ADAPT PARASOL a. Installation - Commissioning - Maintenance ADAPT Parasol - m

Similar documents
ADAPT Parasol EX a. Installation - Commissioning - Maintenance ADAPT Parasol EX a - m A1, B1

ADAPT Parasol EXb. Installation. Installation Commissioning Maintenance A1, B1

ADAPT Parasol EX. Energy-saving, suspended comfort module QUICK FACTS

PARASOL EX. Suspended comfort modules QUICK FACTS

Natural Ventilation Controller with 24vDC drive NVC-1204

PARAGON. Compact comfort module. Key figures

Demand-controlled Ventilation Leading edge products for demand-controlled ventilation

DAP III Zone Master User s Guide

SmartDial. Wireless. User Manual. -en_gb language A004. Document in original

Installation Instruction

System technology. Demand controlled ventilation WISE.

OJ Waterline control system

Swegon PACIFIC. Integrated chilled beam PACIFIC CHILLED BEAM KEY FIGURES

Natural Ventilation Controller with 24vDC drive NVC-1204

SEQUENCE OF OPERATIONS

TECOM SYSTEMS NETWORK MASTER

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h

21-light Remote Annunciator. Owner s Manual

1.0 Digital Controller

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

prestige Control Application Supplement - ACVMax

1.0 Digital Controller

5, SE GÅNGHESTER,

P2267 NETWORK INTERFACE

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

SIRe Advanced Air Curtains Water Ambient, no heat

iq Star LYRA II chilled beam cassette

SIRe Advanced Air Curtains Electric With quick guide. SIReAA GB DE FR For wiring diagram, please see last pages. ES

2017 products.koer.com Page 1 of 14

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

OVEN INDUSTRIES, INC.

Halton Rex for Vario R6O - Variable air volume chilled beam

PRODUCT DATA COMFORT 1200 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 1400 m 3 /h

Control Application. Supplement - ACVMax

Air heater/cooler in combination with ground source heat pump

Digital Marine Exhaust Temperature Alarm

FCCP 200: Fume-cupboard indicator and monitor

SIRe Competent Air Curtains Water With quick guide. SIReAC. For wiring diagram, please see p Original instructions

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

HVAC Controls Upgrades: Requirement Details ( )

SCAN200E USER S MANUAL

ARO Series. Description. Features. Modbus CO2 VOC. Networkable* ARO AROB24TGVH AROB24TGH. room controller. (AROB series only) or network

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

Reference Guide for Microprocessor Controller

WLM2 WLTA WLTD WLTP WLCT2

PARAGONTM Comfort module for hotel rooms and hospital wards

PRODUCT DATA COMBI 300 POLAR BY NILAN. Ventilation with passive & active heat recovery. Active heat recovery. Passive heat recovery.

Pre-programmed room controller with communication

Installation Instructions for the TBLZ-2-66 control box. for controlling two air handling units (Twin Function) GOLD RX

VCM-X / RNE Controller Operator Interface SD Technical Guide

EBC20. Instructions for fitting, installation and operation. Read and save these instructions!

SC-F3G User Manual 1.0

prestige Control Application Supplement - TriMax

Corrigo E. Second generation which contains all applications and languages

ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys

EXcon zone control. Control for up to 4 individual zones _ fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov

Reference Guide for Microprocessor Controller

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

Primo Hotel. General. Indoor climate units for hotel rooms

Digital Precise Air Control - DPAC

Pre-programmed room controller with communication and hidden setpoint

prestige Control Application Supplement - TriMax

Room controllers with manual forced ventilation function

VAV CHILLED BEAMS Pi FUNCTION DESIGN GUIDE

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

Product Manual SZ1009

Original instructions. SIRe Basic Quick guide. SIReB

Contents. Box contents: JGSTAT2B (Black) Fixing screws (White) Icons used in this manual:

Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses

I/O ZONE 560/583 USERS GUIDE

iq Star LYRA II chilled beam cassette

sintra Sintra is a trademark of Asya Traffic INC.

User Guide: *IG1605EW*

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

EASY ZONE TOUCH. User Manual. 6 Zone Control System with Active Temperature Management. Ver 1.0

Copyright AB Regin, Sweden, Corrigo E manual Ventilation application

Product Manual SZ1022/SZ1031/SZ1035/

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

Controllers. Centralization of Access Control Devices Made Easy. Installer Guide

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Swegon CASA. duct coils for heating. the supply air

MBS Therma-Fuser Standalone Motorized Swirl VAV Diffuser

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Simple Self-Diagnosis by Malfunction Code

EXact Control System Basic instructions for the VEX200 series

INDUSTRIAL AIR CURTAIN. IndAC 2

ETO 2 - Controller for ice and snow melting

User's Guide. CTS6000 control panel

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

ADRIATIC VF. Active chilled beam with cooling, heating and ventilation QUICK FACTS

CUMULUS CUMULUS. Key figures. Construction. Function Integrated chilled beams

PRODUCT DATA COMFORT 600 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 800 m 3 /h

INDUSTRIAL AIR CURTAIN. IndAC 2

MicroTech Unit Ventilator

Sauter flexotron 800 ventilation Manual

Transcription:

ADAPT PARASOL a Installation - Commissioning - Maintenance 2013-12-04 ADAPT Parasol 600 / 600 PF ADAPT Parasol 1200 / 1200 PF M6 1

Water Position of waterpipes ADAPT Parasol 600 / 600 PF 600 Värme retur/ Heating return Värme tillopp/ Kyla tillopp/ Heating supply Cooling supply Note that clamp ring couplings require support sleeves inside the pipes. Kyla retur/ Cooling return 200 ADAPT Parasol 1200 / 1200 PF Värme retur/ Heating return Värme tillopp/ Heating supply Kyla tillopp/ Cooling supply Kyla retur/ Cooling return 200 1200 y Note the need for a empty space in front of the motor in order to facilitate service. Water connections with factory-fitted valves Connection dimensions Cooling energy Male threads, DN15 (1/2 ) Heat Male threads, DN15 (1/2 ) (An ADAPT Parasol 1200 is shown in the example) Water connections without factory-fitted valves Connection dimensions Cooling energy, flat tube end (Cu) Ø 12 x 1.0 mm Heating, flat tube end (Cu) Ø 12 x 1.0 mm (An ADAPT Parasol 1200 is shown in the example) Air Unit 2 A= ADAPT Parasol 600 Ø 125 ADAPT Parasol 600 PF Ø 160 ADAPT Parasol 1200 Ø 125 ADAPT Parasol 1200 PF Ø 160

RoHS Wiring CO 2 sensor Temperature sensor/ Window contact Condensation sensor white black white brown black brown blue grey black 13 14 15 16 17 18 19 20 21 green blue red yellow red black white Sensor Condens 24V 0-10V DC 24V 0-10V DC G Sensor Condens 24V 24V white blue (US=black) brown brown (US=white) blue (US=black) brown (US=white) Valve actuator heating Key card Cable converter USB-RJ12 Adapter RJ12- wire/bms Adapter 3xRJ12 Motor Valve actuator cooling Sensor module 1. 2. Pressure sensor (Modbus) Sensor module 24 V AC / DC 1. Wiring when not using VOC sensor 2. Wiring when using VOC sensor VOC Sensor 3

Super WISE Next Zone CONTROL Zone 1 2 3 4 MB2 5 6 7 8 MB1 RS -485 type Belden 9842 MB id 1 G 24 A B G 24 A B ADAPTER RJ12/WIRE / with SuperWISE system Modular 6/6 RJ12 22 23 24 25 22 23 24 25 22 23 24 25 MB id 4 MB id 8 MB id 12 /Slave with SuperWISE system 22 23 24 25 22 23 24 25 22 23 24 25 MB id 4 MB id 1 Slave id 1 MB id 2 Slave id 2 BMS RS 485 /Slave with BMS sytem 22 23 24 25 22 23 24 25 22 23 24 25 MB id 1 MB id 2 Slave id 1 MB id 3 Slave id 2 4

ADAPT PARASOL a Installation - Commissioning -Maintenance 2013-12-04 K factor side 1 + 2 + 3 + 4 = k2 = max. flow 1 Air Water K factor side 1 + 3 = k1 = min. flow 1 Air Water 2 4 ADAPT Parasol Nozzle setting k-factor per side Side per side * ** 600 L 1&3 0.253 0.253 600 L 2&4 0 0.253 600 M 1&3 0.44 0.44 600 M 2&4 0 0.44 600 H 1&3 0.693 0.693 600 H 2&4 0 0.693 600 PF L 1&3 0.28 0.82 600 PF L 2&4 0 0.745 600 PF M 1&3 0.435 0.98 600 PF M 2&4 0 0.905 600 PF H 1&3 0.685 1.23 600 PF H 2&4 0 1.15 1200 L 1&3 0.253 0.253 1200 L 2&4 0 0,665 1200 M 1&3 0.44 0.44 1200 M 2&4 0 1,16 1200 H 1&3 0.693 0.693 1200 H 2&4 0 1,825 1200 PF L 1&3 0.28 0.82 1200 PF L 2&4 0 2,05 1200 PF M 1&3 0.435 0.98 1200 PF M 2&4 0 2,43 1200 PF H 1&3 0.685 1.23 1200 PF H 2&4 0 2,98 * ) = k-factor for adjusting the min. flow. ** ) = k-factor for adjusting the max. flow. 3 q i ( ) 2 p = [Pa] k q = k p [l/s] [pi Pa] q [l/s] k = k-factor i ADAPT Parasol Example nozzle setting k pl *** ) k1 k2 600 LLLL 0.51 1.01 600 LHLH 0.51 1.89 600 MMMM 0.88 1.76 600 HHHH 1.39 2.77 600 PF LLLL 0.56 3.13 600 PF LHLH 0.56 3.95 600 PF MMMM 0.87 3.77 600 PF HHHH 1.37 4.76 1200 LLLL 0.51 1,84 1200 LHLH 0.51 4,16 1200 MMMM 0.88 3,20 1200 HHHH 1.39 5,04 1200 PF LLLL 0.56 5,74 1200 PF LHLH 0.56 7,61 1200 PF MMMM 0.87 6,82 1200 PF HHHH 1.37 8,42 *** ) All four sides on the unit can be set individually. The designation of the nozzle setting follows the order of figures above. k1 = No occupancy flow k2 = Max. occupancy flow k1 / k2 K p = 0.50 / 3.66 NOTE: When changing between max- and min flow nozzle pressure will change slightly. 3 5

Commissioning/checking the airflows Constant pressure in the zone with zone damper CONTROL Zone or equivalent. 1. Check that all the Wise products are energised. T-25 Nozzle configuration H M L H = M= L = 1 x 8 2. Ensure that all the ADAPT Parasol modules have their correct k-factors and minimum and maximum flows preset. Ensure that all are set to the maximum flow commissioning position, (3 blue + 3 red LEDs are lit). 3. Check the present flow compared with the maximum flow in the zone; adjust the pressure setpoint until the correct flow is obtained with TUNE Control. If Max. flow is not attained, temporarily close another zone damper / other zone dampers. 4. Measure and record airflow in the max flow position on one ADAPT Parasol in the zone. 5. Reset to the min flow position, measure and record airflow. 6. Set back to maximum flow. 7. Perform the same procedure on all the ADAPT Parasol modules in the zone. 8. Reduce the pressure setpoint setting on the zone damper if pressure is required for other zones, e.g. 5 Pa. 9. Commission the remaining zones, following the same procedure. 10. Check/commission the previous shut-off zones in the same way. X-shape 11. Restore the pressure setpoints on all the zone dampers. 12. Identify the reference zone, i.e. the zone with the lowest flow compared with the design maximum flow (e.g. by checking present airflow across each zone damper; using the TUNE Control hand unit). 13. Set the minimum flow on a number of ADAPT Parasol modules or use the zone damper for setting the minimum flow so that the ventilation system responds to the simultaneous load. Fan-shape 14. Now adjust the air handling unit s pressure setpoint until the zone damper of the reference zone is 85-90% open, (done by the SuperWISE, if it is used). 15. Restore all the settings and set all the ADAPT Parasol modules to normal position. 6

Menu: To reach the menu, hold the left-hand and right-hand buttons down for five seconds. With the left-hand button ( ) you advance through the menus. With the right-hand button ( ) you confirm your selection and return to the menu. Press the left-hand button and select: 1. Alarm list 2. Commissioning 6. Return to menu Press the righthand button to confirm your selection 1. Alarm list: See the complete alarm list to the right. 2. Commissioning: There are then six selections in the commissioning menu, (press the left-hand button to advance in the menu). When you have marked a selection, the controller goes directly to that operating mode. 2.1. Min airflow holiday 2.2. Min airflow unoccupied 2.3. Min airflow occupied 2.4. Max airflow occupied 2.5. Open cool valve 2.6. Open heat valve Press the right-hand button to return to the menu. 1 and 3 are not used if ECOPulse and 2Step are in use 3, 4, 5: Not used 6. Return to menu: Presence detector Diodes for temperature, commissioning or alarm indication Function button Diode-indicating function - Green = Ok - Flashing Green = Condensation alarm - Yellow = Alarm - Green/Yellow=Comfort alarm Temperature sensor (not acute) Function button Alarm list for the sensor module Alarm no. Type of alarm 32 16 8 4 2 1 Alarm 1 Supply voltage low Alarm 2 Supply voltage critically low Alarm 3 Ext temp missing Alarm 4 Ext temp error Alarm 5 Condensation sensor error Alarm 6 SM temp sensor error Alarm 7 SM button error Alarm 8 CO 2 sensor missing Alarm 9 VOC Error Alarm 10 Low pressure Alarm 17 SM comm error Alarm 18 Slave comm error Alarm 19 Pressure sensor comm error Alarm 20 VOC sensor comm error Alarm 21 No master request (slave) Alarm 22 Slave incompatible version Alarm 25 Heating comfort alarm Alarm 26 Cooling comfort alarm Alarm 27 Temp. Set point overlap alarm Alarm 28 Air quality comfort alarm Alarm 29 Condensation Alarm 33 24 V Out 1 overload error Alarm 34 24 V Out 2 overload error Alarm 35 24 V Out 3 overload error Alarm 41 Slave input common alarm Alarm 42 Slave output common alarm The alarm is displayed by a number of diodes when you have selected Alarm list (1) in the menu. Each diode represents a number as shown in the table above and the numbers should be added up to form an alarm number. Ex. The centremost blue and the two last red diodes are lit (xoxxoo) The centremost blue one corresponds to 16, the penultimate red one to 2 and the last red one to 1. The sum of these is 19, which is the alarm number. 3 parallel RJ12 ports (Modbus) for connecting a controller, another sensor module or a computer, for example, by means of a Cable converter USB-RJ12 ON 1 2 Dial for addressing the appropriate sensor module if several are used in the same loop. 10 senormodules can be connected to the same master, and each and one of them need an unique address. Switch/Termination resistance. Switch 1 should be on for the last sensormodule in the loop. 7

ADAPT PARASOL a Installation - Commissioning - Maintenance 2013-12-04 1 3 AIR OPEN THIS SIDE 4 OPEN THIS SIDE 2 5 OPEN THIS SIDE Art.no 942428019 8