QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

Similar documents
MicrofastHP EC/QREC FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK611 (K5.6) TECHNICAL DATA

microfast sr/qr extended coverage pendent sprinkler

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

TECHNICAL DATA. MicrofastHP QUICK RESPONSE FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK318 (K5.6)

Microfast quick response Fusible element hsw sprinkler

standard response fusible link sidewall sprinkler VK112 (K5.6)

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

MicrofastHP EC/QREC FUSIBLE ELEMENT HSW HIGH PRESSURE SPRINKLER VK613 (K5.6) TECHNICAL DATA

TECHNICAL DATA. Refer to Approval Chart 1 and Design Criteria for culus Listing requirements that must be followed.

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

microfast quick response extended coverage hsw sprinkler vk606

QUICK RESPONSE FUSIBLE ELEMENT HSW SPRINKLERS VK308 AND HP VK320 (PART NOS AND 13955) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

standard response Fusible Link Upright sprinkler VK204 (K8.0)

TECHNICAL DATA OBSOLETE

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

MICROFAST SR/QR EXTENDED COVERAGE HSW SPRINKLER VK605 (K5.6) TECHNICAL DATA

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

TECHNICAL DATA. Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed.

micromatic Standard response Horizontal Sidewall sprinkler

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA

microfast quick response Pendent sprinkler VK302 (K5.6)

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

TECHNICAL DATA. Page 1 of 6

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

micromatic Standard response Horizontal Sidewall sprinkler

standard/quick response extended coverage light and ordinary hazard elo sprinklers

STANDARD/quick. Sprinkler 42o. August 8, 2011

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

MicrofastHP QUICK RESPONSE HORIZONTAL SIDEWALL HIGH PRESSURE SPRINKLER VK319 (K5.6) TECHNICAL DATA

MICROMATIC STANDARD RESPONSE PENDENT SPRINKLER VK102 (K5.6) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

MICROMATIC STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK104 (K5.6) TECHNICAL DATA

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK3311 (K4.2) TECHNICAL DATA

micromatic standard response Upright sprinkler VK100 (K5.6)

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

quick response horizontal sidewall sprinkler vk360 (K8.0)

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

standard response/ quick response extended coverage

standard response/qr extended coverage concealed pendent sprinklers vk614 & vk616

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

TECHNICAL DATA. The Web site may include a more recent Frame Casting: Brass UNS-C84400

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

standard response elo upright sprinkler

standard response elo upright and pendent sprinklers (storage-density/area)

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK486 (K4.0) TECHNICAL DATA

Form No. F_ Rev 14.1 Page 1 of 6 TECHNICAL DATA

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK120 (K8.0) TECHNICAL DATA

VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) TECHNICAL DATA

micromatic standard response stainless steel sprinklers

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

MIRAGE EC/QREC OH-ELO CONCEALED PENDENT SPRINKLER VK538 (K11.2) TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

HORIZON MIRAGE QUICK RESPONSE LARGE ORIFICE CONCEALED PENDENT SPRINKLER VK406 TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

standard response large orifice dry

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

TECHNICAL DATA vk470 (K3.0)

freedom residential horizontal sidewall lead free sprinkler VK4840 (k4.2)

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

freedom residential pendent sprinkler vk466 (K5.2)

sprinkler vk538 (K11.2)

quick response Sprinkler 105a October 25, 2010

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK470 (K3.0) TECHNICAL DATA

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

TECHNICAL DATA. Page 1 of 5

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart.

HORIZON QUICK RESPONSE FLUSH PENDENT SPRINKLERS TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

standard response dry horizontal sidewall sprinklers

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE CONCEALED HSW SPRINKLER VK630 (K8.0) TECHNICAL DATA

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK479 (K3.0) TECHNICAL DATA

Standard Spray concealed horizontal sidewall sprinkler VK481

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK460 (K5.8) TECHNICAL DATA

microfast and microfasthp quick conventional sprinklers

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

mirage Quick response concealed pendent sprinkler vk464 (K8.0)

FREEDOM RESIDENTIAL PENDENT LEAD FREE SPRINKLER VK4700 (K3.0) TECHNICAL DATA

mirage standard response concealed pendent sprinkler vk492 (K5.6)

Transcription:

Page 1 of 6 1. DESCRIPTION Viking QREC Fusible Element Pendent Sprinkler VK601 is a thermosensitive solder link spray sprinkler available in several different finishes and temperature ratings to meet varying design requirements. The fusible operating element and special deflector characteristics meet the challenges of quick response extended coverage standards. The special Polyester coatings can be used in decorative applications where colors are desired. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2020 Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements, and refer to Approval Chart 2 and FM Design Criteria for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Minimum Operating Pressure: Refer to the Approval Charts. Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar). Thread sizes: 1/2 (15 mm) NPT Nominal K-Factors: 5.6 U.S. (80.6 metric ) Metric K-factor measurement shown is in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. Overall Length: 2-5/16 (59 mm) Material Standards: Sprinkler Frame: Brass UNS-C84400 Deflector: Brass UNS-C26000 Fusible Element Assembly: Nickel Alloy Trigger and Support: Stainless Steel UNS-S31600 Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Seat and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Screw: Brass UNS-C36000 For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.) Order QREC Fusible Element Pendent Sprinkler VK601 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, and Black Polyester = M-/B Temperature Suffix: 165 F (74 C) = C and 205 F (96 C) = E For example, sprinkler VK601 with a Brass finish and a 165 F (74 C) temperature rating = Part No. 13969AC Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the Viking website.) Sprinkler Wrenches: A. Standard Wrench: Part No. 21475M/B (available since 2017) B. Wrench for coated and/or recessed sprinklers: Part No. 13655W/B (available since 2006) A ½ ratchet is required (not available from Viking). Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A (available since 1971) B. Twelve-head capacity: Part No. 01725A (available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. For Light Hazard Occupancies Only Replaces Form No. F_072114 Rev 17.1 (Added P65 Warning.)

Page 2 of 6 5. OPERATION During fire conditions, the heat-sensitive fusible element assembly disengages, releasing the seat and spring assemblies to open the waterway. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Model VK601 Sprinkler is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking s current list price schedule or contact Viking directly. Sprinkler Temperature Classification TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Nominal Temperature Rating 1 Maximum Ambient Ceiling Temperature 2 Frame Paint Color Ordinary 165 F (74 C) 100 F (38 C) None Intermediate 205 F (96 C) 150 F (65 C) White Sprinkler Finishes: Brass, Chrome, White Polyester 3, and Black Polyester 3 Footnotes 1 Decorative sprinklers may not be color coded. The temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester coatings. Wrench Flat Protective Sprinkler Clip Figure 1: Standard Sprinkler Wrench 21475M/B

Page 3 of 6 Sprinkler Base Part Number 1 SIN Approval Chart 1 (UL) Quick Response Extended Coverage Pendent Fusible Element Sprinkler VK601 NPT Thread Size For Light Hazard Occupancies Only. Maximum 175 PSI (12 Bar) WWP Nominal K-Factor Maximum Areas of Coverage 4 Minimum Water Supply Requirements 4 Flow/Pressure Listings and Approvals 3 (Refer also to Design Criteria below.) Inches mm U.S. metric 2 (Length x Width) culus 5 NYC Sprinkler Temperature Ratings A - 205 F (96 C) B - 165 F (74 C) Approved Finishes 1 - Brass, Chrome, White Poly-ester, and Black Polyester 16 x 16 (4.9 m x 4.9 m) 18 x 18 (5.5 m x 5.5 m) Footnotes 26 gpm @ 21.6 psi (98.4 L/min @ 1.49 Bar) 33 gpm @ 34.7 psi (124.9 L/min @ 2.39 Bar) A1Y, B1Z See Footnote 6. B1Z See Footnote 6. Approved Escutcheons Y - Standard surface-mounted escutcheons or the Viking Microfast Model F-1 Adjustable Escutcheon Z - Standard surface-mounted escutcheons or the Viking Microfast Model F-1 Adjustable Escutcheon, or recessed with the Micromatic Model E-1 or E-2 Recessed Escutcheon 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 4 For areas of coverage smaller than shown, use the Minimum Water Supply Requirement for the next larger area listed with sprinklers of similar K- factor. Flows and pressures listed are per sprinkler. 5 Listed by Underwriter s Laboratories, Inc. for use in the U.S. and Canada for Light Hazard occupancies with smooth, flat, horizontal ceilings only. 6 Meets New York City requirements, effective July 1, 2008. culus Listing Requirements: DESIGN CRITERIA - UL (Also refer to Approval Chart 1 above.) QREC Pendent Sprinkler VK601 is culus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for extended coverage pendent spray sprinklers: Limited to Light Hazard occupancies with smooth, flat, horizontal ceilings only. Minimum spacing allowed is 8 ft. (2.4 m) unless baffles are installed in accordance with NFPA 13. Minimum distance from walls is 4 in. (102 mm). Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall. The sprinkler installation and obstruction rules contained in NFPA 13 for extended coverage pendent spray sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Page 4 of 6 Sprinkler Base Part Number 1 SIN Approval Chart 2 (FM) Quick Response Extended Coverage Pendent Fusible Element Sprinkler VK601 NPT Thread Size Nominal K-Factor Maximum 175 PSI (12 Bar) WWP Maximum Areas of Coverage 4 Inches mm U.S. metric 2 (Length x Width) Minimum Water Supply Requirements 4 Flow/Pressure FM Approvals 3 (Refer also to Design Criteria below.) 16 x 16 (4.9 m x 4.9 m) 26 gpm @ 21.6 psi (98.4 L/min @ 1.49 Bar) A1Z 18 x 18 (5.5 m x 5.5 m) 33 gpm @ 34.7 psi (124.9 L/min @ 2.39 Bar) A1Z Sprinkler Temperature Rating A - 165 F (74 C) Approved Finishes 1 - Brass, Chrome, White Polyester, and Black Polyester Approved Escutcheons Z - Standard surface-mounted escutcheons or the Viking Microfast Model F-1 Adjustable Escutcheon, or recessed with the Micromatic Model E-1 or E-2 Recessed Escutcheon Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 4 For areas of coverage smaller than shown, use the Minimum Water Supply Requirement for the next larger area listed with sprinklers of similar K- factor. Flows and pressures listed are per sprinkler. DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above.) QREC Sprinkler VK601 is FM Approved as a quick response Non-Storage extended coverage pendent sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from culus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Page 5 of 6 Step 1: Carefully slide the wrench sideways around the deflector, ensuring engagement with the sprinklger wrench flats. Sprinkler wrench 12144W/B** must be used for installing recessed Sprinkler VK601. ** A 1/2 ratchet is required (not available from Viking) Step 2: Carefully press the wrench upward and ensure engagement with the sprinkler wrench flats. Figure 2: Wrench 12144W/B for Recessed Pendent Sprinklers 2-1/8 (54 mm) Ceiling Opening Size: 2-5/16 (59 mm) minimum 2-1/2 (64 mm) maximum 2-5/16 (60 mm) 1-3/4 (45 mm) 2 (51 mm) Max. 1-1/2 (38 mm) Min. 1-3/8 (35 mm) Installed with a standard 1/8 surface-mounted escutcheon Installed with a Microfast Model F-1 Adjustable Escutcheon Note: At maximum, adapter is exposed 1/2 (13 mm) from face of ceiling Figure 3: Sprinkler Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon

Page 6 of 6 Ceiling Opening Size: 2-5/16 (59 mm) minimum 2-1/2 (64 mm) maximum 2-1/8 (54 mm) 2-1/8 (54 mm) 1-3/4 (45 mm) Max. 1-1/8 (29 mm) Min. 2 (51 mm) Max. 1-1/8 (29 mm) Min. Installed with a Model E-1 Recessed Escutcheon Installed with a Model E-2 Thread-on Recessed Escutcheon Figure 4: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons Replaces Form No. F_072114 Rev 17.1 (Added P65 Warning.)