STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16

Similar documents
STAS SERIES SELECTRONIC ALARM ANNUNCIATORS

ST Series. SELECTRONIC TATTLETALE Remote Alarm Annunciators

Selectronic Tattletale Remote Alarm Annunciators

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

SELECTRONIC TATTLETALE Remote Alarm Annunciators ST Series

Selectronic Tattletale Remote Alarm Annunciators

ENGINE GENERATORS AND ACCESSORIES

DGC-500 DIGITAL GENSET CONTROLLER

PowerCommand FT-10 Network LONWORKS System Annunciator

B. Section Transfer Switches: Automatic transfer switch.

21-light Remote Annunciator. Owner s Manual

DGC-1000 DIGITAL GENSET CONTROLLER

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

INSPECTION AND TESTING FORM

DIESEL Engine Fire Pump Controllers Features

ANNUNCIATOR FIXED MODULE

TECHNICAL DATA OBSOLETE

This Addendum includes the following changes and clarifications to the Contract Documents:

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

Technical Data Submittal Documents

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

FDF Foam Pump Controllers Features

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

AL800ULADA. NAC Power Extender. Installation Guide

MR-2602 Two Zone Fire Alarm Control Panel

AS DIGITAL FIRE PUMP CONTROLLER

20 Light Remote Annunciator

1 INCA INCA MODEL FPC FIRE PUMP CONTROL PANEL. (Star Delta/D.O.L) USER MANUAL Inca Reference FPC Revision 1.0

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

Fire Pump Supervision - Part 2 by Dean K. Wilson, P.E.

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

The Murphy EVS Electronic Vibration Switch. Installation and Operations Manual Section 20

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

AL600ULADA. NAC Power Extender. Installation Guide

Spectron LSN (Life Safety Network) Suggested Specifications

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

Commercial and Light Industrial Fire Alarm Control Panel

Installation, Operating and Maintenance Manual

Application, Installation, Operation & Maintenance Manual

Public Safety DAS Annunciator Panel

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

VA301C CONTROLLER WITH BACnet OPTION

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

PowerWizard Range. Digital Control Systems & Remote Communication Options. PowerWizard Providing Safe Control of Your.

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

DIESEL Engine Fire Pump Controllers Features

User s Manual. For the SHORE POWER CONNECTION MONITOR MODEL 9151

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

LifeAlarm Fire Alarm Controls

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS.

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

M2000 Engine Controller

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

July 14, 1999 DF C-100.

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

Digital Control Systems & Remote Communications Options

ANALOX 3000 Carbon Monoxide Monitor

M2500 Engine Controller Installation Manual

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES

NS (A) ECN

Exit Stopper. STI-6400 Series

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

PowerWizard Range. Digital Control Systems & Remote Communication Options.

M2000 Engine Controller

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

1U ULTRA Compact System

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

30.45 Electric Release PDRP-2001

Addendum for STI-6406 with Dual Access Control

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

SP-1000X. Panic Device Power Controller Installation Guide. Rev

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

Architectural and Engineering Specification for a Personal Alarm System System (PAS)

Installation Guide for models:

LifeAlarm Fire Alarm Control Panels

SCR/SCRF Series Battery Charger

MASTER DIESEL FIRE PUMP CONTROLLER

Exit Stopper. STI-6400 Series

TCA-9102 Series Surface Mount Temperature Controllers with High and Low Alarm

SECTION AUTOMATIC TRANSFER SWITCHES

Transcription:

ST-97106N Revised 07-04 Section 25 (00-02-0283) STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16

Certain danger to human safety and to equipment may occur if some equipment is stopped without prewarning. It is recommended that monitored functions be limited to alarm-only or to alarm before shutdown. WARNING BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT Disconnect all electrical power to the machine. Make sure the machine cannot operate during installation. Follow all safety warnings of the machine manufacturer. Read and follow all

Table of Contents Section 1: Introduction page 1 Section 2: Specifications 1 A. Power Requirements 1 B. Voltage Sensing Circuits 1 C. Output Ratings 1 D. Temperature Range 1 E. Dimensions 1 F. Enclosure 1 Section 3: Standard Features 1 A. General Operation 1 C. STA16 2 E. Optional Features 2 Section 4: Installation Operation 2 A. Electrical 2 B. Mechanical 2 C. Applications 2 D. Voltage Sensing Circuits 2 Figures: Figure 1a: STA16 Typical LED Display with Terminal Designation and Label Installation 3 Figure 3: STA16-N Circuit Diagram 4 Figure 8: STA16 Dimensions for Installation 4 Appendix A: Battery Charging Rates 5

CAUTION: Certain dangers to human safety and to equipment may occur if some equipment is stopped without prewarning. It is recommended that monitored functions be limited to alarm-only or to alarm before shutdown. Section 1: Introduction A. This manual is directed to the design, installation, and operation of the Murphy model STA16 remote alarm annunciator. This remote annunciator monitors generator sets and indicates the cause of alarm when an operational fault occurs. B. The Murphy family of remote alarm annunciators is designed to indicate the cause of an alarm using both visual and audio means. The audible alarm can be silenced by the operator, but the flashing warning light remains on to indicate the fault. These models are compatible with SWICHGAGE s: the most versatile and practical engine sensor/switch available. C. Application The STA16 is a remote annunciator designed for emergency power systems. This model has sixteen LED alarm points which can be both visual and audible or visual only when specified. A high battery voltage and a low battery voltage sensor are included. The STA16 can be configured to meet NFPA-110 Level 1 requirements for remote alarm annunciators. This unit is typically used where a remote annunciator is needed at a 24 hour manned post to monitor the generator set. STA16 series is available with N (negative) switch inputs only. Section 2: Specifications A. Power Requirements 1. Voltage: STA16: 12 V or 24 V 2. Current STA16 12 V negative, standby 23 ma, max current (test) 60 ma 24 V negative, standby 23 ma, max current (test) 70 ma B. Voltage Sensing Circuits sense input voltage to ST family. Standard voltage set points are for lead acid batteries. Other battery types require different voltage settings. STA16: 12 VDC - High battery voltage sensing circuit; set at 14.5V. Low battery voltage sensing set at 10 V. STA16: 24 VDC - High battery voltage sensing circuit; set at 29 V. Low battery voltage sensing set at 20 V. NOTE: Other nominal voltages (8-40 VDC) can be provided upon request. Specify Battery Charger Malfunction low and high voltage sensing circuit set points if they are different from the settings listed under B. Voltage Sensing Circuits. C. Output Ratings STA16: 500 ma@ rated voltage for an external relay. D. Temperature Range: -4 F to 158 F (-20 C to 70 C) E. Dimensions (see Figures 7 and 8 page 9) STA16 a. Height 9-3/4 in. (248 mm) b. Width 6-1/2in. (165 mm) c. Depth 2-1/2 in. (64 mm) F. Enclosure STA16: Black ABS Plastic Section 3: Standard Features A. General Operation A remote contact closure will turn on the alarm light and the common audible alarm. If the remote contact opens, the light and the audible alarm will turn off. If the alarm silence switch is operated, the audible alarm will turn off, but the light will remain on as long as the contact is closed. If another remote contact closes before all previous alarm contacts clear, the light will turn on, but the audible alarm will not sound. The alarm silence switch circuit used in the STA16 is an automatic reset type that complies with the exception to paragraph 3-5.6.2 of NFPA-110-1996. The alarm silence circuit does not require manual reset after all previous faults clear to sound the audible alarm on another fault. B. STA16 1. 16 red LED alarm points; (unlabeled) A label sheet is included which contains all required and optional labels per NFPA 110. (See figure 1a, page 3 for LED and label information.) 2. Mini-siren audible alarm. 3. Output for external relay. 4. Alarm silence push button. 5. Test push button checks the alarm LEDs. 6. Green power on LED. 7. All 16 alarm points are both visual and audible. 8. High battery voltage sensing circuit with output at terminal 10. As long as input voltage remains below set point, there will be no alarm output (output sinks 50 ma). 9. Low Battery Voltage sensing circuit with output at terminal 9. As long as input voltage is above set point there will be no alarm output. (output sinks 50 ma). 10. The low voltage bypass input at terminal 21 may be used to prevent low battery voltage alarm while engine is cranking. C. Optional Features (These features must be ordered separately.) STA16: All 16 lights can be changed in color and function. The color choices are green, amber, and red. The alarm points can be both visual and audible or visual only when specified. Section 4: Installation Operation A. Electrical: Circuit configuration for STA16-N is shown in Fig. 3. Remote Annunciator wire size: Most STA16 series remote annunciators are installed in the cover of a pull box or similar enclosure and should be wired with the smallest stranded copper wire that complies with local codes. This will make it easier to stuff the excess wire into the pull box when the cover is installed and will put less strain on the ST terminal block and printed circuit board. Although the signal wires for the remote annunciators may be almost any size, the STA16 internal voltage sensing circuits require that the power wiring be sized so that full voltage is available at the input power terminals. The maximum voltage drop between the battery and the remote ST must be less than the difference between the low voltage set point and the battery float charging voltage or the alarm will sound prematurely. The maximum current requirements for the ST family is shown in Section 2: A.2. Section 2:B lists the standard voltage sensing set points. With maximum current, low voltage set point, the float charging voltage (see Appendix A) and the average resistance of copper wire you can calculate the minimum wire size or maximum distance of any wire size that you can run to the remote ST location. As an example, the STA16-N-24 draws a maximum current of 250 ST-97106N page 1 of 5

ma in the test mode and the low voltage setting of the low battery voltage sensing circuit is 20 volts. On a 24 volt lead acid battery system, the typical float charge is 26.04 volts. Therefore you cannot have more than 6.04 volt drop in the wiring without the alarm sounding. Maximum resistance would be maximum volt drop (6.04) divided by maximum current (250 ma) or 24.2 ohms on the STA16-N-24 with a 1/3 safety factor, the maximum resistance should be no more than 16.1 ohms. Using the average resistance of stranded copper wire per 1000 foot, you can then determine the distance that a given wire size can be run without causing a problem. Remember that two wires are required for the battery power so divide the result by 2 to get maximum length for each wire. How far can an STA16-N-24 be installed from the battery using 24 AWG wire? Wire resistance is 24 ohms per 1000 feet. The following chart can be used for wire sizes from 24 thru 14 AWG, on lead acid battery systems. The above formula can be applied to any type battery system. Because DC circuits can be affected by capacitance and other affects in long wire runs, we do not recommend runs longer than 1000 ft. B. Mechanical: The dimensions and installation for the STA16 are shown on page 4. C. Voltage Sensing Circuits: The Voltage sensing circuits are preset at the factory as shown in Section 2, B. All voltage sensing is done at the input terminals of the STA16 so it is very important that the input power wires are large enough to prevent unwanted voltage drops. Set points in the STA16 cannot be adjusted in the field since their enclosures should not be opened by field personnel. STA16-N 12V STA16-N 24V MODEL 24 AWG (.22 mm 2 ) 24 Ohm/1000 22 AWG (.5 mm 2 ) 14 Ohm/1000 Standard Copper Wire 20 AWG (.75 mm 2 ) 10 Ohm/1000 18 AWG (1.0 mm 2 ) 6 Ohm/1000 16 AWG (1.5 mm 2 ) 4 Ohm/1000 334 573 800 1338 2000 3200 670 1150 1610 2680 4025 6440 14 AWG (2.5 mm 2 ) 2.5 Ohm/1000 ST-97106N page 2 of 5

Figure 1a: STA16 Typical LED display and label sheet information Select the needed labels and follow directions for their application. These are permanent, precut and pressure sensitive labels. Be sure the unit s faceplate is clean and free of oil. 1. Peel one label at the time and position on the unit s faceplate. 2. Before pressing down, be sure the label is correct. 3. Rub down firmly and leave untouched for several hours. AFTERCOOLER TEMPERATURE AFTERCOOLER WATER LEVEL AIR FILTER AIR PRESSURE BEARING PRESSURE BEARING TEMPERATURE BILGE LEVEL CLUTCH AIR PRESSURE DAY TANK #1 DAY TANK #2 DAY TANK #3 DAY TANK #4 ENGINE OIL PRESSURE ENGINE OIL TEMPERATURE ENGINE ROOM TEMPERATURE ENGINE WATER LEVEL ENGINE WATER PRESSURE ENGINE WATER TEMPERATURE EXHAUST TEMPERATURE FIRE ALARM FUEL FILTER FUEL LEVEL FUEL PRESSURE FUEL RESTRICTION Label sheet supplied with STA16 FUEL SEPARATOR WATER LEVEL GEAR OIL PRESSURE GEAR OIL TEMPERATURE GENERATOR OIL PRESSURE GENERATOR WATER TEMP. GENERATOR #1 OIL PRESSURE GENERATOR #1 WATER TEMP. GENERATOR #1 WATER LEVEL GENERATOR #2 OIL PRESS. GENERATOR #2 WATER TEMP. GENERATOR #2 WATER LEVEL HYDRAULIC LEVEL LOW VOLTAGE MANIFOLD BOOST MANIFOLD TEMPERATURE OVERSPEED PORT PORT GENERATOR ENGINE PORT MAIN ENGINE PORT OIL PRESSURE PORT WATER TEMPERATURE PORT OIL TEMPERATURE PORT WATER LEVEL PORT WATER PRESSURE RAW WATER PRESSURE STARBOARD STARBOARD GENER. ENGINE STARBOARD MAIN ENGINE STARBOARD OIL PRESSURE STARBOARD WATER TEMP. BILGE LEVEL STARBOARD OIL TEMPERATURE STARBOARD WATER LEVEL STARBOARD WATER PRESSURE TRANSMISSION OIL FILTER TRANSMISSION PRESSURE TRANSMISSION TEMPERATURE OIL PRESSURE/LEVEL WATER PRESSURE/LEVEL Label sheet supplied with STA16 AIR DAMPER CLOSED LOW OIL LEVEL ALARM SILENCE LOW OIL PRESSURE BATTERY CHARGER MALFUNCTION LOW OIL PRESSURE PREALARM C/B CLOSED LOW OIL TEMPERATURE C/B OPEN LOW STARTING AIR PRESSURE C/B TRIPPED LOW STARTING HYDRAULIC PRESS. COMMON FAILURE LOW WATER LEVEL CONTROL SWITCH NOT IN AUTO LOW WATER PRESSURE. EPS SUPPLYING LOAD LOW WATER TEMPERATURE FALLING OIL TEMP. OVERCRANK GENERATOR NOT IN AUTO OVERCURRENT GENERATOR IN AUTO OVERSPEED GENERATOR OPERATING OVER/UNDER FREQUENCY GENERATOR SUPPLYING LOAD OVERVOLTAGE HIGH BATTERY VOLTAGE POWER ON HIGH ENGINE TEMPERATURE RISING WATER TEMPERATURE HIGH ENGINE TEMP. PREALARM SELECTOR NOT IN AUTO HIGH OIL TEMPERATURE TEST HIGH OIL TEMP. PREALARM VIBRATION HIGH WATER TEMPERATURE LOW WATER LEVEL SHUTDOWN HIGH WATER TEMP. PREALARM HIGH COOLANT TEMPERATURE LOW BATTERY VOLTAGE HIGH COOLANT TEMP. PREALARM LOW FUEL LEVEL LOW COOLANT TEMPERATURE LOW FUEL DAY TANK LOW COOLANT TEMP. PREALARM LOW FUEL MAIN TANK BATTERY CHARGER AC FAILURE LOW FUEL PRESSURE STA16 Typical LED display (terminal numbers are in parenthesis) NOTE: STA16 faceplate is blank labels must be applied. LED 1 (1) LED 9 (13) LED 2 (2) LED 3 (3) LED 4 (4) LED 5 (5) LED 6 (6) Generator Operating Low Oil Pressure Pre-Alarm Low Oil Pressure Low Water Temperature High Water Temp. Pre-Alarm High Water Temperature Overspeed Low Fuel Supply Control Switch Not in Auto High Battery Voltage Low Battery Voltage Battery Charger AC Failure LED 10 (14) LED 11 (15) LED 12 (16) LED 13 (17) LED 14 (18) LED 7 (7) LED 8 (8) Overcrank LED 15 (19) LED 16 (20) POWER ON Power ON ALARM SILENCE ALARM TEST Alarm Silence Alarm Test ST-97106N page 3 of 5

* Figure 3: STA16-N 13 (LED 9) (LED 1) 1 14 (LED 10) (LED 2) 2 15 (LED 11) (LED 3) 3 16 (LED 12) (LED 4) 4 17 (LED 13) (LED 5) 5 18 (LED 14) (LED 6) 6 19 (LED 15) (LED 7) 7 20 (LED 16) (LED 8) 8 Low Voltage Bypass * 21 9 Low Battery Voltage Switch Output 50 ma max. sinking output * Remote Alarm Relay 22 23 10 11 * High Battery Voltage Switch Output 50 ma max. sinking output 24 12 Low Voltage sensing circuit bypass switch Battery NOTE: Internal voltage sensing circuit switch outputs. These can be wired to any of the alarm inputs for high or low battery voltage alarm. Low voltage bypass prevents the low voltage switch from operating when terminal 21 is connected to battery positive. Figure 8: STA16 Dimensions and Installation 6-1/2 in. (165 mm) 2-33/64 in. (64 mm) 6 in. (152 mm) 3 in. (76 mm) 1/8 in. (3 mm) dia. 4-places 9-3/4 in. (248 mm) 4-21/32 in. (118 mm) 9-5/16 in. (238 mm) 3-3/8 in. (86 mm) 6-3/4 in. (171 mm) 5-9/16 in. (141 mm) 2-26/32 in. (71 mm) ST-97106N page 4 of 5

Appendix A Battery Charging Rates Model STA16 includes a voltage sensing circuit to detect battery charger malfunction. This is done by sensing that the battery voltage is either below or above normal charging voltage of a properly operating battery charger. Standard setting is for lead acid type batteries. Most battery chargers have two operating modes; float and equalize. The sensing circuits of the STA16 is set at 96% of the equalize voltage so that normal operation of the charger is covered. Typical battery charging rates. Lead Acid Batteries Float Charge Equalize Charge Nickel Cadmium Batteries Float Charge Equalize Charge Nominal battery sizes. Lead Acid Batteries 12 Volt 6 cells 24 volt 12 cells Nickel Cadmium Batteries 12 Volt 10 cells 24 Volts 20 cells 2.17 Volts per cell 2.33 Volts per cell 1.4 Volts per cell 1.5 Volts per cell Therefore the charging voltage will be: Lead Acid Batteries 12 volt float 13.02 Volts 12 Volts equalize 13.98 Volts 24 Volt float 26.04 Volts 24 Volts equalize 27.96 Volts Nickel Cadmium Batteries 12 Volt float 14 Volts 12 Volt equalize 15 Volts 24 Volt float 28 Volts 24 Volt equalize 30 Volts The standard settings for the low and high battery voltage circuit in the STA16 are shown below. Lead Acid Batteries 12 Volt low 10.00 Volts 12 Volt high 14.50 Volts 24 Volt low 20.00 Volts 24 Volt high 29.00 Volts Nickel Cadmium Batteries 12 Volt low 10.78 Volts 12 Volt high 15.60 Volts 24 Volt low 21.56 Volts 24 Volt high 31.20 Volts Although the above figures are our standards, we can set the sensing circuits at any value that is required to match the sensor to a battery charger or alternator. The sensors can be factory set to any value between 8 and 40 volts DC. Warranty A limited warranty on materials and workmanship is given with this FW Murphy product. A copy of the warranty may be viewed or printed by going to www.fwmurphy.com/support/warranty.htm RE GISTE RED USA ISO 9001:2000 FM 28221 UK ISO 9001:2000 FM 29422 Printed in U.S.A. ST-97106N page 5 of 5