BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

Similar documents
BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:

BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.

Method of test defined in IEC for determining the circuit integrity performance of a cable under fire conditions.

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products

BS EN : 2001 & IEC :2000

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.

BS 476: Part 6: 1989+A1:2009

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited

BS 476: Part 6: 1989+A1:2009

BS EN ISO : 2010

BS EN ISO : 2010

NF X : Parts 1, 2, 3, 4 & 5

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

Review Fire Test Report

BS EN ISO : 2010

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.

EN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015

IMO Resolution MSC 61(67): Annex 1: Part 2

Test Report No: ICL/H17/7967

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

FIRE PERFORMANCE CABLE

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31.

Title: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy

The Fire Resistance Performance Of Timber Or Mineral Composite Based Insulated Doorsets When Fitted With D & E Architectural Hardware Spring Hinges

600/1000V SR Insulated Flexibles Control Cables (2-4 Cores & Multicores)

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

ENHANCED FIRE PERFORMANCE CABLE

25 th November Title:

Flame Retardant Overall Screened Instrumentation Cables (multicore)

High Performance LSZH Fire Resistant Cable

Catalogue Telecommunication Cables INTRODUCCIÓN

Caledonian Flame Retardant Coaxial Cables

fire resistant cables

CERTIFICATE OF APPROVAL No CF 5236 EMVER PAINTS INDUSTRIES LLC

Multi-Core Fire Resistant Cable

600/1000V XLPE Insulated, LSZH Sheathed, Double steel tape Armoured Power Cables (3 Cores)

Telecommunication Cables

IEC ; EN ; DIN VDE ; CEI 20-37/2-1 ; BS * No Corrosive Gas Emission

CERTIFICATE OF APPROVAL No CF 5635 P3 SRL

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

FIRE RESISTANT CABLES

Caledonian Fire resistant Coaxial Cables

Fire Test Reports for Interpon D Powder Coatings

FIRE RESISTANT CABLES FP200 GOLD

UV RESISTANT ACCORDING TO HD 605 RULE

SAS Security and Alarm Safety Cables

CERTIFICATE OF APPROVAL No ME 5085

Fire alarm cables. for highest safety requirements TRADITION INNOVATION PASSION

All Prysmian FP400 cables are manufactured under an ISO 9001 Quality System certified by BASEC and LPCB.

Tratos Railway Cables

FIRE RESISTANT CABLES FP PLUS. New Generation. Now with enhanced Insudite TM insulation

Firetuf OFC-UT-CST Fire resistant Armoured Central Tube Cable, variant in red

Introduction.

IEC ; EN ; DIN VDE ; CEI 20-37/2-1 ; BS * No Corrosive Gas Emission

Caledonian fire Resistant signal & Data cables

INTRODUCTION. Our diverse range of world-class Specialty Insulated Wires and Cablesinclude: LV Cables -

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

FIRE RESISTANT CABLES FP200 GOLD

LSOH Flexible Cables

Firetuf OFC-UT-CST Fire resistant Armoured Central Tube Cable, variant in red

PRODUCT CATALOGUE Norröna

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

TYPE APPROVAL CERTIFICATE

Traction Cable Radox 3 GKW

Core identification code. J-YY...BD Indoor Cable. J-YY...BD Indoor Cable. VDE 0815 Mutual capacitance. J-YY...BD Indoor Cable. Cu conductor 0.

Caledonian. FIREFLIX ire Resistant Coaxial Cables

Total Fire Solutions. Includes BS 8519 and the updated BS :

Photovoltaic Cables EN H1Z2Z2-K

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

AFIREFENIX SZ1-K 0,6/1 kv PH120 (AS+)

AFUMEX LSX BASEC APPROVED LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

Lloyd s Register Type Approval System Test Specification Number 3

Test Report: ICL/CR15/11/087

Power Cables. Introduction 3 RV 4 RVMV 5 RVSV 6 RVFV 7. ELECWIRES 2 Page

STANDARDS INSTALLATION. Certificate No 077m

Compact Module. Category 6A FTP Cabling System 1.1

BS /1000V XLPE Insulation LSZH Sheath Cables

Test report for a Teldor Cables SLA-6-01X08- ZAHRH-DD Fibre Optic cable to IEC :1999

BS FP600 achieves the maximum 120 minute rating under the BS test conditions, which is required for fire fighting applications.

Table of Contents. TELE-FONIKA KABLE SA (DMCC Branch). 4 TELE-FONIKA Kable Group 6 FLAME-X 950 SERIES 1 11 FLAME-X 950 SERIES 2

THE TRUE FIRE SURVIVAL CABLE

600/1000V XLPE Insulated, PVC Sheathed, Armoured Power Cables (Multicore)

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415

Classification Report

IEC UNE DESIGN. 1. Conductor. 2. Insulation. Cross-linked polyethylene (XLPE) 3. Outer sheath. Flexible PVC, black colour.

FIRE RESISTANT CABLES FP400

System Circuit integrity in the event of fire. Safety cables and systems from a pro. Cabling Solutions

Firetuf Cables ZERO HALOGEN, LOW SMOKE (0HLS ) CABLE

Agencavi Srl has been specializing in the distribution of special cables and accessories for industrial automation since 1983.

Firetuf Cables ZERO HALOGEN, LOW SMOKE (0HLS ) CABLE

Firecel Safety Cables

Fire Resistant Cables

Transcription:

BS EN 60332-1-2:2004 Test On Electric And Optical Fibre Cables Under Fire Conditions WF Report Number 177603 Date: 14 th November 2008 Test Sponsor: FTC Fabbrica Trentina Conduttori Srl 0249

Page 2 of 9 Bodycote warringtonfire Test Report No. 177603 BS EN 60332-1-2: 2004 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kw pre-mixed flame Sponsored By FTC - Fabbrica Trentina Conduttori Srl Sud Tirol Kabelwerke Via Pineta 21B 38068 Rovereto (TN) Italy

Page 3 of 9 CONTENTS PAGE NO. TEST DETAILS... 4 DESCRIPTION OF TEST SPECIMENS... 6 TEST RESULTS... 8 SIGNATORIES... 9

Page 4 of 9 Test Details Purpose of test To determine the performance of a specimen of a cable when it is subjected to the conditions of test specified in BS EN 60332-1-2:2004, "Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for resistance to vertical flame propagation for a single insulated cable Procedures for 1kW pre-mixed flame. The test was performed in accordance with the procedure specified in BS EN 60332-1-2:2004 and this report should be read in conjunction with that Standard. The burner was applied for 60 seconds. Scope of test BS EN 60332-1-2:2004 specifies a method of test for resistance to vertical flame propagation for a single electrical insulated conductor or cable, or optical cable, under fire conditions. Part 1 specifies the test apparatus and Part 1-2 specifies the test procedures. BS EN 60332-1-2:2004 specifies the use of a 1kW pre-mix flame and is for general use, except that the procedure specified may not be suitable for the testing of small single insulated conductors or cables of less than 0.5mm 2 total cross-section because the conductor melts before the test is completed, or for the testing of small optical fibre cables because the cable is broken before the test completed. In these cases, the procedure given in BS EN 60332-2 is recommended. The performance requirements for a particular type or class of insulated conductor or cable should preferably be given in the individual cable standard. In the absence of any given requirement it is recommended that those given below should be taken as a minimum level. The single insulated conductor or cable shall pass the test if the distance between the lower edge of the top support and the onset of charring is greater than 50mm. In addition, a failure should be recorded if burning extends downwards to a point greater than 540mm from the lower edge of the top support. If a failure is recorded two more tests shall be carried out. If both tests result in passes the insulated conductor or cable shall be deemed to have passed the test. Fire test study group/egolf Instruction to test Certain aspects of some fire test specifications are open to different interpretations. The Fire Test Study Group and EGOLF have identified a number of such areas and have agreed Resolutions which define common agreement of interpretations between fire test laboratories which are members of the Groups. Where such Resolutions are applicable to this test they have been followed. The test was conducted on the 4 th November 2008 at the request of FTC - Fabbrica Trentina Conduttori Srl, the sponsor of the test.

Page 5 of 9 Provision of test specimens Conditioning of specimens The specimens were supplied by the sponsor of the test. Bodycote warringtonfire was not involved in any selection or sampling procedure. The specimens were received on the 6 th October 2008 and were conditioned at a temperature of (23±5) 0 C for a minimum period of 16 hours at a relative humidity of (50±20)%.

Page 6 of 9 Description of Test Specimens The description of the specimens given below has been prepared from information provided by the sponsor of the test. All values quoted are nominal, unless tolerances are given. Plate 1 Photograph of test specimen Product reference Eurosafe E 30/60 Cable marking EUROSAFE E 30/60 JE-H(ST)H 2x2x0.8 MM SCR. FIRE RESISTANT VDE 0815, DIN 4102, EN 50200 PH 120, EN 60332-1-2, EN 61034-2, FIPEC(EN)50339-2-1 CE 09/08 Cable function Fire systems data connections Number of cores x core size 4 x 0.8mm 2 Voltage rating 300/500V Overall diameter 8.2mm (stated by sponsor) 8.3mm (determined by Bodycote warringtonfire) Overall weight per unit length 77.52kg/km (stated by sponsor) Product reference Solid Plain Annealed Copper Wire Solid copper wire Conductors Name of manufacturer Cross sectional area 0.8mm 2 Weight per unit length 4.2kg/km Product reference Special Silicone Rubber Silicone rubber Name of manufacturer FTC Fabbrica Trentina Conduttori Srl Insulation Colour Yellow, Grey, Blue and Red Thickness 0.6mm Weight per unit length 8.6kg/km Flame retardant details Product reference Solid Tinned Copper Wire Solid tinned copper wire Drain wire Name of manufacturer Cross sectional area 0.28mm 2 Weight per unit length 2.5kg/km Product reference Glass Fibre Glass fibre tape Name of manufacturer Glass fibre tape Colour White (surrounding Thickness 0.12mm conductors Density / weight per unit length Flame retardant details Continued on next page

Page 7 of 9 Foil tape (surrounding conductors and plastic tape) Product reference Name of manufacturer Colour Thickness Density / weight per unit length Flame retardant details Product reference Name of manufacturer Outer sheath Colour Thickness Weight per unit length Flame retardant details Brief description of manufacturing process Aluminium / Polyester Laminate Tape Aluminium / polyester Blue / Silver 25μm Special Halogen Free LSZH Low smoke zero halogen Red 1mm 39.6kg/km The conductor wires are insulated by extrusion of a continuous silicone rubber layer, which has been high temperature cross-linked. The cores are then separated into pairs, twisted together and shielded. Finally, the sheathing is applied by a semi-compression extrusion process. Note 1. The sponsor of the test was unwilling to provide this or further information.

Page 8 of 9 Test Results Results of test The distance between the lower edge of the top support and the upper onset of charring was 385mm. The distance between the lower edge of the top support and the lower edge of charring was 500mm. Conclusion The specimen therefore meets the recommended performance requirements given in Annex A of BS EN 60332-1-2: 2004. Validity The specification and interpretation of fire test methods are the subject of ongoing development and refinement. Changes in associated legislation may also occur. For these reasons it is recommended that the relevance of test reports over five years old should be considered by the user. The laboratory that issued the report will be able to offer, on behalf of the legal owner, a review of the procedures adopted for a particular test to ensure that they are consistent with current practices, and if required may endorse the test report. This report may only be reproduced in full. Extracts or abridgements shall not be published without permission of Bodycote warringtonfire.

Page 9 of 9 Signatories Responsible Officer S. Deeming * Approved M. Dale * Deputy Operations Manager Authorised C. Dean * Operations Manager * For and on behalf of Bodycote warringtonfire. Report Issued: 14 th November 2008 This version of the report has been produced from a.pdf format electronic file that has been provided by Bodycote warringtonfire to the sponsor of the report and must only be reproduced in full. Extracts or abridgements of reports must not be published without permission of Bodycote warringtonfire.

Bodycote warringtonfire Head Office Holmesfield Road Warrington Cheshire WA1 2DS United Kingdom Tel: +44 (0) 1925 655 116 Fax: +44 (0) 1925 655 419 Email: Info@warringtonfire.net Website: www.warringtonfire.net