Catalog C: RoofPak Singlezone Heating and Cooling Units. Type RPS/RFS/RCS 18 to 135 Tons MEA N. See page 3

Similar documents
RoofPak Applied Rooftop Systems

RoofPak Applied Rooftop Systems Air Handler

Catalog Maverick II Commercial Packaged Rooftop Systems. Engineered for flexibility and performance

Catalog Modular Self-Contained Air Conditioning Systems. Type: SWT Models: 023C 040C Size: 20 through 45 Tons

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

Modular Supply Make-Up Air Unit

RoofPak Applied Rooftop Systems Air Handler

Maverick II Commercial Rooftop Systems 15 to 75 tons

VariCool VAV Engineering Guide

RoofPak Applied Rooftop Systems Air Handler

Vision and Skyline Semi-custom Air Handlers

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

Direct Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air

SECTION ROOFTOP REPLACEMENT AIR UNITS

Modular Heating & Ventilating Unit Model IGX-HV

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

Commercial Packaged Rooftop Systems

THE ULTIMATE ROOFTOP SOLUTION

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

62DA,DB,DC,DD,DE,DF07-38

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

1.1 This section applies to air handling units for HVAC Systems.

Direct Fired Heater Model AD Specification

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Energy Recovery with Cooling and Heating Model ERCH

Digital Precise Air Control - DPAC

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Job Name Control Systems Description Date

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

Catalog RoofPak Singlezone, Heating and Cooling Systems with Evaporative Condensers

Verasys System Operation Overview Technical Bulletin

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

Direct Gas-Fired Make-Up Air Models DG and DGX

Voyager. 12½ to 25 Ton Light Commercial Packaged Units with ReliaTel Microprocessor Controls

Advance Release September 2009

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

SKYPAK II, 3 Ton Series, gives you a

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

SECTION AIR HANDLING UNIT

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

SECTION WATER-SOURCE UNITARY HEAT PUMPS

Catalog RoofPak Applied Rooftop Systems with Energy Recovery Wheels

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

MicroTech Self-Contained Air Conditioning System

Submittal Data Performance Data Electrical Data

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series.

Heat Pumps M2 SERIES. Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features:

SEQUENCE OF OPERATIONS

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

HVAC Controls Upgrades: Requirement Details ( )

Submittal Summary Page

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

THE RIGHT SPEC. RIGHT NOW.

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

CHAPTER 4. HVAC DELIVERY SYSTEMS

ALL PRODUCTS BROCHURE

COMcheck Software Version Review Mechanical Compliance Certificate

York 25-Ton VAV Rooftop Unit

MODULE-AIRE VERTICAL PACKAGE UNITS MB SERIES MB SERIES. Energy Wise HVAC Equipment

PRODUCT SERIES. VPR Series VPRX Series VPRE Series VPRP Series VPRC Series

Gas-Fired Indoor and Outdoor Duct Furnaces

Flexible & Innovative. Cooling Solutions

RHEEM PACKAGE GAS/ELECTRIC

SECTION (15733) - DEDICATED OUTDOOR AIR UNITS

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.

RTU. Roof Top Units 8 30 Ton. Maxi-Kool.

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

MicroTech Rooftop/RMC

Cultivator & Hybrid Cultivator

FEATURES AND BENEFITS

THE WALL-MOUNT ONE TON AIR CONDITIONER. Green Refrigerant. 12,000 Btuh EER Right Side Control Panel. Engineered Features

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

VERTICAL FAN COIL UNITS

48PGD/E/F/L/M/N PG20-28

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

THE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features

Document # R01

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

Transcription:

Catalog C: 214-5 RoofPak Singlezone Heating and Cooling Units Type RPS/RFS/RCS 18 to 135 Tons MEA 368-93-N See page 3

A New Standard in Rooftop Systems 15 through 135 tons with the flexibility to provide 200 to 600 cfm/ton. DX or future cooling. Full factory operation test. 100% make-up air, dehumidification, VAV or CV operation. Modular construction and customized application flexibility. Multiple fan, coil, filter and heat selections, and high efficiency compressor combinations. Factory integrated and commissioned MicroTech II advanced DDC control system. McQuay s innovative Protocol Selectability provides building automation system interoperability with BACnet and LonMark communications capability. Durable, double wall construction with access doors on both sides of each section. Blow through configuration for high sensible cooling and quite operation. Draw through configuration for high latent cooling or high humidity applications. Agency Listed MEA 368-93-N Nomenclature Contents McQuay s unique features and options.........2 Introduction................................4 Features and Options........................5 Variable Air Volume........................11 MicroTech II Unit Controls.................13 Application Considerations..................23 Unit Selection.............................30 Physical Data..............................34 Cooling Capacity Data......................38 Heating Capacity Data......................53 Component Pressure Drops.................64 Fan Performance Data - Supply Fans........................ 68 Fan Performance Data - Propeller Exhaust Fans............... 79 Fan Performance Data - Return Fans........................ 81 Dimensional Data.......................... 84 Roof Curbs.............................. 92 Recommended Clearances................ 100 Electrical Data........................... 102 Unit Weights............................ 109 Engineering Guide Specification............ 113 Document Number: Cat 214-5 HI-F, MicroTech II, RoofPak, Protocol Selectability, SpeedTrol, VaneTrol, DesignFlow, SuperMod, and UltraSeal are trademarks and McQuay is a registered trademark of McQuay International, Minneapolis, Minnesota. The McQuay HI-F fin surface is covered by U.S. Patent No. 3,645,330. 2002 McQuay International. All rights reserved throughout the world. Bulletin illustrations cover the general appearance of McQuay International products at the time of publication and we reserve the right to make changes in design and construction at anytime without notice. Cat 214-5 1

McQuay s unique features and options... Modular Flexibility Allows you to specify the unit you want, optimized for high energy efficiency, good IAQ, and quiet operation. 100% make-up air, dehumidification, CV, and VAV system control provided by MicroTech II control system. Blow through configuration (shown) provides higher sensible cooling, a quiet tenant environment, and energy savings. Draw through configuration provides higher latent cooling for make-up air systems or systems with high humidity loads. Multiple filter, fan, coil, and heating options in flexible sizes to match system needs. Extended face area filters and coils reduce system pressure drops, improving operating and energy efficiency. Multiple high efficiency compressor combinations match system needs. Optional return/supply locations match system configuration requirements at lower installed costs, reduced air pressure drops, and quieter operation. Return or Exhaust Fan Customize the unit to fit the application and return duct pressure drop. Return fans typically provide better building pressure and ventilation control as return duct pressure drop increases. Exhaust fans typically save energy as return duct pressure drop increases. Factory-Mounted Variable Frequency Drives Control fan motor speed for lower fan operating costs and lower noise. MicroTech II Advanced DDC Control System Factory-installed and tested to minimize costly field commissioning. Open Protocol for direct incorporation into BACnet or LonMark systems provides maximum building automation system compatibility. Easily accessed for system diagnostics and adjustments via a keypad/display on every unit. Minimum outdoor air and humidity control logic ensure fresh air intake and optimum humidity levels. High Efficiency Condensing Section Open air design for unrestricted airflow and access to compressors and refrigerant piping. Up to 8 steps of compressor capacity control, with hot gas bypass on each circuit, provides a stable discharge temperature and humidity control. High efficiency Copeland Compliant Scroll or Discus semi-hermetic compressors provide optimum system performance and proven reliability. Economizer Outside air enters from both sides, improving mixing for better temperature control. Maintains minimum outside air intake for good IAQ. Monitors outside air conditions for "free" cooling. DesignFlow Precision Outdoor Air Measurement System accurately measures outdoor air intake. Patented UltraSeal low leak dampers minimize air leakage, reducing energy costs. Generous face area intakes/outlets and dampers reduce system pressure drops, improving operating and energy efficiency. Hinged Access Doors On both sides of every section for easy access to all components. Single lever latch and door holders provide easy entry. Double-wall construction protects insulation during maintenance. Durable Construction Pre-painted exterior cabinet panels pass ASTM B 117 Salt Spray Test for durability. Capped seams prevent water leaks into cabinet. Cross-broken top panels eliminate standing water. Heavy-duty R-6.5 insulation minimizes heat loss for reduced energy costs. Double-wall construction protects insulation and provides wipe clean surface to inhibit microbial growth. Stainless steel, sloped drain pans eliminate standing water. Full unit base rail with heavy-duty lifting lugs provide single piece rigging of units up to 135 tons. Airfoil Fans More energy efficient and improved sound performance versus forward curve fans. Double width, double inlet (DWDI) variety. Blank Sections Available throughout unit to factory-mount air blenders, carbon or charcoal filters, sound attenuators, humdifiers, or other specialty equipment (air purification system shown). Allow customization for maximum system performance and efficiency. Reduce design and installation costs. SuperMod High Turndown Gas Burner Full 20:1 turndown and multiple sizes enable precise temperature control at reduced design, installation, and life-cycle costs. Maintain comfortable tenant environment in VAV, 100% make-up air, and dehumidification applications. Note: Air Handler Configuration The benefits of McQuay s packaged rooftop system are available in a rooftop air handler configuration. For details, see Catalog 206. 6 Cat 214-5 Cat 214-5 7

Introduction McQuay RoofPak applied rooftop systems are the semicustom, HVAC system solution for your 1 to 8 story building projects. Available with cooling capacities from 18 to 135 tons, RoofPak systems offer the installation cost and interior space savings of a roof-mounted system, while providing comparable flexibility and operating and maintenance efficiencies to central heating and cooling systems. Applications range from offices, schools and libraries, to airport terminals, manufacturing facilities, shopping malls, supermarkets, casinos, and condominiums. McQuay RoofPak systems feature the benefits of a modular design, extensive component flexibility, MicroTech II DDC controls with Protocol Selectability and a durable, completely accessible design for easy maintenance and service, and extended unit life. Modular Design Flexibility to Meet Your Application s Energy, Sound, And IAQ Requirements The unique, modular construction of McQuay Roofpak systems allows units to be configured with the features and options required for your specific installation, creating a cost-effective, customized rooftop system. Units are available for 100% make-up air, dehumidification, constant volume, or variable air volume applications. Units can be configured with the cooling coil in the Blow Through position for high sensible cooling operation, or in the Draw Through position for high latent cooling demands in specialty applications or high humidity climates. Blank sections along the length of the unit allow air blenders, carbon or charcoal filters, sound attenuators, humidifiers, and other specialty equipment to be designed-in and factory-mounted. A wide range of fan, coil, filter and heat selections, and high efficiency compressor combinations, allow the designer to optimize component selections for energy, sound, and IAQ requirements. Easy, Low Cost Installation, Maintenance, and Service McQuay RoofPak systems arrive at the job site as a complete package, factory-assembled and fully tested with controls, eliminating the need for expensive field assembly, refrigerant piping, and control installation. To promote regular maintenance for peak system performance, hinged access doors on both sides of each section, with single lever latches and door holders, put all components within easy reach for maintenance and service personnel. MicroTech II controls are easily accessed for equipment diagnostics and adjustments via a keypad/display on the unit. In addition, Protocol Selectability enables MicroTech II controls to have interoperability with today s building automation systems (BAS), including those using the BACnet or LonMark protocols, providing easy access to all unit operating data and allowing the unit to be operated along with other building systems from a central control station. Durable Construction For Long Life For durability and long life in harsh outdoor conditions, McQuay RoofPak systems feature a leak resistant cabinet design with pre-painted exterior surfaces. Full double-wall construction protects the unit s heavy duty R-6.5 insulation during maintenance and service, and provides a wipe-clean surface McQuay RoofPak Applied Rooftop System - Modular Design Flexibility and Complete Access 4 Cat 214-5

Features and Options McQuay RoofPak systems are built to perform, with features and options that provide for low installed costs, high energy efficiency, good indoor air quality, quiet operation, low cost maintenance and service, and longevity. Completed systems are factory tested and shipped with an ETL or ETL Canada Safety Listing. Unit Construction Nominal unit cooling capacities from 15 to 135 tons. Units up to 52 feet long can be shipped completely assembled. Weather resistant cabinet design with standing top seams and cross-broken top panels to provide positive drainage. Pre-painted exterior surfaces that withstand a minimum 0 hour salt spray test per ASTM B117. Full size, double wall hinged access doors on both sides of each section. All positive pressure door latches have a second catch to prevent the door from opening rapidly if it is opened when the fan is on. Single lever latch mechanism and door holders on each access door. Heavy-gauge galvanized steel unit base with formed recess to seat on roof curb gasket and provide positive weathertight seal. Heavy duty lifting brackets strategically placed for balanced cable or chain hook lifting. Full double-wall construction is available throughout the unit to protect R-6.5 insulation, enhance performance and satisfy IAQ requirements. Perforated liners are available in the plenum areas to enhance sound performance. Available auxiliary blank sections provide the flexibility for factory or field-installed specialty equipment. Factory-mounted and wired service lights with switch and outlet are available in each fan section. Full Double-Wall Construction Condensing Section Open design permits unrestricted condenser airflow, access to compressors, refrigeration components and piping, and access for roof maintenance. Unique rail support system allows the roof deck and insulation to help block compressor noise from entering the building. High efficiency Copeland scroll compressors (15 to ton units). High efficiency Copeland Discus semi-hermetic compressors (70 to 135 ton units). Spring compressor isolation with refrigerant line vibration absorbers available for all semi-hermetic selections. Each refrigerant circuit is furnished with an accessible sightglass, filter drier, manual shutoff valve, high pressure switch, low pressure switch, liquid line solenoid valve, TXV, manual control circuit switch, and manual pumpdown switch. All units feature dual refrigeration circuits for redundancy and efficient capacity control. Large face area condenser coils, with integral subcooling circuits, are constructed of high efficiency, enhanced copper tubing and aluminum fins, for high operating efficiencies. Vertical air discharge minimizes noise. Three-phase condenser fan motors eliminate reverse rotation failures. Up to eight steps of compressor capacity control, with hot gas bypass (on one or both circuits) provides for stable discharge temperature and humidity control. SpeedTrol head pressure control allows mechanical cooling to 0 F ambient temperatures. Part winding start provides two-step starting to reduce current inrush on large capacity compressors. Copper fin condenser coils are available for application in seacoast atmospheres. Cross wire PVC coated condenser coil guards are available to protect condenser fins. Cooling Coil Section Large face area evaporator coils with high efficiency, enhanced copper tubing and aluminum fins, provide for low air pressure drop and high full and part load operating efficiencies. All evaporator coils feature interlaced circuiting to keep the full face of the coil active and eliminate air temperature stratification. Long life painted galvanized steel or stainless steel, sloped (1/8 in./foot incline) drain pans. An intermediate drain pan in the coil bank helps to provide condensate removal without carryover. 3, 4, or evaporator coils with 8, 10, or 12 fins/inch spacing allow a custom match to specific design loads. Multiple coil face areas allow units to be properly matched to wide ranging conditions from 100% outside air to high cfm comfort cooling applications. Cat 214-5 5

Extended Face Area Coils Open drip-proof or totally enclosed motors comply with EPACT efficiency requirements. Premium efficiency motor upgrades available. All fan drives are factory sized according to job specific airflow, static pressure, and power requirements. Single width, single inlet (SWSI) airfoil return fans effectively handle high return duct static pressures and provide superior building static pressure control in VAV systems. For seismic sensitive regions, spring fan isolators are available with seismic restraints. 150% service factor drives extend service life of the fan belts. Fan motor power correction to a minimum of 0.90. Fan motor and drive assembly belt guards. NA to exhaust fans (See 0 to 100% Economizer with Propeller Exhaust Fans on page 8. Variable Air Volume Control Fan Section Multiple double width, double inlet (DWDI) forward curved and airfoil supply air fan selections provide efficient, quiet operation at wide ranging static pressure and CFM requirements. Each fan assembly is dynamically trim balanced at the factory before shipment. Neoprene gasket isolates the fan housing and eliminates vibration transmission to the fan bulkhead. Solid steel fan shafts rotate in 200,000 hour, greaseable ball bearings. All fan assemblies are isolated from the main unit on RIS or 2 in. deflection spring mounts. Airfoil Fans Simple variable inlet vane control is available with all airfoil supply and return fan selections. Energy saving advanced technology variable frequency drive (VFD), fan speed control is available with the convenience and cost savings of factory mounting and testing. All VFD selections are plenum rated and are conveniently mounted within the filtered air stream for extended service life and easy accessibility to maintenance and service personnel. To manage building static pressure dedicated VFDs are used for the supply and return fans. MicroTech II controls provide advanced duct and building static pressure control and equipment diagnostics capability. Factory-Installed Variable Frequency Drive 6 Cat 214-5

Supply and Return Air Plenum Application flexibility of bottom, side, top and front (RFS only) discharge locations and bottom and back return locations to match complex system configuration requirements. Available with burglar bars for added security in both the discharge and return openings. Main Heat Section Wide ranging natural gas, electric, steam and hot water heat selections effectively handle almost any heating demand from morning warm-up control to full heat. Control of all heating options is fully integrated into the unit s MicroTech II control system. Gas Heat Extensive selection flexibility from 200-2,000 MBH output can satisfy wide ranging needs. Two-stage, 3:1 and patented SuperMod 20:1 modulating control provides the flexibility to solve diverse needs. All gas burners exceed ASHRAE Standard 90.1 efficiency requirement of 78% for low fire and % for high fire with efficiencies as high as 88% and % respectively. Gas burners and piping trains are U.L. approved with the complete furnace assembly ETL or ETL-Canada Listed. Special order capability with FM or IRI/FIA gas trains. All burner assemblies are factory tested and adjusted prior to shipment. Heat exchangers are a two-pass, drum-and-tube design with stainless steel primary surfaces. Air temperature rise capability of up to 100 F on most models. Burners are forced draft type with all controls and valves housed in the burner vestibule. Designed for ease of inspection, cleaning and maintenance. Patented design of integral flue improves combustion gas distribution, resulting in lower surface temperatures, reduced stresses and higher efficiencies. High-pressure regulators (2-10 psi) also available. All stainless steel heat exchangers provide long life in 100% outside air applications. Fuel lines may be conveniently routed through the curb or the burner vestibule door. Heating control fully integrated into the unit s MicroTech II control system. SuperMod High Turndown Gas Burner Full 20:1 turndown with continuous modulation between 5% and 100% of rated capacity provides precise temperature control for a comfortable tenant environment, even in demanding applications such as dehumidification, 100% make-up air and VAV systems. Solves the mixed air tempering requirements of VAV systems when meeting ASHRAE 62.1-1999 ventilation requirements at cold ambient, light load conditions. Operates at normal inlet gas pressures, throughout the entire modulation range. 14 burner sizes ranging from 200 to 2,000 MBH output capacity. Patent pending design featuring 4 unique design innovations and 37 patent claims. SuperMod 20:1 Burner Versus 3:1 Burner Electric Heat 40-320 kw selections factory assembled, installed and tested. Single or multi-stage capability for application flexibility. Constructed of low watt density, nickel chromium elements for long lasting durability. Entire heat bank protected by a linear high limit control with each heater element protected by an automatic reset high limit control. Fuses provided in each branch circuit. MicroTech II controls sequence circuits for operating economy and reduced cycling wear. Steam Heat Steam heating coils are 1- or 2-row, 5/8 in. O.D. copper tube/aluminum fin jet distributing type with patented HI- F5 fin design. Rated in accordance with ARI Standard 430. Four different steam coil selections offered to size heating output to application needs. Factory-installed two-way modulating control valve, piping and modulating spring return actuator provide system control and full flow through the coil in the event of a power failure. Available with factory-mounted freezestat. Hot Water Heat Hot water coils are 1- or 2-row, 5/8 in. O.D. copper tube/aluminum fin design with patented HI-F5 fins. Multiple coil selections offered to size heating output to application needs. Factory-installed three-way modulating control valve, piping and modulating spring return actuator provide system control and full flow through the coil in the event of a power failure. Heating control fully integrated into the unit s MicroTech II control system. Available with factory-mounted freezestat. Cat 214-5 7

Figure 1: Airflow Configuration Outside/Return Air Section 100% Return Air Option Includes a return air plenum with a bottom, back or top return air opening. 0 to 30% Return Air Option Includes return air plenum and 0-30% outside air intake hood with patented UltraSeal low leak dampers to minimize leakage during off cycles. Damper is field adjusted to a fixed open position that is easily set using the MicroTech II keypad. Available with two-position or modulating control. 100% Outside Air Option Includes a weather hood factory mounted to the filter section, bird screen to prevent infiltration of foreign objects and UltraSeal low leak dampers to minimize leakage during off cycles. Dampers arranged vertically and controlled by a twoposition actuator, factory wired to sequence open when the supply fan is running and to close when the supply fan is off. Economizer Airflow 0 to 100% Economizer Option Includes return air plenum with back or bottom opening, exhaust air dampers and UltraSeal low leak economizer intake dampers to minimize leakage during off cycles. Available with or without a full return air fan. Outside air is introduced from both sides of the unit through outside and return air dampers that are arranged vertically to converge the multiple air streams in circular mixing patterns, minimizing temperature stratification and improving system performance. 0-100% economizer sections use horizontal louvered intakes, eliminating unsightly hood assemblies. Economizer control is fully integrated into the unit s MicroTech II control system and features spring return actuator, adjustable minimum outside air set point and adjustable changeover. DesignFlow outdoor air control system measures outside air intake volume and automatically adjusts damper position to maintain minimum volume requirements. Outside air enthalpy, comparative enthalpy or dry-bulb temperature changeover provides control flexibility to bring in the most economical amount of outside air for free cooling. Exhaust dampers exhaust air out the back of the unit. 0 to 100% Economizer with Centrifugal Return Fan Figure 1 shows return fan air flow configuration. All 0 to 100% economizer components are included Includes a DWDI forward curved or SWSI air foil, centrifugal return fan Return fans are in series with the supply, and operate simultaneously with the supply fan to control building pressure, and handle the return duct ESP at all times. Return fans and exhaust fans have different performance characteristics and are not interchangeable. See page 25 for application recommendations. 0 to 100% Economizer with Propeller Exhaust Fans Figure 2 on page 9 shows exhaust fan air flow configuration. All 0 to 100% economizer components are included Includes one to three propeller fans, depending on required capacity, all controlled from one VFD. exhaust fans are in parallel with the supply fan, and may only operate during the economizer mode to control building pressure, and do not handle the return duct ESP design. Return fans and exhaust fans have different performance characteristics and are not interchangeable.see page 25 for application recommendations. 8 Cat 214-5

Figure 2: Airflow Configuration - Return Fan Multiple Filter Options - N D = K I J 4 A JK H 5 K F F O DesignFlow Precision Outdoor Air Control System Patent pending, precision mass flow sensor assemblies directly measure the total mass volume of air flowing through the outdoor air intakes with accuracy exceeding 95% Repeatable accuracy helps provide adequate ventilation air for good indoor air quality (IAQ), energy efficiency and compliance with ASHRAE Standard 62.1-1999.See Table 1 for ventilation airflow measurement ranges verified by Intertek Testing Services, Inc. Table 1: Ventilation Airflow Measurement Range Unit Size 015C-030C 036C-040C 045C-0C 0C-135C Pre-engineered, factory-installed and calibrated system requires no additional field-installed devices or complicated field calibration. MicroTech II controls automatically respond to mass flow sensor signals and adjusts outdoor air damper position to maintain ventilation rate set point. Filter Section Ventilation Airflow Measurement Range 540-9,400 cfm 8-13,120 cfm 10-18,000 cfm 1594-37,126 cfm Selection flexibility includes large face area angular filter racks with 2 in., 30% panel filters, or high efficiency cartridge filter assemblies with pre-filters. Multiple access doors allow easy filter changes from either side of the unit. 65% and 95% efficient filter selections feature permanent gaskets to seal against the cartridge filters and include a 2 in., 30% pre-filter. Extended filter face area arrangements meet a wide range of airflow requirements. Double wall, 95% efficient final filter selections are available as the last section before the discharge plenum. Static Air Mixers Factory installed between the outside/return air section and the filter section. Provides blended air temperatures to minimize the potential for freezestat trips when using a hydronic heating source. Blended outside/return air streams improve system control and avoid uneven temperature distribution at the duct take-offs. Sound Attenuators Factory-installed downstream of the supply fan to dampen fan noise in sound sensitive applications. Can reduce sound levels by as much as half in the lower octave bands and more than half in the higher octave bands. Tedlar coating available for added protection of the acoustic insulation. Factory Installed Sound Attenuators Cat 214-5 9

Humidifiers Factory installed steam humidifier distribution grids downstream of the supply air fan. Unit Controls Integrated advanced MicroTech II DDC controls with unit mounted human interface featuring a 4-line, 20 character English display for fast equipment diagnostics and adjustments. Controls factory installed and commissioned prior to shipment. 100% make-up air, dehumidification, VAV, or CV control capabilities. Factory integrated minimum outdoor airflow measurement and control capability. Protocol Selectability allows interoperability with today s BAS, including those using the BACnet and LonMark protocols. MicroTech II Keypad/Display Electrical Units are completely wired and tested at the factory, with control wiring routed in an accessible, protective wire raceway at the base of the unit. Wiring complies with NEC requirements and all applicable U.L. standards. For ease of use, wiring and electrical components are number coded and labeled according to the electrical diagram. Units have a 115V convenience receptacle. Supply and return air fan motors, compressor motors, and condenser fan motor branch circuits are individually fused. A single point power connection with power block or disconnect switch is standard. A unit mounted disconnect includes a service handle on the exterior of the control panel door. Electrical power feeds inside the perimeter roof curb through factory provided knockouts in the bottom of the main control panel. Dual disconnects are available on size 045C-135C units to satisfy emergency power requirements. Supply and return fan motors and controls are on the emergency power circuit and the balance of the unit is on the other. Phase failure/under voltage protection is available to protect three phase motors. Roof Curbs Constructed in accordance with NRCA guidelines with 12-gauge galvanized steel. Fits inside the unit base around the perimeter of air handling section. Duct frames are provided as part of each curb assembly to allow duct connections to be completed before the unit is placed. Gasket seals between the curb duct frame and the unit. Separate, factory-supplied steel rail supports condensing section to isolate noise and vibration from the air handling section, and to allow open roof access under the condensing section. 10 Cat 214-5

Variable Air Volume McQuay RoofPak variable air volume systems (VAV) employ the concept of varying the air quantity to a space at a constant temperature thereby balancing the heat gains or losses and maintaining the desired room temperature. This true variable volume system is commonly referred to as a squeeze-off or pinch-off system. Unlike a bypass or dump system, supply air is diverted from areas where it is not required to areas that need cooling and at system part load conditions the total fan volume is reduced. This ability to reduce supply air quantities not only provides substantial fan energy savings at partial load conditions, but it also minimizes equipment sizing. The minimum air volume capability of an inlet vane application is also difficult to determine. Whenever a VAV system with terminal boxes is controlled by a static pressure sensor, a system resistance curve is developed which passes through the design operating point and a minimum static pressure control point. This system curve determines where the fan crosses into its unstable operating region. Figure 3 illustrates inlet vane turndown. The following equation calculates the minimum airflow (turndown) available. Figure 3: Min. cfm= ( cfm 1 ) Inlet Vane Turndown SP ------------------------------------------------------------- 2 cfm 1 SP 3 ----------- 2 + SP cfm 2 SP 1 3 1/ 2 Variable volume systems offer the following advantages: 1. Lowers system first cost by using system diversity to reduce equipment and duct sizes. 2. Lowers operating costs by reducing fan energy demands, especially at part load conditions. 3. Lowers first cost by reducing space requirements for duct trunks and mechanical equipment. 4. Provides system flexibility to match changing occupancy demands. Two effective means for modulating air delivery are available with the RPS and RFS units. These VAV options include variable inlet vanes and variable frequency drives. Both means offer reliable operation over a wide range of airflow, with variable frequency drives offering advantages in sound and energy performance. Inlet Vanes Fan volume reduction with inlet vanes is accomplished by pre-spinning the air in the direction of fan rotation. The effect of pre-spinning results in decreased airflow, decreased static pressure and decreased fan brake horsepower. For each position of a variable inlet vane, a new fan curve is created. Consequently, fan brake horsepower reductions cannot be read directly from the fan curve in inlet vane applications. Variable Frequency Drives Variable frequency drives provide the most efficient means of variable volume control by taking advantage of the fan law relation between fan speed (rpm) and fan brake horsepower (bhp). Also, since airflow reduction is accomplished by changing fan speed, the noise penalties often associated with mechanical control devices, e.g. inlet vanes, are not introduced. The following equation illustrates how fan bhp varies as the cube of the change in fan speed: density 2 hp 2 hp 1 --------------------- density 1 rpm ------------ 2 3 = rpm 1 In an ideal system, at 50% fan speed, brake horsepower would be reduced to 12.5% of that at full speed. Variable frequency control varies the speed of the fan by adjusting the frequency and voltage to the motor. Keeping a constant volts/frequency ratio (constant magnetic flux) to the motor allows the motor to run at its peak efficiency over a wide range of speeds and resulting fan airflow volumes. Figure 4 on page 12 illustrates on a fan curve the effect of varying air volume with a variable frequency drive. Cat 214-5 11

Figure 4: Variable Frequency Drive Control 1. Higher operating efficiencies than commonly used forward curved fans, reducing system energy demands. 2. Higher operating efficiencies than commonly used forward curved fans, reducing electrical requirements. 3. A non-overloading brake horsepower curve. 4. A single wheel design, eliminating potential problems with fan paralleling at light loads. Airfoil Fans To further enhance VAV system performance, McQuay RoofPak VAV systems use efficient airfoil fan selections. McQuay airfoil fan selections feature: MicroTech II VAV Fan Tracking Control A key element in successful VAV application is the ability to track supply and return air fan volumes so that proper building static pressure is maintained. McQuay International, a pioneer in the development of rooftop VAV systems, developed its exclusive VaneTrol fan tracking control logic to solve just this issue. Incorporating over 30 years of rooftop VAV system experience, the latest generation MicroTech II controls with VaneTrol logic provide advanced and accurate duct static pressure control plus supply and return fan tracking control that effectively and efficiently manages building static pressure. The MicroTech II controller provides complete control of your variable inlet vane or variable frequency drive applications. For further information on this control, See MicroTech II Unit Controls on page 13. 12 Cat 214-5

MicroTech II Unit Controls Designed with the system operator in mind, McQuay RoofPak systems continue to provide industry leading performance, featuring the microprocessor based Micro- Tech II Applied Rooftop Unit Control system. The latest in microprocessor technology and software innovation have been used in each MicroTech II controller to give you the ultimate in rooftop control and flexibility. In addition to providing stable, efficient temperature and static pressure control, the controller is capable of providing comprehensive diagnostics, alarm monitoring and alarm specific component shutdown if critical equipment conditions occur. A user interface featuring an 8-key keypad and a 4-line x 20 character display, comes as standard with each Micro- Tech II control system, providing system operators with superior access to temperatures, pressures, operating states, alarm messages, set points, control parameters and schedules. All messages are displayed in plain English text. This high degree of system interface and diagnostics capability makes MicroTech II controls a recognized standard for total performance. Password protection is included to protect against unauthorized or accidental set point or parameter changes. The MicroTech II Applied Rooftop Unit Control system is capable of complete, stand-alone rooftop unit control. If desired, it can also provide interoperability with building automation systems (BAS) through McQuay s innovative Protocol Selectability. Protocol Selectability allows the unit control system to be factory or field configured for BACnet MS/TP, BACnet/IP or LonMark protocols. In addition, MicroTech II unit controls can be accessed via modem using a standard MicroTech II service tool. MicroTech II controls with Protocol Selectability provide more energy saving, comfort, indoor air quality, and operation management features than can be found in any other standard microprocessor-based system on the market today. Protocol Selectability MicroTech II unit control systems are factory configured for either standalone operation or for incorporation into independent building automation systems (BAS) through Protocol Selectability. By using industry recognized communication protocols, BACnet MS/TP, BACnet / IP or LonMark, McQuay MicroTech II controls expand the horizon of opportunities for BAS choice without the sacrifice of system performance. The same extensive range of functionality is available to the user if they use the independent BAS supplier of their choice as if they were to use a McQuay control network. BACnet communications conform to the BACnet Standard, ANSI/ASHRAE Standard 135-1995, and are supported by a protocol implementation conformance statement (PICS). LonMark communications are in accordance with either the Discharge Air Controller (DAC) or Space Comfort Controller (SCC) profiles and are LonMark certified. The building automation system can interact with one or multiple rooftop unit controllers in the following ways: Set the unit s operating and occupancy modes Monitor all controller inputs, outputs, set points, parameters, and alarms Set controller set points and parameters Clear alarms Reset the cooling discharge air temperature set point (VAV and CAV-DTC units) Reset the heating discharge air temperature set point (VAV and CAV-DTC units with modulating heat) Reset the duct static pressure set point (VAV units) Set the heat/cool changeover temperature (VAV and CAV-DTC units) Set the representative zone temperature (CAV-ZTC units) Provide common fan control for multiple units on a common duct system. Components Each RoofPak applied rooftop system is equipped with a complete MicroTech II unit control system that is pre-engineered, preprogrammed, and factory tested prior to shipment. Each MicroTech II unit control system is composed of several components that are individually replaceable for ease of service. These components include: Keypad/display user interface Main control board Cooling control boards Electric heat control board (optional) Communication protocol module (optional) Pressure transducers Unit mounted temperature sensors Zone temperature sensor packages Main Control Board (MCB) The main control board (MCB) contains a microprocessor that is preprogrammed with the software necessary to control the unit. This can keep schedules, set points and parameters from being lost, even during a long-term power outage. The microprocessor board processes system input data and then determines and controls output responses. An RS-232 communication port is provided as standard to allow for direct or modem access with a PC based service tool. Cooling Control Boards (CCB1, CCB2) A cooling control board (CCB) is used on each refrigeration circuit to expand the input and output capability of the main control board (MCB). Each CCB communicates with the MCB via serial data communications. These microprocessor based boards provide independent operation and alarm response even if communication is lost with the MCB. Electric Heat Control Board (EHB1) An electric heat control board (EHB1) is used to expand the input and output capability of the main control board (MCB) whenever multi-stage electric heat is used. The EHB1 communicates with the MCB via serial data communications. This microprocessor based board provides independent operation and alarm response even if communication is lost with the MCB. Cat 214-5 13

Communication Protocol Module (CPM) The communication protocol module (CPM) provides the means to factory or field configure MicroTech II unit controls for interoperability with an independent BAS using McQuay s innovative Protocol Selectability. Communication protocol modules are available to support industry recognized communication protocols including BACnet MS/TP, BACnet / IP and LonMark. Keypad/Display All MicroTech II RoofPak controls include a keypad/display that provides user interface with the main control board (MCB). The keypad/display has eight easy-to-use, touch-sensitive membrane key switches that are used for positioning the display and entering changes. The display is a supertwist nematic type with highly visible black characters on a yellow background. The 4-line by 20-character format allows for easy to understand plain English display messages. All operating conditions, system alarms, control parameters and schedules can be monitored from the keypad/display. If the correct password has been entered, any adjustable parameter or schedule can be modified from the keypad. MicroTech II Keypad/Display Temperature and Humidity Sensors With the exception of the zone sensor, all temperature sensors are factory installed and tested. Zone sensor packages are available to suit any application. When required for dehumidification applications, a humidity sensor is available for field installation. Static Pressure Transducers All pressure transducers are factory installed and tested. Connection and routing of sampling tubes is done at time of unit installation. Zone Temperature Sensors Two optional zone temperature sensors are available: 1. Zone sensor with tenant override switch. 2. Zone sensor with tenant override switch and remote set point adjustment. Timed tenant override is a standard MicroTech II control feature. Zone sensors are required to utilize the controller s purge cycle, space reset of supply air set point, and night setback or setup features. All zone sensors are field installed with field wiring terminated at a separate, clearly marked terminal strip. Stand-alone Controller Features MicroTech II applied rooftop unit controls include all of the essential features required to make them capable of completely independent, stand-alone operation. Additional multiple unit control capabilities are available through optional MicroTech II system products or through control provided by a BAS. Internal Time Clock An internal, battery-backed time clock is included in the MicroTech II unit controller. Current date and time can be quickly and easily set at the user interface keypad. Internal Schedule Seven daily schedules and one holiday schedule can be entered at the keypad of all unit controllers. For each of these eight schedules, one start and one stop time can be entered. Up to 16 holiday periods, of any duration, can be designated. The unit will automatically run according to the holiday schedule on the holiday dates. To handle special occasions, an additional one event schedule can also be used. In lieu of its internal schedule, the unit can be operated according to a network schedule from a BAS. External Time Clock or Tenant Override Input An input is supplied that can be used to accept a field wired start/stop signal from a remote source. An external time clock, a tenant override switch, or both may be connected. Whenever the external circuit is closed, the controller overrides the internal schedule (if activated) and places the unit into the occupied mode. If the internal schedule or a BAS network schedule is used, field wiring is not required. Timed Tenant Override Off-hour operation flexibility is a must in today s office environments and even stand-alone MicroTech II controls handle it with ease. When unit operation is desired during unoccupied hours, timed tenant override can be initiated by pressing the tenant override button on either of the optional zone sensor packages. The unit will then start and run in the occupied mode for a keypad adjustable length of time (up to five hours). If the button is pressed again while the unit is operating, the timer will reset to the full time allowance without interrupting unit operation. Tenant override operation can also be initiated by a BAS. Remote Set Point Adjustment All constant air volume-zone temperature control (CAV- ZTC) unit controllers include an input that can be used to remotely adjust the zone cooling and heating set points. To utilize this feature, the optional zone sensor package 14 Cat 214-5

with set point adjustment must be wired to the controller. The remote set point adjustment feature can be enabled or disabled from the keypad at any time. When enabled, remote set point adjustment is available even if the return temperature is selected to be the Control Temperature. Auto/manual operation selection Automatic or manual operation can be controlled either remotely or at the keypad. All controllers include two inputs that can be used to enable or disable cooling, heating, and fan operation from remote switches. With the heat enable and cool enable terminals, the operator can enable cooling, heating, or both as desired. Using the system off terminals, the operator can disable the fans, and thus the entire unit, without the unit being able to be started remotely. From the keypad, there are a variety of occupancy and auto/manual control mode selections available to the operator: Occupancy modes Auto Occupied Unoccupied Bypass (tenant override) Control modes Off manual Auto Heat/cool Cool only Heat only Fan only Compressor Lead-lag Selection All unit controllers are capable of automatic compressor, lead-lag control. If automatic control is not desired, the operator can assign fixed lead and lag designations to the compressor circuits. Compressor Sequencing Selection Because all applications are not the same, MicroTech II controls provide two choices for compressor capacity staging. For high sensible demand, comfort cooling applications, cross-circuit unloading can be chosen to maximize part load efficiency. Cross circuit unloading takes maximum advantage of available condenser and evaporator surface areas. Lead-loading can be selected whenever part load dehumidification capability is of primary importance. Economizer Changeover Selection On units equipped with an economizer, there are three methods of determining whether the outdoor air is suitable for free cooling: two methods sense enthalpy (dry bulb temperature and humidity) and one senses outdoor air dry bulb temperature. The two enthalpy changeover methods use external, factory installed controls. One compares the outdoor ambient enthalpy to a set point; the other is a solid state device that compares the outdoor ambient enthalpy to the return air enthalpy. This comparative enthalpy control can improve total economizer performance. All unit controls include an internal dry bulb changeover strategy that can be selected at the keypad. When this method is selected, the controller compares the outdoor air dry-bulb temperature to a keypad programmable set point. The external enthalpy control input is then ignored. Cooling and Heating Lockout Control All unit controls include separate keypad programmable set points for locking out mechanical cooling and heating. Mechanical cooling is locked out when the outdoor temperature is below the cooling lockout set point; heating is locked out when the outdoor temperature is above the heating lockout set point. This feature can save energy cost by eliminating unnecessary heating and cooling during warm-up or cool-down periods or when the outdoor air temperature is mild. Night Setback and Setup Control When one of the zone temperature sensors is connected to the unit controller, night setback heating and night setup cooling control are available. Separate, keypad programmable night heating and cooling set points are used to start the unit when necessary. After the unit starts, night setback and setup control is similar to normal occupied control except that the minimum outside air damper position is set to zero. If the outside air is suitable for free cooling, it will be used during night setup operation. Except for 100% outside air applications, night setback control is available even if the unit is not equipped with any heating equipment. When the space temperature falls to the night setback set point, the fans simply start and run until the temperature rises above the differential. This feature might be useful for applications that utilize, for example, duct mounted reheat coils. Morning Warm-up Control If the space temperature is below set point when the unit enters the occupied mode, the morning warm-up control function will keep the outside air dampers closed while heat is supplied to satisfy set point. The outside air damper will remain closed until either the space temperature rises to the heating set point or the keypad adjustable morning warm-up timer expires (default is 90 minutes). The morning warm-up timer supplies the minimum required amount of outdoor air after a certain time regardless of the space temperature. Morning warm-up control is automatically included on all except 100% outside air units. It is available even if the unit is not equipped with any heating equipment, for applications that utilize, for example, duct mounted reheat coils. Outdoor Air Purge Control Designed to take advantage of cool early morning outside air conditions, purge control will start the fans and modulate the economizer dampers to maintain occupied cooling requirements during unoccupied periods if conditions are appropriate. This provides the opportunity to flush the space with fresh outdoor air prior to occupancy. Purge operation is possible only during a keypad adjustable time window prior to occupancy (0 to 240 minutes). When the purge-cycle is active, mechanical cooling is disabled. To utilize the purge feature, one of the zone temperature sensors must be connected to the unit controller. Following is a description of purge control operation. Cat 214-5 15

During the purge time window, the unit will start and run whenever these three requirements are met: The space temperature must be warm enough to enable occupied cooling. The outside air enthalpy must be low enough to enable the economizer. The outside air temperature must be at least 4 F less than the space temperature. When any one of these conditions is no longer true, the unit will be shut down again. As conditions allow, purge cycles the unit in this manner until it enters the occupied mode. Proportional Integral Derivative (PID) Control The Proportional-Integral-Derivative (PID) control algorithm controls modulating actuators to maintain a measured variable (temperature or pressure) at or near its set point. For example, it controls economizer dampers to maintain the discharge cooling set point and it controls the supply fan variable frequency drives to maintain the duct static pressure set point. The integral control feature effectively eliminates proportional droop (load dependent offset) resulting in the tightest possible control. For each PID loop, five keypad adjustable parameters allow the control loop to be properly tuned for any application: (1) period, (2) dead band, (3) proportional band, (4) integral time and (5) derivative time. Appropriate default values for these parameters are loaded into each controller. These default values will provide proper control for most applications; therefore, field tuning is usually not required and thus start-up time is reduced. Change Algorithm The PID function is also used to adjust set points instead of controlling variable speed drives or actuators directly. For example, in zone control applications, the PID loop automatically changes the discharge temperature set point (cooling or heating) as the Control Temperature deviates from the zone set point. Another PID loop then controls the economizer actuator or heating valve actuator using the current discharge temperature set point. Unlike a typical master-submaster reset strategy, this cascade control continuously adjusts the discharge set point, even if the Control Temperature s deviation from set point remains constant. This means that the unit s cooling or heating output is set according to the actual load, not just the current zone temperature. The tightest possible zone temperature control results because proportional droop (load dependent offset) is eliminated. Calibrate When initiated at the keypad by an operator, the Calibrate function automatically calibrates all actuator position feedback inputs and all pressure transducer inputs. It does this by shutting the unit down and then driving all actuators to the full closed and full open positions. The controller records the input voltage values that correspond to these positions. The pressure transducer input voltages, which are assumed for 0.00 in. W.C., are also recorded. When Calibrate is finished, an operator command must be entered at the keypad to start the unit. The Calibrate feature can reduce start-up time and assist in periodic maintenance. Field Output Signals All MicroTech II RoofPak controls include two solid-state relay outputs that are available for field connection to any suitable device: the remote alarm output and the occupied output. On VAV units, an additional VAV box output is available. These three outputs are used to signal field equipment of unit status. Remote Alarm Output: The remote alarm output can be used to operate a 24V relay to provide a remote alarm signal to a light, audible alarm, or other device when an alarm condition exists at the unit. Fan Operation Output: The fan operation output is used to control field equipment that depends on fan operation; for instance, to open field installed isolation dampers or VAV boxes. To allow actuators enough time to stroke, the fan operation output is energized three minutes before the fans start. It then remains energized until thirty seconds after the unit airflow switch senses no airflow. The fan operation output is on whenever the unit airflow switch senses airflow. VAV Box Output: The VAV box output provides a means of interfacing unit and VAV box control. When the output is energized (closed), the VAV output indicates that the unit is in the cooling mode. When de-energized (open), it indicates that the unit is either providing heat or circulating air to equalize temperature conditions just after start-up (this is the Recirculate operating state). On units with singlestage morning warm-up heat, the open VAV box output contact is meant to provide a signal to drive the boxes wide open. To prevent duct over pressurization, fan variable speed drives or inlet vanes are driven to a minimum position before the output s contacts are de-energized again for normal cooling operation (this is the Post Heat operating state). Standard Control Options Model RPS and RFS applied rooftop systems are available for most any constant or variable air volume application. MicroTech II controls offer three basic control configurations: variable air volume with discharge temperature control (VAV-DTC), constant air volume with zone temperature control (CAV-ZTC), and constant air volume with discharge temperature control (CAV-DTC), that use sophisticated state change control logic to provide stable, reliable and efficient control. When combined with Micro- Tech II s many available control capabilities, both factory installed and keypad programmable, these three basic configurations can be customized to meet the requirements of the most demanding applications. Variable Air Volume with Discharge Temperature Control (VAV) All VAV units provide true discharge temperature control in addition to duct static pressure control. Cooling only, cooling with single-stage morning warm-up heat, and cooling with modulating heat configurations are available. On units with a return fan, two building static pressure control options are available: VaneTrol logic tracking or direct building pressure control. Because proper ventilation rates have been identified as critical to maintaining good 16 Cat 214-5

indoor air quality, all RoofPak VAV controllers include software algorithms designed to maintain minimum outside air volume at all times when the unit is in the Occupied mode. Constant Air Volume with Zone Temperature Control (CAV-ZTC) CAV-ZTC units are available in either cooling only or cooling with modulating heat configurations. Either of these configurations is available for 100% recirculated, mixed, or 100% outdoor air applications. On units that have a return fan, a direct building static pressure control option is also available. Figure 5: Control Temperature: Discharge Temperature Control Constant Air Volume with Discharge Temperature Control (CAV-DTC) CAV-DTC units are available in cooling only, cooling with single-stage morning warm-up heat, or cooling with modulating heat configurations. This unit configuration can be used for applications that have zone controlled terminal reheat coils or for constant volume, 100% outdoor air applications. The discharge temperature control strategies used with the hybrid CAV-DTC unit are identical to those used with the VAV-DTC unit. On units that have a return fan, a direct building static pressure control option is available (constant supply air volume applications only). Discharge Temperature Control MicroTech II VAV-DTC and CAV-DTC controls provide sophisticated and flexible discharge air temperature control that is only possible with DDC systems. Separate discharge air temperature set points are used for cooling and modulating heating control. At the keypad, the operator can either enter the desired set points or select separate reset methods and parameters for each set point (see Supply Air Reset on page 17). Control Temperature The Control Temperature makes the heat/cool changeover decision. It determines whether cooling or heating is enabled; the discharge temperature then determines whether cooling or heating is actually supplied. At the keypad, the operator can choose the source of the Control Temperature from among the following selections. Space temperature sensor Return temperature sensor Outside air temperature sensor (modulating heat only) Network communication The operator enters separate cool and heat enable set points and deadbands that the Control Temperature is compared with (see Figure 5). When the Control Temperature is greater than or equal to the cooling set point, cooling is enabled. When the Control Temperature is less than or equal to the heat set point, heating is enabled. If desired, these set points and differentials can be set so that there is a dead band in which both cooling and heating are disabled. The controller s software prevents simultaneous cooling and heating. Proportional Integral Derivative Modulation When operating in economizer free cooling or unit heating, the previously described PID algorithm maintains discharge temperature control. The PID algorithm provides precise control of the economizer dampers, modulating gas heat, steam or hot water valves. Compressor Staging Two staging algorithms are available to control a unit s multiple steps of capacity control, Degree-Time and Nearest. These control algorithms provide reliable discharge temperature control while managing compressor cycling rates. Constraints on compressor staging are essential for preventing the short cycling which can reduce compressor life by causing improper oil return and excessive heat buildup in the motor windings. The Degree-Time Compressor staging algorithm keeps track of the discharge temperature and stages cooling up or down to maintain an average temperature that is equal to the discharge cooling set point. A stage change can only occur (1) after the keypad adjustable inter-stage timer has expired (five minute default setting) and (2) if the discharge temperature is outside a keypad programmed dead band. After these two conditions have been met, staging occurs as the controller attempts to equalize two running totals: degree-time above set point and degreetime below set point. The result is that the average discharge temperature is maintained at the cooling set point. The Nearest Compressor staging algorithm keeps track of the discharge temperature and stages cooling up or down to maintain the discharge temperature as close as possible to set point. A stage change can only occur (1) after the keypad adjustable inter-stage timer has expired (five minute default setting) and (2) if the control logic calculates that a stage change will result in a discharge temperature closer to set point than the existing condition. The controller logic continually calculates the expected effect of a stage change and uses this information before making a change. A change is made only if it will bring the discharge temperature closer to set point, resulting in a more consistent discharge temperature, reduced compressor cycling and more stable control VAV box control. Supply Air Reset By automatically varying the discharge air temperature to suit a building s cooling or heating needs, supply air temperature reset can increase the energy efficiency of VAV Cat 214-5 17

and CAV-DTC systems. MicroTech II controllers offer a variety of different reset strategies that can be selected at the keypad. Because they are keypad programmable, reset strategies can be changed or eliminated as desired. Separate strategies can be selected for both cooling and modulating heat. If reset is not desired, a fixed discharge cooling or heating set point can be entered. The following reset methods are available: Space temperature Return temperature Outdoor air temperature Supply airflow (VAV, cooling set point only) External 1-5 VDC or 4-20mA signal Network communication For all temperature reset methods, the minimum and maximum cooling and heating set points are keypad programmable along with the corresponding minimum and maximum space, return or outdoor air temperature parameters. For the supply airflow method, the discharge set point will be reset as the supply fan modulates between 30% and 100%. For the external method, the discharge set point will be reset as the voltage or current signal varies over its entire range. For units in a BAS network, the discharge set points are reset via the communication signal. Multiple Unit Applications Common heat/cool changeover control for multiple unit applications is available with optional MicroTech II system products. Zone Temperature Control MicroTech II CAV-ZTC controls provide the sophisticated and flexible zone temperature control that is only possible with DDC systems. Zone temperature sensors are available with or without a remote set point adjustment. With the remote adjustment model, the space set point can be set at the keypad or at the zone sensor package. (Even if a zone sensor is connected, remote set point adjustment can be enabled or disabled as desired at the keypad.) Control Temperature The Control Temperature is the representative zone temperature. When compared with the zone set points, the Control Temperature determines whether the unit supplies heating, cooling, or neither. It also determines the amount of cooling or heating required to satisfy the load. Its source can be selected at the keypad from among the following selections: Zone temperature sensor Return temperature sensor Because it is the representative zone temperature, the Control Temperature is the primary input to the MicroTech II zone temperature control algorithms. Control Temperature parameters are described below. The controller s software will prevent cooling and heating from being inadvertently enabled at the same time. Change and Proportional Integral Derivative Modulation When economizer free cooling or unit heating is required, the two MicroTech II PID loops combine for cascade-type control, providing the tightest possible zone temperature control. By controlling the discharge temperature along with the zone temperature, these functions eliminate temperature variations near the diffusers that could otherwise occur as a result of traditional zone control s inherent lag effect. Change: If the Control Temperature is above or below the set point by more than the dead band, the Change PID loop periodically adjusts the cooling or heating discharge air temperature set point either up or down as necessary. The amount of this set point change corresponds to the Control Temperature s position in the modulation range. The farther the Control Temperature is from the set point, the greater the discharge set point change will be. The Change-adjusted discharge cooling and heating set points are limited to ranges defined by keypad programmable maximum and minimum values. PID: Using the Change function s current discharge set point, the PID function maintains precise discharge temperature control by modulating the economizer dampers and gas heat, steam or hot water heating valves. Compressor Staging Compressor staging is controlled directly by the Control Temperature. When the Control Temperature is warmer than the zone cooling set point, cooling is staged up; when the Control Temperature is cooler than the zone cooling set point, cooling is staged down. However, a stage change can only occur when the Control Temperature is outside the dead band (see Figure 6). Staging is constrained by an inter-stage delay timer (five minute default setting) and minimum and maximum discharge air temperature limits (all keypad programmable). These constraints protect the compressors from short cycling while eliminating temperature variations near the diffusers. Figure 6: Compressorized Discharge Temperature Cooling Project Ahead Algorithm Because the inherent lag effect in zone temperature control applications can cause overshoot during warm-up or cool-down periods, MicroTech II features a unique Project Ahead control algorithm. Project Ahead calculates the rate at which the Control Temperature is changing and reduces the unit s cooling or heating output as the zone temperature nears its set point, essentially eliminating overshoot. A separate, keypad programmable Project Ahead time parameter for both heating and cooling allows for control fine tuning. Duct Static Pressure Control On all VAV-DTC units, duct static pressure control is maintained by the PID algorithm, which provides precise control of the supply fan variable speed drive or inlet vanes. 18 Cat 214-5

The keypad programmable set point can be set between 0.20 in. W.C. and 4.00 in. W.C. On larger buildings with multiple floors, multiple trunk runs or large shifts in load due to solar effects (East/West building orientation), an optional second duct static sensor is offered. The MicroTech II controller will automatically select and use the lower of the two sensed pressures to control fan volume to provide adequate static pressure to the most demanding space at all times. Multiple Unit Applications For applications in which multiple units are connected in a common duct system, it is important to control all units from a common duct static pressure sensor and to control all operating units in unison. Centralized duct static pressure control is available through optional MicroTech II system products or through control provided by a BAS. Building Static Pressure Control VaneTrol Fan Tracking Control (Does Not Apply to Exhaust Fans) VaneTrol fan tracking control logic offers close and reliable building static pressure control for VAV units equipped with a return air fan. With the VaneTrol logic method, the return fan s variable speed drive or inlet vane assembly tracks the supply fan volume as the supply fan maintains the required duct static pressure using the additional parameter of maintaining a field programmable offset between supply fan and return fan volume. The result is that building pressure is maintained, regardless of the building cooling load, because the proper relationship between supply and return fan volume is maintained. Because the return fan/supply fan tracking relationship is established once during controlled test and balance conditions, ongoing building pressure control is not affected by a fluctuating ambient pressure reference signal or the temporary effects of opening and closing doors on a pressure sensor in the lobby. VaneTrol control logic uses four keypad programmable parameters to maintain the required relationship between return fan and supply fan volumes. These are the supply and corresponding return fan volumes as measured by inlet vane or variable speed drive position, at both maximum and minimum airflow conditions. If the building includes an additional, remote intermittent exhaust fan(s) that will affect building pressure when energized, the VaneTrol logic provides the capability to compensate for it through the use of a second set of inputs. Table 2 shows an example of how supply and return air fan modulation must vary to maintain the correct balance of supply and return air volumes based on the building s parameters, and therefore maintain building pressure. MicroTech II makes determining the building s correct VaneTrol parameters easy with its Balance feature. With Balance, start-up time is reduced because final adjustments are made at the keypad. Table 2: VaneTrol Logic Air Balancing SAF CFM RAF CFM Building Exhaust Remote Exhaust Off Remote Exhaust On Remote Exhaust Off Remote Exhaust On 16000 (100%) 14000 (100%) 13000 (93%) 2000 3000 14000 (88%) 12000 (%) 11000 (79%) 2000 3000 12000 (%) 10000 (71%) 9000 (64%) 2000 3000 10000 (63%) 00 (57%) 7000 (50%) 2000 3000 00 (50%) 6000 (43%) 5000 (36%) 2000 3000 Direct Space Pressure Control (For Return or Exhaust Fans) Any constant or variable air volume unit equipped with a variable volume return or exhaust fan can be provided with direct building static pressure control capability. With the direct method, building static pressure is measured and processed by the PID algorithm. This algorithm provides precise control of the return fan variable speed drive or inlet vanes to maintain the space pressure set point. The range of the keypad programmable set point is between minus 0.25 in. W.C. and 0.25 in. W.C. This type of control can be used for either whole building or lab pressurization (positive or negative) applications, or exhaust fan control, where VaneTrol control logic does not apply. Minimum Ventilation Air Volume Control Consistently maintaining the minimum outdoor air requirements of ASHRAE Standard 62-1999 has been a long standing control challenge for VAV systems. As supply air fan volumes were reduced, the volume of air introduced through a fixed position, minimum outdoor air damper was also reduced, compromising indoor air quality. To meet this challenge, MicroTech II controls feature three user selected control methods for maintaining outdoor air volume. 1. The MicroTech II controller can accept a signal from a DesignFlow Precision Outdoor Air Control system, that is continuously measuring outdoor air volume, and adjust outdoor air damper position to maintain the minimum volume set point. 2. MicroTech II controls have a keypad selected control function that automatically adjusts outdoor air damper position in response to changes in supply air fan volume. Regardless of supply air volume, this strategy maintains a nearly constant outdoor air volume at all times. 3. The MicroTech II controller can accept an external 1-5 VDC signal from a CO2 sensor or other control device and adjust outdoor air damper position. Cat 214-5 19

4. If desired, a fixed minimum damper position can be keypad programmed. This selection may be acceptable when ventilation requirements are met through other sources. During cold ambient conditions where outdoor/return mixed air conditions can become too low, MicroTech II controls will maintain the cooling discharge temperature set point by controlling the unit heating system. For applications in which ambient temperatures and minimum outdoor air requirements can generate this condition, the RoofPak unit should be ordered with modulating heating equipment, such as the SuperMod gas burner. Table 3 illustrates the effect of minimum ventilation control and cold ambient conditions on unit discharge air temperature and how it dictates the need for mixed air tempering capability at the light load/low ambient conditions. It assumes a VAV unit with a 20% outdoor air requirement at design conditions and a 40% minimum airflow requirement. Table 3: Effect of Minimum Ventilation Control on Discharge Temperature Supply Fan Volume (cfm) Outdoor Air Volume (cfm) Operating States Outdoor Air Volume (%) Outdoor Air Temp. ( F) Mixed Air Temp. ( F) 10,000 2,000 20 95 79 8,000 2,000 25 70 73.8 6,000 2,000 33.3 40 63.3 4,000 2,000 50 0 37.5 Operating states define the current overall status of the rooftop system. At the user interface, the operator can display the current operating state and thereby quickly assess the unit s operating condition. Figure 7 shows all possible operating states and the status information they summarize. Depending on unit options, some operating states may not apply. For example, a 100% outside air unit will not have a Morning Warm-Up, Economizer or Unoccupied Economizer operating state. Following are descriptions of each operating state. Off There are five different Off operating states. In any Off operating state, the fans are off, the outdoor air dampers are closed, any variable speed drives or inlet vanes are driven to 0% and cooling and heating are disabled. The Fan Operation output is de-energized (open) and the VAV box output is energized (closed). The specific Off operating state displayed, provides the reason the unit is in Off. The five different Off operating states are: 1. Off - Alarm This state is displayed whenever an active alarm of the fault type has the unit shut down. 2. Off - Manual The unit is in the Off-Manual state whenever the Control Mode parameter is set to Off. Off - Network This state is displayed when the unit operating mode has been set to Off by a network communication signal. 3. Off - Unoccupied This state is displayed when the unit is being scheduled on and off by a time clock function and the schedule indicates an unoccupied period. 4. Off - Switch This state is displayed when the contacts of a field supplied enable switch are closed. Off states are prioritized as shown above, with Off-Alarm having the highest rank. If a unit is in the Off-Alarm state, the unit can not be started until the alarm is cleared. Figure 7: Operating State Sequence Chart ) O 5 J= JA BB 5 J= HJK F 4 A? EH? K = JA 7? + C + E C 9 7 0 A = JE C 7? 0 JC 7? -? -? E A H = O E, ) 6 20 Cat 214-5

Startup Whenever a unit is commanded to start the control always enters the Startup operating state from the Off state. The unit remains in the Startup operating state for an adjustable time period (default set at 3 minutes) before entering the Recirculate state. During the Startup operating state the fans remain off, outdoor air dampers are driven closed, variable speed drives or inlet vanes are driven to their 0% or closed position, cooling and heating remain disabled, the Fan Operation Output is closed and the VAV Box output is open. The Startup operating state will help start fans unloaded while allowing airflow status to be proven quickly. Recirculate Units with return air always enter the Recirculate operating state after completion of the StartUp operating state. In the Recirculate state the fans are energized while the outdoor air dampers remain closed. This allows temperature conditions throughout the unit and space to equalize before temperature control begins. During the Recirculate operating state, cooling and heating are disabled, the outside air dampers are closed, the Fan Operation output is closed, the VAV box output is open, and the variable speed drives or inlet vanes are modulated to maintain the duct static pressure set point. The unit operates in the Recirculate operating state until a field set Recirculate State Time period (2 to 60 minutes) expires. Fan Only The Fan Only operating state occurs during occupied operation when cooling and heating are either not required or disabled. In the Fan Only operating state, the outside air dampers are at minimum position, and cooling and heating are disabled and the Fan Operation output is closed. The VAV box output may be closed or open depending on the time and the previous operating state. Post Heat Operation When a VAV unit enters the Fan Only operating state from Recirculate or any heating state, a special post heat mode of operation occurs. In VAV systems, the VAV boxes are typically forced to a wide-open position during operation in the Recirculate or any heating state, using the VAV Box output signal, to facilitate rapid heat transfer to the space. As a result, since the unit is being controlled to maintain duct static pressure, the discharge fan capacity will be at a maximum position. During post heat operation, normal duct static pressure control is overridden and the discharge fan variable speed drive or inlet vanes are forced to a minimum position while the VAV boxes remain open. This eliminates potential duct over-pressurization problems that can otherwise occur during the transition from heating to cooling operation when the VAV boxes regain zone temperature control. The VAV Box output is held in the open (heat) position for a time period set at the keypad or the supply fan variable speed drive drops below 25% (inlet vane position drops below 17%), at which time normal Fan Only operation occurs. Economizer In the Occupied mode, the unit enters the Economizer operating state when cooling is required and outdoor air enthalpy or dry bulb control indicates free cooling is available. During the Economizer operating state, mechanical cooling and heating are disabled. The economizer dampers are modulated to maintain the cooling discharge temperature set point. The Fan Operation output is closed and the VAV Box output is closed (cool). When conditions are such that the outside air is unable to satisfy the cooling load, the transition from the Economizer state to the Cooling operating state occurs. Cooling In the Occupied mode, the unit enters the Cooling operating state when cooling is required and the economizer is either fully open or disabled. Mechanical cooling is supplied as required to maintain the Occupied discharge temperature cooling set point. The Fan Operation output is closed, the VAV Box output is closed (cool) and heating is disabled. Morning Warm-Up The unit enters the Morning Warm-Up (MWU) operating state when the unit transitions from unoccupied to occupied and when heating is required to bring the Control Temperature up to the occupied heating set point. The unit may go into MWU even when no heating resides in the unit. The MWU operating state is similar to Heating with the difference being that the outside air dampers are held shut rather than at minimum position. The control will remain in the MWU state until either the Control Temperature rises to the occupied heating set point or until the Maximum MWU timer expires. The Fan Operation output is closed, the VAV Box output is open (heat), cooling is disabled and the fan is controlled to maintain normal duct static pressure. Heating The Heating operating state is entered when heating is required during Occupied operation to maintain the Control Temperature above the heating set point. During the Heating operating state, the outdoor air dampers are maintained at minimum position. The Fan Operation output is closed, the VAV Box output is open (heat), cooling is disabled and the fan is controlled to maintain normal duct static pressure. Minimum Discharge Air Temperature The unit enters the Minimum Discharge Air Temperature (DAT) state during Occupied operation when the Control Temperature indicates that neither cooling or heating is required but the discharge temperature falls below the discharge temperature cooling set point. The Minimum DAT state prevents cold discharge air temperatures during what would normally be Fan Only operation. During the Minimum DAT state, the outdoor air dampers are maintained at minimum position and cooling is disabled. The Fan Operation output is closed and VAV Box output is closed (cool). Unoccupied Economizer If outdoor air is suitable for free cooling when purge or night setup operation is required, the unit will operate in the Unoccupied Economizer operating state. During Unoccupied Economizer, the outdoor air dampers are modulated to maintain the discharge temperature cooling set point, heat- Cat 214-5 21

ing is disabled and fan volume is controlled to maintain normal duct static pressure. The Fan Operation output is closed and the VAV Box output is closed (cool). For night setup operation, the transition from Unoccupied Economizer to Unoccupied Cooling is similar to the occupied transition described in Economizer. For purge operation, mechanical cooling is disabled. Unoccupied Cooling The unit enters the Unoccupied Cooling state when night setup operation is required and outdoor air conditions are not suitable for free cooling or cannot satisfy the unoccupied cooling set point. During Unoccupied Cooling, outdoor air dampers are either in the 100% open position for free cooling or closed, fan volume is controlled to maintain normal duct static pressure and heating is disabled. The Fan Operation output is closed and VAV Box output is closed (cool). Unoccupied Heating The unit enters the Unoccupied Heating state when night setback operation is required. During Unoccupied Heating, outdoor air dampers are closed, fan volume is controlled to maintain normal duct static pressure and cooling is disabled. The Fan Operation output is closed and the VAV Box output is open (heat). Alarm Management and Control MicroTech II unit controllers are capable of sophisticated alarm management and controlled response functions. Each alarm is prioritized, indicated, and responded to with the appropriate action. The current alarm (up to four alarms, arranged by alarm priority) and previous alarm (up to eight alarms, arrange by date/time cleared), each with a time and date stamp, can be displayed at the user interface. Whenever a current alarm is cleared, it is logged as a previous alarm and the current alarm becomes the new previous alarm, and the oldest previous alarm is removed. Alarm Priority The various alarms that can occur are prioritized according to the severity of the problem. Three alarm categories are used: faults, problems, and warnings. 1. Faults are the highest priority alarms. If a fault condition occurs, the complete unit will be shut down until the alarm condition is gone and the fault has been manually cleared at the keypad. A fault example would be Fan Fail alarm. 2. Problems are the next lower priority to faults. If a problem occurs, the complete unit will not be shut down, but its operation will be modified to compensate for the alarm condition. A problem will automatically clear when the alarm condition that caused it is gone. Compressor Fail would be an example of a problem, where just the affected compressor is shut down. 3. Warnings are the lowest priority alarms. No control action is taken when a warning occurs; it is simply indicated to alert the operator that the alarm condition needs attention. To remind the operator to read warnings, they must be manually cleared. Dirty Filter indication would be an example of a warning. Generally, a specific alarm condition will generate an alarm that falls into only one of these categories. Under different sets of circumstances, however, the freezestat and most of the sensor failure alarm conditions can generate alarms that fall into multiple categories. Adjustable Alarm Limits Four alarm triggers have adjustable limits. The high return temperature alarm and the high and low supply temperature alarms are adjusted at the user interface. The dirty filter alarm(s) is adjusted at the sensing device. Table 4: MicroTech II Alarm Summary Alarm Name Fault Problem Warning Freeze X X Smoke X Temperature Sensor Fail X X Duct High Limit X High Return Temp X High Discharge Temp X Low Discharge Temp X Fan Fail X Fan Retry X Discharge Air Capacity Feedback X OA Damper Stuck X X Auxiliary Control Board Enable X Auxiliary Control Board Communications X Low Airflow X Heat Fail X Circuit 1 & 2 High Pressure X Circuit 1 & 2 Low Pressure X Circuit 1 & 2 Frost Protect X Compressor 1-4 Fail X Circuit 1 & 2 Incomplete Pumpdown X Auxiliary Control Board Enable Hardware X Airflow Switch (False Airflow) X Dirty Filter X Dirty Final Filter X MicroTech II System Products Multiple Unit Control Multiple RoofPak units in a common system can be controlled using MicroTech II system products. A MicroTech II network can be established to access and set all common control parameters, such as: Common duct static pressure control of multiple VAV units. Common heat/cool changeover control of multiple VAV or CAV-DTC units. Common zone temperature control of multiple CAV-ZTC units. Personal Computer Based Service Tool A personal computer (PC) can be equipped with Windows -based MicroTech II service tool software to provide a high-level operator interface with the MicroTech II unit controls for expanded diagnostic and service capability. The service tool can be connected directly to the MicroTech II controller, or used remotely with the addition of an optional unit mounted phone modem. 22 Cat 214-5

Application Considerations The following section contains basic application and installation guidelines that must be considered as part of the detailed analysis of any specific project. General Units are intended for use in normal heating, ventilating and air conditioning applications. Consult your local McQuay sales representative for applications involving operation at high ambient temperatures, high altitudes, non-cataloged voltages and for applications requiring modified or special control sequences. Consult your local McQuay sales representative for job specific unit selections that fall outside of the range of the catalog tables, such as 100% outside air applications. For proper operation, units should be rigged in accordance with instructions stated in IM 4. Fire dampers, if required, must be installed in the ductwork according to local or state codes. No space is allowed for these dampers in the unit. It is strongly recommended that factory check, test and start procedures be explicitly followed to achieve satisfactory start-up and operation (see IM 4). Most rooftop applications take advantage of the significant energy savings provided with economizer operation. When an economizer system is used, mechanical refrigeration is typically not required below an ambient temperature of 50 F. Standard RoofPak refrigeration systems are designed to operate in ambient temperatures down to 45 F. For applications where an economizer system cannot be used, McQuay s SpeedTrol head pressure control system is available on size 045C-135C units to permit operation down to 0 F. However, if the condenser coils are not properly shielded from the wind, the minimum ambient conditions stated above must be raised. Unit Location The structural engineer must verify that the roof has adequate strength and ability to minimize deflection. Take extreme caution when using a wooden roof structure. Locate the unit fresh air intakes away from building flue stacks or exhaust ventilators to reduce possible reintroduction of contaminated air to the system. Unit condenser coils should be located to avoid contact with any heated exhaust air. Allow sufficient space around the unit for maintenance/service clearance as well as to allow for full outside air intake, removal of exhaust air and for full condenser airflow. Refer to Recommended Clearances on page 100 for recommended clearances. Consult your McQuay sales representative if available clearances do not meet minimum recommendations. Where code considerations, such as the NEC, require extended clearances, they take precedence. In applications utilizing a future cooling unit (RFS), care should be taken in choosing a location of the unit so it will provide proper roof support and service and ventilation clearance necessary for the later addition of a mechanical cooling section (RCS). Split Units Units may sometimes have to be split into multiple pieces to accommodate shipping limitations or jobsite lifting limitations. Units exceeding 52 feet in length may need to be split for shipping purposes. Units exceeding the rating of an available crane or helicopter may also need to be split for rigging purposes. Unit can be split at the condensing section or split between the supply fan and heat section. Contact your local McQuay sales representative for more details. Curb Installation The roof curb is field assembled and must be installed level (within 1/16 in. per foot side to side). A sub-base has to be constructed by the contractor in applications involving pitched roofs. Gaskets are furnished and must be installed between the unit and curb. For proper installation, follow NRCA guidelines. Typical curb installation is illustrated in Roof Curbs on page 92. In applications requiring post and rail installation, an I-beam securely mounted on multiple posts should support the unit on each side. Applications in geographic areas that are subjected to seismic or hurricane conditions must meet code requirements for fastening the unit to the curb and the curb to the building structure. For acoustical considerations, the condensing section is provided with a support rail versus a full perimeter roof curb. When curbs are installed on a built-up roof with metal decking, an inverted 6 in. channel should be provided on both sides of the unit. Acoustical material should be installed over the decking, inside the roof curb. Only the supply and return air ducts should penetrate the acoustical material and decking. Appropriate acoustical and vibration design practices should be applied during the early stages of design to provide noise compatibility with the intended use of the space. Consult your McQuay sales representative for unit sound power data. Acoustical Considerations Good acoustical design is a critical part of any installation and should start at the earliest stages in the design process. Each of the four common sound paths for rooftop equipment must be addressed. These are: (1) radiated sound through the bottom of the unit bottom [air handling section and condensing section] and into the space, (2) structure borne vibration from the unit to the building, (3) airborne sound through the supply air duct and (4) airborne sound through the return air duct. Locating rooftop equipment away from sound sensitive areas is critical and the most cost effective means of avoiding sound problems. If possible, rooftop equipment should always be located over less sensitive areas such Cat 214-5 23

as corridors, toilet facilities or auxiliary spaces and away from office areas, conference rooms and classrooms. Some basic guidelines for good acoustical performance are: 1. Always provide proper structural support under all areas of the unit. 2. Always locate the unit s center of gravity close to a main support to minimize roof deflection. Maintaining a roof deflection under 1/3 in. will assist in minimizing vibration induced noise. 3. Use a concrete deck or pad when a unit has to be located over an occupied space where good acoustics are essential. 4. Only the supply and return air ducts should penetrate the acoustical material and decking within the curb perimeter, and the openings should be sealed once the duct is installed. 5. Don t overlook the return air path. Never leave a clear line of sight into a return or exhaust fan, always include some duct work (acoustically lined tee) at the return inlet. 6. Place an acoustical material in the area directly beneath the condensing section. 7. Minimize system static pressure losses to reduce fan sound generation. 8. Select the appropriate fan for the application. Fans should be selected as close as possible to their peak static efficiency. To assist you, peak static efficiency is identified by the first system curve to the right of the shaded Do not select region, as illustrated in Figure 8 on page 24 9. Design duct systems to minimize turbulence. 10. Account for low frequency duct breakout in system design. Route the first 20 ft. of rectangular duct over non-sensitive areas and avoid large duct aspect ratios. Consider round or oval duct to reduce breakout. 11. When an added measure of airborne fan sound control is required, sound attenuators can be supplied, factory installed in a unit discharge air section, to treat the supply fan. On the return side, additional attenuation can often be achieved by routing the return duct within the curb area beneath the unit. Figure 8: Optimal Fan Selection Line There are many sound sources in rooftop systems. Fans, compressors, condenser fans, duct take-offs, etc. all generate sound. For guidelines on reducing sound generation in the duct system, refer to the 1995 ASHRAE Applications Handbook, Chapter 43. Contact your local McQuay sales representative for equipment supply, return and radiated sound power data specific to your application. Ductwork A well-designed duct system is required to allow the rooftop equipment to provide rated performance and to minimize system resistance and sound generation. Duct connections to and from units should allow straight, smooth airflow transitions. Avoid any abrupt change in duct size and sharp turns in the fan discharge. Avoid turns opposed to wheel rotation as they will generate air turbulence and result in unwanted sound. If 90 turns are necessary, turning vanes should be used. Refer to the 1995 ASHRAE Applications Handbook, Chapter 43 for specific guidelines relevant to rooftop equipment. Return Duct The return path is the most often overlooked. A section of return duct is required to avoid a line of sight to the return air opening and to provide attenuation of return air sound. Install an insulated tee with a maximum duct velocity of 1000 to 1200 feet per minute. Extend the duct 15 feet to provide adequate attenuation. Supply Duct Insulate supply air ductwork for at least the first 20 feet from the unit. Consider the use of round or oval ductwork, as it will significantly reduce low frequency breakout noise near the equipment. If rectangular duct is used, keep the 24 Cat 214-5

aspect ratio of the duct as low as possible. The large flat surfaces associated with high aspect ratios will increase low frequency breakout to the space and can generate noise, such as oil canning. The maximum recommended supply duct velocity is 10 to 2000 feet per minute. Duct High Limit All McQuay RoofPak systems with VAV control include an adjustable duct high limit switch as a standard feature. This is of particular importance when fast acting, normally closed boxes are used. The switch is field adjustable and must be set to meet the specific rating of the system ductwork. Vibration Isolation Make duct attachments to the unit with a flexible connection. Economizer, Return Fan and Exhaust Fan Application Maintaining proper building pressure of approximately +0.05 to 0.1", or perhaps a neutral pressure in the winter, is very important: 1. Excessive space pressure can cause strong drafts when doors open, resulting in large fluctuations in the local zone pressure and poor zone temperature and supply air control. 2. Insufficient space pressure control can allow unconditioned air to infiltrate, resulting in poor perimeter temperature control, summer condensation in the walls, and excessive energy expenses. Powered return [RAF] or exhaust fans [EAFs] are often required to prevent excessively high building pressure on rooftop applications. This is illustrated in Figures 1 and 2. Figure 9: $ ) J5 ) K J A J Supply Air Fan Only System Static Pressures, Return duct ESP is 1.0" ' ) J5 ) 1 A J ) ' 1 4 BJ F -? E A H 5 A? JE - ) building pressure for the conditions listed in Figure 1assuming the wide open return damper APD is 0.2". Figure 10: Required Rooftop Unit Static Pressures, SAF Only, Return duct ESP is 1.0" ' ) J5 ) 1 A J $ ) J5 ) K J A J There are two reasons why building pressure or ventilation air control will suffer if no RAF or EAF is provided: 1. No exhaust will occur from the rooftop since the economizer section must be controlled to be at negative pressure. The building must naturally exhaust the minimum OA. This generally causes excessively positive building pressure. See Table 56 on page 67. 2. The air balancer must adjust the minimum OA dampers to bring in the right amount of OA, and also generate a relatively large OA damper APD of 1.1", in order to maintain the necessary economizer static pressure. This is not practical with conventional OA dampers: a. The required 1.1" pressure drop will only occur when the damper is virtually closed. b. Damper airflow is extremely volatile when the damper is virtually closed. Figure 11 illustrates how to add a RAF to Figure 10, obtain proper exhaust, and properly control design building pressure. The return fan always draws negative pressure at the unit's inlet to allow for the 1.0" return duct APD while maintaining a space pressure at the desired 0.1" ) J I F D A HE? 2 HA I I K HA ' 1 4 BJ F -? E A H 5 A? JE Figure 11: RAF System Pressures Allow proper Exhaust And Outdoor Air Control 4 ) ) J I F D A HE? 2 HA I I K HA # 5 K F F O - 5 2 1 JA H = 5 2?? K F EA @ 5 F =? A ) J 5 J= JE? 2 HA I I K HA 4 A JK H - 5 2 ' ) J5 ) 1 A J ) J4 ) K J A J ) J ) 1 A J Because air flows from higher to lower static pressure, if the space static pressure is 0.1", then the rooftop's economizer section static pressure must be -0.9" for the conditions listed in Figure 9. $ ) J5 ) K J A J ' ) J4 ) 1 A J Figure 10 details the static pressures that must exist in the mixing box of the rooftop unit in order to maintain proper EAF operation is quite different than RAF operation. First of all there are two modes of operation Cat 214-5 25

1. The EAF does not operate when the unit's economizer is at the minimum OA position, such as when the unit experiences design cooling capacity, or else operates at extremely light load. 2. An EAF only operates near full capacity during the economizer mode. Exhaust fans have trouble controlling building pressure and minimum OA in mode of operation #1, particularly when return ESP increases, as illustrated in Figures 1 and 2. Essentially, if the EAF is off, or barely operating, the system reacts like the previously discussed, SAF only system. 1. The unit's economizer section must be negative and no exhaust will occur if the fan is off. If the EAF is on, it will have difficulty exhausting the correct amount, because volume must generally be controlled between 5 and 15% of design airflow. 2. The OA dampers must generate a relatively large APD at minimum position in order to allow sufficient negative pressure in the unit's economizer section. Conventional minimum OA damper control is not accurate at these pressures. These problems diminish or disappear when return duct ESP is reduced to 0.4" as shown in Figure 12. 1. The unit's economizer section must only be slightly negative to allow proper building pressure. 2. The minimum OA damper APD need only be about 0.5" and conventional dampers generally provide satisfactory operation. 3. These problems are further reduced if an accurate minimum OA control damper, like McQuay's Design- Flow, is utilized. Figure 12: EAF system static pressures at 0.4" return ESP and minimum OA [EAF off]! ) J5 ) 1 A J $ ) J5 ) K J A J # ) J ) 1 A J ) J I F D A HE? 2 HA I I K HA! 1 4 BJ F -? E A H 5 A? JE! ) J- ) 1 A J The major advantage offered by EAFs is the opportunity to save energy. EAF systems often draw less energy than RAF systems, if equal fans are compared, for 2 reasons. 1. They operate at a relatively lighter load because properly controlled EAFs turn down in response to two criteria and RAFs turn down in response to just one. a. Both turn down equally in response to a reduction in SAF CFM on VAV systems. b. EAFs only operate at full CFM when the economizer is at 100% OA,and turn down as OA CFM drops, for both CV and VAV systems. 2. The SAF is generally operating at a more efficient point of operation [greater TSP] than either an EAF or RAF. Therefore turning off the EAF, and shifting return ESP to the SAF, generally takes less BHP than operating a system with a separate SAF and RAF. Conclusions are as follows: 1. A powered RAF or EAF is generally required to properly control building pressure and minimum OA intake whenever economizers are included on a rooftop unit unless provisions for remote exhaust are made. 2. Return fan and exhaust fan performance is not the same. Some applications are better suited for a return fan and others for an exhaust fan. a. Return fans are recommended when return duct ESP exceeds 0.8 due to their superior control on minimum outdoor air intake and building pressure. b. Exhaust fans are recommended when they save energy and when return duct ESP is less than 0.4. c. Either fan may be better suited when return duct ESP is between 0.4 and 0.8. However, they are not necessarily interchangeable in a given design. 3. RAFs are recommended when the return ESP exceeds 0.8", because of their superior control of minimum OA and building pressure, and because they are effective at any return duct APD. 4. EAFs are recommended whenever they save energy and return duct ESP is less than 0.4". 5. EAFs generally should not be used above 0.8" return ESP, therefore, propeller fans are utilized. Filters General Filters should be routinely replaced to minimize filter loading. As filters get dirty, the filter pressure drop increases, causing a decrease in airflow. Depending on fan type, forward curved or airfoil, this airflow change can be significant. The effect of filter loading is the most critical when using 65% and 95% efficient filters. When making a fan selection, a pressure drop component for filters as they get dirty should be included in the system total static pressure. A value midway between clean and dirty filter ratings is recommended. If a minimum airflow is critical, the fan selection should be made using the higher, dirty filter pressure drop value. Following these recommendations should limit airflow fluctuation as the filters load. Final Filters The application of final filters (filters downstream of the fan) places special requirements on unit selection. When final filters are employed, cooling coils must be located in the draw-through position so that the filters will not be in a saturated air stream. Also, final filters applications for a unit with gas heat requires the filters to be rated for 500 F. Instruct maintenance personnel to use properly rated replacement filters. 26 Cat 214-5

Variable Air Volume Application RoofPak units are available with variable inlet vanes or variable speed drives to provide variable air volume (VAV) control. Refer to Variable Air Volume on page 11 for further information on VAV systems. In placing a duct static pressure sensor, locate a pressure tap near the end of the main duct trunk. Adjust The static pressure setpoint so that at minimum airflow all of the terminals receive the minimum static pressure required plus any downstream resistance. Locate the static pressure sensor tap in the ductwork in an area free from turbulence effects and at least ten duct diameters downstream and several duct diameters upstream from any major interference, including branch takeoffs. A second sensor is available and should be used on installations having multiple duct trunks, multiple floors, or significantly varying zones (i.e., east/west). The MicroTech II controller will control the inlet vanes or variable speed drive to satisfy the supply duct requiring the most static pressure. On units with discharge air control, maximum compressor unloading and hot gas bypass is recommended. Fan Operating Range The acceptable system operating range of the McQuay rooftop is determined by all of the following characteristics. Each of these limiting factors must be considered for proper performance and component design life. 1. Unstable fan operation 2. Maximum fan rpm 3. Maximum cabinet static pressure 4. Maximum face velocity (cooling coil is not important) 5. Minimum furnace or electric heater velocity 6. Turndown capability on VAV applications 7. Compressor operating pressures Figure 13 illustrates these limiting factors with exception of items 6 and 7. The shaded area indicates the design operating range of the fan. For optimal efficiency, select fans as close to the fan s peak static efficiency line as possible. This line is the first system curve to the right of the unstable line illustrated. Figure 13: Fan Selection Boundary Fan Isolation All McQuay RoofPak systems feature internally isolated fans. All supply and return air fans are statically and dynamically balanced in the factory and mounted on rubber-in-shear (RIS) or 2 in. deflection spring isolators. Flexible isolation is provided as standard between the fan outlet and the discharge bulkhead to prevent hard contact and vibration transmission. Spring isolated fan assemblies are also available with seismic restraints. The choice of 2 in. deflection spring isolation or RIS isolation depends on an analysis of the roof structure and whether or not an isolation curb is being provided. When using an isolation curb, consult with the curb manufacturer before selecting spring isolation in the rooftop unit. Doubling or stacking spring isolation can cause a resonant vibration to be generated. Fan Heat Sensible heat gain from the supply and return fan, fan motor and drives occurs in all fan systems and must be considered in selecting rooftop equipment. It is an added load in cooling and an added source when in heating. Exhaust fan heat generally is not a cooling load or source of winter heat. The majority of the heat gain (95%) occurs through the fan itself, as the air is elevated from the lowpressure side to the high-pressure side of the fan. Moving the motor out of the air stream has a negligible effect on overall fan heat gain. A unit with higher fan power requirements/higher fan heat will have less net cooling capability and may not have enough left to satisfy system loads. As a rule of thumb, a typical supply fan heat gain is 3 F. However, fan heat gain can be quickly calculated once the fan has been selected and the fan brake horsepower has been determined. Using Figure 14, select your fan brake horsepower on the horizontal axis, move up vertically until you intersect with the heat gain curve and then move horizontally to find the fan heat gain in Mbh. Fan temperature rise = Fan Heat (Mbh)/(1.0 x Fan cfm) In addition to its effect on the sensible load of the system, where fan heat is introduced effects the sensible heat ratio capability of the rooftop system. Orientation of the fan and cooling coil determines if the heat gain is introduced as preheat or reheat. Figure 14: Fan and Motor Heat Gain Cat 214-5 27

Draw Through A draw through unit has the fan located after the DX cooling coil. In this arrangement, fan heat is applied as reheat to the cold, conditioned air coming off of the coil. This arrangement has a lower sensible heat ratio and higher dehumidification capability than a blow through coil arrangement. Draw through arrangements are well suited for 100% outside air applications and applications needing more dehumidification. A draw through arrangement is mandatory for all applications requiring final filters. The discharge temperature available to the supply duct is always the sum of the coil leaving air temperature plus the fan temperature rise. This must be considered when selecting the supply air volume required to satisfy space requirements. Example: 55 F leaving coil temp. + 3 F fan temp. rise = 58 F discharge air temp. All RFS and RPS units are available with a draw through configuration. Blow Through A blow-through unit has the fan located before the DX cooling coil. In this arrangement, fan heat is applied as preheat to the coil. Preheating the air lowers its relative humidity, giving this arrangement a high sensible heat ratio. Blow through arrangements are well suited for comfort conditioning applications where space heat gains are primarily sensible and the primary latent load is from ventilation air. The discharge temperature available to the supply duct is the coil leaving air temperature. All RFS and RPS036C - 135C units are available with a blow through configuration. Air Density Correction Fan Performance Fan performance data is based on standard 70 F air temperature and zero feet altitude (sea level). For applications other than standard, a density ratio must be multiplied to actual static pressure values. Density correction factors are expressed as a function of temperature and altitude in Table 5 on page 28. Table 5: Temperature and Altitude Conversion Factors Air Temp ( F) Altitude (Feet) 0 1000 2000 3000 4000 5000 6000 7000 00-20 1.20 1.16 1.12 1.08 1.04 1.00 0.97 0.93 0.89 0 1.15 1.10 1.08 1.02 0.99 0.95 0.92 0.88 0. 20 1.11 1.06 1.02.098 0.95 0.92 0.88 0. 0.82 40 1.06 1.02 0.98 0.94 0.91 0.88 0.84 0.81 0.78 60 1.02 0.98 0.94 0.91 0.88 0. 0.81 0.79 0.76 70 1.00 0.96 0.93 0.89 0.86 0.83 0. 0.77 0.74 0.98 0.94 0.91 0.88 0.84 0.81 0.78 0. 0.72 100 0.94 0.91 0.88 0.84 0.81 0.78 0. 0.72 0.70 120 0.92 0.88 0. 0.81 0.78 0.76 0.72 0.70 0.67 140 0.89 0. 0.82 0.79 0.76 0.73 0.70 0.78 0.65 Gas Heat Performance Gas heat performance data is based on standard 70 F air temperature and zero feet altitude (sea level). For applications other than standard, gas heat performance must be de-rated 4% for every 1,000 feet above sea level. System Operating Limits McQuay RoofPak systems are designed to operate over an extensive operating range, however, for proper system operation some limits do apply. To prevent moisture blow-off, design guidelines have been established for cooling coil selection. Based on laboratory testing, average coil face velocities should not exceed the following limits: 650 ft./min. for 8 & 10 fpi selections 600 ft./min. for selections For applications outside of these limits, consult your McQuay sales representative. Velocities exceeding these limits not only present the potential for moisture carry-over, but also high face velocities generate high air pressure drops, resulting in poor fan energy performance. In addition to maximum face velocity limitations, minimum velocity guidelines must also be followed. In order to maintain proper refrigeration performance, the minimum coil face velocity is 200 ft./min., regardless of coil fin spacing. When selecting a variable air volume unit, is necessary to design the system such that the 200 ft./min. limit is maintained at light load conditions. 28 Cat 214-5

Coil Freeze Protection When applying roof mounted equipment in geographic areas that experience subfreezing conditions, coil freeze protection measures must be provided. Subfreezing temperatures can adversely affect water and steam coils during controlled or uncontrolled unit shutdowns and even during unit operation. McQuay RoofPak economizer dampers are arranged to direct the outside and return air streams in multiple mixing patterns, minimizing air stratification. Even though this is one of the most effective mixing arrangements available, there may not always be a uniform unit temperature profile under all load and ambient temperatures. Some temperature stratification will occur, particularly at low ambient temperatures and the associated reduced airflow inherent with VAV systems. When required, static air mixers/blenders are available that can significantly improve mixing and reduce stratification. This can result in improved protection against freeze-up. Glycol is strongly recommended as a positive means of freeze protection for water coils. No control sequence can prevent coil freezing in the event of a power failure or equipment malfunction. During those periods, glycol is the only positive means of freeze protection. When selecting water coils, glycol should be specified to account for performance differences. An optional non-averaging freezestat equipment protection control can be provided, located downstream of the heating coil. If a potential freezing condition is sensed, a sequence is initiated by the unit control system, closing outdoor air dampers, opening the heating valve and deenergizing the fan. The freezestat setting should be some increment higher than freezing to provide an added margin of protection. The use of a freezestat control may cause nuisance trips. It cannot prevent freeze-up in the event of power failure or equipment malfunction. Freeze protection control strategies must be designed to keep unit cabinet temperatures from exceeding 150 F during a unit shutdown. Temperatures in excess of 150 F may exceed the design limits of motors, electrical components, gaskets, etc. potentially leading to premature failure of components. Piping and Condensate Drainage Always follow good industry practice in the design of the water piping system. Apply no undue stress at the connection to coil headers. In addition, piping should be supported independent from the coils with adequate piping flexibility for thermal expansion. Provide all drain pans with a properly sized p-trap to allow free drainage of coil condensate. Traps should be provided to prevent cabinet static pressure from leaking air at the drain line in blow-through coil applications. For draw through coil applications, a properly sized and installed trap is essential to allow for proper condensate drainage. An improper trap could cause condensate to build up in the drain pan and overflow into the unit. For trap sizing, follow instruction given in IM 4. All traps and drain lines should be run full size from the threaded unit connection to the roof drain. Units providing steam heat must be installed level to provide proper drainage and adequate steam pressure at steam valve and coil. Condensate must be properly trapped with vacuum breakers installed on the coil (See Figure 15). For steam piping recommendations, see McQuay Steam Coil Catalog 413. Figure 15: Drain Pan Traps Zone Sensor Placement Placement of the zone temperature sensor is critical for proper and economical operation of the heating and cooling system. It is generally recommended that the space sensor be located on an inside wall (3 to 5 feet from an outside wall) in a space having a floor area of at least 400 square feet. The sensor should not be located below the outlet of a supply diffuser, in the direct rays of the sun, on a wall adjacent to an unheated or abnormally warm room (boiler or incinerator room), or near any heat producing equipment. Where zone sensor placement is a problem, all zone control systems, as standard, have the capability to use a return air sensor for heating and cooling. Unit Wiring All units require three phase, 60 Hz, 208, 230, 460 or 5 volt power or three phase, 50 Hz, 400 volt power. Units will operate satisfactorily at ±10% of rated voltage, at the power connections to the units. All units include branch circuit fusing and are available with one or multiple power blocks or non-fused disconnect switches. Each unit is provided with a 115-volt convenience outlet circuit. Per the NEC, this circuit must be fed independent of the main unit power supply. All wiring must be installed in accordance with the National Electric Code (NEC) and local codes. Winter Shipment Flat bed shipment in winter can expose units to harsh road chemicals. Since equipment size and configuration precludes covering during transit, units should be washed free of these chemicals as soon as possible to prevent corrosion Cat 214-5 29

Unit Selection Achieving the optimal performance of a rooftop system requires both accurate system design and proper equipment selection. Factors which control the unit selection include applicable codes, ventilation and air filtration requirements, heating and cooling loads, acceptable temperature differentials, and installation limitations. McQuay RoofPak units offer a wide selection of component options providing the capability to meet diverse application requirements. The McQuay SelectTools software selection program allows your local McQuay sales representative to provide you with fast, accurate and complete selection of McQuay RoofPak units. Unit selection can also be accomplished through reference to physical, performance, dimensional and unit weight data included in this catalog. Due to the variety of cooling coil options available, only a sample of cooling capacity data has been presented in the catalog. Proper selection of unit equipment can be accomplished by following these three simple steps: 1. Select unit size and cooling coil 2. Select heating coils and equipment 3. Select fans and motors The following examples are provided to illustrate the equations and catalog references utilized in the unit selection process. Selection Example A constant volume system with DX cooling and natural gas heat. System design: Supply air volume 20,000 cfm Return air volume 16,000 cfm Minimum outside air volume 4,000 cfm Maximum face velocity 550 fpm Supply fan external SP 2.00 in. w.g. Return fan external SP. in. w.g. Altitude Sea level Economizer with return air fan 30% throwaway filters 460V/60Hz/3Ph Fully modulating heat Double wall construction Stainless steel drain pan Summer design: Space conditions F/50%Rh Space sensible load 435,000 Btu/hr Space total load 4,000 BTU/hr Space supply air temperature 55 F Ambient conditions 95 F/76 F Return sensible heat gain 2 F Est. Supply fan sensible heat rise 3 F Winter design: Return air temperature 70 F Ambient temperature 10 F Space heating load 450,000 Btu/hr Selection of Unit Size to Satisfy Summer Design Unit size is based on coil face area and cooling capacity requirements. Supply air capacity and maximum face velocity constraints should serve as a guide for selecting coil dimensions and cabinet size. Many model sizes are available with a standard and a high airflow coil selection. This flexibility prevents the need to increase cabinet size to accommodate high airflow per ton applications. Based on the given data, the appropriate coil face area may be determined as follows: Minimumfaceareasupplyairvolume/maximumfacevelocit = y =20,000 cfm/550 fpm =36.4 square feet Note: Unit data is based on standard air conditions of 70 F at sea level. Refer to Application Considerations on page 23 for temperature/altitude conversion factors for non-standard conditions. Referring to Physical Data on page 34, the 39.5 square foot, small face area coil of the RPS045C-0C units is found to satisfy the required face velocity. Plotting system conditions for a unit with a blow-through cooling coil on a Psychrometric Chart yields total summer cooling requirements (space + OA + return + supply fan) of: Mixed air temperature 81 F/66 F Coil entering air temperature 84 F/67 F (MAT+fan Τ) Supply fan volume 20,000 cfm Ambient air temperature 95 F Sensible cooling load 630,000 Btu/hr. Total cooling load 6,000 Btu/hr. Using the tables found in Cooling Capacity Data on page 38, the unit selection is an RPS060C with a small face area,, 12 fins/inch DX coil. Unit performance equals 8,000 Btu/hr Total, 636,000 Btu/hr Sensible. Supply air dry bulb = 84 F - 636Mbh/(1.0 x 20,000 cfm) = 55 F Once the initial unit selection has been made, the actual supply fan heat rise should be determined and the selection checked and verified for net capacity and supply air temperature. 30 Cat 214-5

Selection of Unit Heating System Heating equipment and coils can be specified directly from figures and tables incorporated in Heating Capacity Data on page 53. Calculating Total Heating Load Total heating load = space heating load + outdoor air load - supply fan heat. From the data given, the outdoor air load is 217 Mbh and supply fan heat is 65.1 MBH. Total heat load = 450 Mbh + 260 Mbh - 65 Mbh = 645 Mbh Gas Heat. When selecting a gas furnace, the system heating load, minimum airflow and maximum temperature rise constraints are needed. Refer to Figure 16 on page 53 for furnace model size selection. Enter the graph at 20,000 cfm and move up vertically to the intersection of 602 MBh output. In this example, the intersection of Minimum cfm and MBh Output occurs between model lines. Therefore, the larger model size, Model 640, should be selected for adequate heating. For all heat exchangers, there exist a maximum temperature rise. This limitation is determined by the heat exchanger surface area to airflow ratio. Refer to Table 40 on page 54 for verification of the temperature rise capability of the furnace selected. This table should also be used when specifying baffle position based on minimum airflow design. Note: In VAV applications, range of airflow modulation should be considered when selecting furnace model and baffle position. Hot Water Heat. Selection Example data along with other needed constraints shall be used to illustrate manual selection of unit hot water coils. The water temperature drop (t) is as follows: t Hot water capacity figures provided in Heating Capacity Data on page 53 are based on a standard initial temperature difference (ITD) of 140 F. The ITD value for the given example is determined as follows: ITD Hot water design: Entering water temperature Leaving water temperature 1 F 165 F = Ent. water temp. - Lvg. water temp. = 1-165 = 15 F = Ent. water temp. - Ent. air temp. = 1-70 = 110 F Therefore, the specified capacity (Q t ) must be adjusted to the cataloged base conditions as follows: t b = t x 140/ITD = 15 x 140/110 = 19.1 F Enter Figure 17 on page 58 at 20,000 cfm and 17.5 F water temperature drop. Read a capacity of 820 MBh and water flow rate of 95 gpm for a low capacity coil. Correct the capacity to 110 ITD as follows: Q t = Q b x ITD/140 = 820 x 110/140 = 645 MBh Since the corrected capacity meets design, the low capacity hot water coil for the unit is acceptable. At a water temperature drop of 15 F, the water flow rate required is 95 gpm. Enter Figure 26 on page 60 at 105 gpm and select a valve size that has a pressure drop greater than 11.5 feet of water. The valve pressure drop should be as large as possible to maintain proper valve modulation. The valve pressure drop should be at least 50% of the total water pressure drop. If more than one valve selection meets the requirement, the valve size decision should be made based on first cost versus pumping head. The total water pressure drop of the unit water coil is the sum of the coil, valve, and valve piping. The pressure drop of the hot water coil including header is found in Figure 25 on page 59 for the given water flow rate. Valve and valve piping pressure drops are illustrated in Figure 26 and Figure 27 on page 60. For the given example, the total water pressure drop is as follows: Unit water coil pressure drops: Low capacity coil, 045C-0C 7.5 ft. of water 1-1/2 in. valve 19.0 ft. of water 1-1/2 in. valve piping 10.0 ft. of water Total water pressure drop 36.5 ft. of water The pressure drop of the 1-1/2 in. valve is 52% of the total pressure drop and shall be acceptable. If a glycol solution is to be used in the water coil, adjust for glycol performance factors for coil and valve sizing or contact your McQuay sales representative. Steam Heat. Selection Example data shall be used along with other needed constraints to illustrate manual selection of unit steam coils. Steam design: Steam supply pressure With an % pressure drop across the valve, the steam coil pressure is determined as follows: Steam coil pressure = 10 - (10 x 0.) = 2 psig Enter Figure 28 on page 61 at 20,000 cfm and 70 F entering air temperature. Move up vertically to the 2 psig curve and read a capacity of 730 MBh for the low capacity coil. This heating capacity meets design; therefore, the low capacity steam coil for the unit is acceptable. Valve size can be determined from the condensation rate of steam for a given coil pressure. Table 48 and Table 49 on page 63 have been provided to allow for manual steam valve selection for systems with atmospheric return mains and supply main pressure not exceeding 25 psig at stated conditions. For the given example, the appropriate valve size may be found as follows: Condensation Rate 10 psig = Capacity/Latent heat of steam = 730,000 / 966.1 = 6 lbs./hr. Cat 214-5 31

Enter Table 49 on page 63, at 10 psig and 6 lbs./hr. The correct valve size is 1-1/2 in. Steam traps must be furnished and mounted in the field. Refer to Application Considerations on page 23 of this catalog or McQuay Steam Coil Catalog 413 for piping recommendations. Electric Heat. Referring to Electric Heat Capacity Table 47 on page 57 for the RPS060C, the design load of 645 Mbh falls between heater models 200 and 240. The Model 240 heater would be chosen to satisfy the design conditions. Selection of Fans and Motors Fan and motor selections are based on total static pressure drop and design airflow. Total static pressure includes internal air pressure drops of unit components and external air pressure drops in supply and return ducts. Refer to Component Pressure Drops on page 64 for internal pressure drops of unit components. Fan curves provided in Fan Performance Data - Supply Fans on page 68 and Fan Performance Data - Propeller Exhaust Fans on page 79 should be used when selecting unit fans and motors. To optimize fan performance, select the fan size having design airflow and static pressure intersecting as close to the first system curve after the shaded Do Not Select region as possible. Refer to Application Considerations on page 23 and Figure 8 on page 24 for illustration. When selecting motor size, the motor should be selected as close below the horsepower curve as possible to prevent motor oversizing. An oversized motor (large horsepower to load ratio) can greatly increase electric consumption due to the reduction in motor performance. Return Fan and Motor An economizer with a return fan must be selected for the given system. A return (or exhaust fan) system is often necessary for maintaining proper pressure in a building. Refer to Application Considerations on page 23 for further discussion on economizer, exhaust fan and return fan application. The external air pressure drop of the return duct along with the design return airflow are used to select a return fan. Based on Figure 64 on page 82, the optimal return fan size is 40 in. The required fan motor size is 5.0 hp. Exhaust Fan and Motor Exhaust fans must be sized for maximum exhaust CFM and return duct ESP at those conditions. See Fan Performance Data - Propeller Exhaust Fans on page 79 for more information. Supply Fan and Motor Since this system includes a return fan, the return duct static pressure drop is not added to the supply fan pressure drop. Therefore, the total static pressure for the supply fan in the Example is as follows: Internal pressure drops: 0-100% economizer, with RAF 0.33 in. w.g. 30% angular filters 0.14 in. w.g. Gas furnace Evaporative coil (small 5-row, ) Total internal pressure drop External pressure drops: Supply duct Total external pressure drop Total static pressure Note: When gas or electric heat is provided, do not add the cooling coil diffuser pressure drop. In VAV applications with gas heat, consult your McQuay sales representative for design pressure drop determinations. For a constant volume system a forward curve or airfoil type fan can be selected. Reference Application Considerations on page 23 for discussion on acoustical consideration. Considering its favorable brake horsepower, an airfoil type fan will be selected. Entering the standard 30 in. airfoil fan curve (see Figure 47 on page 73) at 20,000 cfm and 3.48 in. w.g., the required fan motor size is 20 hp operating at 1230 rpm. Fan brake horsepower is 16.2 horsepower. Supply Power Wiring Units Without Electric Heat Sizing supply power wire for a unit is based on the circuit with the largest amperage draw. All electrical equipment is wired to a central panel for single or optional multipower connections. Refer to Electrical Data on page 102 for FLA and RLA ratings of equipment. Determination of Minimum Circuit Ampacity (MCA) is as follows: Fans and Cooling: Therefore, 0.20 in. w.g. 0.81 in. w.g. 1.48 in. w.g. 2.00 in. w.g. 2.00 in. w.g. = internal drops + external drops = 1.48 + 2.00 = 3.48 in. w.g. MCA = 1.25 x RLA or FLA of largest motor + 1.00 x FLA of other loads Example Compressor 1, 15 hp Compressor 2, 3, and 4 15 hp ea Condenser fan motors, (6) 1 hp Supply fan motor, 20 hp Return fan motor, 5 hp Select power supply wire based on 146 amperes. FLA/RLA 24 amps 24 amps ea 2 amps ea 25 amps 6.7 amps MCA = 1.25 x 25 + 1.00 x [(4)24 + (6)2 + 6.7] = 146 amps 32 Cat 214-5

Supply Power Wiring for Units with Electric Heat When selecting units with nonconcurring electric heat, MCA must be calculated for both the cooling mode and the heating mode, and then the greater of the two used. For heating: MCA= 1.25 [FLA of electric heater + FLA of all other loads] = 1.25 x [287.2 + 25 + 6.7] = 399 amps For cooling: MCA = 146 amps. The controlling load is when in the electric heat mode. Unit MCA = 399 amps. Calculating Unit Length Referring to unit Dimensional Data on page 84 for a blow-through RPS060C, Figure 73 on page 86: Note: Note: = 72 in. + 24 in. + 72 in. + 48 in. + 24 in. + 48 in. + 83 in. = 371 inches. When selecting unit curb length, do not include the length of the condensing unit. Calculating Unit Weight Referring to unit Unit Weights on page 109 for a RPS060C, Table 71 on page 110: Total unit weight= RPS basic unit + economizer + 30% filters + 30 AF SAF + 40 AF RAF + 5 row, Al. fin small face area coil + 640 mbh gas furnace + SAF motor + RAF motor + cabinet liners = 6915 + 1065 + 4 + 965 + 629 + 600 + 428 + 266 + 82 + (25 x 288/12) = 11,554 lbs. Total unit length = economizer w/raf + angular filter + fan section + heat section + DX coil section + discharge plenum + condensing unit Cat 214-5 33

Physical Data Table 6: Physical Data RPS015C-040C Data Nominal Capacity (tons) a Unit Size 015C 018C 020C 025C 030C 036C 040C 16.3 19.8 24.2 29.4 32.1 38.4 44.8 Nominal Airflow (cfm) 6000 7000 00 10000 12000 14000 16000 Compressor Condenser Coil (aluminum fins) Type Scroll Quantity - hp 1-6.7, 1-10 1-6.7, 1-15 2-6.7, 1-13 2-6.7, 1-15 2-6.7, 2-10 4-10 Std. capacity control 100-60-40-0 100-69-31-0 100--50-25-0 100--50-25-0 100-70-50-20-0 100--50-25-0 Rows/FPI 2/16 2/16 2/16 3/16 3/16 2/16 2/16 Face area (sq. ft.) 36.8 36.8 36.8 36.8 36.8 76.2 76.2 No. - Dia. (In.) 2-26 2-26 2-26 3-26 3-26 4-26 4-26 Condenser Fans Std. airflow (cfm) 14552 14552 14552 16047 16047 29376 29376 Cond. Fan Motors No. - Hp 2-1.0 2-1.0 2-1.0 3-1.0 3-1.0 4-1.0 4-1.0 Supply Fans Return Fans Evaporator Coils Hot Water Coils Steam Coils Gas Furnace b Electric Heat c Panel Filters Prefilters (for Cartridge Filters) Cartridge Filters Type Forward Curved LP Forward Curved LP/MP No. - Dia. (In.) 2-15x6 2-15x6 2-15x6 2-15x6 2-15x6 1-24 1-24 No. - Dia. (In.) 2-15x15 2-15x15 2-15x15 2-15x15 2-15x15 - - Airflow Range (cfm) 4000-12000 4000-12000 4000-12000 5400-16000 5400-16000 5400-150 5400-150 Motor hp range 1-20 1-20 1-20 1-20 1-20 1-25 1-25 Type DWDI Airfoil, With or Without Variable Inlet Vanes No. - Dia. (In.) 1-20 1-20 1-20 1-20 1-20 1-24 1-24 Airflow Range (cfm) 4000-10000 4000-12000 4000-12000 5400-16000 5400-16000 5400-150 5400-150 Motor hp range 1-20 1-20 1-20 1-20 1-20 1-25 1-25 Type Forward Curved Diameter (in.) 2-15x15 2-15x15 2-15x15 2-15x15 2-15x15 - - Airflow Range (cfm) 4000-10000 4000-12000 4000-12000 5400-16000 5400-16000 - - Motor hp range 1-10 1-10 1-10 1-10 1-10 - - Type SWSI Airfoil, With or Without Variable Inlet Vanes No. - Dia. (In.) 1-30 1-30 1-30 1-30 1-30 1-30, 1-40 1-30, 1-40 Airflow Range (cfm) 4000-10000 4000-12000 4000-12000 5400-16000 5400-16000 5400-150 5400-150 Motor hp range 1-10 1-10 1-10 1-10 1-10 1-10 1-10 Rows 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 FPI 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 F.A., small (sq. ft.) 18.5 18.5 18.5 27.0 27.0 27.0 27.0 Type - Rows 5WH-1 5WH-1 5WH-1 5WH-1 5WH-1 5WH-1 5WH-1 Type - Rows 5WS-2 5WS-2 5WS-2 5WS-2 5WS-2 5WS-2 5WS-2 FPI 9 9 9 9 9 9 9 Face area (sq. ft.) 20.3 20.3 20.3 20.3 20.3 20.3 20.3 Type - Rows 5JA-1 5JA-1 5JA-1 5JA-1 5JA-1 5JA-1 5JA-1 FPI 6, 12 6, 12 6, 12 6, 12 6, 12 6, 12 6, 12 Face area (sq. ft.) 20.3 20.3 20.3 20.3 20.3 20.3 20.3 Input (MBh) 250, 312, 400, 500, 625, 0, 812, 988, 1000, 1250 Nom. Output (MBh) 200, 250, 320, 400, 500, 640, 650, 790, 0, 1000 Nom. Output (kw) 20, 40, 60,, 100, 120, 140, 160, 1, 200, 220, 240 Type 30% Pleated Area (sq. ft.) 50.0 50.0 50.0 50.0 50.0 50.0 50.0 No. - size (in.) 10-16x20x2 10-16x25x2 10-16x20x2 10-16x25x2 10-16x20x2 10-16x25x2 10-16x20x2 10-16x25x2 10-16x20x2 10-16x25x2 10-16x20x2 10-16x25x2 a. Rated in accordance with ARI Standard 360 b. Gas furnace size availability is limited by minimum airflow, See Table 40: Gas Furnace Design Maximum Air Temperature Rise ( F) and Minimum Air Flow on page 54 c. Electric heat availability is limited by minimum airflow, See Table 42 through Table 44. 10-16x20x2 10-16x25x2 Type Prefilter, Standard Flow Area (sq. ft.) 24.0 24.0 24.0 24.0 24.0 24.0 24.0 No. - size (in.) 4-24x24x2 4-12x24x2 4-24x24x2 4-12x24x2 4-24x24x2 4-12x24x2 4-24x24x2 4-12x24x2 4-24x24x2 4-12x24x2 4-24x24x2 4-12x24x2 4-24x24x2 4-12x24x2 Type 65% or 95%, Standard Flow Area (sq. ft.) 24.0 24.0 24.0 24.0 24.0 24.0 24.0 No. - size (in.) 4-24x24x12 4-12x24x12 4-24x24x12 4-12x24x12 4-24x24x12 4-12x24x12 4-24x24x12 4-12x24x12 4-24x24x12 4-12x24x12 4-24x24x12 4-12x24x12 4-24x24x12 4-12x24x12 34 Cat 214-5

Table 7: Physical Data, RPS045C-0C Data Unit Size 045C 050C 060C 070 Scroll 070 Recip Nominal Capacity (tons) a 46.1 55.1 65.9 73.0 77.2 Nominal Airflow (cfm) 16000 20000 24000 200 200 Compressor Condenser Coil (aluminum fins) Type Scroll Reciprocating Quantity - hp 4-10 4-13 4-15 6-10 2-35 Std. capacity control 100--50-25-0 100-83-67-33-0 Opt. capacity control - - - 100-83-67-50-33-16-0 Rows/FPI 2/16 2/16 2/16 2/16 2/16 Face area (sq. ft.) 78.0 78.0 78.0 117.0 117.0 No. - Dia. (In.) 4-26 4-26 6-26 6-26 6-26 Condenser Fans Std. airflow (cfm) 29558 29558 38624 400 400 Condenser Fan Motors No. - Hp 4-1.0 4-1.0 6-1.0 6-1.0 6-1.0 Supply Fans Return Fans Exhaust Fans Evaporator Coils Hot Water Coils Type Forward Curve, LP/MP No. - Dia. (In.) 1-27,30 1-27,30 1-30, 33 1-30, 33 1-30, 33 Airflow Range (cfm) 00-24000 00-30000 00-30000 00-30000 00-30000 Motor hp range 3-50 3-50 3-50 3-50 3-50 Type DWDI Airfoil, With or Without Variable Inlet Vanes No. - Dia. (In.) 1-27,30 1-27,30 1-30, 33 1-30, 33 1-30, 33 Airflow Range (cfm) 00-24000 00-30000 00-30000 00-30000 00-30000 Motor hp range 3-50 3-50 3-50 3-50 3-50 Type SWSI Airfoil, With or Without Variable Inlet Vanes No. - Dia. (In.) 1-40 1-40 1-40 1-40 1-40 Airflow Range (cfm) 00-24000 00-30000 00-30000 00-30000 00-30000 Motor hp range 2-30 2-30 2-30 2-30 2-30 Type Propeller Diameter (In.) 36 36 36 36 36 Quantity 1 or 2 per unit 1 or 2 per unit 1 or 2 per unit 1 or 2 per unit 1 or 2 per unit Motor hp 5 each 5 each 5 each 5 each 5 each Airflow Range (cfm) 11000-20000 each (within cabinet limitations) Rows 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 FPI 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 F.A., small (sq. ft.) 39.5 39.5 39.5 39.5 39.5 F.A., large (sq. ft.) - 47.1 47.1 47.1 47.1 Type - Rows 5WH-1 5WH-1 5WH-1 5WH-1 5WH-1 Type - Rows 5WS-2 5WS-2 5WS-2 5WS-2 5WS-2 FPI 9 9 9 9 9 Face area (sq. ft.) 29.7 29.7 29.7 29.7 29.7 Type - Rows 5JA-1, 2 5JA-1, 2 5JA-1, 2 5JA-1, 2 5JA-1, 2 Steam Coils FPI 6, 12 6, 12 6, 12 6, 12 6, 12 Face area (sq. ft.) 29.7 29.7 29.7 29.7 29.7 Gas Furnace b Input (MBh) 250, 312, 400, 500, 625, 0, 812, 988, 1000, 1250 Nom. Output (MBh) 200, 250, 320, 400, 500, 640, 650, 790, 0, 1000 Electric Heat c Nom. Output (kw) 40, 60,, 100, 120, 160, 200, 240 Panel Filters Prefilters (for Cartridge Filters) Type 30% Pleated Area (sq. ft.) 73.9 73.9 73.9 73.9 73.9 No. - size (in.) 7-16x20x2 21-16x25x2 7-16x20x2 21-16x25x2 7-16x20x2 21-16x25x2 7-16x20x2 21-16x25x2 7-16x20x2 21-16x25x2 Type Prefilter, Standard Flow Area (sq. ft.) 40.0 40.0 40.0 40.0 40.0 No. - size (in.) 4-12x24x2 8-24x24x2 4-12x24x2 8-24x24x2 4-12x24x2 8-24x24x2 Prefilter, Medium Flow 4-12x24x2 8-24x24x2 4-12x24x2 8-24x24x2 Type Area (sq. ft.) 48.0 48.0 48.0 48.0 48.0 No. - size (in.) 8-12x24x2 8-24x24x2 8-12x24x2 8-24x24x2 8-12x24x2 8-24x24x2 8-12x24x2 8-24x24x2 8-12x24x2 8-24x24x2 Cat 214-5 35

Table 7: Physical Data, RPS045C-0C Cartridge Filters Data Type 65% or 95%, Standard Flow Area (sq. ft.) 40.0 40.0 40.0 40.0 40.0 No. - size (in.) 4-12x24x12 8-24x24x12 4-12x24x12 8-24x24x12 4-12x24x12 8-24x24x12 4-12x24x12 8-24x24x12 4-12x24x12 8-24x24x12 Type 65% or 95%, Medium Flow Area (sq. ft.) 48.0 48.0 48.0 40.0 40.0 No. - size (in.) 8-12x24x12 8-24x24x12 8-12x24x12 8-24x24x12 Unit Size 045C 050C 060C 070 Scroll 070 Recip 8-12x24x12 8-24x24x12 4-12x24x12 8-24x24x12 4-12x24x12 8-24x24x12 a. Rated in accordance with ARI Standard 360 b. Gas furnace size availability is limited by minimum airflow, See Table 40: Gas Furnace Design Maximum Air Temperature Rise ( F) and Minimum Air Flow on page 54 c. Electric heat availability is limited by minimum airflow, See Table 42 through Table 44. Table 8: Physical Data, RPS0C-135C Data Unit Size 0S 0R 0C 090C 105C 115C 125C 135C Nominal Capacity (tons) a 82.0 84.7 82.1 91.3 106.3 120.7 132.8 143.6 Nominal Airflow (cfm) 30000 30000 32000 36000 40000 46000 400 50000 Compressor Condenser Coil (aluminum fins) Condenser Fans Condenser Fan Motors Supply Fans Return Fans Exhaust Fans Evaporator Coils Type Reciprocating Quantity - hp 6-13 2-40 2-35 2-40 4-25 4-30 2-30, 2-35 4-35 Std. capacity control Opt. capacity control 100-83-67-33-0 100--50-25-0 100-83-67-50-33-16-0 100-88--63-50-38-25-12-0 100-72-44-22- 0 100-89-79-61- 44-32-22-11-0 100--50-25- 0 100-92-83-67- 50-42-33-16-0 Rows/FPI 2/16 2/16 2/16 2/16 2/16 2/16 2/16 2/16 Face area (sq. ft.) 117.0 117.0 117.0 135.0 135.0 181.3 181.3 181.3 No. - Dia. (In.) 8-26 8-26 8-26 8-26 9-26 10-26 12-26 12-26 St. airflow (cfm) 59100 59100 59100 62000 66900 79100 90000 90000 No. - Hp 8-1.0 8-1.0 8-1.0 8-1.0 9-1.0 10-1.0 12-1.0 12-1.0 Type Forward Curved, LP/MP No. - Dia. (In.) 1-30,33 1-30,33 1-33, 36 1-33, 36 1-36, 40 1-36, 40 1-36, 40 1-36, 40 Airflow Range (cfm) 00-30000 00-30000 11000-39520 11000-39520 12200-49400 12200-49400 15200-49400 15200-49400 Motor hp range 3-50 3-50 5-5- 5-5- 5-5- Type DWDI Airfoil, With or Without Variable Inlet Vanes No. - Dia. (In.) 1-30, 33 1-30, 33 1-33, 36 1-33, 36 1-36, 40 1-36, 40 1-36, 40 1-36, 40 Airflow Range (cfm) 00-30000 00-30000 11000-39520 11000-39520 12200-49400 12200-49400 15200-49400 15200-49400 Motor hp range 3-50 3-50 5-5- 5-5- 5-5- Type SWSI Airfoil, With or Without Variable Inlet Vanes No. - Dia. (In.) 1-40 1-40 1-44.5 1-44.5 1-44.5 1-44.5 1-44.5 1-44.5 Airflow Range (cfm) 00-30000 00-30000 11000-39520 11000-39520 12200-49400 12200-49400 15200-49400 15200-49400 Motor hp range 2-30 2-30 5-60 5-60 5-60 5-60 5-60 5-60 Type Propeller Diameter (In.) 36 36 36 36 36 36 36 36 Quantity 1-2 per unit 1-2 per unit 1-3 per unit 1-3 per unit 1-3 per unit 1-3 per unit 1-3 per unit 1-3 per unit Motor hp 5 each 5 each 5 each 5 each 5 each 5 each 5 each 5 each Airflow range (cfm) 11000-20000 each (within cabinet limitations) Rows 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 3, 4, 5 FPI 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 12 8, 10, 1253.9 F.A., small (sq. ft.) 39.5 39.5 53.9 53.9 60.8 - - - F.A., large (sq. ft.) 47.1 47.1 60.8 60.8 76.0 76.0 76.0 76.0 36 Cat 214-5

Table 8: Physical Data, RPS0C-135C Hot Water Coils Steam Coils Gas Furnace b Electric Heat c Panel Filters Data Prefilters (for Cartridge Filters) Cartridge Filters Type - Rows 5WH-1 5WH-1 5WH-1 5WH-1 5WH-1 5WH-1 5WH-1 5WH-1 Type - Rows 5WS-2 5WS-2 5WS-2 5WS-2 5WS-2 5WS-2 5WS-2 5WS-2 FPI 9 9 9 9 9 9 9 9 Face area (sq. ft.) 29.7 29.7 42.2 42.2 42.2 42.2 42.2 42.2 Type - Rows 5JA-1, 2 5JA-1, 2 5JA-1, 2 5JA-1, 2 5JA-1, 2 5JA-1, 2 5JA-1, 2 5JA-1, 2 FPI 6, 12 6, 12 6, 12 6, 12 6, 12 6, 12 6, 12 6, 12 Face area (sq. ft.) 29.7 29.7 42.2 42.2 42.2 42.2 42.2 42.2 250, 312, 400, Input (MBh) 500, 625, 0, 812, 988, 625, 0, 812, 988, 1000, 1250, 13, 10, 18, 2500 1000, 1250 Nom. Output (MBh) Nom. Output (kw) 200, 250, 320, 400, 500, 640, 650, 790, 0, 1000 40, 60,, 100, 120, 160, 200, 240 500, 640, 650, 790, 0, 1000, 1100, 1400, 1500, 2000, 100, 120, 160, 200, 240, 2, 320 Type 30% Pleated Area (sq. ft.) 73.9 73.9 116.1 116.1 116.1 116.1 116.1 116.1 No. - size (in.) 7-16x20x2 7-16x20x2 11-16x20x2 11-16x20x2 11-16x20x2 11-16x20x2 11-16x20x2 11-16x20x2 21-16x25x2 21-16x25x2 33-16x25x2 33-16x25x2 33-16x25x2 33-16x25x2 33-16x25x2 33-16x25x2 Type Prefilter, Standard Flow Prefilter, Medium Flow Area (sq. ft.) 56.0 56.0 64.0 64.0 64.0 64.0 No. - size (in.) 4-12x24x2 8-24x24x2 4-12x24x2 8-24x24x2 4-12x24x2 12-24x24x2 4-12x24x2 12-24x24x2 16-24x24x2 16-24x24x2 16-24x24x2 16-24x24x2 Type Prefilter, Medium Flow Prefilter, High Flow Area (sq. ft.) 64.0 64.0.0.0.0.0 No. - size (in.) 8-12x24x2 8-24x24x2 8-12x24x2 8-24x24x2 16-24x24x2 16-24x24x2 8-12x24x2 16-24x24x2 8-12x24x2 16-24x24x2 8-12x24x2 16-24x24x2 8-12x24x2 16-24x24x2 Type 65% or 95% Standard Flow 65% or 95% Medium Flow Area (sq. ft.) 56.0 56.0 64.0 64.0 64.0 64.0 No. - size (in.) 4-12x24x12 8-24x24x12 4-12x24x12 8-24x24x12 4-12x24x12 12-24x24x12 4-12x24x12 12-24x24x12 16-24x24x12 16-24x24x12 16-24x24x12 16-24x24x12 Type 65% or 95% Medium Flow 65% or 95% High Flow Area (sq. ft.) 40.0 40.0 64.0 64.0.0.0.0.0 No. - size (in.) Unit Size 0S 0R 0C 090C 105C 115C 125C 135C 4-12x24x12 8-24x24x12 4-12x24x12 8-24x24x12 16-24x24x12 16-24x24x12 8-12x24x12 16-24x24x12 8-12x24x12 16-24x24x12 8-12x24x12 16-24x24x12 a. Rated in accordance with ARI Standard 360 b. Gas furnace size availability is limited by minimum airflow, See Table 40: Gas Furnace Design Maximum Air Temperature Rise ( F) and Minimum Air Flow on page 54 c. Electric heat availability is limited by minimum airflow, See Table 42 through Table 44. 8-12x24x12 16-24x24x12 Cat 214-5 37

Cooling Capacity Data Table 9: RPS015C Low Airflow Coil Unit Data 5000 cfm 6000 cfm 7000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 184 136 11.3 178 134 124 171 63 13.8 67 197 113 11.5 190 110 12.6 18.3 107 14.0 71 212 90 11.8 204 87 12.9 63 1 164 11.3 178 161 12.4 171 158 13.8 67 198 141 11.5 191 138 12.6 183 135 14.0 71 212 117 11.7 204 114 11.9 63 189 189 11.4 183 183 12.5 178 178 13.9 67 198 169 11.5 191 166 12.7 184 163 14.0 71 212 145 11.8 204 142 12.9 63 190 150 11.4 183 147 12.5 1 144 13.8 67 203 122 11.6 196 120 12.7 188 116 14.0 71 63 191 183 11.4 1 181 12.6 178 177 13.9 67 203 155 11.6 196 153 12.8 188 150 14.1 71 63 201 201 11.6 195 195 12.7 188 188 14.1 67 205 189 11.7 197 186 12.8 140 183 14.1 71 63 194 164 11.4 187 161 12.6 179 158 13.9 67 207 131 11.7 200 128 12.8 191 125 14.1 71 63 198 198 11.5 192 192 12.7 1 1 14.0 67 207 170 11.7 200 167 12.8 192 16.4 14.1 71 63 210 210 11.7 203 203 12.8 67 210 208 11.8 204 204 12.9 71 Table 10: RPS018C Low Airflow Coil Unit Data 6000 cfm 7000 cfm 00 cfm Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a Table 7 continues on the next page. a. Compressor kw 63 226 166 14.8 217 162 16.4 208 158 18.2 67 242 138 15.2 233 134 16.7 223 130 18.6 71 259 110 15.5 249 106 17.1 239 102 18.9 63 227 199 14.9 218 196 16.4 209 192 18.2 67 242 171 15.2 233 168 16.7 223 164 18.6 71 259 143 15.5 249 139 17.1 239 135 18.9 63 231 228 14.9 224 222 16.5 216 216 18.4 67 242 204 15.2 233 201 16.8 224 197 18.6 71 259 176 15.5 249 172 17.1 239 169 18.9 63 232 1 15 223 176 16.5 213 172 18.3 67 248 147 15.3 238 143 16.9 228 140 18.7 71 264 114 15.7 254 111 17.2 243 107 19 63 233 218 15 225 215 16.6 216 210 18.4 67 248 186 15.3 238 182 16.9 228 178 18.7 71 264 153 15.7 254 149 17.2 243 145 19 63 242 242 15.2 234 234 16.8 226 226 18.6 67 249 225 15.3 240 221 16.9 230 217 18.7 71 265 191 15.7 254 188 17.2 244 184 19 63 236 193 15.1 227 189 16.6 217 1 18.4 67 252 156 15.4 242 152 17 232 148 18.8 71 269 119 15.8 258 115 17.3 63 240 234 15.1 232 228 16.7 223 221 18.5 67 252 200 15.4 243 196 17 232 193 18.8 71 269 163 15.8 258 159 17.3 63 252 252 15.4 244 244 17 235 235 18.8 67 255 244 15.4 246 239 17 236 232 18.9 71 269 207 15.8 259 203 17.3 38 Cat 214-5

Table 11: RPS020C Low Airflow Coil Unit Data 6000 cfm 00 cfm 10000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 268 1 19.6 257 1 21.9 246 1 24.5 67 287 157 20 276 152 22.3 264 147 24.9 71 308 128 20.4 296 124 22.7 283 119 25.3 63 268 218 19.6 258 213 21.9 247 208 24.5 67 287 190 20 276 1 22.3 264 1 24.9 71 308 161 20.4 296 157 22.7 283 152 25.3 63 269 252 19.6 259 247 21.9 248 242 24.5 67 287 223 20 276 219 22.3 265 214 24.9 71 307 194 20.4 296 190 22.7 283 1 25.3 63 283 213 19.9 271 208 22.2 259 203 24.8 67 302 176 20.3 290 171 22.6 277 166 25.2 71 323 138 20.7 310 133 23 63 284 257 19.9 272 252 22.2 260 247 24.8 67 303 220 20.3 290 215 22.6 277 210 25.2 71 323 182 20.7 310 177 23 63 291 291 20.1 281 281 22.4 271 271 25.1 67 303 264 20.3 291 259 22.6 278 254 25.2 71 323 226 20.7 310 221 23 63 292 239 20.1 2 234 22.4 267 229 24.9 67 311 193 20.5 298 188 22.8 2 183 25.4 71 63 296 290 20.2 284 283 22.5 273 273 25.1 67 312 248 20.5 299 243 22.8 2 238 25.4 71 63 311 311 20.5 301 301 22.8 289 289 25.5 67 314 301 20.5 302 295 22.9 290 287 25.5 71 Table 12: RPS025C Low Airflow Coil Unit Data 00 cfm 10000 cfm 12000 cfm Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a a. Compressor kw Table 8 continues on the next page. 63 330 234 23.3 318 229 26 303 222 29 67 354 197 23.8 340 191 26.5 325 1 29.6 71 379 159 24.3 364 153 27 348 147 30.2 63 331 279 23.3 318 273 26 304 267 29.1 67 354 241 23.8 340 235 26.5 325 229 29.6 71 379 203 24.3 364 197 27 348 191 30.2 63 333 323 23.3 321 317 26 308 308 29.2 67 354 2 23.8 340 2 26.5 326 274 29.6 71 379 247 24.3 364 242 27 348 236 30.2 63 344 262 23.6 330 256 26.2 315 250 29.3 67 367 215 24.1 352 210 26.8 336 203 29.9 71 392 168 24.6 377 163 27.3 63 345 318 23.6 332 312 26.3 317 305 29.4 67 367 271 24.1 353 265 26.8 337 259 29.9 71 393 224 24.6 377 218 27.3 63 356 356 23.8 345 345 26.6 332 332 29.8 67 369 326 24.1 354 320 26.8 338 314 29.9 71 393 279 24.6 377 273 27.3 63 352 289 23.8 338 283 26.4 323 276 29.5 67 376 233 24.3 360 227 27 344 221 30.1 71 63 357 353 23.8 344 343 26.6 330 330 29.7 67 377 299 24.3 361 294 27 345 287 30.1 71 63 377 377 24.3 364 364 27 350 350 30.2 67 3 365 24.3 365 358 27.1 350 349 30.2 71 Cat 214-5 39

Table 13: RPS030C Low Airflow Coil Unit Data 10000 cfm 12000 cfm 14000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 366 272 26.1 351 266 29.1 335 259 32.6 67 391 225 26.7 3 219 29.7 358 212 33.2 71 418 178 27.2 401 171 30.3 63 367 327 26.1 352 321 29.2 336 314 32.6 67 391 2 26.6 3 274 29.7 358 267 33.2 71 418 233 27.2 401 227 30.3 63 374 374 26.3 362 362 29.4 349 349 33 67 392 336 26.7 376 329 29.7 359 322 33.2 71 418 288 27.2 401 282 30.3 63 376 299 26.3 360 292 29.4 344 2 32.8 67 401 243 26.9 384 236 29.9 366 230 33.4 71 63 379 364 26.4 364 357 29.4 349 347 32.9 67 402 309 26.9 3 303 29.9 367 296 33.4 71 63 397 397 26.8 383 383 29.9 368 368 33.5 67 404 3 26.9 388 368 30 370 360 33.5 71 63 384 325 26.5 367 318 29.5 350 311 33 67 409 261 27 391 254 30.1 373 247 33.6 71 63 392 391 26.7 377 377 29.8 362 362 33.3 67 410 337 27.1 392 331 30.1 374 324 33.6 71 63 414 414 27.2 399 399 30.3 67 415 409 27.2 399 398 30.3 71 Table 14: RPS036C Low Airflow Coil Unit Data 12000 cfm 14000 cfm 16000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 437 325 28.9 420 318 32.3 403 310 36.1 67 468 270 29.4 450 262 32.8 431 255 36.6 71 502 213 30 63 439 392 29 423 384 32.3 405 376 36.1 67 469 336 29.4 451 329 32.8 431 321 36.6 71 502 2 30 482 272 33.4 63 450 443 29.1 434 432 32.5 418 418 36.3 67 470 402 29.5 452 395 32.8 433 387 36.6 71 502 346 30 63 448 352 29.1 431 345 32.5 412 337 36.3 67 4 288 29.6 461 281 33 440 273 36.8 71 63 453 426 29.2 437 415 32.5 419 403 36.4 67 4 365 29.6 461 357 33 441 350 36.8 71 63 470 470 29.4 455 455 32.9 439 439 36.7 67 484 440 29.7 465 432 33 446 421 36.9 71 63 457 378 29.2 439 370 32.6 420 362 36.4 67 488 305 29.7 468 298 33.1 447 290 36.9 71 63 466 451 29.4 448 439 32.8 431 427 36.6 67 489 393 29.8 470 3 33.1 449 377 36.9 71 63 488 488 29.8 67 496 470 29.9 71 40 Cat 214-5

Table 15: RPS040C Low Airflow Coil Unit Data 12000 cfm 14000 cfm 16000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 498 352 36.1 479 344 40.4 458 334 45.2 67 535 296 36.7 514 288 41 491 279 45.9 71 573 240 37.3 551 231 41.7 527 222 46.6 63 500 419 36.1 4 410 40.4 459 401 45.2 67 535 363 36.6 514 354 41 491 345 45.9 71 573 306 37.3 550 297 41.7 526 288 46.6 63 502 4 36.1 484 4 40.5 465 463 45.3 67 535 429 36.6 514 420 41 492 411 45.9 71 573 372 37.3 551 363 41.7 527 355 46.6 63 513 3 36.3 492 371 40.6 470 361 45.4 67 549 315 36.9 527 306 41.2 503 297 46.1 71 588 249 37.5 564 241 41.9 539 232 46.8 63 514 457 36.3 495 448 40.6 473 438 45.5 67 549 392 36.9 527 383 41.2 504 374 46.1 71 588 326 37.5 564 317 41.9 539 308 46.8 63 524 524 36.5 507 507 40.9 489 489 45.8 67 551 469 36.9 529 460 41.3 506 450 46.1 71 588 403 37.5 564 394 41.9 539 3 46.8 63 524 406 36.5 502 397 40.8 4 388 45.6 67 560 333 37.1 537 324 41.4 513 315 46.3 71 599 259 37.7 5 250 42.1 549 241 47 63 527 493 36.5 506 483 40.9 484 472 45.7 67 561 420 37.1 538 411 41.4 513 402 46.3 71 599 346 37.7 5 337 42.1 548 328 47 63 546 546 36.8 528 528 41.3 509 509 46.2 67 563 507 37.1 540 497 41.5 516 487 46.4 71 599 433 37.7 5 424 42.1 549 415 47 Table 16: RPS045C Low Airflow Coil Unit Data 12000 cfm 16000 cfm 20000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 512 359 36.4 491 350 40.8 470 340 45.7 67 550 303 37 527 294 41.4 504 284 46.4 71 590 246 37.6 566 237 42.1 540 227 47.1 63 512 426 36.4 492 416 40.8 470 407 45.7 67 550 370 37 528 360 41.4 504 351 46.4 71 589 313 37.6 565 303 42.1 540 294 47.1 63 515 493 36.4 495 483 40.8 474 473 45.8 67 550 436 37 528 427 41.4 504 417 46.4 71 589 379 37.6 565 370 42.1 539 360 47.1 63 540 415 36.8 517 405 41.2 492 395 46.1 67 577 341 37.4 553 331 41.8 527 321 46.8 71 618 266 38 592 256 42.5 564 246 47.6 63 542 503 36.8 519 493 41.3 496 483 46.2 67 578 429 37.4 553 419 41.8 528 409 46.8 71 618 354 38 592 345 42.5 564 335 47.6 63 561 561 37.1 542 542 41.7 522 522 46.7 67 5 517 37.4 556 508 41.9 531 497 46.9 71 618 442 38 592 433 42.5 564 423 47.6 63 556 468 37.1 532 458 41.5 507 447 46.4 67 594 376 37.7 568 366 42.1 541 356 47.1 71 63 567 567 37.2 546 546 41.7 524 524 46.8 67 596 486 37.7 570 476 42.1 543 466 47.1 71 63 600 600 37.7 578 578 42.3 555 555 47.4 67 603 592 37.8 579 578 42.3 555 555 47.4 71 Cat 214-5 41

Table 17: RPS050C Low Airflow Coil Unit Data 100 cfm 20000 cfm 22000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 635 479 48.6 608 467 54.2 578 454 60.7 67 6 395 49.6 651 383 55.3 618 371 61.9 71 727 310 50.7 696 299 56.5 661 286 63.2 63 639 578 48.6 612 566 54.3 582 553 60.8 67 681 494 49.6 651 483 55.3 619 470 61.9 71 726 409 50.7 695 398 56.5 661 3 63.1 63 654 654 49 632 632 54.8 606 606 61.5 67 682 593 49.6 653 581 55.4 621 569 62 71 726 508 50.6 695 497 56.4 660 484 63.1 63 646 505 48.8 618 494 54.5 587 481 61 67 690 413 49.8 660 401 55.6 627 388 62.2 71 738 319 50.9 705 308 56.7 63 650 614 48.9 622 602 54.6 593 587 61.1 67 691 523 49.8 661 511 55.6 627 498 62.2 71 737 429 50.9 705 418 56.7 63 676 676 49.5 652 652 55.3 625 625 62.1 67 694 632 49.9 663 620 55.6 632 606 62.3 71 737 539 50.9 706 527 56.7 63 655 532 49 626 520 54.7 594 506 61.2 67 699 430 50 668 419 55.8 634 406 62.4 71 746 328 51.1 63 661 648 49.1 634 633 54.9 607 607 61.5 67 700 551 50 668 539 55.8 634 526 62.4 71 746 449 51.1 63 695 695 49.9 670 670 55.8 642 642 62.6 67 705 669 50.1 6 656 55.9 643 640 62.6 71 747 569 51.1 Table 18: RPS050C High Airflow Coil Unit Data 16000 cfm 20000 cfm 24000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 631 455 48.5 605 444 54.1 5 431 60.6 67 676 3 49.5 647 369 55.2 616 356 61.8 71 724 304 50.6 693 293 56.4 659 2 63.1 63 632 544 48.5 606 532 54.2 577 519 60.7 67 676 469 49.5 648 457 55.2 615 444 61.8 71 723 393 50.6 692 381 56.4 659 369 63.1 63 637 632 48.6 614 614 54.4 590 590 61.1 67 677 558 49.5 648 546 55.2 617 533 61.8 71 723 481 50.6 692 469 56.4 659 457 63.1 63 656 510 49 627 498 54.7 596 4 61.2 67 700 417 50 668 405 55.8 636 392 62.4 71 748 323 51.1 63 658 620 49.1 631 608 54.8 601 593 61.4 67 701 527 50 670 516 55.8 636 503 62.4 71 748 433 51.1 63 6 6 49.7 661 661 55.6 633 633 62.3 67 703 638 50.1 673 625 55.9 640 612 62.5 71 748 544 51.2 63 671 563 49.4 643 551 55.1 610 537 61.6 67 715 452 50.4 683 440 56.2 648 427 62.8 71 63 683 683 49.6 657 657 55.5 628 628 62.2 67 718 584 50.4 686 572 56.2 651 559 62.8 71 63 722 722 50.5 695 695 56.4 665 665 63.3 67 725 712 50.6 696 695 56.5 665 665 63.3 71 42 Cat 214-5

Table 19: RPS060C Low Airflow Coil Unit Data 16000 cfm 20000 cfm 24000 cfm b Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a a. Compressor kw b. Maximum airflow is 23,700 cfm Table 20: RPS060C High Airflow Coil 63 707 490 56.4 678 476 63.1 647 462 70.6 67 9 415 57.3 727 402 64.1 695 388 71.8 71 813 339 58.4 7 326 65.3 745 312 73 63 708 578 56.4 6 565 63.1 649 551 70.6 67 8 503 57.3 727 490 64.1 694 476 71.8 71 812 427 58.4 779 414 65.2 744 400 73 63 710 667 56.4 683 654 63.1 653 639 70.7 67 760 592 57.3 729 579 64.1 695 564 71.8 71 812 515 58.4 778 502 65.3 745 489 73 63 738 545 57 706 531 63.7 673 517 71.2 67 790 452 57.9 6 439 64.8 721 425 72.5 71 845 358 59 9 345 65.9 772 332 73.7 63 740 655 57 709 641 63.7 676 627 71.3 67 790 562 57.9 6 548 64.7 721 535 72.4 71 844 468 59 9 455 65.9 771 441 73.7 63 2 2 57.2 726 726 64.1 699 699 71.9 67 791 672 58 8 658 64.8 723 644 72.5 71 844 577 59 8 564 65.9 771 551 73.7 63 9 598 57.4 726 584 64.1 691 569 71.7 67 811 488 58.4 776 474 65.2 739 460 72.9 71 867 376 59.5 829 363 66.4 790 349 74.2 63 763 727 57.4 732 712 64.2 698 694 71.8 67 811 619 58.4 776 605 65.2 740 591 72.9 71 866 507 59.4 829 494 66.3 790 4 74.2 63 796 796 58.1 768 768 65 738 738 72.8 67 816 748 58.4 781 734 65.3 745 719 73 71 867 638 59.4 830 625 66.3 791 611 74.2 Unit Data 20000 cfm 24000 cfm 200 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 1 552 57.2 719 538 63.9 6 523 71.5 67 4 458 58.2 769 445 65 734 430 72.7 71 860 364 59.3 823 350 66.2 7 337 74.1 63 2 662 57.2 721 648 64 687 633 71.6 67 4 569 58.2 770 555 65 734 541 72.7 71 9 474 59.3 823 460 66.2 7 447 74 63 763 763 57.4 737 737 64.3 710 710 72.1 67 5 679 58.2 772 665 65.1 736 651 72.8 71 860 584 59.3 822 571 66.2 784 557 74 63 773 606 57.6 739 591 64.4 704 577 72 67 826 494 58.6 790 481 65.5 2 466 73.2 71 882 382 59.8 844 369 66.7 63 778 736 57.7 744 721 64.5 711 704 72.2 67 827 626 58.6 791 613 65.5 3 598 73.2 71 882 514 59.8 844 500 66.7 63 9 9 58.3 781 781 65.3 0 0 73.2 67 830 7 58.7 794 742 65.6 8 728 73.3 71 882 645 59.7 845 632 66.7 63 790 657 57.9 5 643 64.7 718 628 72.3 67 842 529 59 5 516 65.8 766 501 73.6 71 63 0 799 58.1 770 770 65 739 739 72.9 67 844 682 59 5 667 65.8 767 653 73.6 71 899 553 60.1 63 846 846 59 815 815 66 782 782 74 67 1 830 59.1 816 812 66.1 782 782 74 71 Cat 214-5 43

Table 21: RPS 070C Low Airflow - Scroll Unit Data 100 cfm 22000 cfm 26000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a Table 22: RPS070C Low Airflow Coil - Reciprocating Unit Data 100 cfm 10 fpi 22000 cfm 10 fpi 26000 cfm b 10 fpi 63 745 526 55.2 716 512 61.8 6 499 69.2 67 799 442 56.1 768 430 62.8 735 416 70.3 71 7 358 57.0 823 345 63.8 788 332 71.4 63 747 624 55.2 718 611 61.8 687 597 69.2 67 798 540 56.1 768 528 62.8 735 514 70.2 71 6 456 57.0 823 443 63.8 787 430 71.3 63 0 721 55.3 722 707 61.9 693 690 69.4 67 0 639 56.1 768 626 62.8 735 612 70.2 71 5 554 57.0 823 542 63.8 787 528 71.3 63 772 579 55.6 741 565 62.3 708 551 69.7 67 827 478 56.5 794 465 63.2 8 451 70.8 71 886 377 57.5 0 364 64.3 812 350 71.9 63 7 697 55.7 744 683 62.3 712 668 69.7 67 827 598 56.5 794 584 63.2 9 570 70.7 71 8 496 57.5 849 483 64.3 811 469 71.9 63 791 791 55.9 765 765 62.7 738 738 70.3 67 828 715 56.5 795 702 63.3 760 688 70.8 71 886 615 57.5 0 602 64.3 812 588 71.9 63 792 630 56.0 9 616 62.6 725 601 70.1 67 847 513 56.9 812 499 63.6 7 4 71.1 71 906 395 57.9 869 382 64.7 829 368 72.2 63 797 764 56.0 765 747 62.7 733 729 70.2 67 848 652 56.9 813 638 63.6 776 624 71.1 71 906 534 57.9 868 521 64.6 829 507 72.2 63 832 832 56.6 4 4 63.4 7 7 71.1 67 2 788 56.9 817 773 63.7 782 7 71.2 71 907 673 57.8 869 660 64.6 830 646 72.2 Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a a. Compressor kw b. Maximum airflow is 25,6 cfm 63 7 554 65.6 773 538 70.1 739 523 74.1 67 867 471 67.6 832 456 72.3 795 441 76.4 71 934 388 69.6 895 373 74.5 5 357 78.9 63 7 652 65.6 773 637 70.1 739 621 74.1 67 866 569 67.5 832 555 72.2 794 539 76.4 71 932 486 69.6 894 471 74.5 4 455 78.9 63 9 0 65.6 776 734 70.2 743 718 74.2 67 866 668 67.5 831 652 72.2 795 637 76.4 71 931 584 69.6 892 569 74.5 2 553 78.9 63 841 609 66.7 6 594 71.3 769 577.3 67 903 509 68.7 864 493 73.4 825 477 77.7 71 969 408 70.8 929 393.7 8 377.2 63 840 727 66.7 5 711 71.3 768 695.3 67 902 628 68.6 863 612 73.4 824 596 77.7 71 969 527 70.8 927 511.7 884 495.2 63 847 840 66.9 816 816 71.7 786 786 76.1 67 902 746 68.7 864 730 73.4 824 714 77.7 71 967 645 70.8 926 630.7 883 614.2 63 865 661 67.5 828 645 72.1 788 628 76.2 67 929 544 69.5 888 528 74.3 846 512 78.6 71 996 426 71.7 953 411 76.7 907 395 81.1 63 866 798 67.5 829 7 72.2 791 763 76.3 67 928 683 69.5 887 667 74.3 845 651 78.6 71 995 566 71.7 951 550 76.6 905 534 81.1 63 893 893 68.3 861 861 73.3 828 828 77.8 67 928 821 69.5 888 4 74.3 847 787 78.6 71 994 705 71.7 950 689 76.7 905 673 81.1 44 Cat 214-5

Table 23: RPS070C High Airflow Coil - Scroll Unit Data 20000 cfm 24000 cfm 200 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 782 565 55.8 0 552 62.5 717 537 69.9 67 838 472 56.7 4 459 63.4 768 444 71.0 71 898 378 57.7 862 364 64.5 823 350 72.1 63 7 676 55.8 2 662 62.5 719 647 69.9 67 838 583 56.7 5 569 63.4 769 555 70.9 71 897 488 57.7 861 474 64.5 823 460 72.1 63 790 784 55.9 763 763 62.7 736 736 70.3 67 840 693 56.7 6 679 63.5 771 665 71.0 71 898 599 57.7 862 5 64.5 822 570 72.1 63 6 620 56.2 773 606 62.9 738 591 70.3 67 863 509 57.1 827 495 63.9 789 4 71.4 71 923 397 58.2 8 383 65.0 844 369 72.6 63 811 1 56.2 778 736 62.9 743 720 70.4 67 864 641 57.1 828 627 63.9 791 612 71.4 71 923 528 58.1 884 515 64.9 844 500 72.6 63 837 837 56.7 810 810 63.5 7 7 71.2 67 866 772 57.2 831 8 63.9 793 742 71.5 71 922 660 58.1 884 646 64.9 845 632 72.6 63 825 672 56.5 790 658 63.2 3 642 70.6 67 881 544 57.4 843 530 64.2 5 515 71.7 71 941 415 58.5 901 401 65.3 207 63 833 819 56.6 0 0 63.3 769 769 71.0 67 883 697 57.4 844 682 64.2 5 667 71.7 71 941 567 58.5 902 554 65.3 207 63 877 877 57.4 847 847 64.2 814 814 71.9 67 889 846 57.5 3 830 64.3 816 812 71.9 71 942 720 58.5 902 706 65.3 207 Table 24: RPS070C High Airflow Coil - Reciprocating Unit Data 20000 cfm 24000 cfm 200 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 1 597 67.1 815 5 71.7 778 564.7 67 916 505 69.1 877 488 73.9 836 472 78.2 71 984 411 71.3 943 395 76.3 898 378.8 63 1 707 67.1 815 691 71.7 7 674.8 67 915 615 69.1 876 598 73.9 836 582 78.1 71 983 521 71.3 941 505 76.3 897 488.8 63 6 818 67.2 819 0 71.8 786 783 76 67 914 725 69.1 876 708 73.9 836 692 78.2 71 982 631 71.3 940 615 76.3 896 598.8 63 882 653 68 843 636 72.7 3 619 76.8 67 948 543 70.1 906 526 74.9 862 509 79.3 71 1017 431 72.4 973 415 77.4 925 397 81.9 63 883 784 68.1 846 768 72.7 5 749 76.9 67 947 674 70.1 905 657 74.9 862 640 79.3 71 1016 562 72.4 971 546 77.4 924 529 81.9 63 899 899 68.5 868 868 73.5 835 835 78.1 67 947 5 70.2 906 788 863 771 79.3 71 1015 694 72.4 970 677 77.4 923 660 81.9 63 904 706 68.8 864 689 73.4 822 671 77.6 67 971 579 70.9 926 561.7 881 544.1 71 1040 449 73.2 994 433 78.2 944 416 82.8 63 908 7 68.9 869 839 73.6 828 819 77.9 67 970 731 70.9 926 714.7 881 697.1 71 1040 602 73.1 992 5 78.2 942 568 82.8 63 946 946 70 911 911.1 8 8 79.8 67 972 882 71 929 865.9 8 846.3 71 1038 4 73.2 991 738 78.2 942 720 82.8 Cat 214-5 45

Table 25: RPS0C Low Airflow Coil - Scroll Unit Data 100 cfm 10 fpi 22000 cfm 10 fpi 26000 cfm b 10 fpi Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a a. Compressor kw b. Maximum airflow is 25,6 cfm 63 848 573 68.5 816 558 76.4 7 542.4 67 910 490 69.6 876 4 77.6 839 459. 86.8 71 977 405 70.8 941 391 78.9 900 3 88.1 63 848 672 68.5 817 657 76.4 782 641.4 67 909 588 69.6 876 574 77.6 839 557 86.7 71 976 503 70.8 939 489 78.9 899 473 88.1 63 0 770 68.5 819 5 76.4 784 738.5 67 910 687 69.6 876 672 77.6 839 656 86.7 71 976 602 70.8 939 587 78.9 899 571 88.1 63 884 628 69.1 849 613 77.1 812 596 86.2 67 948 528 70.3 911 512 78.3 871 496 87.5 71 1016 425 71.5 976 411 79.6 933 394 88.9 63 8 747 69.1 1 732 77.1 813 715 86.2 67 948 647 70.3 911 631 78.3 871 615 87.5 71 1015 544 71.5 9 529 79.6 932 513 88.9 63 890 863 69.2 7 845 77.2 823 823 86.4 67 948 766 70.3 912 0 78.3 872 734 87.5 71 1015 663 71.5 9 648 79.6 932 632 88.9 63 911 681 69.6 874 665 77.6 835 648 86.7 67 9 563 70.8 936 547 78.8 894 531 88.0 71 1044 444 72.0 1002 429.2 956 412 89.4 63 913 818 69.6 877 2 77.6 837 784 86.7 67 9 702 70.8 937 687 78.8 895 670. 88.0 71 1043 583 72.0 1001 568.1 956 551 89.4 63 930 930 69.9 900 900 78.1 867 867 87.4 67 977 840 70.8 938 825 78.8 896 7 88.0 71 1042 722 72.0 1002. 707.1 957 691 89.4 Table 26: RPS0C Low Airflow Coil - Reciprocating Unit Data 100 cfm 22000 cfm 26000 cfm Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a a. Compressor kw Maximum airflow is 25,6 cfm b. Maximum airflow is 25,6 cfm 63 881 589 77.6 843 571 84 4 553 90.3 67 947 506.5 904 488 87.2 862 469 94 71 1015 421 83.6 971 403 90.7 926 3 97.9 63 881 688 77.6 843 670 84 4 651 90.3 67 946 604.5 905 586 87.2 861 567 94 71 1014 519 83.6 970 501 90.6 925 483 97.8 63 883 786 77.6 844 768 84 6 749 90.4 67 945 702.5 904 684 87.2 862 666 94 71 1013 617 83.6 969 599 90.6 923 581 97.8 63 921 645 79.4 879 626.9 836 607 92.4 67 987 544 82.4 942 525 89.2 897 506 96.1 71 1060 442.5 1011 424 92.7 961 405 100.1 63 922 765 79.4 8 745.9 837 726 92.4 67 986 663 82.4 941 644 89.2 896 625 96.1 71 1058 561.5 1009 542 92.7 960 524 100 63 923 881 79.5 884 861 86.1 843 838 92.8 67 986 782 82.4 941 763 89.2 896 744 96.1 71 1057 679.4 1008 661 92.7 959 642 100 63 951 698.7 906 678 87.2 861 659 93.9 67 1017 5 83.7 970 561 90.6 921 542 97.6 71 1090 461 86.9 1040 442 94.2 988 424 101.7 63 950 836.8 907 816 87.3 862 796 94 67 1016 719 83.7 968 699 90.6 921 681 97.7 71 1090 600 86.9 1038 581 94.2 986 562 101.6 63 961 961 81.2 925 925 88.2 887 887 95.6 67 1017 7 83.7 969 838 90.6 921 818 97.7 71 1088 739 86.8 1036 720 94.1 986 702 101.7 46 Cat 214-5

Table 27: RPS0C High Airflow Coil - Scroll Unit Data 22000 cfm 10 fpi 26000 cfm 10 fpi 30000 cfm 10 fpi a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 905 640 69.5 870 624 77.5 831 607 86.6 67 97 538 70.7 933 523 78.8 892 506 88.0 71 1040 435 72.0 1000 420.1 955 403 89.4 63 907 760 69.5 872 744 77.5 833 727 86.6 67 970 658 70.7 933 642 78.7 891 625 87.9 71 1039 555 72.0 999 539.1 954 523 89.4 63 912 878 69.6 878 861 77.6 842 840 86.8 67 972 779 70.7 933 762 78.7 892 745 87.9 71 1038 674 72.0 999 659.1 954 643 89.4 63 933 693 70.0 896 677 78.0 5 659 87.1 67 999 574 71.2 959 558 79.3 915 541 88.5 71 1070 454 72.5 1026 438.7 9 421 90.0 63 936 833 70.0 899 817 78.0 9 798 87.2 67 999 715 71.2 959 699 79.3 916 682 88.5 71 1069 594 72.5 1026 579.6 979 562 89.9 63 952 952 70.3 921 921 78.5 887 887 87.8 67 1000 5 71.2 961 838 79.3 917 821 88.5 71 1069 735 72.5 1026 720.6 979 703 89.9 63 954 744 70.4 915 728 78.4 873 710 87.6 67 1021 609 71.6 979 593 79.7 934 5 88.9 71 1091 472 72.9 1047 456 81.1 998 439 90.4 63 959 901 70.5 920 883 78.5 8 863 87.7 67 1021 770 71.6 979 3 79.7 934 736 88.9 71 1091 632 72.9 1046 617 81.0 998 600 90.4 63 994 994 71.1 962 962 79.3 925 925 88.7 67 1025 928 71.7 984 911 79.8 939 891 89.0 71 1091 794 72.9 1047 778 81.0 998 761 90.3 Table 28: RPS0C High Airflow Coil - Reciprocating Unit Data 22000 cfm 10 fpi 26000 cfm 10 fpi 30000 cfm b 10 fpi Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a a. Compressor kw b. Maximum airflow is 25,6 cfm 63 945 658.5 900 638 87 6 618 93.7 67 1013 556 83.5 966 536 90.5 919 517 97.5 71 1088 453 86.7 1037 434 94.1 986 415 101.6 63 945 778.5 901 7 87.1 7 737 93.7 67 1011 6 83.5 965 656 90.4 917 636 97.5 71 1086 573 86.7 1035 553 94 9 534 101.5 63 947 896.6 904 8 87.3 862 3 94 67 1012 795 83.5 966 776 90.4 918 6 97.5 71 1084 692 86.7 1034 673 94 983 653 101.5 63 974 711 81.8 929 691 88.5 882 671 95.3 67 1045 593 84.9 995 572 92 945 552 99.1 71 1120 473 88.2 1067 453 95.6 1013 434 103.2 63 9 1 81.9 929 831 88.6 883 810 95.3 67 1043 733 84.9 994 713 92 944 693 99.1 71 1119 613 88.2 1066 593 95.6 1012 574 103.2 63 986 983 82.3 947 947 89.4 908 908 96.8 67 1044 873 84.9 994 3 92 945 832 99.2 71 1117 3 88.1 1065 734 95.6 1011 714 103.2 63 998 763 82.9 949 742 89.6 901 722 96.4 67 1069 628 86 1017 607 93.1 964 587 100.3 71 1146 491 89.3 1091 471 96.8 1034 452 104.5 63 1000 921 83 952 899 89.8 905 877 96.7 67 1069 788 86 1016 768 93.1 964 748 100.3 71 1144 652 89.3 1089 632 96.8 1033 612 104.4 63 1030 1030 84.2 989 989 91.6 948 948 99.3 67 1069 947 86.1 1018 926 93.2 966 904 100.5 71 1144 813 89.3 1088 793 96.8 1032 773 104.4 Cat 214-5 47

Table 29: RPS0C Low Airflow Coil Unit Data 24000 cfm 200 cfm 32000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 909 665 66.6 870 648 71.5 830 631.8 67 978 555 68.5 935 538 73.6 891 520 78.2 71 1051 443 70.6 1005 427.9 958 409.7 63 910 797 66.6 871 7 71.5 831 762.9 67 977 687 68.5 934 670 73.6 890 652 78.2 71 1050 5 70.6 1004 558.9 956 541.7 63 923 923 66.9 891 891 72.1 7 7 76.9 67 977 819 68.5 935 2 73.6 892 784 78.3 71 1048 707 70.5 1003 690.9 955 673.7 63 933 720 67.2 892 702 72.2 849 684 76.6 67 1003 592 69.2 958 5 74.3 912 557 79 71 1077 463 71.3 1028 445 76.7 979 428 81.6 63 937 872 67.3 896 4 72.3 5 835 76.9 67 1002 745 69.2 958 728 74.3 911 710 79 71 1076 616 71.3 1027 599 76.7 977 581 81.5 63 972 972 68.3 938 938 73.6 901 901 78.6 67 1004 898 69.3 961 8 74.5 916 862 79.2 71 1074 769 71.3 1026 2 76.7 977 734 81.6 63 952 772 67.8 909 4 72.8 865 736 77.2 67 1022 628 69.7 9 610 74.9 927 592 79.6 71 1096 481 71.9 63 960 942 68 921 919 73.1 883 883 77.9 67 1021 2 69.8 9 784 74.9 928 766 79.6 71 1095 655 71.9 63 1014 1014 69.5 976 976 74.9 937 937 79.9 67 1027 973 69.9 983 954.2 938 932 71 1094 829 71.9 Table 30: RPS0C High Airflow Coil Unit Data 200 cfm 32000 cfm 36000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 942 725 67.5 900 707 72.5 7 689 76.9 67 1013 596 69.5 967 579 74.6 920 561 79.3 71 1087 467 71.6 1039 450 77 63 946 878 67.6 905 860 72.6 863 841 77.1 67 1012 0 69.5 967 732 74.7 920 714 79.3 71 1086 620 71.6 1037 603 77 63 981 981 68.5 946 946 73.9 909 909 78.8 67 1014 904 69.6 970 886 74.8 924 867 79.5 71 10 774 71.6 1036 7 77 63 962 778 68 918 760 73.1 873 741 77.6 67 1032 633 70 9 615.2 937 596 79.9 71 63 970 950 68.3 929 927 73.4 892 892 78.2 67 1032 7 70.1 9 789.3 937 771 71 1106 660 72.2 63 1023 1023 69.7 986 986.2 946 946.2 67 1037 981 70.2 992 961.5 947 940.3 71 63 978 830 68.5 933 811 73.5 887 792 78.1 67 1048 668 70.5 999 650.7 949 631.4 71 63 998 998 69 960 960 74.4 920 920 79.3 67 1048 863 70.5 1000 845.8 950 826.5 71 63 1059 1059 70.8 1019 1019 76.3 977 977 81.4 67 1060 1050 70.9 1019 1019 76.3 976 976 81.5 71 48 Cat 214-5

Table 31: RPS090C Low Airflow Coil Unit Data 200 cfm 10 fpi 32000 cfm 10 fpi 35000 cfm 10 fpi a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 1016 2 81.6 966 731 88.4 917 709 95.3 67 1089 624 84.6 1037 603 91.8 983 582 99.1 71 1168 495 87.8 1113 4 95.3 1056 454 103.1 63 1017 903 81.7 968 881 88.5 919 9 95.5 67 1088 776 84.6 1035 5 91.8 982 734 99.1 71 1167 647 87.8 1111 626 95.3 1054 606 103 63 1034 1034 82.3 994 994 89.7 953 953 97.3 67 1089 927 84.6 1036 905 91.9 984 884 99.2 71 1166 798 87.7 1110 778 95.3 1053 7 103.1 63 1037 4 82.5 986 782 89.4 936 761 96.3 67 1112 659.5 1057 638 92.8 1002 617 100.1 71 1193 514 88.7 1134 493 96.4 1076 473 104.2 63 1041 973 82.7 991 949 89.6 941 925 96.8 67 1111 831.5 1056 810 92.8 1001 789 100.2 71 1191 686 88.7 1133 665 96.3 1074 644 104.1 63 1079 1079 84.1 1036 1036 91.7 992 992 99.5 67 1113 1001.6 1059 979 93 1006 956 100.4 71 1190 8 88.7 1132 837 96.4 1073 816 104.2 63 1051 841 83.1 998 819 90 946 797 97 67 1126 6 86.1 1070 663 93.4 1013 642 100.8 71 1207 527 89.3 1149 506 97 1088 486 104.8 63 1057 1022 83.3 1007 995 90.4 961 961 97.8 67 1125 872 86.1 1069 0 93.4 1013 829 100.8 71 1206 714 89.3 1146 693 97 1086 673 104.8 63 1108 1108.3 1063 1063 93 1018 1018 101 67 1129 1054 86.3 10 1030 93.6 1021 1005 101.3 71 1205 901 89.3 1145 8 97 1086 9 104.8 Table 32: RPS090C High Airflow Coil Unit Data 200 cfm 32000 cfm 36000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 1037 766 82.5 986 743 89.4 935 721 96.3 67 1113 636.5 1058 614 92.8 1003 593 100.2 71 1194 506 88.8 1137 4 96.5 1078 463 104.3 63 1038 919 82.6 988 897 89.5 937 8 96.5 67 1111 790.5 1057 768 92.8 1002 746 100.2 71 1193 659 88.8 1135 638 96.4 1076 617 104.2 63 1056 1056 83.2 1015 1015 90.7 973 973 98.4 67 1112 943.6 1058 922 92.9 1004 900 100.3 71 1192 813 88.8 1134 792 96.4 10 771 104.3 63 1059 819 83.4 1007 797 90.4 954 7 97.4 67 1136 673 86.5 1079 651 93.8 1022 629 101.3 71 1219 525 89.8 1160 504 97.5 1099 482 105.4 63 1063 993 83.6 1012 970 90.6 961 946 97.8 67 1136 848 86.5 1079 826 93.9 1022 4 101.3 71 1218 700 89.8 1157 678 97.5 1096 657 105.4 63 1104 1104.1 1059 1059 92.8 1014 1014 100.8 67 1138 1022 86.6 1082 999 94 1027 977 101.6 71 1217 8 89.8 1157 3 97.5 1096 832 105.4 63 1078 872 84.2 1023 849 91.2 969 826 98.3 67 1155 708 87.3 1096 686 94.6 1037 664 102.1 71 1239 543 90.6 1178 522 98.4 63 1086 1063 84.5 1035 1034 91.7 990 990 99.4 67 1154 904 87.3 1096 882 94.7 1038 9 102.2 71 1238 739 90.6 11 717 98.4 63 1144 1144 86.7 1097 1097 94.6 1050 1050 102.7 67 1160 1097 87.5 1104 1073 95 1049 1045 102.8 71 1237 935 90.6 Cat 214-5 49

Table 33: RPS105C Low Airflow Coil Unit Data 32000 cfm 10 fpi 36000 cfm 10 fpi 40000 cfm b 10 fpi Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a a. Compressor kw b. Maximum airflow is 39,520 cfm 63 1167 862 90.6 1107 836 98.1 1052 812 105.4 67 1256 718 93.9 1193 692 101.7 1132 668 109.6 71 1351 572 97.3 1283 547 105.6 1216 522 114 63 1166 1034 90.7 1109 1008 98.1 1055 983 105.6 67 1255 891 93.9 1192 866 101.7 1131 842 109.6 71 1349 744 97.3 1281 719 105.6 1214 695 114 63 1186 1186 91.3 1139 1139 99.4 1094 1094 107.5 67 1255 1063 93.9 1193 1038 101.8 1133 1013 109.7 71 1348 918 97.3 12 893 105.6 1213 869 114 63 1190 914 91.5 1129 888 99 1072 864 106.5 67 1281 3 94.8 1215 728 102.7 1151 703 110.7 71 13 590 98.3 1305 565 106.6 1236 540 115.1 63 1192 1105 91.6 1134 1077 99.2 1078 1051 106.8 67 12 947 94.8 1214 921 102.7 1151 897 110.7 71 1374 783 98.3 1303 8 106.6 1234 734 115 63 1234 1234 93 1184 1184 101.3 1135 1135 109.7 67 1281 1138 94.9 1217 1112 102.8 1155 1086 110.9 71 1373 977 98.3 1302 952 106.6 1233 927 115.1 63 1210 965 92.2 1147 939 99.8 1089 914 107.3 67 1301 788 95.5 1233 762 103.5 1167 737 111.5 71 1397 608 99.1 1324 582 107.5 1252 558 116 63 1216 1171 92.4 1156 1141 100.1 1103 1103 108 67 1300 1001 95.6 1232 9 103.5 1167 950 111.5 71 1394 821 99 1321 796 107.4 1250 771 115.9 63 12 12 94.6 1222 1222 102.9 1169 1169 111.6 67 1303 1210 95.7 1238 1182 103.8 1177 1153 112 71 1393 1035 99 1320 1009 107.4 1249 984 115.9 Table 34: RPS105C High Airflow Coil Unit Data 36000 cfm 40000 cfm 44000 cfm a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 1233 941 93.1 1169 913 100.8 1108 888 108.4 67 1327 777 96.5 1258 749 104.6 1190 723 112.7 71 1424 609 100.2 1350 583 108.7 63 1237 1138 93.3 11 1110 101 1115 1083 108.8 67 1326 974 96.5 1257 947 104.6 1190 921 112.8 71 1422 7 100.1 1347 7 108.6 63 1279 1279 94.7 1226 1226 103.1 1174 1174 111.8 67 1329 1171 96.7 1261 1144 104.8 1195 1117 113 71 1421 1004 100.2 1347 977 108.6 63 1254 995 93.9 1188 967 101.6 1125 940 109.3 67 1348 813 97.3 1277 7 105.4 1206 9 113.6 71 1445 628 101 63 1262 1211 94.2 1199 1181 102 1143 1143 110.1 67 1347 1032 97.3 1276 1004 105.5 1207 977 113.7 71 1443 846 100.9 63 1324 1324 96.3 1268 1268 104.9 1211 1211 113.8 67 1352 1249 97.6 1283 1220 105.8 1216 1191 114.2 71 1442 1065 101 63 1273 1047 94.5 1204 1019 102.3 1140 992 110.1 67 1365 848 98 1292 820 106.1 1221 794 114.3 71 63 1287 1277 95 1228 1228 103.3 1173 1173 111.7 67 1365 1088 98 1292 1060 106.2 1221 1033 114.5 71 63 1363 1363 97.8 1303 1303 106.5 1244 1244 115.5 67 1374 1323 98.4 1305 1290 106.7 1243 1243 115.6 71 50 Cat 214-5

Table 35: RPS115C Low Airflow Coil Unit Data 32000 cfm 10 fpi 36000 cfm 10 fpi 40000 cfm b 10 fpi Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a a. Compressor kw b. Maximum airflow is 39,520 cfm 63 1287 915 105.1 1231 890 112.8 1174 865 120.1 67 1381 769 108.7 1321 744 116.8 1258 718 124.5 71 1479 620 112.5 1417 596 120.9 1348 571 129 63 1288 1089 105.2 1232 1063 112.8 1173 1037 120.1 67 1379 942 108.7 1319 917 116.7 1256 891 124.4 71 1478 793 112.5 1415 769 120.8 1346 744 129 63 1293 1258 105.4 1242 1230 113.2 1189 1189 121 67 1379 1115 108.7 1320 1090 116.8 1256 1064 124.5 71 1476 966 112.4 1412 942 120.8 1344 916 128.9 63 1314 968 106.2 1259 944 114 1197 917 121.3 67 1408 4 109.8 1347 7 117.9 1281 4 125.7 71 1509 638 113.6 1444 615 122.1 1373 589 130.3 63 1316 1161 106.3 1258 1135 114 1198 1108 121.4 67 1407 998 109.8 1347 974 117.9 1281 947 125.7 71 1508 832 113.6 1441 8 122 1370 782 130.2 63 1333 1333 106.9 1287 1287 115.2 1236 1236 123.3 67 1408 1191 109.9 1347 1166 118 1281 1139 125.8 71 1505 1025 113.6 1441 1002 122.1 1370 976 130.3 63 1338 1020 107.2 1278 994 114.9 1215 967 122.3 67 1433 839 110.7 1369 814 118.9 1301 788 126.7 71 1533 656 114.5 1466 632 123 1393 607 131.3 63 1340 1230 107.2 1281 1203 115.1 1219 1174 122.5 67 1432 1053 110.8 1368 1028 118.9 1300 1002 126.7 71 1532 871 114.5 1464 846 123 1390 820 131.2 63 1378 1378 108.7 1329 1329 117.1 12 12 125.4 67 1432 1264 110.8 1370 1238 118.9 1303 1211 126.9 71 1531 10 114.5 1463 1060 123 1390 1034 131.2 Table 36: RPS115C High Airflow Coil Unit Data 300 cfm 42000 cfm 46000 cfm b Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a a. Compressor kw b. Maximum airflow is 45,600 cfm 63 13 1026 108.7 1317 999 116.6 1251 971 124.2 67 1478 0 112.5 1411 823 120.7 1340 796 128.7 71 1583 672 116.3 1510 646 125 1435 619 133.4 63 1382 1234 108.9 1320 1207 116.8 1255 1178 124.4 67 1476 1058 112.5 1410 1032 120.7 1339 1004 128.7 71 15 8 116.3 1509 4 125 1433 826 133.3 63 1410 1410 109.8 1359 1359 118.4 1304 1304 126.8 67 1478 1266 112.5 1412 1239 120.9 1342 1211 128.9 71 1578 1088 116.3 1507 1062 125 1431 1035 133.4 63 1402 10 109.6 1338 1052 117.5 1269 1023 125.1 67 1500 886 113.3 1432 9 121.6 1358 831 129.6 71 1605 690 117.2 1533 664 125.9 1454 637 134.3 63 1406 1307 109.8 1343 1279 117.8 1277 1248 125.6 67 1499 1115 113.3 1431 1088 121.7 1358 1060 129.7 71 1603 920 117.2 1529 893 125.9 1451 866 134.3 63 1456 1456 111.6 1402 1402 120.3 1344 1344 128.8 67 1502 1344 113.5 1435 1316 121.9 1364 1287 130 71 1601 1149 117.2 1528 1123 125.9 1450 1095 134.3 63 1420 1132 110.3 1355 1104 118.3 12 10 125.9 67 1519 921 114 1449 894 122.4 1374 866 130.4 71 1624 708 118 1550 682 126.7 63 1429 1377 110.6 1366 1346 118.8 1303 1303 126.8 67 1518 1171 114.1 1448 1144 122.4 1374 1116 130.5 71 1622 958 117.9 1547 932 126.6 63 1496 1496 113.1 1440 1440 121.9 1379 1379 130.6 67 1524 1418 114.3 1456 1390 122.7 1384 1358 131 71 1621 1208 117.9 1546 1182 126.6 Cat 214-5 51

Table 37: RPS125C High Airflow Coil Unit Data 40000 cfm 10 fpi 44000 cfm 10 fpi 400 cfm 10 fpi a. Compressor kw Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a 63 1511 1101 121.4 1446 1072 129.7 1379 1043 137.3 67 1621 918 125.3 1551 890 134 1478 860 142 71 1738 733 129.5 1664 705 138.5 1584 676 146.9 63 1512 1316 121.4 1447 1287 129.7 13 1257 137.4 67 1619 1134 125.2 1551 1106 134 1477 1077 142 71 1737 949 129.4 1661 921 138.5 1582 893 146.9 63 1526 1520 121.9 1473 1473 130.7 1417 1417 139 67 1620 1350 125.3 1550 1322 134 1478 1292 142.1 71 1734 1165 129.4 1660 1138 138.5 1581 1109 146.9 63 1536 1153 122.3 1468 1124 130.6 1399 1094 138.3 67 1647 953 126.2 15 925 134.9 1499 895 143 71 1764 1 130.5 1688 724 139.5 1606 694 148 63 1538 1388 122.4 1472 1358 130.7 1404 1327 138.5 67 1646 1191 126.2 1574 1162 135 1498 1132 143 71 1763 988 130.4 16 960 139.5 1604 931 147.9 63 1573 1573 123.6 1518 1518 132.6 1459 1459 141.1 67 1646 1426 126.3 15 1396 135 1501 1366 143.1 71 1762 1226 130.5 16 1198 139.5 1603 1168 148 63 1557 1204 123.1 1489 11 131.4 1416 1144 139.1 67 1669 988 127 1595 959 135.7 1517 929 143.8 71 1789 770 131.3 1709 741 140.4 1625 712 148.9 63 1561 1456 123.2 1494 1425 131.7 1426 1392 139.5 67 1668 1245 127 1594 1216 135.7 1516 1186 143.9 71 17 1026 131.2 1706 998 140.3 1622 969 148.8 63 1617 1617 125.1 1559 1559 134.2 1498 1498 142.9 67 1670 1499 127.1 1597 1468 135.9 1522 1436 144.1 71 1784 1284 131.3 1705 1255 140.3 1621 1226 148.9 Table 38: RPS135C High Airflow Coil Unit Data 42000 cfm 10 fpi 46000 cfm 10 fpi 50000 cfm b 10 fpi Ambient Air Temperature ( F) Entering Air 95 105 DB WB TH SH KW a TH SH KW a TH SH KW a a. Compressor kw b. Maximum airflow is 49,400 cfm 63 1631 1174 136.5 1562 1144 144.9 1493 1113 152.3 67 11 983 140.8 1677 953 149.6 1600 922 157.3 71 1878 789 145.6 1799 9 154.6 1715 729 162.7 63 1631 1400 136.5 1563 1370 145 1493 1338 152.4 67 1748 1209 140.8 16 1179 149.5 1600 1149 157.4 71 1876 1016 145.5 1796 986 154.6 1713 955 162.7 63 1642 1618 136.9 1581 1579 145.6 15227 1522 153.7 67 1749 1436 140.9 16 1406 149.6 1599 13 157.4 71 1873 1242 145.5 1793 1212 154.5 1713 1183 162.7 63 1660 1228 137.5 1590 1197 145.9 1516 1165 153.4 67 1779 1019 141.8 1703 988 150.6 1623 957 158.4 71 1905 7 146.7 1825 778 155.7 1739 747 163.9 63 1659 1472 137.5 1589 1441 146 1519 1409 153.5 67 1776 1265 141.8 1702 1236 150.7 1622 1204 158.4 71 1904 1055 146.6 1822 1025 155.7 1736 994 163.8 63 16 16 138.5 1629 1629 147.5 1567 1567 155.7 67 1777 1512 141.9 1702 1481 150.7 1623 1449 158.5 71 1901 1301 146.6 1822 1272 155.7 1736 1241 163.9 63 1681 1278 138.4 1611 1248 146.8 1535 1216 154.2 67 12 1053 142.7 1724 1023 151.5 1643 991 159.3 71 1931 826 147.6 1847 796 156.7 19 765 164.8 63 1683 1542 138.4 1612 1509 147 1541 1476 154.5 67 12 1321 142.8 1723 1290 151.6 1642 1258 159.4 71 1928 1093 147.5 1844 1063 156.6 16 1032 164.8 63 1729 1729 140.1 1670 1670 149.3 1606 1606 157.6 67 12 15 142.8 1724 1553 151.7 1645 1520 159.5 71 1928 1361 147.6 1844 1330 156.7 15 1299 164.8 52 Cat 214-5

Heating Capacity Data Gas Heat Figure 16: Gas Heat Capacity Table 39: RPS015C-135C Gas Furnace Air Temperature Rise ( F) Unit Size Nominal Airflow (cfm) Furnace Size (MBH Output) a 200 250 320 400 500 640 650 790 0 1000 1100 1400 1500 2000 015C 7000 26.3 32.9 42.1 52.7 65.8 --.6 -- -- -- -- -- -- -- 020C 00 23.0 28.8 36.9 46.1 57.6 -- 74.9 -- 92.2 -- -- -- -- -- 025C 10000 18.4 23.0 29.5 36.9 46.1 59.0 59.9 -- 73.7 -- -- -- -- -- 030C 12000 15.4 19.2 24.6 30.7 38.4 49.2 49.9 60.7 61.4 -- -- -- -- -- 036C 14000 13.2 16.5 21.1 26.3 32.9 42.1 42.8 52.0 52.7 -- -- -- -- -- 040C 16000 11.5 14.4 18.4 23.0 28.8 36.9 37.4 45.5 46.1 57.6 -- -- -- -- 045C 16000 11.5 14.4 18.4 23.0 28.8 36.9 37.4 45.5 46.1 57.6 -- -- -- -- 050C 20000 9.2 11.5 14.7 18.4 23.0 29.5 30.0 36.4 36.9 46.1 -- -- -- -- 060C 24000 7.7 9.6 12.3 15.4 19.2 24.6 25.0 30.3 30.7 38.4 -- -- -- -- 070C 200 6.6 8.2 10.5 13.2 16.5 21.1 21.4 26.0 26.3 32.9 -- -- -- -- 0C 30000 6.1 7.7 9.8 12.3 15.4 19.7 20.0 24.3 24.6 30.7 -- -- -- -- 0C 32000 -- -- -- -- 14.4 18.4 18.7 22.8 23.0 28.8 31.7 40.3 43.2 57.6 090C 36000 -- -- -- -- 12.8 16.4 16.6 20.2 20.5 25.6 28.2 35.8 38.4 51.2 105C 40000 -- -- -- -- 11.5 14.7 15.0 18.2 18.4 23.0 25.3 32.3 34.6 46.1 115C 46000 -- -- -- -- 10.0 12.8 13.0 15.8 16.0 20.0 22.0 28.1 30.1 40.1 125C 400 -- -- -- -- 9.6 12.3 12.5 15.2 15.4 19.2 21.1 26.9 28.8 38.4 135C 50000 -- -- -- -- 9.2 11.8 12.0 14.6 14.7 18.4 20.3 25.8 27.6 36.9 a. Output is % of input. Cat 214-5 53

Table 40: Gas Furnace Design Maximum Air Temperature Rise ( F) and Minimum Air Flow Maximum Temperature Rise ( F) Baffle Position Minimum Airflow (cfm) Column Number for Pressure Drop (See Table 55: Furnace Pressure Drop (in. W.C.) - RPS015C-135C on page 67) Furnace Size (MBh) 200 250 320 400 500 640 650 790 0 1000 1100 1400 1500 2000 A B C 61 100 61 100 61 100 61 100 61 100 61 100 61 2300 30 2950 6000 4600 9600 5970 12000 7340 15000 10100 21000 13700 30000 1 1 1 1 2 2 3 3 3 3 4 4 7 7 62 42 78 35 63 42 73 52 76 50 73 34 82 49 3000 5500 30 10500 7400 14000 8200 14000 90 100 14000 300 17000 300 4 4 4 4 5 5 4 4 4 4 6 6 8 8 46 15 59 31 55 37 65 46 71 40 64 33 73 40 4000 15000 5000 12000 8400 16000 9200 16000 10400 23000 16000 39000 19000 46000 9 9 9 9 10 10 10 10 10 10 10 10 10 10 Note: Temperature rise and airflow limit applicable to all burner types. Note: For VAV application, consider the minimum turndown airflow when selecting baffle position. Table 41: Gas Burner Connection Size (inches) Description Furnace Size (MBh Output) 200 250 320 400 500 640 650 790 0 1000 1100 1400 1500 2000 Natural Gas (CFH) 250 312 400 500 625 0 812 1000 1000 1250 13 10 18 2500 Minimum Gas Inlet Pressure (In. W.C.) Gas Pipe Connection Size (N.P.T.) Standard Burner 6.00 6.00 7.00 7.00 7.00 7.00 7.00 7.50 7.50 9.00 7.00 8.00 8.00 9.00 20:1 Burner 4.50 5.50 6.00 5.00 5.50 7.00 7.00 6.50 6.50 6.50 5.00 5.00 5.00 6.00 Through.5 psi 0. 0. 0. 1.00 1.00 1.25 1.25 1.25 1.25 1.25 1.50 1.50 1.50 2.00 2-3 psi 0. 0. 0. 1.00 1.00 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.50 5-10 psi 0. 0. 0. 1.00 1.00 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 54 Cat 214-5

Electric Heat 208 Volts Table 42: RPS015C-040C-208V Electric Heat Air Temperature Rise ( F) Electric Heater Model Number Airflow 20 40 60 100 120 140 160 (cfm) Electric Heater Capacity (MBH) 51 102 154 204 255 306 359 408 6000 7.8 15.7 23.7 31.3 39.2 47.0 55.1 n/a 7000 6.7 13.4 20.3 26.9 33.6 40.3 47.3 53.7 00 5.9 11.8 17.7 23.5 29.4 35.3 41.4 47.0 9000 5.2 10.4 15.8 20.9 26.1 31.3 36.8 41.8 10000 4.7 9.4 14.2 18.8 23.5 28.2 33.1 37.6 11000 4.3 8.5 12.9 17.1 21.4 25.6 30.1 34.2 12000 3.9 7.8 11.8 15.7 19.6 23.5 27.6 31.3 13000 3.6 7.2 10.9 14.5 18.1 21.7 25.5 28.9 14000 3.4 6.7 10.1 13.4 16.8 20.1 23.6 26.9 15000 3.1 6.3 9.5 12.5 15.7 18.8 22.1 25.1 16000 2.9 5.9 8.9 11.8 14.7 17.6 20.7 23.5 Note: The maximum temperature rise allowed for electric heat is 60 F with leaving air temperature not to exceed 140 F. Note: The minimum airflow required for unit sizes 015C-040C with electric heat is 6,000 cfm. Table 43: RPS045C-0C-208V Electric Heat Air Temperature Rise ( F) Electric Heater Model Number Airflow (cfm) 40 60 100 120 160 200 240 Electric Heater Capacity (MBH) 102 154 204 255 306 408 510 612 14000 6.7 10.1 13.4 16.8 20.1 26.9 33.6 40.3 15000 6.3 9.5 12.5 15.7 18.8 25.1 31.3 37.6 16000 5.9 8.9 11.8 14.7 17.6 23.5 29.4 35.3 17000 5.5 8.3 11.1 13.8 16.6 22.1 27.6 33.2 100 5.2 7.9 10.4 13.1 15.7 20.9 26.1 31.3 19000 4.9 7.5 9.9 12.4 14.8 19.8 24.7 29.7 20000 4.7 7.1 9.4 11.8 14.1 18.8 23.5 28.2 21000 4.5 6.8 9.0 11.2 13.4 17.9 22.4 26.9 22000 4.3 6.5 8.5 10.7 12.8 17.1 21.4 25.6 23000 4.1 6.2 8.2 10.2 12.3 16.3 20.4 24.5 24000 3.9 5.9 7.8 9.8 11.8 15.7 19.6 23.5 25000 3.8 5.7 7.5 9.4 11.3 15.0 18.8 22.6 26000 3.6 5.5 7.2 9.0 10.8 14.5 18.1 21.7 27000 3.5 5.3 7.0 8.7 10.4 13.9 17.4 20.9 200 3.4 5.1 6.7 8.4 10.1 13.4 16.8 20.1 29000 3.2 4.9 6.5 8.1 9.7 13.0 16.2 19.5 30000 3.1 4.7 6.3 7.8 9.4 12.5 15.7 18.8 Note: The maximum temperature rise allowed for electric heat is 60 F with leaving air temperature not to exceed 140 F. Note: The minimum airflow required for unit sizes 045C-0C with electric heat is 14,000 cfm. Cat 214-5 55

Table 44: RPS0C-135C-208V Electric Heat Air Temperature Rise ( F) Electric Heater Model Number Airflow (cfm) 100 120 160 200 240 2 320 Electric Heater Capacity (MBH) 204 255 306 408 510 612 714 816 22000 8.5 10.7 12.8 17.1 21.4 25.6 29.9 34.2 24000 7.8 9.8 11.8 15.7 19.6 23.5 27.4 31.3 26000 7.2 9.0 10.8 14.5 18.1 21.7 25.3 28.9 200 6.7 8.4 10.1 13.4 16.8 20.1 23.5 26.9 30000 6.3 7.8 9.4 12.5 15.7 18.8 21.9 25.1 32000 5.9 7.3 8.8 11.8 14.7 17.6 20.6 23.5 34000 5.5 6.9 8.3 11.1 13.8 16.6 19.4 22.1 36000 5.2 6.5 7.8 10.4 13.1 15.7 18.3 20.9 300 4.9 6.2 7.4 9.9 12.4 14.8 17.3 19.8 40000 4.7 5.9 7.1 9.4 11.8 14.1 16.5 18.8 42000 4.5 5.6 6.7 9.0 11.2 13.4 15.7 17.9 44000 4.3 5.3 6.4 8.5 10.7 12.8 15.0 17.1 46000 4.1 5.1 6.1 8.2 10.2 12.3 14.3 16.3 400 3.9 4.9 5.9 7.8 9.8 11.8 13.7 15.7 50000 3.8 4.7 5.6 7.5 9.4 11.3 13.2 15.0 Note: The maximum temperature rise allowed for electric heat is 60 F with leaving air temperature not to exceed 140 F. Note: The minimum airflow required for units 0C-135C with electric heat is 22,000 cfm. 230, 460, and 5 Volts Table 45: RPS015C-040C-230,460, 5V Electric Heat Air Temperature Rise ( F) Airflow (CFM) Electric Heater Model Number 20 40 60 100 120 140 160 1* 200* 220* 240* Electric Heater Capacity (MBH) 63 125 188 249 312 374 439 499 564 624 689 748 6000 9.7 19.2 28.9 38.2 47.9 57.5 n/a n/a n/a n/a n/a n/a 7000 8.3 16.5 24.8 32.8 41.1 49.2 57.8 n/a n/a n/a n/a n/a 00 7.3 14.4 21.7 28.7 35.9 43.1 50.6 57.5 n/a n/a n/a n/a 9000 6.5 12.8 19.3 25.5 32.0 38.3 45.0 51.1 57.8 n/a n/a n/a 10000 5.8 11.5 17.3 22.9 28.8 34.5 40.5 46.0 52.0 57.5 n/a n/a 11000 5.3 10.5 15.8 20.9 26.1 31.3 36.8 41.8 47.3 52.3 57.7 n/a 12000 4.8 9.6 14.4 19.1 24.0 28.7 33.7 38.3 43.3 47.9 52.9 57.5 13000 4.5 8.9 13.3 17.7 22.1 26.5 31.1 35.4 40.0 44.2 48.8 53.0 14000 4.1 8.2 12.4 16.4 20.5 24.6 28.9 32.9 37.1 41.1 45.4 49.2 15000 3.9 7.7 11.6 15.3 19.2 23.0 27.0 30.7 34.7 38.3 42.3 46.0 16000 3.6 7.2 10.8 14.3 18.0 21.5 25.3 28.7 32.5 35.9 39.7 43.1 Note: The maximum temperature rise allowed for electric heat is 60 F with leaving air temperature not to exceed 140 F. Note: The minimum airflow required for units 015C-040C with electric heat is 6,000 cfm. Note: 1, 200, 220, and 240 electric heaters available at 460 or 5 Volts only. 56 Cat 214-5

Table 46: RPS045C-0C-230,460, 5V Electric Heat Air Temperature Rise ( F) Electric Heater Model Number Airflow (CFM) 40 60 100 120 160 1 200 240 Electric Heater Capacity (MBH) 125 188 249 312 374 499 564 624 748 14000 8.2 12.4 16.4 20.5 24.6 32.9 37.1 41.1 49.2 15000 7.7 11.6 15.3 19.2 23.0 30.7 34.7 38.3 46.0 16000 7.2 10.8 14.3 18.0 21.5 28.7 32.5 35.9 43.1 17000 6.8 10.2 13.5 16.9 20.3 27.1 30.6 33.8 40.6 100 6.4 9.6 12.7 16.0 19.2 25.6 28.9 32.0 38.3 19000 6.1 9.1 12.1 15.1 18.1 24.2 27.4 30.3 36.3 20000 5.8 8.7 11.5 14.4 17.2 23.0 26.0 28.8 34.5 21000 5.5 8.3 10.9 13.7 16.4 21.9 24.8 27.4 32.8 22000 5.2 7.9 10.4 13.1 15.7 20.9 23.6 26.1 31.3 23000 5.0 7.5 10.0 12.5 15.0 20.0 22.6 25.0 30.0 24000 4.8 7.2 9.6 12.0 14.4 19.2 21.7 24.0 28.7 25000 4.6 6.9 9.2 11.5 13.8 18.4 20.8 23.0 27.6 26000 4.4 6.7 8.8 11.1 13.3 17.7 20.0 22.1 26.5 27000 4.3 6.4 8.5 10.7 12.8 17.0 19.3 21.3 25.5 200 4.1 6.2 8.2 10.3 12.3 16.4 18.6 20.5 24.6 29000 4.0 6.0 7.9 9.9 11.9 15.9 17.9 19.8 23.8 30000 3.8 5.8 7.6 9.6 11.5 15.3 17.3 19.2 23.0 Note: The maximum temperature rise allowed for electric heat is 60 F with leaving air temperature not to exceed 140 F. Note: The minimum airflow required for units 045C-0C with electric heat is 14,000 cfm. Table 47: RPS0C-135C-230,460, 5V Electric Heat Air Temperature Rise ( F) Electric Heater Model Number Airflow (cfm) 100 120 160 200 240 2 320 Electric Heater Capacity (MBH) 249 312 374 499 624 748 873 998 22000 10.4 13.1 15.7 20.9 26.1 31.3 36.6 41.8 24000 9.6 12.0 14.4 19.2 24.0 28.7 33.5 38.3 26000 8.8 11.1 13.3 17.7 22.1 26.5 30.9 35.4 200 8.2 10.3 12.3 16.4 20.5 24.6 28.7 32.9 30000 7.6 9.6 11.5 15.3 19.2 23.0 26.8 30.7 32000 7.2 9.0 10.8 14.4 18.0 21.5 25.1 28.7 34000 6.7 8.5 10.1 13.5 16.9 20.3 23.7 27.1 36000 6.4 8.0 9.6 12.8 16.0 19.2 22.4 25.6 300 6.0 7.6 9.1 12.1 15.1 18.1 21.2 24.2 40000 5.7 7.2 8.6 11.5 14.4 17.2 20.1 23.0 42000 5.5 6.8 8.2 11.0 13.7 16.4 19.2 21.9 44000 5.2 6.5 7.8 10.5 13.1 15.7 18.3 20.9 46000 5.0 6.3 7.5 10.0 12.5 15.0 17.5 20.0 400 4.8 6.0 7.2 9.6 12.0 14.4 16.8 19.2 50000 4.6 5.8 6.9 9.2 11.5 13.8 16.1 18.4 Note: The maximum temperature rise allowed for electric heat is 60 F with leaving air temperature not to exceed 140 F. Note: The minimum airflow required for units 0C-135C with electric heat is 22,000 cfm. Cat 214-5 57

Hot Water Heat RPS015C-040C Figure 17: Hot Water Coil, Low Capacity, RPS015C-040C Figure 19: Hot Water Coil Pressure Drop (Headers Included), RPS015C-040C Figure 20: Hot Water Valve and Piping Pressure Drop, RPS015C-040C Figure 18: Hot Water Coil, High Capacity, RPS015C-040C 58 Cat 214-5

RPS045C-135C Figure 21: Hot Water Coil, Low Capacity, RPS045C- 0C Figure 22: Hot Water Coil, High Capacity, RPS045C- 0C Figure 23: Hot Water Coil, Low Capacity, RPS0C- 135C Figure 24: Hot Water Coil, High Capacity, RPS0C- 135C Figure 25: Hot Water Coil Pressure Drop (Headers Included), RPS045C-135C Cat 214-5 59

Figure 26: Hot Water Valve Pressure Drop RPS045C-135C Figure 27: Hot Water Valve Piping Pressure Drop RPS045C-135C 60 Cat 214-5

Steam Heat Figure 28: Steam Coil, Low Capacity, RPS015C-040C Figure 29: Steam Coil, High Capacity, RPS015C-040C Figure 30: Steam Coil, Low Capacity, RPS045C-0C Figure 31: Steam Coil, Medium Capacity, RPS045C-0C Cat 214-5 61

Figure 32: Steam Coil, High Capacity, RPS045C-0C Figure 33: Steam Coil, Low Capacity, RPS0C-135C Figure 34: Steam Coil, Medium Capacity, RPS0C- 135C Figure 35: Steam Coil, High Capacity, RPS0C- 135C 62 Cat 214-5

Table 48: Saturated Steam Properties Pressure (psig) Temperature ( F) Latent Heat (Btu/lb.) 2 218.5 966.1 5 227.1 960.6 10 239.4 952.6 15 249.7 945.7 25 266.8 934.0 Table 49: Steam Valve Selection Chart Condensate Rate, lb./hr. Valve Size (inches) Steam Supply Pressure a 5 psig 10 psig 15 psig 25 psig 1 196-260 301-3 391-4 571-650 1-1/4 261-3 381-560 481-700 651-940 1-1/2 381-600 561-870 701-1090 940-1470 2 601-950 871-1390 1091-10 1471-2350 2-1/2 951-1330 1391-1940 11-2450 2351-3290 3 1331-2020 1941-2950 2451-3716 - a. Based on valve pressure drop of % of saturated steam supply pressure. Cat 214-5 63

Component Pressure Drops Table 50: RPS015C-040C (in. w.g.) Unit Airflow (cfm) Angular Rack 30% Pleated Pre- Filters Filter Evaporator Coils a Flat Rack 018C - 020C 025C - 040C 65% Cartr. 95% Cartr. 5-row 8 fpi 5-row 10 fpi 5-row 5-row 8 fpi 5-row 10 fpi 5-row 4,000.02.06.08.12.16.19.23 - - - 5,000.03.08.12.17.22.27.33 - - - 6,000.04.10.16.23.30.35.42.17.20.24 7,000.05.13.20.29.37.44.53.21.25.30 8,000.07.16.25.35.45.54.64.26.31.37 9,000.08.19.31.42.54.64..31.36.43 10,000.09.22.36.49.63.74.87.36.42.50 11,000.10.25.43.56.72.84.99.41.49.58 12,000.12.28.49.64.81.95 -.46.55.65 13,000.13.32.56.72 - - -.54.64. 14,000.14.35.63.81 - - -.60.71.84 15,000.16.39.71.89 - - -.67.79.92 16,000.18.43.79.98 - - -.73.86 1.01 17,000.19.47.87 1.07 - - -..94-18,000.21.50.95 1.17 - - - - - - a. Pressure drop is for wet coil. Table 51: RPS015C-040C (in. w.g.) Unit Airflow (cfm) Dampers Coils Discharge Return Hot Water Steam 018C-030C 018C-030C Low Cap. High Cap. Low Cap. High Cap. Economizer Return Damper 100% O.A. Hood With Dampers 4,000.02.01.03.05.02.04.01.01 5,000.03.01.04.08.03.06.02.01 6,000.05.02.06.11.04.07.03.01 7,000.06.03.08.14.05.09.04.02 8,000.08.04.09.18.06.11.05.02 9,000.10.05.12.22.07.13.07.03 10,000.13.06.14.27.08.14.08.03 11,000.15.07.17.31.09.16.10.04 12,000.18.08.20.36.10.18.12.05 13,000.22.09.22.41.11.20.15.06 14,000.25.11.26.46.12.23.17.06 15,000.29.13.29.53.13.25.20.07 16,000.33.14.32.60.15.27.23.08 17,000.35.15.36.66.16.30.26.09 18,000.37.16.40.74.17.32.29.10 64 Cat 214-5

Table 52: RPS045C-0C Outdoor/Re turn Air Options a b Filter Options Plenum Options Cooling Options c d Heating Options c Airflow (cfm) Component 14,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 0-30% outside air hood w/damper 0.06 0.08 0.10 0.12 0.15 0.18 0.21 0.24 0.28 100% outside air hood w/damper 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.05 0.06 0-100% economizer, w/o RAF 0.08 0.10 0.13 0.16 0.19 0.23 0.27 0.31 0.36 0-100% economizer, w/raf 0.21 0.25 0.29 0.33 0.38 0.43 0.48 0.54 0.59 30% pleated 0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.25 0.27 Prefilter, standard flow 0.17 0.20 0.24 0.28 0.32 0.37 0.41 - - Prefilter, medium flow 0.13 0.15 0.18 0.21 0.25 0.28 0.32 0.35 0.39 65% cartridge, standard flow 0.27 0.34 0.41 0.49 0.57 0.66 0.76 - - 65% cartridge, medium flow 0.20 0.25 0.31 0.36 0.43 0.49 0.56 0.63 0.71 95% cartridge, standard flow 0.38 0.46 0.55 0.64 0.74 0.84 0.95 - - 95% cartridge, medium flow 0.29 0.35 0.42 0.49 0.56 0.64 0.72 0.81 0.89 Return, isolation damper 0.02 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 Discharge, isolation damper 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 DX, low airflow, 5-row, 10 fpi 0.41 0.50 0.59 0.69 0.79 0.89 - - - DX, low airflow, 5-row, 0.49 0.59 0.70 0.81 0.93 - - - - DX, high airflow, 5-row, 10 fpi - 0.38 0.45 0.52 0.60 0.68 0.79 0.88 0.98 DX, high airflow, 5-row, - 0.45 0.54 0.62 0.71 0. 0.93 1.04 - DX, high airflow, 6-row, 10 fpi f - 0.46 0.54 0.62 0.72 0.82 0.95 1.06 1.28 Cooling diffuser e 0.04 0.05 0.06 0.08 0.10 0.11 0.13 0.15 0.18 Hot water, 1-row 0.12 0.15 0.19 0.22 0.26 0.30 0.35 0.39 0.44 Hot water, 2-row 0.24 0.30 0.37 0.44 0.52 0.61 0.69 0.78 0.88 Steam, 1-row, 6 fpi 0.10 0.12 0.15 0.18 0.21 0.24 0.27 0.31 0.35 Steam, 1-row, 0.16 0.20 0.24 0.28 0.33 0.38 0.43 0.48 0.54 Steam, 2-row, 6 fpi 0.19 0.24 0.30 0.35 0.41 0.48 0.55 0.62 0.70 Electric heat 0.07 0.10 0.12 0.15 0.18 0.22 0.25 0.29 0.34 Gas heat See Table 55: Furnace Pressure Drop (in. W.C.) - RPS015C-135C on page 67 a. Pressure drop through hood and damper is based on 30% of listed airflow. b. Pressure drop through the economizer assumes that all of the air will be passing through the return air dampers. c. Pressure drop through coils can be found in the McQuay selection program output. d. DX coil pressure drops are based on wet coils. e. A cooling diffuser is provided on units with blow-through cooling only. f. Only available on RPS 0 C with reciprocating compressors. Cat 214-5 65

Table 53: RPS0C-135C Outdoor/ Return Air Options a b Filter Options Plenum Options Airflow (cfm) Component 18,000 22,000 26,000 30,000 34,000 38,000 42,000 46,000 50,000 0-30% outside air hood w/damper 0.05 0.08 0.11 0.14 0.18 0.23 0.28 0.34 0.40 100% outside air hood w/damper 0.01 0.02 0.03 0.03 0.04 0.06 0.07 0.08 0.09 Economizer, w/o RAF 0.06 0.10 0.15 0.20 0.26 0.32 0.39 0.46 0.54 Economizer, w/raf 0.16 0.22 0.29 0.36 0.44 0.52 0.61 0.70 0. 2" throwaway 0.15 0.07 0.09 0.11 0.13 - - - - 30% pleated 0.06 0.08 0.11 0.13 0.15 0.18 0.21 0.24 0.27 Prefilter, standard flow 0.15 0.20 0.24 0.31 0.37 - - - - Prefilter, medium flow 0.12 0.16 0.21 0.25 0.31 0.36 - - - Prefilter, high flow 0.09 0.12 0.15 0.18 0.22 0.26 0.30 0.34 0.39 65% cartridge, standard flow 0.24 0.33 0.43 0.55 0.68 - - - - 65% cartridge, medium flow 0.19 0.27 0.35 0.44 0.54 0.65 - - - 65% cartridge, high flow 0.13 0.18 0.24 0.31 0.38 0.45 0.53 0.62 0.71 95% cartridge, standard flow 0.33 0.45 0.57 0.71 0. - - - - 95% cartridge, medium flow 0.27 0.37 0.47 0.58 0.70 0.83 - - - 95% cartridge, high flow 0.19 0.26 0.34 0.42 0.50 0.59 0.69 0.79 0.89 Return, isolation damper 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.03 0.03 Discharge, isolation damper 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 Cooling Cooling diffuser 0.04 0.05 0.07 0.10 0.13 0.16 0.19 0.23 0.28 Options c Cooling coils See Table 54: Cooling Coil Air Pressure Drops-RPS0C-135C on page 66 Hot water, 1-row 0.10 0.14 0.19 0.24 0.30 0.36 0.43 0.50 0.58 Hot water, 2-row 0.20 0.28 0.38 0.48 0.60 0.72 0.86 1.00 1.16 Heating Options d Steam, 1-row, 6 fpi 0.10 0.12 0.15 0.19 0.24 0.29 0.34 0.40 0.46 Steam, 1-row, 0.14 0.19 0.25 0.31 0.37 0.45 0.52 0.60 0.69 Steam, 2-row, 6 fpi 0.16 0.23 0.30 0.39 0.48 0.58 0.68 0. 0.92 Electric heat 0.07 0.10 0.14 0.19 0.24 0.30 0.37 0.45 0.53 Gas heat See Table 55: Furnace Pressure Drop (in. W.C.) - RPS015C-135C on page 67 a. Pressure drop through hood and damper is based on 30% of listed airflow. b. Pressure drop through the economizer assumes that the majority of air will be passing through the return air dampers. If large quantities of outside air are required, pressure drops will increase causing airflow to decrease. c. A cooling diffuser is provided on units with blow-through cooling only. d. Pressure drop through coils can be found in the McQuay selection program output. Table 54: Cooling Coil Air Pressure Drops-RPS0C-135C Unit Size Cooling Coil Airflow (cfm) 200 30000 32000 34000 36000 300 40000 42000 44000 46000 400 50000 DX, low airflow, 5-row, 10fpi 0.72 0.78 0.87 0.95 - - - - - - - - 0C- 090C 105C- 135C DX, low airflow, 5-row, 12fpi 0. 0.92 1.02 - - - - - - - - - DX, high airflow, 5-row, 10fpi 0.60 0.65 0.72 0.79 0.86 0.93 - - - - - - DX, high airflow, 5-row, 12fpi 0.71 0.77 0. 0.93 1.01 - - - - - - - DX, low airflow, 5-row, 10fpi 0.60 0.67 0.74 0.81 0.88 0.95 - - - - - - DX, low airflow, 5-row, 12fpi 0.72 0. 0.87 0.95 1.04 - - - - - - - DX, high airflow, 5-row, 10fpi 0.43 0.48 0.53 0.58 0.63 0.68 0.73 0.78 0.84 0.89 0.95 1.01 DX, high airflow, 5-row, 12fpi 0.52 0.57 0.62 0.68 0.74 0. 0.86 0.92 0.98 1.05 - - Note: DX coil pressure drops are based on wet coils. Note: Pressure drop of cooling coils not shown can be found in the McQuay selection program output. 66 Cat 214-5

Table 55: Furnace Pressure Drop (in. W.C.) - RPS015C-135C Airflow (cfm) Column Number See Table 40 on page 54 1 2 3 4 5 6 7 8 9 10 4000 0.06 0.05 - - - - - - - - 6000 0.13 0.1 - - - - - - - - 00 0.24 0.17 0.14 0.08 0.07 - - - - - 10000 0.37 0.27 0.22 0.12 0.11 0.09 0.08 - - - 12000 0.53 0.39 0.32 0.17 0.16 0.13 0.12 0.09 0.08-14000 0.72 0.54 0.44 0.24 0.21 0.18 0.16 0.12 0.1 0.1 16000 0.94 0.7 0.57 0.31 0.28 0.24 0.2 0.15 0.13 0.12 100 1.19 0.89 0.72 0.39 0.35 0.3 0.26 0.19 0.17 0.16 20000-1.09 0.89 0.48 0.43 0.37 0.32 0.24 0.21 0.2 22000 - - 1.08 0.58 0.52 0.44 0.39 0.29 0.25 0.24 24000 - - - 0.69 0.62 0.53 0.46 0.34 0.3 0.28 26000 - - - 0.81 0.73 0.62 0.54 0.4 0.35 0.33 200 - - - 0.94 0. 0.72 0.63 0.47 0.41 0.38 30000 - - - 1.08 0.97 0.83 0.72 0.54 0.47 0.44 32000 - - - 1.23 1.11 0.94 0.82 0.61 0.53 0.5 34000 - - - - 1.25 1.06 0.92 0.69 0.6 0.56 36000 - - - - - 1.19 1.04 0.77 0.68 0.63 300 - - - - - - 1.15 0.86 0. 0.7 40000 - - - - - - - 0.95 0.84 0.78 42000 - - - - - - - 1.05 0.92 0.86 44000 - - - - - - - 1.15 1.01 0.94 46000 - - - - - - - - 1.11 1.03 400 - - - - - - - - 1.2 1.12 50000 - - - - - - - - - 1.22 Table 56: Gravity Relief Damper Air Pressure Drop - 0-100% Economizer Exhaust CFM 5000 10000 15000 20000 25000 30000 35000 40000 Size 15-40 -.25.54 - - - - - Size 45- - -.36.61 1.00 - - - Size -135 - - -.25.35.48.66. Note: If all exhaust must occur through the economizer gravity relief damper, and no return or exhaust fan is provided, then the building may be pressurized by the sum of the return duct pressure drop plus the gravity relief pressure. Cat 214-5 67

Fan Performance Data - Supply Fans Figure 36: RPS/RFS015C-030C (2) 15 in.x6 in. Forward Curved Supply Fan Figure 37: RPS/RFS015C-030C (2) 15 in.x15 in. Forward Curved Supply Fan 68 Cat 214-5

Figure 38: RPS/RFS015C-030C 20 in. Airfoil Supply Fan without Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Figure 39: RPS/RFS015C-030C 20 in. Airfoil Supply Fan with Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Cat 214-5 69

Figure 40: RPS/RFS036C-040C 24 in. Forward Curve Supply Fan Class II Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Figure 41: RPS/RFS036C-040C 24 in. Airfoil Supply Fan without Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). 70 Cat 214-5

Figure 42: RPS/RFS036C-040C 24 in. Airfoil Supply Fan with Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Figure 43: RPS/RFS045C-050C 27 in. Forward Curved Supply Fan Class II Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Cat 214-5 71

Figure 44: RPS/RFS045C-050C 27 in. Airfoil Supply Fan without Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Figure 45: RPS/RFS045C-050C 27 in. Airfoil Supply Fan with Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). 72 Cat 214-5

Figure 46: RPS/RFS045C-0C 30 in. Forward Curved Supply Fan Class II Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Figure 47: RPS/RFS045C-0C 30 in. Airfoil Supply Fan without Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Cat 214-5 73

Figure 48: RPS/RFS045C-0C 30 in. Airfoil Supply Fan with Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Figure 49: RPS/RFS060C-0C 33 in. Forward Curved Supply Fan Class II Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). 74 Cat 214-5

Figure 50: RPS/RFS060C-0C 33 in. Airfoil Supply Fan without Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Figure 51: RPS/RFS060C-0C 33 in. Airfoil Supply Fan with Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Cat 214-5

Figure 52: RPS/RFS0C-090C 33 in. Airfoil Supply Fan without Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Figure 53: RPS/RFS0C-090C 33 in. Airfoil Supply Fan with Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). 76 Cat 214-5

Figure 54: RPS/RFS0C-135C 36 in. Airfoil Supply Fan without Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Figure 55: RPS/RFS0C-135C 36 in. Airfoil Supply Fan with Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Cat 214-5 77

Figure 56: RPS/RFS105C-135C 40 in. Airfoil without Vanes Note: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops cannot exceed 5.0 in). Figure 57: RPS/RFS105C-135C 40 in. Airfoil with Vanes 78 Cat 214-5

Fan Performance Data - Propeller Exhaust Fans Figure 58: RPS/RFS045C-135C (1) 36 in. Propeller Exhaust Fan # 4 2 % # # - N JA H = 5 J= JE? 2 H A I I K H A E M C # % # ' & % " # $ > D F # $! # # " " $ & " $ & ) EH B M? B Figure 59: RPS/RFS045C-135C (2) 36 in. Propeller Exhaust Fan # 4 2 % # - N JA H = 5 J= JE? 2 H A I I K H A E M C # # % # # ' & % $ * 0 2 & # $ # " " " & $ " &!! $ " ) EH B M? B Cat 214-5 79

Figure 60: RPS/RFS0C-135C (3) 36 in. Propeller Exhaust Fan # 4 2 % # - N JA H = 5 J= JE? 2 H A I I K H A E M C # # % # # ' & % $ # & * 0 2 # ' # " $! $ & "!! $ " " & # " $ ) EH B M? B Cat 214-5

Fan Performance Data - Return Fans Figure 61: RPS/RFS015C-030C, (2) 15 in.x15 in. Forward Curved Return Fan Figure 62: RPS/RFS015C-040C, 30 in. Airfoil Return Fan without Vanes Figure 63: RPS/RFS015C-040C, 30 in. Airfoil Return Fan with Vanes Back return performance correction. For 30 in. airfoil fan with back return, add the following static pressure to the design return duct static pressure. Enter Figure 63 and Figure 62 at this greater static pressure and the design airflow to determine actual back return performance. Additional back return static pressure, 30 in. airfoil with or without vanes. Airflow (cfm) 4,000 6,000 8,000 10,000 12,000 14,000 Back Return SP (in. W.G.) 0.05 0.12 0.21 0.33 0.48 0.65 Cat 214-5 81

Figure 64: RPS/RFS036C-040C, 40 in. Airfoil Return Fan without Vanes (Bottom Return Only) Figure 65: RPS/RFS036C-040C, 40 in. Airfoil Return Fan with Vanes (Bottom Return Only) Figure 66: RPS045C-0C 40 in. Airfoil Return Fan without Vanes! 5 J= JE? 2 HA I I K HA E M C # # # % $ # " " $ & " $ & " $ &!!! " ) EHB M? B 82 Cat 214-5

Figure 67: RPS045C-0C 40 in. Airfoil Return Fan with Vanes! 5 J= JE? 2 HA I I K HA E M C # # # % $ # "! & " $ & " $ & " $ &!!! " ) EHB M? B # ' % # # #! * 0 2 # Figure 68: RPS0C-135C, Standard 44 in. Airfoil Return Fan without Vanes 5 J= JE? 2 HA I I K HA E M C! # # # $ # % & # ' #! " $ * 0 2 # 4 2 % # # " & $ " &!! $ " " " " & # ) EHB M? B Figure 69: RPS0C-135C 44 in. Airfoil Return Fan with Vanes! 5 J= JE? 2 HA I I K HA E M C # # # $ # % # % # & ' # #! " # 4 2 $ * 0 2 " & $ " &!! $ " " " " & # ) EHB M? B Cat 214-5 83

Dimensional Data Section Options and Locations Figures show section options, curb lengths, and relative positions. Curb lengths (in inches) are shown below each icon. Figure 70: RPS/RFS/RCS015C-030C - Draw-through Coil Section 84 Cat 214-5

Figure 71: RPS/RFS/RCS036C and 040C Blow-through Coil Section (NA Final Filters) Figure 72: RPS/RFS/RCS036C and 040C Draw-through Coil Section Cat 214-5

Figure 73: RPS/RFS/RCS045C-0C Blow-through Coil Section (NA Final Filters) Outdoor/ Return Air Mandatory Filter Mandatory Blank Optional Supply Air Fan Mandatory Heat Mandatory Blank Optional DX Coil Mandatory Discharge Plenum Mandatory Blank Compartment Optional Air-cooled Condensing Unit Outdoor Air Hood Angular Blank 045C-050C 27 & 30 Dia Steam/Hot Water Blank 045C (39.5 sq. Ft.) Discharge Plenum 070C-0C Blank Compartment 045C-060C Air-cooled Condenser 0 Plenum 24 Cartridge (40 sq. Ft) 48 VFD Section 72 060C-0C 30 Dia 48 Electric 48 Sound Attenuator 24 050C-0C (39.5 sq. ft.) 48 72 83 (Does not affect curb length) 48 30% Outside Air 24 Cartridge (48 sq. Ft.) 48 72 33 Dia 48 Gas 48 Sound Attenuator* 24 (47.1 sq. ft.) 070C-0C Air-cooled Condenser 48 Economizer 48 Blender & Angular or 40 sq ft Cartridge 96 48 Blank 72 48 119 (Does not affect curb length) 72 Economizer w/ Return Air Fan 72 Blender & 48 sq ft Cartridge 48 72 Econ w/ Prop. Exh. Fans, Bottom or Back Ret. Fans 96 Blank 72 Econ w/ Prop. Exh. & Side Ret. Fans 24 or 48 120 Figure 74: RPS/RFS/RCS045C-0C Draw-through Coil Section Outdoor/ Return Air Mandatory Filter Mandatory Blank Optional DX Coil Mandatory Supply Air Fan Mandatory Heat Mandatory Blank Optional Final Filter Optional Discharge Plenum Mandatory Blank Compartment Optional Air-cooled Condensing Unit Outdoor Air Hood Angular Blank 045C (39.5 sq. Ft.) 045C-050C 27 & 30 Dia Steam/ Hot Water Blank Cooling Only, Steam or Hot Water (40 sq. Ft.) Discharge Plenum 070C-0C Blank Compartment 045C-060C Air-cooled Condenser 0 Plenum 24 Cartridge (40 sq. Ft.) 48 VFD Section 24 050C-070C (39.5 sq. Ft.) 72 060C-0C 30 Dia 48 Electric 48 Cooling Only, Steam or Hot Water Sound Attenuator 48 Gas or Electric Heat (48 sq. Ft.) 48 72 83 (Does not affect curb length) 070C-0C 48 30% Outside Air 48 Economizer 24 Cartridge (48 sq. Ft.) 48 Blender & Angular or 40 sq ft Cartridge 48 24 (47.1 sq. ft.) 48 72 33 Dia 96 48 Gas 48 Blank 48 Gas or Electric Heat Sound Attenuator* 72 Blank 48 Air-cooled Condenser 119 (Does not affect curb length) 72 Blank 72 Economizer w/ Return Air Fan 72 Blender & 48 sq ft Cartridge 48 72 72 96 Econ w/ Prop. Exh. Fans, Bottom or Back Ret. Fans Blank 24 or 48 72 Econ w/ Prop. Exh. & Side Ret. Fans 120 Note: Exhaust Fan Section dimensions do not include the hood. See page 98. 86 Cat 214-5

Figure : RPS/RFS/RCS0C-135C Blow-through Coil Section (NA Final Filters) Outdoor/ Return Air Mandatory Filter Mandatory Blank Optional Supply Air Fan Mandatory Heat Mandatory Blank Optional DX Coil Mandatory Discharge Plenum Mandatory Blank Compartment Optional Air-cooled Condensing Unit Outdoor Air Hood Angular Blank 0C-090C 33 Dia Steam/ Hot Water Blank 0C-090C (53.9 sq. Ft.) Discharge Plenum Blank Compartment 0C-105C Air-cooled Condenser 0 Plenum 24 Cartridge (56 sq. Ft.) (0C-090C only) 48 VFD Section 72 36 Dia 48 Electric 48 Sound Attenuator 24 (60.8 sq. Ft.) 48 72 119 (Does not affect curb length) 115C-135C 72 30% Outside Air 24 Cartridge (64 sq. Ft.) (0C-135C only) 48 96 105C-115C 36 & 40 Dia 48 Gas 48 Sound Attenuator* 48 105C-115C (60.8 sq. Ft.) Air-cooled Condenser 72 Economizer 48 Cartridge ( sq. Ft.) (105C-135C only) 96 48 Blank 72 48 (76.0 sq. Ft.) 139 (Does not affect curb length) 96 48 Economizer w/ Return Air Fan 72 Blender & Angular or 56 sq ft Cartridge 72 125C-135C (76.0 sq. Ft.) 96 72 Econ w/ Prop. Exh. Fans, Bottom or Back Ret. Fans Blender & 64 sq ft Cartridge 72 72 Econ w/ Prop. Exh. & Side Ret. Fans 96 Blank 120 24 or 48 Figure 76: RPS/RFS/RCS0C-135C Draw-through Coil Section Outdoor/ Return Air Mandatory Filter Mandatory Blank Optional DX Coil Mandatory Supply Air Fan Mandatory Heat Mandatory Blank Optional Final Filter Optional Discharge Plenum Mandatory Blank Compartment Optional Air-cooled Condensing Unit Outdoor Air Hood Angular Blank 0C-090C (53.9 sq. Ft.) 0C-090C 33 Dia Steam/ Hot Water Blank Cooling Only, Steam or Hot Water (56 sq. Ft.) (0C-090C only) Discharge Plenum Blank Compartment 0C-105C Air-cooled Condenser 0 Plenum 72 30% Outside Air 24 Cartridge (56 sq. Ft.) (0C-090C only) 24 Cartridge (64 sq. Ft.) (0C-135C only) 48 VFD Section 48 24 (60.8 sq. Ft.) 48 105C-115C 72 36 Dia 96 105C-135C 48 Electric 48 Gas 48 Cooling Only, Steam or Hot Water Sound Attenuator 48 48 Gas or Electric Heat (64 sq. Ft.) 48 72 119 (Does not affect curb length) 115C-135C Air-cooled Condenser 72 Economizer 48 Cartridge ( sq. Ft.) (105C-135C only) (60.8 sq. Ft.) 48 (76.0 sq. Ft.) 36 & 40 Dia 96 48 Blank Gas or Electric Heat Sound Attenuator* 72 72 ( sq. Ft.) (105C-135C only) 96 139 (Does not affect curb length) 96 72 48 Blank Economizer w/ Return Air Fan Blender & Angular or 56 sq ft Cartridge 72 125C-135C 48 (76.0 sq. Ft.) Blank 96 72 Econ w/ Prop. Exh. Fans, Bottom or Back Ret. Fans Blender & 64 sq ft Cartridge 72 72 72 Econ w/ Prop. Exh. & Side Ret. Fans 96 Blank 120 24 or 48 Note: Exhaust Fan Section dimensions do not include the hood. See page 99. Cat 214-5 87

Use Figure 70 through Figure 76 to determine the total air handler length and total unit length. The total air handler length is needed to determine roof curb knockouts. The total air handler length incudes all unit sections except the air cooled condensing section. Example: RPS 045C with Draw-through Coil Section (from Figure 78) Section Description Length (in.) Economizer with return air fan 72 Angular filters 24 Cooling coil 24 Supply fan 72 Gas heat 48 Final filter, standard flow 48 Discharge plenum 48 Air cooled condensing unit 83 Total air handler length = 336 Total unit length (including condensing 419 unit)= Consult you local McQuay sales representative for a custom certified drawing of your specific requirements. Table 57: RPS/RFS015C-040C Return Air Opening Size Unit Size Return Air Selection Bottom Return Back Return A B C D E Plenum, with or without 30% OA Hood 24 82 6 20 86.5 RPS/RFS/015C-040C Economizer 24 82 6 20 86.5 Economizer with 2-15 in. x 15 in. RAF 24 82 6 20 86.5 Economizer with 30 in. RAF 30 76 9 16 86.5 RPS/RFS036C-040C Economizer with 40in. RAF 36 78 8 NA NA 88 Cat 214-5

Figure 77: RPS/RFS/RCS015C-040C Typical Configuration! & + ) 5 K F F O ) EH F A E C # 2 6, H= E $! & 7 EJ5 D M $ + 4 A JK H ) EH2 K ) C K = H E JA H5 A? JE " 5 K F F O ) EH = 0 A = J M ) EHB M, : + E 5 A? JE, EI? D = HC A 2 A K ' " - * % $ & $ # * =? 4 A JK H F A E C F JE =! & + 4 A JK H ) EH 2 A K * JJ 4 A JK H F A E C! & 4 5 5 A A, A J= E!! & 4 2 5 5 K F F O = 0 A = J5 A? JE, EI? D = HC A ) EH 2 A K # " " "! & 4 + 5 H J F A E C F JE = -, O # # #, % &! $ E JA H5 A? JE 4 5 & %, H= E + A? JE! $ = E + JH 2 = A - L = F + E I Note: 1. Unit length varies depending on the configuration (sections and options ordered). See Figure 70 through Figure 72 for air handler section lengths. 2. Figures illustrate an RFS/RCS configuration. An RPS would be a single piece. Figure 78: RPS/RFS/RCS045C-0C Note: 1. Unit length varies depending on the configuration (sections and options ordered). See Figure 73 through Figure 74 for air handler section lengths. 2. Figures illustrate an RFS/RCS configuration. An RPS would be a single piece. Cat 214-5 89

Figure 79: RPS/RFS/RCS0C-090C & $! & 5 K F F O ) EH F A E C # 2 6, H= E & $ & 7 EJ5 D M $ + 4 A JK H ) EH2 K ) C K = H E JA H5 A? JE! 5 K F F O ) EH = 0 A = J M ) EHB M, : + E 5 A? JE, EI? D = HC A 2 A K ' ' '! # & % & '! # * =? 4 A JK H F A E C F JE = & $ 4 A JK H ) EH 2 A K * JJ 4 A JK H F A E C $ " 4 5 5 A A, A J= E! " % 4 2 5 5 K F F O = 0 A = J5 A? JE, EI? D = HC A ) EH 2 A K " & " " " & " & " " & & &! 4 + 5 H J F A E C F JE = 4 5 O &! %!! &! & % & % E JA H5 A? JE 4 5 ", H= E + A? JE % = E + JH 2 = A - L = F + E I 4 + 5 Figure : RPS/RFS/RCS105C-135C Note: 1. Unit length varies depending on the configuration (sections and options ordered). See Figure through Figure 76 for air handler section lengths. 2. Figures illustrate an RFS/RCS configuration. An RPS would be a single piece. 3. RPS105C condensing section is 119 in. 90 Cat 214-5

Electrical Knockout Locations Figure 82: Electric Heat/Heat Section Figure 81: Main Control Panel/Discharge Plenum 4 A BA HA? A BH A = L E C = EHA @ BI A? JE & &!, E= 3 JO! % $ ', E= 3 JO " ' ' #! % % & %! "! $ $!, E= 3 JO ', E= '!!!! % $ $ % $ & & Piping Entrance Locations Note: RPS045C-135C only 208/230/60/3, >160kW only Figure 83: Steam and Hot Water Heat/Heat Section Figure : 200-1400MBH Gas Heat/Heat Section 120 to 1400 MBH A l Piping Entrance Holes Should Fa l W ithin This Area UnitSize A B C D 015C -040C 6.0 12.0 5.0 2.7 045C -135C 8.6 6.0 4.2 4.0 B A R ecom m ended Piping Entrance (Through the Curb) D C UnitSize A B C D 015C -030C 6.0 6.5 1.0 29.0 045C -135C 6.0 9.0 1.0 37.0 B A Figure 84: 1500-2000MBH Gas Heat/Heat Section # * 0 C D 4 A? A @ A @ 2 EF E C - JH=? A 4 B2 EJ? D 2? A J4 A G K EHA @ & Cat 214-5 91

Roof Curbs Figure 86: Roof Curb, RPS/RFS015C - 040C (without blank compartment) + ) $ &, # $ 4 2 5 O * 4 ) 2 / 5 ) 2 / % $ ' % * * ), 6 O F " 6 O F ) 7 EJ A C JD E K I $ " 5 A A? K J, A J= E % # $ ' & Note: Roof Curb must be installed level. Figure 87: Roof Curb, RPS/RFS015C - 040C (with blank compartment), + ) " $ & $ & # $ 4 2 5 O * 4 ) 2 / 5 ) 2 / % $ ' % * * ), 6 O F " 6 O F ) 7 EJ A C JD E K I $ " 5 A A? K J, A J= E % # $ ' & Table 58: RPS/RFS015C-040C Roof Curb Dimensions Figure 88: Detail B Model Return Fan A (in.) B (in.) C (in.) D (in.) E (in.) None 24 82 6.8 1.5 42 015C-030C (2) 15 in. FC 24 82 6.8 1.5 42 30 in. AF 30 76 6.8 4.5 42 None 24 82 6.8 1.5 90 036C-040C 30 in. AF 30 76 6.8 4.5 90 40 in. AF 36 78 14.8 3.5 90 Figure 89: RPS/RFS015C-040C Curb Section A-A Figure 90: RPS/RFS015C-040C Curb Section B-B 92 Cat 214-5

Figure 91: Roof Curb, RPS/RFS045C-135C (without blank compartment) Note: Roof Curb must be installed level. Figure 92: Roof Curb, RPS/RFS045C-135C (with blank compartment) Table 59: RPS/RFS045C-135C Variable Dimensions Figure 93: Detail B MODEL SIZE D: SUPPLY AIR OPENING C: RETURN AIR OPENING B 045C-0C 28 38 RPS 0C-090C 38 62 111 105C-135C 46 62 111 Figure 94: RPS/RFS045C-135C Curb Section B-B Figure 95: RPS/RFS045C-135C Curb Section A-A Cat 214-5 93

Figure 96: RCS Roof Installation RCS UNIT SIZE ZZ IN. MM 015C 030C 31.0 787 036C & 040C 94.0 2057 045C 060C 62.0 15 070C 0C 100.0 2540 $ ) * ) $ $ * ) ) $ 4 + 5 4 = E + H I I 5 A? JE # % $ " & "! # 7 EJ* = I A / = L = E A @ + K H>! / = L = E A @ + K EH> + L A H " N " = E A H5 JHEF # 4 EC E@ 1 I K = JE JBK H EI D A @ $ + = J5 JHEF JBK H EI D A @ % = I D E C JBK H EI D A @ & + K H> / = I A JE C ' 1 I K = JE > A JM A A / = L = E A @ + K H> JBK H EI D A @ 4 BE C = JA HE= JBK H EI D A @ ' 94 Cat 214-5

Figure 97: RFS/RCS 015-030 Refrigerant Piping Connections ; : 0 / 5 0 / 5 5 : ; 0 / 0 / 5 Figure 98: RFS/RCS 036 & 040 Refrigerant Piping Connections ; 0 / 0 / : 0 / 5 5 : ; 5 5 0 / Table 60: S1 Component Circuit Suction Line Connection Sizes 015C 020C 025C 030C- 040C Connection Locations RCS 036 RFS/RFR 015-030 RCS 015-030 RFS/RFR 036 & 040 & 040 X (in.) Y (in.) X (in.) Y (in.) X (in.) Y (in.) X (in.) Ckt.1 1-1/8 1-1/8 1-5/8 1-5/8 9.00 5.70 67.60 6.25 8.25 5.70 59.50 S2 Suction Line Ckt.2 1-3/8 1-5/8 1-3/8 1-5/8 14.00 5.70 28.00 6.25 13.25 5.70 34.60 L1 Liquid Line Ckt.1 5/8 5/8 7/8 7/8 56.00 32.00.00 6.25 79.00 25.00 70.50 L2 Liquid Line Ckt.2 7/8 7/8 7/8 7/8 7.60 28.00 21.00 6.25 15.00 25.00 23.50 HG1 HGBP Line Ckt.1 7/8 7/8 7/8 7/8 52.00 10.00 60. 6.25 67.00 6.70 64.60 HG2 HGBP Line Ckt.2 7/8 7/8 7/8 7/8 36.00 16.00 35.50 6.25 32.00 6.70 29.50 Cat 214-5 95

Figure 99: Split Unit Physical Data--RFS, RCS RPS Split at Condensers (045C-135C) 4 5 4 + 5 ; ; : : 5 5 2 0 0 5 0 5 0 Note: This figure illustrates piping locations for and RPS split at the condenser section and for an RFS/RCS construction. Table 61: Connection Sizes and Locations Connection Sizes Component Circuit 045C 050C - 0C 0C - 90C 105C - 135C Connection Locations RPS (Split) RFS/RFR 045-0C RCS 045-0C X (in.) Y (in.) X (in.) Y (in.) S1 Suction Line Ckt.1 1-5/8 2-1/8 2-1/8 2-5/8 11.7 5.2 21. 7.0 S2 Suction Line Ckt.2 1-5/8 2-1/8 2-1/8 2-5/8 7.5 5.2 16.5 7.0 L1 Liquid Line Ckt.1 7/8 7/8 1-1/8 1-1/8 81.5 29.1 81.5 29.1 L2 Liquid Line Ckt.2 7/8 7/8 1-1/8 1-1/8 10.3 29.1 10.3 29.1 HG1 HGBP Line Ckt.1 7/8 7/8 7/8 7/8 52.1 10.4 52.1 10.4 HG2 HGBP Line Ckt.2 7/8 7/8 7/8 7/8 40.9 4.7 40.9 4.7 96 Cat 214-5

Horizontal Duct Connections See Figure 77 & Figure 78 on page 89 and Figure 79 & Figure on page 90 for Back return without exhaust fans. Figure 100: RPS/RFS Cabinet Height A B 015C-040C 55.5 34 43.5 045C-0C 73 42 61 0C-135C 97 42 Figure 101:Internal Cabinet Clearance, Air in the Face RPS/RFS C D E F 015C-040C 50.2 90 86.8 91 045C-0C 67.7 96 91.8 95 0C-135C 91.7 96 91.8 95 C= Ceiling-to-floor (with liners) D= Door-to-door (with liners) E=Upright-to-upright, located between sections F=Base-to-base Cat 214-5 97

Figure 102:RPS 045C - 0C - Back Return Propeller Exhaust Fans (2 shown) Figure 103:RPS 045C - 0C - Side Return Propeller Exhaust Fans 98 Cat 214-5

Figure 104:0C - 135C - Back Return Propeller Exhaust Fans Figure 105:0C - 135C - Side Return Propeller Exhaust Fans Cat 214-5 99

Recommended Clearances Service Clearance Allow recommended service clearances shown in Figure 106. Provide a roof walkway along two sides of the unit for service and access to most controls. Figure 106:Service Clearances Additional clearance, A, is recommended adjacent to the cooling coil, heat, and supply fan sections. See Figure 70 on page 84 through Figure 76 on page 87to identify these sections. Table 62: Service Clearance Unit Size A B C 015C-040C 30 60 60 045C-135C 24 72 72 Overhead Clearance Cooling coil, heat and supply fan service clearance 1. Unit(s) surrounded by screens or solid walls must have no overhead obstructions over any part of the unit. 2. Area above condenser must be unobstructed in all installations to allow vertical air discharge. 3. The following restrictions must be observed for overhead obstructions above the air handler section: a. There must be no overhead obstructions above the furnace flue, or within 9 in. of the flue box. b. Any overhead obstruction shall not be within 2 in. of the top of the unit. c. A service canopy must not protrude more than 24 in. beyond the unit in the area of the outside air and exhaust dampers. Figure 107: Ventilation Clearances Ventilation Clearance Unit(s) surrounded by a screen or a fence: 1. The bottom of the screen should be a minimum of 1 ft. above the roof surface. 2. Minimum distance, unit to screen same service clearance. 3. Minimum distance, unit to unit - 120 in. Unit(s) surrounded by solid walls: 1. Minimum distance, unit to wall - 96 in., all sizes 2. Minimum distance, unit to unit - 120 in. 3. Wall height restrictions: a. Wall on one side only or on two adjacent sides - no restrictions. b. Walls on more than two adjacent sides - wall height not to exceed unit height. 100 Cat 214-5