UEI-1 UNIVERSAL END-OF-LINE / ISOLATOR TESTER

Similar documents
FireNET Plus Wiring Instructions

MR-2602 Two Zone Fire Alarm Control Panel

Print Specification. Publication. Instructions. Specific requirements. General requirements

Notification Appliance Circuit Module

SIGA-CC1 Single Input Signal Module Installation Sheet

Louis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015

Multiple Input and Output Modules

Installation, Operating and Maintenance Manual

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Addressable NAC Output Module D327A

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Instructions Model ABHW-4S

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Booster Power Supply Manual

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Table 1: Attenuation Rating Switch Position. Position Attenuation (db) Attenuation (db) (Approx.)

AL600ULADA. NAC Power Extender. Installation Guide

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

Remote NAC Power Supply D7038

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Multiplex Eight Input Remote Modules

FMR Installation Instructions. Addressable Fire System Controller

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

F220-B6PS/M. Installation Guide. Addressable Detector Bases

Rev. B. TrueAlert Addressable Controller Application Manual

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Multi-Application Peripherals and Accessories

Conventional Fire Alarm System 2014 V1.2

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

AL800ULADA. NAC Power Extender. Installation Guide

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

30.45 Electric Release PDRP-2001

Installation Instructions Model HZM

D7052. Installation Instructions Multiplex Dual Input Module

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

D7044. Installation Instructions Multiplex Single Input Module

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

These instructions detail procedures to follow in order to avoid damage to equipment.

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

Conventional Releasing Control Panel

D7053. Installation Instructions Multiplex Input/Output Module

TECHNICAL DATA OBSOLETE

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

Installation Guide for models:

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

RELEASE DEVICE CONTROLS

Installation Guide for models:

MODEL B2 INSTALLATION MANUAL

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

TrueAlert Non-Addressable, Multi-Candela Notification Appliances Installation Instructions

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

Excel-EN Conventional Fire Control Panel

Conventional Smoke Detectors KFAPO

June 10, 2002 DF C S2424

Electric Release Panel Wiring Tips

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

D250A/D253/D261AW/D280A/D290 Series

KT-100 Door Controller

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

ECC-50/100C. Emergency Command Center

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

PSN-1000 & PSN 1000(E) Installation Manual

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

Intelligent Security & Fire Ltd

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE

Addressable Detectors & Bases

8600 EMR SERIES. INSPK NO Rev.06/ INS NO. GENERAL DESCRIPTION

M O D E L S FIREGARD BV EXTENDED PERFORMANCE RELEASE DEVICE

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

E S L I N S T A L L A T I O N A N D O P E R A T I O N S M A N U A L ESL Fire Alarm Control Panel ESL

Building Name: Our Lady of Sorrows Date: July 10, 2013

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

SAFEPATH SP40/2 D10 D35 AMP P/N P/N Installation, Testing, TONE SW Operation, and W4 Maintenance D54 SHORT

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual

/5121/5122 TrueAlert Power Supply Installation Instructions

TS93 EMR WITH SMOKE DETECTOR

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

FireNET Fire Alarm Control Panel Installation Manual

INPUT / OUTPUT MINI MODULES

Public Safety DAS Annunciator Panel

Expansion Modules & Accessories

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

Instruction Manual EVA-S6 Base

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Transcription:

UEI1 UNIVERSAL ENDOFLE / ISOLATOR TESTER With Easy Testing Technology STALLATION & OPERATG STRUCTIONS These instructions are provided to ensure compliance with the installation requirements of NFPA72 (National Fire Alarm Code), and CAN/ULCS524 (Standard for Installation of Fire Alarm Systems) and the National Electrical Code. The ILSTS UEI1 is intended for permanent installation and can be used in lieu of a standard fire alarm system endofline resistor plate. The ILSTS UEI1 is compatible with all UL/ULC Listed fire alarm systems produced or distributed in North America. When used correctly, the time to complete the required testing for EndofLine Resistors, Insuite Sounder Isolators, and DCL (SLC) Loop Isolators is typically fifteen (15) to thirty (30) seconds. IMPORTANT CAUTIONS: Applications: Ensure the electrical box is properly bonded to ground. For conventional circuit EndofLine applications, follow the testing and maintenance instructions stipulated in CAN/ULCS536 to ensure the proper utilization of the ILSTS UEI1. For applications involving power, audio, or notification buss risers, refer to the applicable fire alarm manufacturer s testing and maintenance procedures. This device is required to be mounted onto an approved single gang electrical box or on a suitable single gang adapter plate and in accordance with the applicable Installation Standard, National Electrical Codes and the authority having jurisdiction. Can be used in damp locations (if mounted on an approved box). Maximum switching current is 3 Amps Maximum operating voltage is 300 V AC/DC Operating temperature range: 20C to 50C CIRCUIT ENDOFLE TEST APPLICATION: The ILSTS UEI1 is not polarity sensitive in this application. Note 2: When terminated correctly the circuit should be clear of faults (normal). Note 3: The ILSTS UEI1 provides an easytouse interface to confirm total current consumption on a notification appliance circuit in this application. With your meter set to read current, position the magnet over the letter O on the face and insert your meter leads between I and I. With the circuit active (i.e. in alarm), the current in the circuit will be displayed. STALLATION (Reference Figure B on page 5): NOTE: Use only EOLR provided or specified by the control panel manufacturer. 1. Mount the ILSTS UEI1 at (or less) than 1800 mm above the floor (measured to the centre of the plate) in order to facilitate access to the testing means. 2. Connect an endofline resistor across the terminals marked and. The UEI1 is not polarity sensitive in this application. 3. Connect the field wiring from the control panel (or from the last device in the circuit) to the terminals marked and. The circuit should indicate a normal condition. If off normal, or trouble is indicated for the zone, check field wiring connections. 4. Mount plate with hardware provided. TESTG PROCEDURE: 1. Place a magnet on the O (Open) indicator on the face of the UEI1. This will cause the control panel to display an open circuit trouble supervisory fault. 2. Remove the magnet. The circuit will restore to normal. 3. Place the magnet on the S (Short) indicator on the face of the UEI1. This will cause a short condition on the circuit. 4. Remove the magnet. Reset the system (as necessary). 5. Insert the test probe from your multimeter into one of the holes on the face of the unit and ground the other end of the probe against one of the exposed screws used to secure the device to the electrical box. The fire alarm control will indicate a trouble condition (some fire alarm controls may indicate a ground fault condition). (Continued on next page) Copyright 2016 by Frank Kurz All Rights Reserved No. 4796FK Revision 041818 P age 1 of 6

Circuit EndofLine Application Testing Continued: 6. With your meter set up for reading volts, you will be able to measure the voltage across the endofline resistor by inserting your test probes into the two holes marked V and V located on the face of the unit (required test in accordance with CAN/ULC S537 Standard for Verification of Fire Alarm Systems). Note: To determine the current on the circuit, insert the leads from your multimeter (set to read Amps) into the two holes marked I and I on the face of the UEI1. Position a magnet over the letter O (Open). Your meter will display the current (in Amps) on the circuit (or circuit segment). Remove the magnet and your meter leads and the circuit will return to normal operation. SUITE SOUNDER ISOLATOR TEST APPLICATION: WARNG: Observe correct polarity when connecting system wiring. Note: When terminated correctly the circuit should be clear of faults (normal). STALLATION (Reference Figure A on page 5): 1. The ILSTS UEI1 should be mounted immediately adjacent to and below the insuite signal isolator it will be testing. A minimum of two (2) units will be required, one for each suite being monitored. The device should be mounted at (or less than) 1800 mm above the floor (measured to the centre of the plate) in order to facilitate access to the testing means. 2. Connect the alarm positive of the suite signal output from the isolator to the terminal marked. 3. Connect the alarm negative of the suite signal output from the isolator to the terminal marked. 4. Connect the alarm positive wire for the insuite sounder(s) to the terminal marked. 5. Connect the alarm negative wire for the insuite sounder(s) to the terminal marked. 6. Connect the return wires from the suite sounders to the applicable return terminals on the isolator. TESTG PROCEDURE: 1. Place a test magnet on the O (Open) indicator on the face of the UEI1. This will impose a open on the circuit which will indicate an open trouble or NAC Fault at the common control. 2. Place your test magnet on the S (Short) indicator on the face of the UEI1. This will impose an open circuit on the NAC which should cause an open trouble fault signal at the common control. With the wire disconnected, initiate a drill test at the common control. The buzzers in the suite under test should sound normally (as should all the suite buzzers in the same floor area. This test confirms that the isolator module you re testing supervises for opens and that the Class A circuit between the isolator and the insuite sounders is wired correctly. 3. Remove the magnet. The circuit should restore to normal. 4. Please the magnet used in Step 1 on the letter S (Short) on the face of the UEI1. This will impose a short circuit on the suite devices under test and cause a trouble fault signal at the common control (some systems may actually indicate a short fault condition. 5. With the magnet still positioned on the S (Short), initiate a Drill Test from the control unit. The sounders associated with the suite to which the activated ILSTS UEI1 is connected will not function. All other sounders in the other suites in the floor area should activate. 6. Remove the magnet. The sounders associated with the suite under test will activate. 7. Return the test magnet to the S (Short) indicator on the face of the UEI1. The sounders associated with the suite under test will stop functioning. All other insuite sounders in the floor area should continue to function. 8. Remove the magnet. The sounders associated with the suite under test will reactivate. 9. Turn off the Drill Test. All circuit indications should read normal at the common control. Move to the next ILSTS UEI1 in the floor area to repeat 1 9. Note 1: If, in step 5, none of the sounders inside the suite you re testing activate, then the NAC is programmed incorrectly! Note 2: For a Verification test (performed to CAN/ULCS53713), you may wish to confirm that the total current draw on the isolator under test hasn t exceeded the rated current for the device. The ILSTS UEI1 makes this a simple test to perform. With your multmeter set to measure current, insert your test leads into the two holes on the face of the unit marked I and I. Position a magnet over the letter O (Open) on the face of the UEI1 and initiate a Drill Test. The current reading on your meter is the total current drawn by all of the insuite signal appliances the isolator your testing is protecting. (Continued on next page) Page 2 of 6 Copyright 2016 by Frank Kurz All Rights Reserved No. 4796FK Revision 041518

STALLATION (Reference Figure C on page 6): DCL (SLC) ISOLATOR TEST APPLICATION: WARNG: Observe correct polarity when connecting system wiring. Note: When terminated correctly the circuit should be clear of faults (normal). 1. The ILSTS UEI1 should be mounted immediately adjacent to and below the DCL (SLC) isolator it will be testing. For systems utilizing smoke detectors with isolator bases, locate the unit on an adjacent wall and wire it as the first device for the floor area circuit being protected. The device should be mounted at (or less than) 1800 mm above the floor (measured to the centre of the plate) in order to facilitate access to the testing means. 2. Connect the positive wire from the data loop to the terminal marked. 3. Connect the negative wire from the data loop the terminal marked. 4. Connect the positive wire for the floor area data loop devices being protected to the terminal marked. 5. Connect the negative wire for the floor area data loop devices being protected to the terminal marked. 6. The system should indicate a normal condition and all programmed field devices should be reporting normally. If off normal, or trouble is indicated for the DCL (SLC) loop, check the field wiring connections. Mount the plate with the hardware provided. TESTG PROCEDURE: 1. Place a test magnet on the O (Open) indicator on the face of the UEI1. This will impose an open on the circuit which will indicate an open trouble at the common control. Programmed field devices associated with the protected portion of the circuit will also indicate a communication fault. 2. Remove the magnet. Communication with programmed field devices will resume. Some control panels may require a reset. 3. Place the magnet on the S (Short) indicator on the face of the UEI1. This will cause a short condition on the circuit and activate a visible indicator on the isolator being tested. 4. With the magnet in place, initiate the required testing for devices connected to the same loop controller outside of the floor area served by the isolator. 5. Remove the magnet. All indications for the designated loop controller at the control panel should read normal. Some control panels may require a reset. 6. Insert the test probe from your multimeter into one of the holes on the face of the unit and ground the other end of the probe against one of the exposed screws used to secure the device to the electrical box. A ground fault condition should be indicated at the common control. 7. With the ground fault condition active, complete the required testing procedure for connected fire alarm devices within the floor area. 8. Remove the probe and disconnect the connection to the building ground. Circuit indications for the DCL (SLC) loop being tested should read normal at the common control. POWER / NOTIFICATION / AUDIO BUSS ISOLATOR TEST APPLICATIONS WARNG: Observe correct polarity when connecting system wiring. Note: When terminated correctly the circuit should be clear of faults (normal). STALLATION (Reference Figure D on Page 6): 1. The ILSTS UEI1 should be mounted immediately adjacent to and below the Buss Isolator it will be testing. The device should be mounted at (or less than) 1800 mm above the floor (measured to the centre of the plate) in order to facilitate access to the testing means. 2. Connect the positive wire from the buss isolator to the terminal marked. (Continued on next page) Copyright 2016 by Frank Kurz All Rights Reserved No. 4796FK Revision 041818 P age 3 of 6

Power / Audio / Notification Buss Isolator Test Procedure continued: 3. Connect the negative wire from the buss isolator to the terminal marked. 4. Connect the positive wire for the floor area powered (or audio) devices being protected to the terminal marked. 5. Connect the negative wire for the floor area powered (or audio) devices being protected to the terminal marked. 6. Mount the plate with the hardware provided. The system should indicate a normal condition and all programmed field devices should be reporting normally. If off normal, or trouble is indicated for the buss, check the field wiring connections. TESTG PROCEDURE: 1. Place a test magnet on the O (Open) indicator on the face of the UEI1. This will impose an open on the circuit which will indicate an open trouble at the common control for supervised devices on the circuit. 2. With the magnet in place, and your multimeter set for reading current (Amps), insert your test probes in the two holes marked I and I provided on the cover. The reading displayed on your meter is the current for the circuit segment the isolator is protecting. 3. Remove the magnet and the test leads. Normal operation of the powered field devices will resume. Some control panels may require a reset. 4. Place the magnet on the S (Short) indicator on the face of the UEI1. This will cause a short condition on the circuit and activate a visible indicator on the isolator being tested. 5. With the magnet in place, initiate the required testing for devices connected to the buss outside of the floor area served by the isolator. 6. Remove the magnet. All indications for the buss at the control panel should read normal. Some control panels may require a reset. 7. Insert the test probe from your multimeter into one of the holes on the face of the unit and ground the other end of the probe against one of the exposed screws used to secure the device to the electrical box. A ground fault condition should be indicated at the common control. 8. With the ground fault condition active, complete the required testing procedure for connected fire alarm devices within the floor area. 9. Remove the probe and disconnect the connection to the building ground. Circuit indications for the buss riser being tested should read normal at the common control. Some panels may require a reset before you move on to the next isolator on the buss. Electrical Specifications: Voltage: Ripple: Supervisory Current: Rated Operating Current: Switching Current (Max): Temperature: Humidity: Installation Requirements: Wire Gauge: Maximum EOLR Value: Agency Listings (Pending): 0 300 VAC/VDC Operation 3 Volts peaktopeak 100µA Maximum 0.1mA 3 Amps 3 Amps 20 C to 49 C (10 F to 120 F) 96% max. Suitable for Damp or Dry Locations (as required) 12 22 AWG 280K Ohms 0.25 Watts Manufactured in Canada By: Integrated Life Safety URL: www.ilsts.ca Testing Solutions Email: info@ilsts.ca Suite 343, Building 151, 10090 152 Street, Surrey, British Columbia V3R 8X8 Tel: 1.778.855.FIRE (3473) Fax: 1.604.552.7909 North American Patent Pending Page 4 of 6 Copyright 2016 by Frank Kurz All Rights Reserved No. 4796FK Revision 041518

Typical InSuite Sounder Connec on Diagram Suite One InSuite Sounders (w. Terminals) Suite Two InSuite Sounder (w. Terminals) Maximum switching current is 3 Amps. Note 1: Install ILSTS UEI1 in accordance with the instruc ons on page 2. Mount units in close proximity to the insuite sounder isolator they Copyright 2016 by Frank Kurz All Rights Reserved No. 4796FK Revision 041818 Page 5 of 6 serve and not more than 1800 mm above grade (to the centre of the plate). Suite One InSuite Isolator (Typical) Suite Two UEI1 Return 1 Output 1 Return 2 Output 2 UEI1 NAC In from FACP (or previous Isolator) NAC Out to next Isolator (or FACP, or EndofLine Device) Figure A Maximum switching current is 3 Amps. Typical Conven onal Zone EndofLine Resistor Applica on Connec on Diagram Note 1: Use only EOLR provided or specified by the control panel manufacturer. Install ILSTS UEI1 in accordance with the requirements for EndofLine Devices and the instruc ons on page 1. NAC or Ini a ng Circuit from previous conven onal field device Figure B UEI1 Drawing #47971FK Revision 180417 Copyright 2016 by Frank Kurz All Rights Reserved No. 4796FK Revision 041818 P age 5 of 6

Typical DCL (SCL) Isolator Connec on Diagram Note 1: Install the ILSTS UEI1 in close proximity to the DCL (SLC) isolator it serves and on a wall (where prac cal), less than 1800 mm above grade (measured to the centre of the device). Follow instruc ons detailed on page 3. Note 2: One ILSTS UEI1 is recommended for every DCL (SLC) isolated sec on in the circuit. Ac ve (or Suppor ng) Ac ve (or Suppor ng) DCL (SLC) to next Ac ve Field Device or Isolator DCL (SLC) In from FACP (or previous Isolator) CAUTION: The maximum switching current is 3 Amps. DCL (SLC) In DCL (SLC) Out DCL (SLC) Isolator (Typical) UEI1 Figure C Typical DCL (SCL) / Auxiliary Power Connec on Diagram (For FACP With Integral Circuit Isola on) Ac ve Suppor ng Class A (Style 6) B out Conven onal 2Wire Fire Alarm Field Device (Output or Input) Out to next device or UEI1¹ DCL (SLC) to FACP, next device (or Isolator) 24VDC Power to next device, Isolator, or EOL Supervisory Relay SLC B AUX PWR SW PWR Fire Alarm Control, Transponder, or individual DCL & Buss Isolators UEI1 Used as DCL (SLC) Isolator Tester UEI1 (Used as Power Buss Isolator Tester) 1 See Figure B (EndofLine Resistor Application). CAUTION: The maximum switching current is 3 Amps. Drawing #47972FK Revision 160922 Figure D Page 6 of 6 Copyright 2016 by Frank Kurz All Rights Reserved No. 4796FK Revision 041518