Page 1 of 4 IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate No.: IECEx BKI 08.0010 issue No.:0 Certificate history: Status: Current Date of Issue: 2008-09-24 Page 1 of 3 Applicant: Cooper Crouse Hinds GmbH previously CEAG Sicherheitstechnik GmbH Neuer Weg Nord 49 D-69412 Eberbach, Germany Germany Electrical Apparatus: Optional accessory: Terminal boxes Type STB and NXT Type of Protection: General requirements, Increased safety, Intrinsic safety, Dust explosion protection Marking: Ex e ia II, IIC T6, T5 Gb Ex e ia II, IIC T 80 C, T 95 C Db -55 C Tamb +55 C (T5) -55 C Tamb +40 C (T6 with HT100 sealing) Ex td A21 IP66 T 80 C, T 95 C Approved for issue on behalf of the IECEx Certification Body: Position: János HANKÓ Director Signature: (for printed version) Date: 1. This certificate and schedule may only be reproduced in full. 2. This certificate is not transferable and remains the property of the issuing body. 3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website. Certificate issued by: Testing Station for Explosion Proof Equipment H 1037 BUDAPEST MIKOVINY S.u. 2-4 Hungary
Page 2 of 4 IECEx Certificate of Conformity Certificate No.: IECEx BKI 08.0010 Date of Issue: 2008-09-24 Issue No.: 0 Page 2 of 3 Manufacturer: Cooper Crouse-Hinds (UK) Ltd Enclosur Division Dorset Road Sheemess Kent ME 12 1LP United Kingdom United Kingdom Manufacturing location(s): Cooper Crouse-Hinds GmbH Neuer Weg Nord 49 D-69412 Eberbach Germany Germany This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex produ covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended. STANDARDS: The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identi documents, was found to comply with the following standards: IEC 60079-0 : 2004 Edition: 4.0 IEC 60079-11 : 1999 Edition: 4 IEC 60079-7 : 2001 Edition: 3 IEC 61241-0 : 2004 Edition: 1 IEC 61241-1 : 2004 Edition: 1 Electrical apparatus for explosive gas atmospheres - Part 0: General requirements Electrical apparatus for explosive gas atmospheres - Part 11: Intrinsic safety 'i' Electrical apparatus for explosive gas atmospheres - Part 7: Increased safety 'e' Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "td" This Certificate does not indicate compliance with electrical safety and performance requirements other than thos expressly included in the Standards listed above. TEST & ASSESSMENT REPORTS: A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in Test Report: HU/BKI/ExTR08.0009/00 Quality Assessment Report: HU/BKI/QAR08.0001/00
Page 3 of 4 IECEx Certificate of Conformity Certificate No.: IECEx BKI 08.0010 Date of Issue: 2008-09-24 Issue No.: 0 Page 3 of 3 Schedule EQUIPMENT: Equipment and systems covered by this certificate are as follows: The terminal box, types STB and Typ NXT, consists of a stainless-steel enclosure designed to Increased Safety e type of protection or IP66. See details in Addendum to IECEx BKI 08.0010. CONDITIONS OF CERTIFICATION: NO Annexe: Addendum to IECEx BKI 08.0010.pdf
Page 4 of 4
ADDENDUM TO IECEx CERTIFICATE OF CONFORMITY IECEx BKI 08.0010 Page 1 of 2 1. Description The terminal box, types STB and Typ NXT, consists of a stainless-steel enclosure designed to Increased Safety e type of protection or IP66. It is to accommodate terminals for intrinsically safe and non-intrinsically safe circuits. The box area intended for intrinsically safe circuits is marked, e.g. by a light-blue colour. Connection is by means of explosion-proof cable entries. The empty enclosure as well as all integrated elements and extension elements have been tested and certified under a separate certificate. 2. Type assortment 2.1 Terminal boxes STB...... 1._, 2._, 3._ 4._, 5._, 6._, 7._, 8._, 9._ 2.2 Terminal boxes NXT...... 1._, 2._, 3._ 4._, 5._, 6._, 7._, 8._, 9._ Code for manufacturer Enclosure size 4._, 5._ Length 6._, 7._ Width 8._, 9._ Depth Code for manufacturer Enclosure size 4._, 5._ Length 6._, 7._ Width 8._, 9._ Depth 3. General parameters 3.1 Type STB...... terminal boxes verion (9 size) Sizes Length Width Depth smallest 120 mm 120 mm 80 mm largest 380 mm 380 mm 220 mm Technical data Rated voltage* up to 750 V Rated current* max. 250 A * depending on the type of terminal and explosion-proof components used Rated values are maximum values, the actual electrical values are determined by mounted electrical apparatus. Within these limiting values complying with the appropriate standards the manufacturer specified the final values dependent on power supply specifications, operating mode, utilization category, etc. 3.2 Type NXT...... terminal boxes version (40 size) Sizes Length Width Depth smallest 260 mm 260 mm 160 mm largest 1050 mm 610 mm 205 mm Technical data Rated voltage* up to 1100 V Rated current* max. 500 A Rated cross section max. 240 mm 2 * depending on the type of terminal and explosionproof components used Rated values are maximum values, the actual electrical values are determined by mounted electrical apparatus. Within these limiting values complying with the appropriate standards the manufacturer specified the final values dependent on power supply specifications, operating mode, utilization category, etc. 4. Ambient temperature subject to the sealing used Ambient temperature -55 C up to +55 C (T5) -55 C up to +40 C (T6) (with HT100 sealing) 5. Ingress protection IP66 to IEC 60529 Notes for manufacturing and operation For the maximum number of conductors for each enclosure size, which is subject to the cross section and the permissible continuous current, reference is made to the data sheets. Equipment designed to Intrinsic Safety I type of protection shall be installed in such a way that, the clearance and creepage distances specified in IEC 60079-14:2003 between intrinsically safe and non-intrinsically safe circuits are complied with. If the clearance requirements specified in IEC 60079-11:2006, are not complied with, terminals and wiring of Increased Safety e standard shall also be used for the intrinsically safe circuits. When connecting more than one intrinsically safe circuit, the rules and regulations for interconnection shall be duly observed.
ADDENDUM TO IECEx CERTIFICATE OF CONFORMITY IECEx BKI 08.0010 Page 2 of 2 Drawings Sheets Description No 4275 4 2004.02.19 Table No. 1 short instruction 1 2004.02.19 Drawings No. 723167 2000.02.11 No. 723168 2000.03.01 No. 723169 2000.02.28 Appendix No. 1 to 9 9 2002.10.21 Drawing No. 723217 1 2000.02.11 No. 724295 Issue 0 1 2002.10.11 No. 724296 Issue 0 1 2002.10.11 Drawing No. 723167 2002.11.06 No. 723168 2002.11.06 No. 723169 2002.11.06 No. 700703 2000.01.10 Drawing No. 724238 Issue 0 1 2002.09.05 No. 724239 Issue 0 1 2002.09.05 No. 701564 Issue 0 1 2002.10.09 Drawing No. 780555 Issue 11 2/1 2002.08.23 No. 780555 Issue 3 2/2 1999.04.22 Drawing No. 723025 Issue 5 1 2002.11.07 No. 780555 Issue 11 2/1 2002.11.06 No. 780555 Issue 3 2/2 2002.11.07 Appendix No. 1 to 34 2000.03.23 No. 35 to 40 2003.01.29 Test record No. MI 0793a issued by BKI Cooper Crouse-Hinds GmbH 4 sheet 2008.08.04 Test record No. MI 0793b issued by BKI Cooper Crouse-Hinds GmbH 4 sheet 2008.08.04 Test record No. MI 0793c issued by BKI Cooper Crouse-Hinds GmbH 4 sheet 2008.08.04 Test record No. MI 0793d issued by BKI Cooper Crouse-Hinds GmbH 4 sheet 2008.08.04 Declaration of consent by Cooper Crouse-Hinds UK 2004.01.13 Test Report PTB Ex 04-14027 3 sheet 2004.02.26