Performance Analysis of Water-Water Heat Pump System of 100 kw Scale for Cooling Agricultural Facilities

Similar documents
Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

A study of Transient Performance of A Cascade Heat Pump System

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Effects of seawater flow rate and evaporation temperature on performance of Sherbet type ice making machine

Purdue e-pubs. Purdue University

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Effects of Fan-Aspirated Radiation Shield for Temperature Measurement in Greenhouse Environment

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Experimental Research on Monomial Cooling Measure of Greenhouse in Summer

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

International Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 1-5

A Study on Smart City Development Project for Regional Innovation: Co-creation and Design Thinking Approach

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

DAYLIGHTING PERFORMANCE ON VENETIAN BLIND FOR HEALTHY APARTMENT HOUSING

Enhancing the performance of the domestic refrigerator with hot gas injection to suction line

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Performance of CO2 Cycles with a Two-Stage Compressor

Development of a Slope Stability Program for Transmission Towers

Global Journal of Engineering Science and Research Management

National Policy, Laws, and Institutions of Urban Agriculture in Korea

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Performance Analysis of Solar Assisted Cascade Refrigeration System of Cold Storage System

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate

Dae-Hyun Jin. 8/2018-Present Assistant Professor of Mechanical Engineering, Taylor University, USA

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Development of magnetic pulse crimping process for highdurability

COMPRESSOR LESS SOLAR REFRIGERATOR

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Exploring the Performance Characteristics of CO2 Cycles in a Breadboard-Type Test Facility

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

Effects of Planting Date and Density on Tuber Production in Sandersonia aurantiaca

Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Storage and hot and cold water in a thermocline for Space heating/cooling and domestic hot water

A STUDY ON THE APPLICABILITY OF THE TIME-DIVISION HOT-WATER SUPPLY HEATING FOR ONDOL - THE RADIANT FLOOR HEATING SYSTEM IN KOREA

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Dynamic Evacuation Guidance Considering Occupant Distribution

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer

Effect of Vacuum Cooling Operation Parameters on Cooling Time and Weight Loss of Chinese Cabbage

COOLING ENERGY SAVING SYSTEM USING A WATER MIST DEVICE ON WINDOWS

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Heat Pump Fluidised Bed Dryer with CO 2 as Refrigerant Measurements of COP and SMER

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Lighting Solutions 2/7/2017. The production environment and culture impacts crop quality and timing February

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

Modified Air Cooler with Split Cooling Unit

REVIEW ON HOT GAS DEFROSTING SYSTEM FOR VAPOR COMPRESSION REFRIGERATION SYSTEM

A Study on Hierarchy of Spatial Configuration in Outpatient Department of General Hospital

ADVANCES in NATURAL and APPLIED SCIENCES

Study on the Effects of Learning by Changing the Color- Temperature LED Lamp

Proceedings Enhanced Characteristics of Nondispersive Infrared CO2 Gas Sensor by Deposition of Hydrophobic Thin Film

GRAFTING OF VEGETABLES TO IMPROVE GREENHOUSE PRODUCTION

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Shortcut Model for Predicting Refrigeration Cycle Performance

Development of Open BIM-based Code Checking Modules for the Regulations of the Fire and Evacuation

Upward Evacuation Experiment for Estimating Evacuation Speed in Water Disaster

Electricity consumption propensity of different household members in apartment house

Effects of Planting Dates and Varieties on Growth and Yield of Broccoli During Rainy Season

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

ScienceDirect. Development progress of critical equipment in the CSNS cryogenic hydrogen system

Development of Smart Phone Applications Linked with Fire Alarm Control Panel in Automatic Fire Detection System

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

INFLUENCE OF DIFFERENT TEMPERING PERIOD AND VACUUM CONDITIONS ON THE RICE GRAIN BREAKAGE IN A THIN LAYER DRYER

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

HVAC Water chiller selection and optimisation of operation

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

Transcription:

Original Article J. of Biosystems Eng. 39(1):34-38. (2014. 3) http://dx.doi.org/10.5307/jbe.2014.39.1.034 Journal of Biosystems Engineering eissn : 2234-1862 pissn : 1738-1266 Performance Analysis of Water-Water Heat Pump System of 100 kw Scale for Cooling Agricultural Facilities Youn Ku Kang*, Young Sun Ryou, Jae Kyung Jang, Young Hwa Kim, Jong Goo Kim, Geum Chun Kang Dept. of Agricultural Engineering, National Academy of Agricultural Science, RDA, Suwon 441-707, Korea Received: November 19 th, 2013; Revised: January 25 th, 2013; Accepted: February 5 th, 2014 Purpose: In this study, the performance of cooling system with the water-water heat pump system of 100kW scale made for cooling agricultural facilities, especially for horticultural facilities, was analyzed. It was intended to suggest performance criteria and performance improvement for the effective cooling system. Methods: The measuring instruments consisted of two flow meters, a power meter and thermocouples. An ultrasonic and a magnetic flow meter measured the flow rate of the water, which was equivalent to heat transfer fluid. The power meter measured electric power in kw consumed by the heat pump system. T-type thermocouples measured the temperature of each part of the heat pump system. All of measuring instruments were connected to the recorder to store all the data. Results: When the water temperature supplied into the evaporator of the heat pump system was over 20 C, the cooling Coefficient Of Performance(COP) of the system was higher than 3.0. As the water temperature supplied into the evaporator, gradually, lowered, the cooling COP, also, decreased, linearly. Especially, when the water temperature supplied into the evaporator was lower than 15 C, the cooling COP was lower below 2.5. Conclusions: In order to maintain the cooling COP higher than 3.0, we suggest that the water temperature supplied into evaporator from the thermal storage tank should be maintained above 20 C. Also, stratification in the thermal storage tank should be formed well and the circulating pumps and the pipe lines should be arranged in order for the relative low-temperature water to be stored in the lower part of the thermal storage tank. Keywords: Agricultural facilities, Coefficient of performance, Heat pump, Thermal storage tank Introduction The heat pump system is a Heating, Ventilation, Air Conditioning (HVAC) equipment. The system is useful for cooling in summer and heating in winter. It has excellent performance compare to the amount of energy it consumes. Thus, usage of the system as a HVAC equipment is, recently, significantly increasing for cooling and heating in the agricultural facilities and many buildings. It is evaluated by the U. S. Environmental Protection Agency (EPA). The EPA states, It is low-energy consumption, eco-friendly and the most cost effective system among the current cooling and heating systems for buildings over the world. *Corresponding author: Youn Ku Kang Tel: +82-31-290-1813; Fax: +82-31-290-1840 E-mail: ykk0977@korea.kr The heat pump system is divided into compression and absorption types. The compression type heat pump system is mainly used, now. The reasons are (1) it is relatively simple to operate and maintain, (2) it has excellent performance. The compression type heat pump system cools and heats by using a compressor, a condenser, expansion valves, an evaporator and a four-way valve, etc. The compression type heat pump system has same components. However, only the heat exchanger type is different due to the different kind of heat source and heat sink. Since the control and operation methods could be different based on the load characteristics of the targeted facilities, it is important to establish the optimum method of operation reflecting the load characteristics. By establishing the optimum method of operation, we can save the power consumption of the heat pump system and improve the Copyright c 2014 by The Korean Society for Agricultural Machinery This is an Open Access article distributed under the terms of the Creative Commons Attribution Non-Commercial License (http://creativecommons.org/licenses/by-nc/3.0) which permits unrestricted non-commercial use, distribution, and reproduction in any medium, provided the original work is properly cited.

coefficient of performance. Totally, we can save the heating and cooling cost. In order to utilize the heat pump system effectively for cooling and heating agricultural facilities, it is necessary to establish design criteria for the load and systemic control must by analyzing the cooling/heating load characteristics of targeted agricultural facilities. After the heat pump system with such design criteria above is made completely, the overall problems should be analyzed with enough trial running. Also, the effective control method of operation should be made. Usually, PE (Polyethylene) or Glass-coated protected cultivation facilities had an adverse effect on plant growth because the indoor temperature of the facilities in summer rises up to 35 40 C (Kim et al., 2011). Regarding the climate circumstances in Korea, the indoor temperature of a greenhouse rises incredibly in summer. Therefore, it is impossible for crops to grow, normally. As a result, many farmers often stop cultivating during summer. The annual utilization rates of the facilities fell down (Nam, 2000). The representative cooling methods used in Korea might include cooling using a refrigerator, evaporation, geothermal heat, ventilation and light shading, etc. The cooling method using refrigerator costs a lot because it spends much energy (Kim et al., 2006). There are studies about promoting growth, increasing the merchandising rates and the number of products by cooling the greenhouses starting with some kinds of higher value-added crops (Yu et al., 2006; Nam et al., 2000; Ryu et al., 1999; Moon, 1999, Lee, 1994; Kim et al., 2011). There are studies about analyses of the cooling effect, the seedling production effect, the power consumption and energy balance of a closed transplant production system (Lee et al., 2006; Kim et al., 2003, 2002). Considering the aspects of the effective usage and the profitability of agricultural facilities, achieving year-round cultivation through the optimization of environment (ex, cooling) inside of greenhouses during summer is a confront subject (Nam, 2000). In this study, the performance of cooling system with the water-water heat pump system of 100 kw scale made for cooling agricultural facilities, especially for horticultural facilities, was analyzed. It was intended to suggest performance criteria and performance improvement for the effective cooling system. Materials and Methods Experiment equipments The water-water heat pump system of 100 kw scale used in this study was made for both cooling and heating. The condenser and evaporator were made as a plate type heat exchanger for exchanging heat between refrigerant and water as heat transfer fluids. Refrigerant condenses in the condenser while high-temperature gas phase refrigerant made contacts with water. The water temperature rises while the water penetrates through the condenser. The water is transferred into the PE pipe type heat exchanger as shown in Figure 1. The water gets cooled. Then, the water gets transferred into the condenser again. The water in the thermal storage tank is supplied into the evaporator. The water in the thermal storage tank cools Figure 1. Photo of the PE pipe type heat exchanger. Figure 2. Photo of the water-water heat pump system of 100 kw scale for cooling performance test. 35

gradually while the refrigerant evaporates in the evaporator. Ryu et al. (2012) suggested the design criteria for the PE pipe type heat exchanger. It has excellent corrosion resistance and low installation costs. In this study, a PE pipe type heat exchanger was, also, made based on the criteria mentioned above. The heat pump system is shown in Figure 2. Experiment methods In order to increase the accuracy of the measurement, the heat pump system was operated longer than 60 minutes to get stabilized. While it was operated continuously for 480 minutes, the data was collected every 10 minutes to analyze the cooling performance. As shown in Table 1, the measuring instruments consisted of two flow meters, a power meter and thermocouples. An ultrasonic and a magnetic flow meter measured the flow rate of the water as heat transfer fluid. The water exchanged heat with refrigerant in the condenser and the evaporator. A power meter measured electric power in kw consumed by the heat pump system. T type thermocouples measured the temperature of each part of the heat pump system. All of measuring instruments were connected to the recorder to store all the data. As shown in Figure 3, the water temperature supplied into the condenser (at the entrance of the condenser) was 27.4 C at the beginning of the experiment. After passing through the condenser (at the exits of the condenser), the temperature was 40.2 C, which increased by 12.8 C. Later, the water temperature supplied into the condenser tends to rise, gradually. It was because the water supplied into the condenser by the pipe was heated up by sunlight. The experiment was conducted during the daytime in summer. After 480 minutes, the water temperature supplied into the condenser was 33.5 C. Moreover, after passing through the condenser, it rose up to 44.0 C, which is increased by 10.5 C. Comparing with the beginning period of the experiment, the difference between the temperatures before and after the water passing through the condenser was lower by 2.3 C. The reason was because the water temperature supplied into the evaporator (at entrance of the evaporator) became lower. That is, it was because as the less amount of heat was absorbed from the evaporator, the less amount of heat was discharged to the condenser. The cooling performance test was conducted after the water temperature in the thermal storage tank was maintained at a constant level. It was designed to form the stratification naturally while the water flows in the Results and Discussion Temperature changes of the water as heat transfer fluid at the entrances and the exits of condenser and evaporator Figure 3 displays the temperature changes of the water at the entrances and the exits of the condenser and the evaporator for 480 minutes. While conducting the cooling performance test, the water temperature at the entrances and the exits of the evaporator became, gradually, lower. The water temperature at the entrances and the exits of the condenser became, gradually, higher. Figure 3. Variation of the water temperature passing through evaporator and condenser. Table 1. Specifications of the measuring instruments for performance test Measuring instruments Ultrasonic flow meter Electromagnetic flow meter Recorder Temperature sensors Power meter Specifications PT868, Panametrics, Norway EF-501, Seoyong Engineering Co., Korea MV-200, Yokogawa, Japan T type, Daehyeon Tech, Korea CW-240, Yokogawa, Japan 36

lower part of the thermal storage tank again after the water flows out from the upper part of the thermal storage tank was cooled by passing through the evaporator. At the beginning of the experiment, the water temperature in the thermal storage tank was 23.4 C. Then, it was cooled down to 15.1 C while passing through the evaporator. The difference of the temperatures was 8.3 C. Later, the water temperature in the thermal storage tank became lower, gradually. In 480minutes, it fell down to 12.9 C. At that time, the water temperature flowed in the tank after passing through the evaporator was 6.6 C. The difference between the temperatures of the entrance and the exit was 6.6 C. As analyzed above, the temperature difference between the water at the side of the condenser and at the side of the evaporator tended to decrease gradually as time passed by. As the lower the water temperature inside the thermal storage tank, the smaller the temperature difference between the water passing through the evaporator and the condenser at the entrances and the exits. Power consumption, amount of heat absorbed/discharged and cooling COP The power consumption, the amount of heat absorbed from the evaporator, discharged out of condenser and the cooling COP sequentially during the cooling performance test are shown in Figure 4. During the cooling performance experiment, the power consumption was 35.43 kw at the beginning of the experiment. It tended to increase more or less up to 38.31 kw, later. It was judged that the reason was because the water temperature supplied into the condenser (at the entrance of the condenser) rose. It tended that the amount of heat discharged out of the condenser decreased from 150.33 kw to 123.31 kw, linearly. The amount of heat absorbed from the evaporator, also, decreased from 115.81 kw at the beginning to 87.91 kw in 480 minutes, linearly. The amount of heat absorbed from evaporator and discharged out of condenser decrease in similar forms almost in parallel lines The cooling COP was 3.27 at the beginning, but it decreased down to 2.29 in 480 minutes. The reason was because the water temperature supplied into condenser rose and the water temperature supplied into the evaporator fell (See Figure 3). Cooling COP based on variation of the water temperature at the entrance of the evaporator The cooling COP of the heat pump system is affected significantly by the water temperature supplied into the evaporator from the thermal storage tank. As shown in Figure 5, in case of the water temperature supplied into the evaporator from the tank was higher than 20 C, the COP exceeded 3.0. However, as the water temperature became lower, the cooling COP became lower, gradually. Therefore, in case of the water temperature was lower than 15 C, it decreased to the level lower than 2.5. Based on the results above, in order to maintain the COP at the level above 3.0, the water temperature supplied into the evaporator from the thermal storage tank should be adjusted to be maintained at the level above 20 C. Thus, if possible, the stratification in the thermal storage tank should be formed well. Also, after the relative hightemperature water in the upper part of the thermal storage tank was cooled in the evaporator, the circulating pumps and the pipe lines should be arranged in order for the water to be stored in the lower part of the thermal storage tank. Figure 4. Variation of power consumption, amount of heat absorbed from evaporator and discharged out of condenser and COP. Figure 5. COP variation of the heat pump system according to water temperature entering into evaporator in cooing test. 37

Conclusions In this study, we analyze the performance of the waterwater heat pump system for cooling agricultural facilities during the high-temperature period in summer. In case that the water temperature supplied into the evaporator was higher than 20 C, the cooling COP was more than 3.0. In case that the water temperature supplied into the evaporator was lower than 15 C, the cooling COP fell down at the level below 2.5. As the water temperature supplied into evaporator of the heat storage tank became lower gradually, the cooling COP falls down linearly. Therefore, we suggest that in order to maintain the COP at a high level while cooling operation, the water temperature supplied into the evaporator from thermal storage tank should be maintained higher, stratification in the thermal storage tank should be formed well and the circulating pumps and the pipe lines should be arranged in order for the relative low-temperature water to be stored in the lower part of the thermal storage tank and the relative high-temperature water to be stored in the upper part of the thermal storage tank. Conflict of Interest The authors have no conflicting financial or other interests. Acknowledgement This study was carried out with the support of Cooperative Research Program for Agricultural Science & Technology Development (Project No. PJ00841303), Rural Development Administration, Republic of Korea and Research Program for Agricultural Science & Technology Development (Project No. PJ008659), National Academy of Agricultural Science, Rural Development Administration, Republic of Korea. References Kim, K. D., E. H. Lee, W. B. Kim, J. G. Lee, D. L. Yoo, Y. S. Kwon, J. N. Lee, S. W. Jang and S. C. Hong. 2011. Effects of several cooling methods and cool water hose bed culture on growth and microclimate in summer season cultivation of narrowhead golden ray (Ligularia stenocephaia). Journal of bio-environment control 20(2): 116-122 (in Korean, with English abstract). Kim, J. K., Y. H. Kim, M. G. Lee, Y. H. Choi and S. H. Lee. 2003. Analysis of electric energy consumption in closed transplants production system as affected by photoperiod and relative humidity. Conference of the Korean society of Agricultural Machinery 2003:145-150 (in Korean, with English abstract). Kim, J. K., Y. H. Kim and S. H. Lee. 2002. Analysis of energy balance in closed transplants production system. Conference of the Korean society of Bio-Environment Control 2002:326-331 (in Korean, with English abstract). Lee, J. H. 1994. Effect of root zone warming by hot water in winter season on rhizosphere environment, growth and yield of greenhouse-grown cucumber (cucuis sativus L.). PhD Diss. Daegu, Kyoungbook: Kyungpook National University, Department of horticultural science (in Korean, with English abstract). Moon, J. H., S. K. Lee and D. K. Ko. 2000. Effect of root zone cooling in summer season on yield and quality. Report of national horticultural research institute: 45-48 (in Korean) Nam, S. W. 2000. Actual utilization and thermal environment of greenhouses according to several cooling methods during summer Season. Journal of bio-environment control 9(1):1-10 (in Korean, with English abstract). Nam, Y. I. 2000. Automatic system of hydroponic culture and production facility. Suwon: Teaching material of R. D. A. (in Korean). Yu, I. H., Y. I. Nam, T. Y. Kim, M. Y. Roh and M. W. Cho. 2006. Effect of newly developed fan and mist evaporative cooling system on greenhouse cooling and growth of cucumber. Journal of Bio-Environment control 15(1): 91-97 (in Korean, with English abstract). Ryu, Y. S., J. T. Chang, Y. J. Kim, K. J. Lee and J. H. Yun. 1999. Performance test of heat pump system for low temperature treatment of Phalaenopsis. Conference of the Korean society of Bio-Environment Control 99: 95-99 (in Korean). Ryou, Y. S., Y. K. Kang, J. K. Jang, Y. H. Kim, J. G. Kim and G. C. Kang. 2012. Heat exchanger design of a heat pump system using the heated effluent of thermal power generation plant as a heat source for greenhouse heating. Journal of Bio-Environment Control 21(4): 372-378 (In Korean, with English abstract). 38