MINUTES. HEALTHCARE INTERPRETATIONS TASK FORCE 7 JUNE 2005 Mandalay Bay: North Convention Center Las Vegas, NV

Similar documents
MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE DECEMBER 8, 2006

Maryland State Fire Marshals Office Rep. International Fire Marshals Association (IFMA)

1. Call to Order. The meeting was called to order at 1:05 PM. (See Enclosure A [Agenda])

MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE Tuesday June 8, 2010 Mandalay Bay Convention Center Las Vegas, NV

HEALTHCARE INTERPRETATIONS TASK FORCE AGENDA

Heathcare Interpretations Task Force

HEALTHCARE INTERPRETATIONS TASK FORCE AGENDA

3. Review / Approval of December 2006 Minutes (See Enclosure A page 3)

FINAL MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE. Tuesday June 11, 2013

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

SAF-BCF SECOND REVISIONS WITH STATEMENTS

Lauzon Life Safety Consulting

AD HOC HEALTHCARE COMMITTEE MEANS OF EGRESS WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B MOE COMMITTEE

MINUTES. HEALTHCARE INTERPRETATIONS TASK FORCE 6 JUNE 2006 Orange County Convention Center Room S210D Orlando, FL

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering

Healthcare Interpretations Task Force AGENDA Mandalay Bay Convention Center Meeting Room Oceanside G Las Vegas, NV

Agency for Health Care Administration

Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

E25 (D) Automatic controls for general means of egress lighting

NFPA 101 Life Safety Code Culture change 2012

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Agency for Health Care Administration

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

Report on First Revisions with Statement June 2014 NFPA 101

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services

Agency for Health Care Administration

Agency for Health Care Administration

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID

Agency for Health Care Administration

Agency for Health Care Administration

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

The blank report forms are enclosed. If additional blank forms are needed you may contact my office at (210) and ask for Maria Castoreno.

Emergency Planning for Institutional Facilities

First Revision No NFPA [ Section No ]

FHCA 2014 Annual Conference & Trade Show

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012

MEETING MINUTES NFPA Technical Correlating Committee on Safety to Life January 6, 2011 ROC Meeting The Wyndham Phoenix, Phoenix, AZ

Following are code change proposals submitted through Adhoc Health from General study group and related changes. General. Position.

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.

CODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

TECHNICAL COMMITTEE MEMBERS WHO PARTICIPATED

26 of 128 9/23/2014 9:25 AM

El Reno Fire Department Fire Alarm Plan Review Worksheet

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015

Defend In Place 2012 IFC Overview of Institutional Occupancies

EC 5.10 FIRE PREVENTION MANAGEMENT

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)

AHC Meeting #7 July 12-13, Fire Safety WG Report. A Cycle Approved Code Changes

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

The Physical Environment Portal: Module 5, LS Leadership

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

Westinghouse UK AP1000 GENERIC DESIGN ASSESSMENT Resolution Plan for GI-AP1000-IH-01 Internal Fire Safety Case Substantiation.

AHC Meeting #7 July 12-13, Occupancy WG Report

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA

Agency for Health Care Administration

FIRE SAFETY INSPECTION REPORT

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE

NFPA Changes

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates

Report on First Revisions with Statement June 2014 NFPA 101

Life Safety Code Comparison

2. Closed circuit television, design and installation.

INITIAL FIRE SAFETY ASSESSMENT

U.S. Codes & Standards for Energy Storage Systems. Joe Cain, P.E. Chair, SEIA Codes & Standards Working Group

Fire Drill Requirements Group E Occupancies

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

Agency for Health Care Administration

Public. Mike Free Health. State of Alabama Department of

Public Health Fax: Web Site:

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING

UNIVERSITY OF TOLEDO

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

Fire Alarm System Fundamentals

FIRE SAFETY INSPECTION REPORT

INITIAL FIRE SAFETY ASSESSMENT

Transcription:

MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE 7 JUNE 2005 Mandalay Bay: North Convention Center Las Vegas, NV 1. The meeting was called to order at 2:10 PM 2. Introduction of members and guests present were completed: Attendance included: MEMBERS Principals Robert Solomon Joe Bermes Ken Bush Gene Cable Philip Hogue Tom Jaeger George Mills Dale Woodin REPRESENTING NFPA (Chair) IHS IFMA VA DOD AHCA JCAHO ASHE Alternates Doug Erickson Josh Elvove John Fishbeck Greg Harrington Jim Merrill Dick Strub ASHE VA JCAHO NFPA CMS AHCA

GUESTS REPRESENTING Jess Beitel Hughes Associates John Biechman NFPA Mike Crowley Rolf Jensen & Associates A. Richard Fasano Russell Phillips & Associates Jeff Mattern Chair, TC on Air Conditioning Systems Dean Samet Smith - Seckman Reid Phil Thomas Beverly Enterprises 3. The Minutes of the 16 November 2004 meeting were approved as submitted. 4. Two questions were submitted in advance for consideration. Two additional items for consideration were handed out. A. Rated Ceilings: This item related to the need, or requirement to physically secure ceiling tiles to an architectural grid or specify a minimum tile density when the ceiling was being used to satisfy the limit the transfer of smoke criteria of NFPA 101. The HITF did issue an interpretation on this subject. See HITF position on enclosure 4A. B. Door Locking: This item related the conditions or circumstances in which clinical needs can be used to justify door locking. NFPA staff position on this subject is that for items like infant abduction or to manage an unruly, yet competent patient, the clinical needs argument should not be used to justify pure security issues. The HITF voted to defer action on this and refer it to a task group. Members of this task group are: Tom Jaeger Chair, Joe Bermes, and Dale Woodin. The task group will consider items such as: acceptable locking mechanisms; acceptable releasing mechanisms; clinical needs versus elopement versus security; what bigger picture items (theft, general security issues) may need to be addressed. Page 2 of 7

C. Delayed Egress Locks: This item related to the need for doors equipped with delayed egress locks to unlock immediately upon activation of the building fire alarm system if activated by a manual fire alarm station. The HITF did issue an interpretation on this subject. See HITF position on enclosure 4C. D. Smoke Detector Functions: This item related to the various supplemental actions that a required smoke detector may trigger. Specifically, the function of required detectors in healthcare and ambulatory healthcare occupancies may have slightly different duties depending on what areas the detectors are installed in. The following table summarizes these combinations. HEALTH CARE OCCUPANCY CONDITION 1. Detectors in elevator lobby, hoistway and machine rooms 2. Detectors used to close fire dampers, shut down HVAC. 3. Detectors used as noted in conditions 1 and 2 above. 4. Detectors used as noted in Condition 2 above. NOTIFICATION Required to notify occupants: NO Required to notify occupants: NO Required to notify emergency forces: YES both the staff and the fire department. Audible and visible supervisory signal to constantly attended location: NO Page 3 of 7

AMBULATORY HEALTHCARE OCCUPANCY CONDITION NOTIFICATION 1. Detectors in elevator lobby, Required to notify occupants: NO hoistway and machine rooms. 2. Detectors used to close fire Required to notify occupants: NO dampers, shut down HVAC. 3. Detectors used for door release Required to notify occupants: NO service. 4. Detectors used as noted in conditions 1, 2 or 3 above. Required to notify emergency forces: YES both the staff and the fire department. 5. Detectors used as noted in Condition 2 and 3 above. Audible and visible supervisory signal to constantly attended location: NO The text in the relevant sections of NFPA 101 (For example, See NFPA 101, 2003: 18.3.4.2, 18.3.4.3.1, A.18.3.4.2, 19.3.4.2, 19.3.4.3.1, A.19.3.4.2, 20.3.4.2, 20.3.4.3, 21.3.4.2, 21.3.4.3) address occupant notification based on operation of any required detection devices, or detection systems. This further speaks to notification of occupants upon operation of any fire alarm activating device. The HITF members do not believe that NFPA 101 intended for these devices to initiate alarms for occupant notification, but rather for notification of staff who may have to take action to relocate or reposition patients. The HITF would like to determine if any changes to the 2006 edition of NFPA 101 will address these issues any further. No formal action is recommended at this time. 5. Three discussion items were brought up. The discussion items involve issues of interest but do not require an HITF action. A. Corridors as Air Plenums: This item was included on the agenda to review the prohibition on corridors being allowed for supply or return air purposes. NFPA 90A: 4.3.11, 2002 Edition, contains the restriction that is applicable to healthcare, detention and correctional and residential Page 4 of 7

occupancies. The GAO Nursing Home Fire Safety Report (July 2004) mentioned a concern with this practice being grandfathered in some nursing home facilities. It is estimated that thousands of nursing homes may exist with throughthe-wall air conditioning units. Make up air for these units would technically come via the corridor and the conditioned air may circulate back to the corridor from the room. In the past, allowances have provided to allow for incidental air use. There has never been a defined limit on how much air would be deemed to be incidental. At one extreme, any amount of air that is taken from, or added to the corridor is technically a violation of NFPA 90A. The allowances and waivers to the NFPA 90A restriction have been based on presence and use of: automatic sprinklers; automatic fan shutdown; other methods that were not described. One solution to the issue may be for CMS to provide guidance or to define incidental air. 50 CFM (normally needed for lavatory ventilation) may be a starting point. Such guidance from CMS would greatly assist nursing home owners/operators with this issue and just as important, it would provide CMS inspectors and their agents with a trigger to flag the issue. If it is feasible, this issue should also be considered by the NFPA 90A committee during their next revision cycle. B. Facility Lock Down/Lock Out Procedures: ASHE has been studying the issue of physical security at healthcare facilities. Situations where there may be a need to prevent access to a hospital (civil disturbance) or there may be a need to prevent egress from a hospital (contagion release) must be carefully managed. ASHE expects to release some draft guidance on this subject in late 2005/early 2006. Page 5 of 7

C. Time Based Standards: JCAHO has been studying the issue of frequency of testing. Specifying that an action be done on a quarterly basis could, in the extreme, be interpreted as follows: FIRST QUARTER: SECOND QUARTER: THIRD QUARTER: FOURTH QUARTER: JAN FEB MAR APR MAY JUNE JULY AUG SEPT OCT NOV DEC An entity that arranged for testing on 31 March and 1 April; and then again on 30 September and 1 October would literally satisfy conditions for a quarterly test. Likewise, could an Annual test be conducted on December 31 st and January 1 st and then not again until December 31 st at the end of the second year? JCAHO does not believe that was ever the intent of either the JCAHO EL Standards, NFPA Codes or Standards on any other document that specifies a frequency. One idea being suggested by JCAHO is to use a quantitative approach with a built in tolerance. An example of this would be: CURRENT TERM PROPOSED TERM Quarterly 90 days from last occurrence +/- 10 days Annually 365 days from last occurrence +/- 10 days JCAHO will continue to consider these issues and determine if further action is needed. Page 6 of 7

6. New Business A. Update on Retrofitting of Automatic Sprinkler in Nursing Homes. This provision has been proposed for the 2006 edition of NFPA 101 that will be voted on later in the week. From the CMS perspective, issues on some form of funding assistance and a phase in period will have to be considered. B. Update on CMS Rulemaking Issues: Provisions for Alcohol Based Hand Rubs (ABHR) in healthcare occupancies and installation of smoke detectors/smoke alarms in existing nursing homes were published in March 2005 as a proposed/final rule. Several HITF members/organizations commented on the rules which took effect on May 25, 2005. 7. Old Business: There were no issues under Old Business. 8. Next Meeting. The next meeting has tentatively been scheduled for 6 June 2006 in Orlando, FL. 9. Adjournment. The meeting was adjourned at 4:50 pm. Minutes prepared and submitted by Robert Solomon, PE, NFPA Page 7 of 7

ENCLOSURE 4A & 4C

Enclosures 4A and 4C HEALTHCARE INTERPRETATIONS TASK FORCE HITF INTERPRETATIONS 7 JUNE 2005 Enclosure 4.A. NFPA Document No: NFPA 101 2000 Edition: Code Language: 19.3.6.2.3* In smoke compartments protected throughout by an approved, supervised automatic sprinkler system in accordance with 19.3.5.3, a corridor shall be permitted to be separated from all other areas by non-fire-rated partitions and shall be permitted to terminate at the ceiling where the ceiling is constructed to limit the transfer of smoke. A.19.3.6.2.3 An architectural, exposed, suspended-grid acoustical tile ceiling with penetrating items such as sprinkler piping and sprinklers; ducted HVAC supply and return-air diffusers; speakers; and recessed lighting fixtures is capable of limiting the transfer of smoke. Did this question arise from an actual field situation? Yes Please state your business interest in the matter and identify other parties involved: This question continues to surface with state officials interpreting the Life Safety Code for CMS. Question: Is it the intent of the LSC to require the architectural suspended-grid ceiling to have the acoustical ceiling tiles clipped in place or of a specific weight ( e.g. one pound per square foot) to meet the requirements of paragraph 19.3.6.2.3? HITF Response: NO. ------------------------------------------------------------------------------------------------------------ Enclosure 4.C. NFPA Document No: NFPA 101-2000 Edition Code Language: 7.2.1.6.1 Delayed-Egress Locks. Approved, listed, delayed-egress locks shall be permitted to be installed on doors serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system in accordance with Section 9.6, or an

Enclosures 4A and 4C approved, supervised automatic sprinkler system in accordance with Section 9.7, and where permitted in Chapters 12 through 42, provided that the following criteria are met. (a) The doors shall unlock upon actuation of an approved, supervised automatic sprinkler system in accordance with Section 9.7 or upon the actuation of any heat detector or activation of not more than two smoke detectors of an approved, supervised automatic fire detection system in accordance with Section 9.6. 18.2.2.2.4 Doors within a required means of egress shall not be equipped with a latch or lock that requires the use of a tool or key from the egress side. Exception No. 2*: Delayed-egress locks complying with 7.2.1.6.1 shall be permitted, provided that not more than one such device is located in any egress path. 19.2.2.2.4 Doors within a required means of egress shall not be equipped with a latch or lock that requires the use of a tool or key from the egress side. Exception No. 2*: Delayed-egress locks complying with 7.2.1.6.1 shall be permitted, provided that not more than one such device is located in any egress path. Did this question arise from an actual field situation? Yes Please state your business interest in the matter and identify other parties involved: Healthcare facilities are being cited for a deficiency if the delayed-egress locks do not automatically unlock upon manual activation of the fire alarm system. Not only are the facilities being cited for a deficiency, but they are also being cited for having immediate jeopardy resulting in endangering the lives of many patients. The immediate jeopardy claim results in heavy financial penalties. Question: Do Sections 18 & 19.2.2.2.4 Exception No. 2 or Section 7.2.1.6.1 of the 2000 Life Safety Code require delayed-egress locks installed on doors in the means of egress to automatically unlock upon manual activation of the fire alarm system? HITF Response: NO.