOP» must be at the top! 3. Mark fixing holes on the wall 4. Drill holes 5. If required, knock out holes on the base for cable entry glands 6. Screw base to the wall 7. Wire up base DIN rail mounting 1. Fit rail 2. Separate base from the controller 3. If required, knock out holes on the base for cable entry glands 4. Fit base to the rail. Marking «TOP» must be at the top! 5. If required, secure base (depending on the type of rail used) 6. Wire up base Flush panel mounting Panel cutout required: 138 x 138 mm (+1 mm / -0 mm) Maximum thickness: 3 mm SIGMAGYR RVL47 1. Separate base from the controller 2. If required, knock out holes on the base for cable entry glands 3. Insert base in the panel cutout from behind until stop is reached. Marking «TOP» must be at the top! 4. Push lateral tongues behind the front panel (refer to illustration) 5. Wire up base. Make sure the cable lengths are such that there is sufficient space to open the control panel door Wrong Correct Place the tongues correctly - they must not be inside the cutout! Commissioning Preparatory checks 1. DO NOT switch on power supply yet 2. Check wiring according to the plant connection diagram 3. Ensure correct position and location of levers by turning the fixing screws (refer to illustration on the lateral wall of the unit). 4. Insert unit in the base until stop is reached. Marking «TOP» must be at the top! 5. Tighten fixing screws alternately 6. Check regulating unit (seat or slipper value): see if - it is correctly installed (observe direction of flow indicated on the valve body) - the slipper travels in the correct angular range (note position indicators) - the hand lever is disengaged 7. Note with underfloor and ceiling heating systems: the limit thermostat must be set to the correct value. During the functional test, the flow temperature may not 2522Z13 2522Z09 CE1G2523E 1

exceed the maximum permissible level (usually 55 C). If it does, proceed immediately as follows: - Either close the valve manually, or - Switch off the pump, or - Close the pump isolating valve 8. Switch on power supply The display must show something (e.g. time of day). If not, the reason may be one of the following: - No mains voltage - Main fuse blown - Main switch not set to ON General information on operation - Setting elements for commissioning: - Heating curve: directly with the little bar - Other variables: in the display; one operating line is assigned to each setting - Buttons for selecting and readjusting the values: Selecting the next operating line below Selecting the next operating line above Decreasing the displayed value Increasing the displayed value - Adopting a setting value: The setting value is adopted by selecting the next operating line (or: press Info button or one of the operating mode buttons) - Entering --.- or --:-- : Press or until the required display appears - Block jump function: To select a single operating line quickly, two button combinations can be used: Press and selecting the next line block above Press and selecting the next line block below Setting procedure 1. Set bar for the heating curve according to the planning documention or according to common local practice 2. Make settings on operating lines 1...17 ("Enduser") (table on page 3) 3. Select plant type on operating line 51 (page 4) 4. Proceed in the respective table "Settings for plant type...": - Plant type 1: table on page 5 - Plant type 2: table on page 5 - Plant type 3: table on page 5 5. Enter the values set in the table! 6. If required, set the sevice functions (independent of plant type, table on page 6) 7. Carry out the final work (locking of settings, etc.; page 7) Commissioning and functional check - Specific operating lines for the functional check: 121 = simulation of outside temperature 122 = relay test 123 = detector test - If ERROR appears in the display: interrogate operating line 50 to pinpoint error (table on page 3) Setting elements 1 Operating mode buttons 2 Info button 3 Display 4 Buttons for selecting and readjusting setting values 5 Buttons for manual operation: A = manual operation ON B = valve OPENS C = valve CLOSES 6 LED for valve OPENS / 1st burner stage ON 7 LED for valve CLOSES / 2nd burner stage ON 8 LED for pump ON 9 Setting knob for room temperature readjustment 10 Heating curve, slider for flow temperature at -5 C outside temperature 11 Heating curve, slider for flow temperature at 15 C outside temperature 12 Fixing screw with sealing facility 13 Sealing facility in the cover Connection diagrams Basic connections on the low voltage side 2 CE1G2523E

AC 230 V AC 230 V Basic connections on the mains voltage side Left: connections for plant types 1, 3, 4 and 6 (mixing valve or district heat) F1 F2 1. 2. 2522A02 Right: connections for plant types 2 and 5 (boiler with a two-stage burner) B1 B5 B7 B71 E1 F1 Room unit QAW50 or QAW70 Flow temperature detector Room temperature detector Return temperature detector Return temperature detector in secondary circuit Outside detector Two-stage burner (With plant type 2, it is possible to control an electro-thermal actuator in place of the burner; electrical connections on request) Thermal reset limit thermostat F2 LPB M1 N1 S1 S2 Y1 * ** Manual reset safety limit thermostat Data bus (Local Process Bus) Circulating or boiler pump Controller RVL47 Remote control "operating mode" Remote control "set value of flow temperature / minimum valve" Actuator for three-position control Wire link for locking the district heat parameters Auxiliary switch for minimum stroke limitation in the actuator (suppression of hydraulic creep) Settings on the "Enduser" level Press or, thus activating the "Enduser" level Legend to the tables: Adjustable value Read only display Line Function, display Factory setting Range Setting Explanations, notes, tips 1 Setpoint for 20.0 C 0...35 NORMAL heating 2 Setpoint for 16.0 C 0...35 REDUCED heating 3 Setpoint for holidays mode / frost potection 10.0 C 0...35 4 Weekday (for heating program) 5 1st heating period, start of NORMAL heating 6 1st heating period, start of REDUCED heating 7 2nd heating period, start of NORMAL heating 8 2nd heating period, start of REDUCED heating 1...7 1...7 1 = Monday 2 = Tuesday 7 = Sunday 1-7 = all days Monday to Fryday: --:--... 24:00... 22:00 Saturday: 23:00 Sunday: 22:00 Monday to Fryday: 22:00 Saturday: 23:00 Sunday: 22:00 --:--... 24:00... --:-- --:--... 24:00...... --:-- --:--... 24:00...... 12 Date of first day of holiday --:-- 01.01.... 31.12. Day.Month 13 Date of last day of holiday --:-- 01.01.... 31.12. 14 Time of day 0...23:59... Hours:Minutes 15 Weekday 1...7... 1 = Monday 2 = Tuesday 7 = Sunday 16 Date 01.01.... 31.12.... Day.Month (e.g. 02.12 for 2 Dec.) 17 Year 1995..2094... CE1G2523E 3

50 Faults Display function Display example for interconnected plants: 10 = error code 2 = segment number 03 = controller address 10 = fault outside detector 30 = fault flow or boiler detector 40 = fault return detector (primary circuit) 42 = fault return detector (secondary circuit) 60 = fault room detector 61 = fault room unit 62 = wrong room unit connected 81 = short-circuit on data bus 140 = wrong controller address (data bus) Settings on the "Heating engineer's" level Press and simultaneously for 3 seconds, thus activating the "Heating engineer's" level for setting the plant type and the plant-related variables. Setting the plant type on operating line 51: The required plant type must be set on operating line 51. This activates all functions and operating lines required for the plant, which can then be set. Ignore the other five plant types! 51 Plant type 1 1...3... 4...6 are disabled Plant types Plant type 1: space heating with mixing zone (three-position control, acting on seat or slipper valve) /B5 B7 Plant type 2: space heating with own boiler (on/off control, acting on burner) /B5 Plant type 3: space heating with district heat connection /B5 B7 B71 B1 B5 B7 B71 E1 E2 LPB M1 N1 Y1 Room unit QAW50 or QAW70 Flow temperature detector Room temperature detector Return temperature detector Return temperature detector in secondary circuit Outside detector Boiler or heat exchanger Load LPB, Data bus (Local Process Bus) for common outside temperature Circulating pump or boiler pump Controller RVL47 Actuator for three-position control * With plant type 2, it is possible to control an electro-thermal actuator in place of the burner; controller settings on request. 4 CE1G2523E

Settings required for plant type 1 (selected on on operating line 51) Line Function, display Factory setting 61 Heating limit for NORMAL heating (ECO day) 62 Heating limit for REDUCED heating (ECO night) 18.0 C --.- or Range Setting Explanations, notes, tips 5.0 C --.- or 63 Building time constant 20 h 0...50...h Light = 10 h, medium = 25 h, heavy = 50 h 65 Source of the room temperature 0 0 / 1 / 2 / 3... 0 = no room detector present or room unit only used for remote control 1 = room unit QAW50 or QAW70 at terminal 2 = room detector at terminal B5 3 = mean value of the two units at terminals and B5 81 Maximum limitation of flow temperature 82 Minimum limitation of flow temperature 101 Minimum limitation of return temperature... e.g. for floor heating 55 C... Settings required for plant type 2 (selected on on operating line 51) Line Function, display Factory setting 61 Heating limit for NORMAL heating (ECO day) 62 Heating limit for REDUCED heating (ECO night) 18.0 C --.- or 5.0 C --.- or Function prevents corrosion of boiler Range Setting Explanations, notes, tips 63 Building time constant 20 h 0...50...h Light = 10 h, medium = 25 h, heavy = 50 h 65 Source of the room temperature 0 0 / 1 / 2 / 3... 0 = no room detector present or room unit only used for remote control 1 = room unit QAW50 or QAW70 at terminal 2 = room detector at terminal B5 3 = mean value of the two units at terminals and B5 94 Switching differential 6 C 1...20. 95 Minimum burner running time 4 min 0...10... min 97 Reset limit, first burner stage to OFF 10.0 C*Min 0...500... C*Min Settings required for plant type 3 (selected on on operating line 51) Line Function, display Factory setting 61 Heating limit for NORMAL heating (ECO day) 62 Heating limit for REDUCED heating (ECO night) 18.0 C --.- or 5.0 C --.- or Range Setting Explanations, notes, tips 63 Building time constant 20 h 0...50...h Light = 10 h, medium = 25 h, heavy = 50 h 65 Room temperature 0 0 / 1 / 2 / 3... 0 = no room detector present or room unit only used for remote control 1 = room unit QAW50 or QAW70 at terminal 2 = room detector at terminal B5 3 = mean value of the two units at terminals and B5 CE1G2523E 5

81 Maximum limitation of flow temperature 82 Minimum limitation of flow temperature 111 Maximum limitation of return temp. Constant limit value 112 Maximum limitation of return temp. Slope S. e.g. for floor heating 55 C.. 0.7 0.0...4.0... T_return 111 112 t return t outside 113 Maximum limitation of return temp. Start of shifting limitation 115 Maximum limitation of differential return temperature 10 C - 50...+ 50. --.- C --.- or 0...50. 113 T_outside Differential temperature (DRT): difference between primary return and secondary return temperature 2523D01E Service functions Note: the service functions are independent of the type of plant Line Function, display Factory setting 121 Simulation of outside temperature --.- --.- or -50...+50 122 Relay test: Relay 1: valve OPENS / 1st burner stage ON Relay 2: valve CLOSES / 2nd burner stage ON Relay 3: circulating pump 123 Setpoints and actual values, detector test 0: outside detector 1: flow* or boiler* detector 2: room detector at terminal B5 3: room unit at terminal 4: primary return detector at B7 5: secondary return detector at B71 124 Corrected flow temperature set value Range Setting Explanations, notes, tips To terminate simulation: press Info button. (Resetting the attenuated outside temperature: set the actual outside temperature, then terminate simulation) 0 0/1/2/3/4 0 = normal operation (no relay test) 1 = no relay energized 2 = relay 1 energized, relay 2 and 3 deenergized 3 =plant with mixing valve: relay 2 energized, relay 1 and 3 deenergized plant with burner: relay 1 and 2 energized, relay 3 deenergized 4 = relay 3 energized, relay 1 and 2 deenergized To terminate relay test: press Info button or select next line Display function SET = setpoint or limit value ACTUAL = actual value = short-circuit = interruption * The setpoint displayed is the effective setpoint including all compensations. Display function Actual set value resulting from heating curve and position of setting knob 125 Corrected heating curve Display function Resulting setpoint incl. position of setting knob Left: flow temperature setpoint at C outside temperature Right: flow temperature setpoint at -5 C outside temperature 128 Controller address 0 0...16 0 = device with no bus 6 CE1G2523E

129 Segment number 0 0...14 Each separate subsection is given a separate number 131 Operating mode when linking terminals H1-M 133 Flow temperature setpoint when linking terminals H2-M 136 Changeover winter-/ summertime 25.03 1.1.... 31.12 137 Changeover summer-/ wintertime 22.10 1.1.... 31.12 0 0/1/2/3 0 = STANDBY 1 = AUTO mode 2 = REDUCED mode 3 = NORMAL mode 70 C. Max. selection between this value and the flow temperature setpoint according to the heating curve... Setting: earliest possible changeover time... Setting: earliest possible changeover time 139 Bus supply A 0/A... Set=0 : central bus supply (to be selected, when connected with SYNERGYR) Set=A : bus supply through the controller 141 Operating hours of controller Display function 142 Controller's software version Display function 143 Identification code of room unit Display function Final work Locking the settings for district heat The settings for district heat can be locked by linking terminals H3 and M. Then, seal the fixing screw at the bottom: insert plug (attached to the key ring) in the screw hole; introduce a wire through both lugs and seal. Finishing the installation work Tighten the fixing screws, if not already done. If settings have been entered in these instructions: keep instructions in a safe place. Keep Operating Instructions inside the controller. Seal the transparent cover, if required. CE1G2523E 7

Dimensions 139 1,5 95 (42,5) 144 19 15 144 26 26 26 26 144 4,5 14 max. 3 18 106 50 39 39 35 36 29 138-0/+1 Dimensions in mm 36 72 106 108 138-0/+1 1997 Landis & Gyr (Europe) Corp. Ordering number: 4 319 2758 0 8 H 4 319 2758 0 c October 15, 1997 CE1G2523E