A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM

Similar documents
Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building

How design fires can be used in fire hazard analysis

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

and SUMMARY current building code provisions, and alternative

The Definition of Scenarios for the CESARE-RISK Model

Considerations in the Design of Smoke Management Systems for Atriums


PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

Probabilistic-deterministic modelling of fire spread

Proulx, G.; Richardson, J.K. NRCC-45663

Design of Fire safety in Multi Occupancy Residential Accommodation

EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS

26 June 2001 GUIDELINES ON ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY

Why Building Occupants Ignore Fire Alarms

Risk-informed Airport Fire Engineering Solutions for Operational Continuity

This document is a preview generated by EVS

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

Adrian Milford Sereca - a Jensen Hughes Company, Project Engineer Vancouver, BC, Canada

Effects of Smoke on Evacuation Martin Lopušniak 1, a

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Modeling a real backdraft incident fire

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL

Abstract. Introduction

Principles of Fire Risk Assessment in Buildings

Case Study 1 Underground Car Park

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD

Simulation study of evacuation in high-rise buildings

Fire Resistance - Implications for regulations and standards of the September 11th terrorist attacks on the world trade centre Tom Lennon, FRS, BRE

Recent BRANZFIRE enhancements and validation

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

Principles of Fire Risk Assessment in Buildings

( )

CERBERUS: A NEW MODEL TO ESTIMATE SIZE AND SPREAD FOR FIRES IN TUNNELS WITH LONGITUDINAL VENTILATION

ECONOMIC JUSTIFICATION FOR SPRINKLER SYSTEMS

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

4 August Islington Fire Protection Transpower NZ Limited

CFD Model of a Specific Fire Scenario

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings

Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces

Date: Place: Technical University of Denmark. Knowledge FOr Resilient society

SURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG

Test One: The Uncontrolled Compartment Fire

A Monte Carlo Approach for the Design of Thermal Fire Detection System

Preliminary investigations of smoke movement through HVAC systems and duct smoke detectors. Lougheed, G.D.; McCartney, C.; Carpenter, D.W.

ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY

F.R.A.M.E. EVENT NETWORKS used in "FRAME".

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS

Gothenburg dance hall, Sweden, 1998

EVACUATION AND SMOKE MOVEMENT INTERACTIVE SIMULATION MODEL

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS

CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

COMPLIANCE ALTERNATIVES

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team

By: Russell Bainbridge March 18th, 2016 FPE 596

Advantages and Disadvantages of Fire Modelling

Feasibility Study of Use of Elevators in Fire Evacuation in a High-rise Building

Tunnel Fire Dynamics and Evacuation Simulations

Computer Models For Evacuation

NYU RESIDENTIAL FIRE SAFETY PLAN PART I - BUILDING INFORMATION SECTION

A SURVEY OF OCCUPANT RESPONSE TOWARDS AN AUDIBLE FIRE ALARM

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

Computer Models For Fire and Smoke

A Model of the Population of Fire Detection Equipment Based on the Geometry of the Building Stock

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

An experimental study of the impact of tunnel suppression on tunnel ventilation

COMPLIANCE ALTERNATIVES

Mathematical Modeling of Fires

Dangerous Assumptions

Research on fire protection methods and a case study "Futurum"

Secretary of State determination under article 36 of the Fire Safety Order

Development of Seismic-induced Fire Risk Assessment Method for a Building

Principles of Fire Risk Assessment in Buildings

Design Occupant Groups Concept Applied to Fire Safety Engineering Human Behaviour Studies

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

Statue of Liberty: A Risk Analysis

Anatomy of a Fire. Christopher Crivello, MSFPE, PE. Douglas Nadeau, MSFPE, PE, CFPS, LEED AP

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

PERFORMANCE COMPLIANCE METHODS

EVACUATION MODELLING IN ROAD TUNNEL FIRES

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Information Bulletin

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

PERFORMANCE COMPLIANCE METHODS

Evacuation Hazards in Crowded Subway Stations

New Approaches to Design for Fire Safety - Residential sprinklers, open plan flat layouts and water mist

Travelling Fires for CFD

IAAI/USFA Abandoned Building Project

Transcription:

, Volume 1, Number 1, p.18-26, 1999 A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM D. Yung, G.V. Hadjisophocleous and G. Proulx Fire Risk Management Program, National Research Council of Canada, Ottawa, Canada ABSTRACT To support the introduction of performance-based building regulations in Canada in the year 23, the National Research Council of Canada (NRC) is developing a computer fire risk-cost assessment model that can be used to assess both the expected risk to life to the occupants and the expected costs of fire protection and fire losses in a building. The computer model that is being developed at NRC is called FiRECAM (Fire Risk Evaluation and Cost Assessment Model). This paper gives a brief description of the probabilistic and deterministic modelling concepts that are used in FiRECAM. In addition, the paper shows the results of its recent application to a six-storey Canadian federal government office building where the existing fire protection systems were being re-evaluated to see how they could be upgraded in a cost-effective manner to meet the current building code requirements. 1. INTRODUCTION To permit flexibility and cost-effectiveness in fire safety designs, many countries in the world, notably New Zealand, Japan, the U.K. and Australia, are moving towards performance-based building regulations, and away from the current restrictive, prescription-based regulations. Canada is also planning to introduce objective/ performance-based requirements in the National Building Code of Canada (NBCC) in the year 23. Unlike prescription-based regulations, performance-based regulations permit greater flexibility in design which often leads to lower construction costs. Similar to other engineering practices, performance-based regulations allow designers and regulatory officials the freedom to apply engineering principles to identify fire safety designs that meet the required fire safety performance. The introduction of performance-based building regulations, however, depends on the successful development of engineering tools that can be used to design the various fire safety systems in a building, as well as risk assessment tools that can be used to assess the overall fire safety performance of a building. To support the introduction of objective/performance-based building regulations in Canada, the National Research Council of Canada (NRC) is developing a computer fire risk-cost assessment model that can be used to assess both the expected risk to life to the occupants and the expected costs of fire protection and fire losses in a building. FiRECAM assesses the expected risk to life to the occupants in a building as a result of all probable fire scenarios over the design life of the building. As well, the model assesses the costs of fire protection and expected fire losses. By comparison to the performance required in a performance-based code, or the implied performance of a code-compliant design as specified in a prescription-based code, the model can assess whether a proposed design meets the performance requirements, or is equivalent in life risk performance to the code-compliant design. In addition, the model can assess the fire costs to determine whether the proposed design has the lowest fire costs of all acceptable designs and, hence, is a cost-effective design. At present, the model being developed can be applied to both apartment and office buildings. In the future, other versions will be developed for other building applications. This paper provides a brief description of the probabilistic and deterministic modelling concepts that are used in FiRECAM. Probabilistic modelling is used to determine the probability of occurrence of a fire scenario, whereas deterministic modelling is used to determine the consequence of a fire scenario. In addition, the paper describes the results of its recent application to a six-storey Canadian federal government office building. This example shows how the model can be used to obtain cost-effective fire safety designs. The objective of this study was to evaluate alternative fire safety designs for such a building that could provide the occupants with the same, or better, 18

level of safety as that required by the current prescriptive building code but at lower costs. 2. FiRECAM A description of FiRECAM and its submodels can be found in previous publications [1-9] and is not repeated here. The model was developed in collaboration with the Victoria University of Technology in Australia [3-4] and in partnership with Public Works and Government Services Canada (PWGSC) and the Canadian Department of National Defence (DND). FiRECAM assesses the fire safety performance of a fire safety design in terms of two decisionmaking parameters : the expected risk to life (ERL) and the fire cost expectation (FCE). The ERL is the expected number of deaths per year. The FCE is the expected total fire cost which includes the capital cost for the passive and active fire protection systems, the maintenance cost for the active fire protection systems and the expected losses resulting from all probable fires in the building. The ERL is a quantitative measure of the risk to life from all probable fires in a building, whereas the FCE quantifies the fire cost associated with a particular fire safety design. The separation of life risks and protection costs in FiRECAM avoids the difficulty of assigning a monetary value to human life and allows the comparison of risks and costs separately. The ERL value can be used for compliance with performance requirements (performance-based codes) or code equivalency considerations (prescription-based codes). The FCE value can be used to assess costeffectiveness of various design options. To calculate the ERL and FCE values, FiRECAM considers the dynamic interaction (time-dependent calculation) among fire growth, fire spread, smoke movement, human behaviour and fire department response. These calculations are performed by a number of submodels interacting with each other as shown in Fig. 1. The computer model includes two optional submodels that can be run if the building fire characteristics and fire department response are not considered typical. Two other submodels are run only once to obtain the failure probability values of boundary elements and the capital and maintenance costs of fire protection systems. The remaining ten submodels are run repeatedly in a loop to obtain the expected risk to life values and the expected fire losses from all probable fire scenarios. Building and Risk Evaluation Evacuation Flashover fire? YES Fire Spread OPTIONAL MODELS NO Fire Department Response Fire Department Effectiveness Smoke Hazard END Boundary Element Failure Occupant Response Life Loss Probability Fire Cost Expectation Economic Smoke Movement Property Loss Expected Risk to Life YES Design Fire Fire Growth Expected Number of Deaths Finished all fires? NO 19

Fig. 1: FiRECAM flowchart 3. MODELLING CONCEPTS USED IN FiRECAM FiRECAM uses statistical data to predict the probability of occurrence of fire scenarios, such as the type of fire that may occur or the reliability of fire detectors. Mathematical models are used to predict the time-dependent development of fire scenarios, such as the development and spread of a fire and the evacuation of the occupants in a building. The life hazard to the occupants posed by a fire scenario is calculated based on how quickly the fire develops and how quickly the occupants evacuate the building in that scenario. The life hazard calculated for a scenario multiplied by the probability of that scenario gives the risk to life from that scenario. The overall expected risk to life to the occupants is the cumulative sum of all risks from all probable fire scenarios in a building. Similarly, the overall expected fire cost is the sum of fire protection costs (both capital and maintenance) and the cumulative sum of all fire losses from all probable fire scenarios in a building. The expected risk to life is expressed as Expected Risk to Life = Σ Pi x Ci (1) where Σ represents the summation of all probable fire scenarios, Pi is the probability of a fire scenario and Ci is the expected number of deaths from that fire scenario. A fire scenario is a description of the conditions of the controlling parameters that would govern the outcome of the fire development and the evacuation of the occupants. For example, controlling parameters and their possible conditions include: (1) the location of the fire in a building; (2) whether the type of fire that has occurred in the compartment of fire origin is a smouldering fire, a small flaming fire or a flashover fire; (3) whether the door to the compartment of fire origin is open or closed; (4) whether smoke detectors, if installed, are operational or not; (5) whether sprinklers, if installed, are operational or not; etc. The probability of a controlling parameter in a particular condition can be obtained from statistics or, in the absence of such statistical information, from expert opinion. For example, the probability of a fire occurring in the compartment of fire origin being a flashover fire can be obtained from statistics; whereas the probability of the door to the compartment of fire origin being open can often be obtained from expert opinion. The probability of a fire scenario is the product of the probabilities of its controlling parameters. For each fire scenario, FiRECAM uses timedependent deterministic models to calculate the life hazard to the occupants and fire losses. These models include fire growth, smoke spread and occupant evacuation. In the following sections, the fire growth and occupant evacuation models are described as examples of NRC s ongoing efforts to develop and validate these deterministic models by experiments. The validation of the smoke spread model has been described previously [5]. 3.1 Design Fires and Fire Growth Model FiRECAM uses six design fires in the compartment of fire origin, and the subsequent fire and smoke spread, to evaluate life risks and protection costs for apartment and office buildings. The six design fires, representing a wide spectrum of possible fire types, are: 1. smouldering fire with the fire compartment entrance door open, 2. smouldering fire with the fire compartment entrance door closed, 3. flaming non-flashover fire with the fire compartment entrance door open, 4. flaming non-flashover fire with the fire compartment entrance door closed, 5. flashover fire with the fire compartment entrance door open, 6. flashover fire with the fire compartment entrance door closed. The probability of occurrence of each design fire is based on statistical data. For example, in Canada, statistics [1] show that the probability of fire starts in office buildings is 7.68 x 1-6 per m 2. Of these fires, 24% reach flashover and become fullydeveloped fires, 54% are flaming fires that do not reach flashover and the remaining 22% are smouldering fires that do not reach the flaming stage [1]. If sprinklers are installed, the model assumes that some of the flashover and nonflashover fires, depending on the reliability and effectiveness of the sprinkler system, are rendered non-lethal [6]. The fire growth model predicts the development of the six design fires in the compartment of fire origin using representative fuels, such as polyurethane slabs for residential furniture and wood cribs for office furniture. Details of this model are described in a previous paper [7]. The 2

model calculates the burning rate, room temperature and the production and concentration of toxic gases as a function of time. With these calculations, the model determines the time of occurrence of five important events: (1) time of fire cue (that can be detected by human senses), (2) time of smoke detector activation, (3) time of heat detector or sprinkler activation, (4) time of flashover, and (5) time of fire burnout. The model also calculates the mass flow rate, the temperature and the concentrations of CO and CO 2 in the hot gases leaving the fire compartment. The output of the fire growth model is used by other submodels in FiRECAM to calculate the spread of smoke to other parts of the building, the response and evacuation of the occupants as well as the response and effectiveness of the fire department. Experiments have been conducted at VUT [11] in Australia as well as at NRC [12] to validate the fire growth model. Fig. 2 shows the results of a recent full-scale fire experiment at NRC [12], where a fire was started in a work space representative of that found in a large open office environment, as well as the model predictions. In this figure, the experimental results and the model predictions of the temperature, mass flowrate, CO and CO 2 concentrations are shown to be in reasonably good agreement. 5 45 4 Experiment - temperature Experim ent - m ass flow rate Model prediction - temperature M odel prediction - m ass flow rate Test term inated 7 6 35 5 Temperature ( 蚓 ) 3 25 2 15 4 3 2 Mass Flow Rate (kg/s) 1 1 5 1 2 3 4 5 6 7 8 9 1 11 12 Tim e from ignition (m in) CO Concentration (%) 1.6 1.4 1.2 1..8.6.4 Experiment - CO concentration Experiment - CO2 concentration Model prediction - CO concentration Model prediction - CO2 concentration Test terminated 35 3 25 2 15 1 CO 2 Concentration (%).2 5. 1 2 3 4 5 6 7 8 9 1 11 12 Tim e from ignition (m in) Fig. 2: Comparison of experimental results with model predictions in an open office arrangement 21

Other experiments are being conducted at VUT and NRC, including those using enclosed offices and residential rooms. The results will be used to improve the fire growth model. 3.2 Occupant Evacuation Model When a fire starts on a specific floor, the Occupant Evacuation Model computes the movement of occupants from their original locations through corridors, stairwells and out of the building. The evacuation procedure involves selecting appropriate paths and evaluating queuing at doorways and stairwells. A network modelling approach, suitable for solving complex evacuation problems, is used. The evacuation paths are generated on the basis of the assumption that occupants will use preferred routes to evacuate. This method relies on a network description of the building and the locations of occupants to solve the problem. A network model is a graphic representation of paths or routes by which persons can move from one point to another. Network nodes representing the compartment doors, corridors, stairwells and exits are used to define travel paths. The initial positions of occupants are assumed to be uniformly distributed in compartments or in open areas, which are also represented by network nodes. The stairwell network is generated assuming that all stairwells have the same dimensions and structural layout. The network nodes specify the turn points in a stairwell. % 1 9 8 where work spaces are defined by 1.6 m high partitions There are two types of nodes in the network that can be weighted by a numerical value; namely, the source nodes and the destination nodes. The source nodes represent nodes of danger, such as the compartment of fire origin and stair exits blocked by smoke. These nodes are weighted by a negative value. The destination nodes represent nodes of safety, such as the exit stairs and building exits. They are weighted by a positive value. Evacuation paths are generated for each occupant by solving the Poisson's equation. The preferred path is towards the node with a higher value. Based on the weights pre-defined for stairs, exits and the compartment of fire origin, the program calculates the appropriate path for each occupant. The higher the weighting of the destination node, the higher its attraction for occupants. To evaluate the predictability of the model, its predictions are compared to results from evacuation drills in apartment and office buildings [13] and are shown in Figs. 3 and 4, respectively. As can be seen from Fig. 3, the evacuation curves for four apartment buildings are quite different. This is mainly attributed to the type of fire protection systems used in the buildings and the conditions of the alarms, including the loudness and audibility of alarm bells [14]. Fig. 3 shows that the model prediction for the case with a central alarm and occupants awake is in good agreement with the results of evacuation drills in Buildings 2 and 3, which had poor central alarm systems. The model prediction, therefore, is on the conservative side when compared to what was observed in evacuation drills. 7 6 5 4 3 Building 1 Building 2 Building 3 Building 4 Voice alarm & Awake Central alarm & Awake 2 1 2 4 6 8 1 12 14 16 18 Time (s) Fig. 3: Comparison of model predictions with results of fire drills in 22

The results for office buildings are shown in Fig. 4, where the percentage of occupants who have evacuated is plotted as a function of time for both model predictions and fire drills. For the central alarm option (CA), two different building populations were used in the model predictions. As expected, the evacuation process for the case with a lower population is shown to be faster than that of the case with a higher population. The voice alarm option is shown to give better evacuation results than the other two options without voice communication. Fig. 4 also shows the model predictions of evacuation to be slightly slower than % 1 apartment buildings what was observed in the fire drills. However, the fire wardens and the occupants in the two buildings used for evacuation drills had received regular fire drill training [15]. These factors, which could have significant impact on evacuation, have not yet been considered in the current Occupant Response Model [9]. The Occupant Response Model calculates the probability of response and the delay time before evacuation. The present Occupant Response and Evacuation Models, therefore, give conservative predictions for building evacuation, which in turn allow FiRECAM to provide conservative assessments of fire safety designs. 9 8 7 6 5 4 London bldg. O ttawa bldg. CA / Low pop. CA / High pop. VA / Low pop. 3 2 1 2 4 6 8 1 12 14 16 Tim e (s) Fig. 4: Comparison of model predictions with results of fire drills in office buildings 4. APPLICATION OF FiRECAM TO A 6-STOREY OFFICE BUILDING FiRECAM was applied to a six-storey Canadian federal government office building, located in London, Ontario. The existing fire protection systems of this building were being re-evaluated to see how they could be upgraded to meet the current building code requirements. One of the difficulties with this building was that it was designated a heritage building. The building was constructed in the 193 s and has unique architectural features. With the heritage designation, no renovation to the building would be permitted unless such renovation would not cause any change to the building s unique architectural characteristics. The objective of this study was to identify possible alternative cost-effective fire safety designs for such a building that could provide the occupants with an equivalent level of safety to that required by the current building code. The building is a six-storey concrete building with three staircases, two passenger elevators and two service elevators. A typical floor layout is shown in Fig. 5. The average usable area on each floor is about 1, m 2. On each floor, there are both closed offices and an open area where work spaces are defined by 1.6 m high partitions. The building is currently occupied by various government departments as well as a post office on the main floor. It has a day-time population of approximately 18 people and a night-time population of mainly one security person. 23

REAR STAIRCASE FRONT STAIRCASE OPEN OFFICE CONCEPT SIDE STAIRCASE Fig. 5: Typical floor layout Currently, the building has no sprinklers installed, except in the basement. It has a central alarm system, but no voice communication system. In the stair shafts, there are closed-door closets that have vents connected to the occupied floor side above the suspended ceiling. These vents could leak smoke from the floor into the stair shafts. The current building code requires that the vents to the closets in the stair shafts be closed. The code does not require a voice communication system nor sprinkler protection. However, since this is a heritage building, PWGSC, which owns the building, wants to install sprinklers throughout the building to protect its value. The code also permits a higher population density of one person per 9.3 m 2, or 11 persons per floor in this building, whereas PWGSC s practice is to limit the population density to a lower value: one person per 12 m 2, or 85 persons per floor in this building. The current population density in this building is very low, about 3 per floor. Table 1: Fire protection options to be considered with the sprinklering and not sprinklering options for a total of 16 options. Design Option Add Voice Alarm Close StairVent A/NSV/HP No Yes 11 (reference) A/NSV/LP No Yes 85 A/SV/HP No No 11 A/SV/LP No No 85 VA/NSV/HP Yes Yes 11 VA/NSV/LP Yes Yes 85 VA/SV/HP Yes No 11 VA/SV/LP Yes No 85 Population Per Floor To compare the safety levels provided to the occupants, 16 fire safety options were considered involving the following : with sprinklers or no sprinklers, voice alarm vs regular alarm, close the vents to the closets in the stair shafts or not, and a lower population density vs a higher population density. Table 1 shows the 8 options that were considered in conjunction with sprinklering and not sprinklering. The first option is the reference option. It is code-compliant with the addition of sprinkler protection. A code-conforming building of this size does not require sprinklers. 5. RESULTS FiRECAM was used to determine the expected number of deaths for the 16 fire safety options shown in Table 1. The results are plotted in Fig. 6, where the expected number of deaths for each option is compared to the first option (the reference option) which has a relative deaths value of 1. The reference option has sprinklers, a central alarm, no vents to the stair shafts, and a population density of 11 persons per floor. The option that represents the current situation before upgrades is the nonsprinkler option that has a central alarm, vents to the closets in the stair shafts and a lower population density (A/SV/LP without sprinklers), which has a relative deaths value of 2.6. In this study, no calculations of the potential fire losses were performed because there was no suitable restoration cost data available for heritage buildings. However, the capital costs of providing some of the fire safety options, which were actual estimates from contractors, are addressed. Fig. 6 shows that all 8 options with sprinklers have a much lower expected number of deaths when compared to similar options without sprinklers. This is expected since sprinklers suppress most of the flashover and non-flashover fires. With or without sprinklers, the results show that a lower population density has a lower expected number of deaths value. This is reasonable since a lower population would usually lead to a quicker evacuation and, therefore, a lower number of occupants that could be trapped in the building. The results also show that closing the vents to the closets in the stair shafts gives a lower expected deaths value. This is again reasonable since 24

closing the vents would lead to a lower possibility of smoke spread to the stairs and upper floors. Finally, Fig. 6 shows that adding a voice alarm results in a lower expected deaths value. This is again expected since voice alarm is known to cause a faster response from the occupants because it provides information on both the fire and the direction to get to a safe area. The results in Fig. 6 show that some of the sprinkler options can provide equivalent life safety, or better, when compared to the reference option (the first option). One such sprinkler option, that can provide better safety but with a lower capital cost, is the one that has the central alarm, but does not close the vents to the closets in the stair shafts and has a lower population density (A/SV/LP with sprinklers). This option has a lower relative deaths value of.89. The lower population density compensates for the higher smoke spread through the stair vents. The saving in not having to close the stair vents is about $37, when compared with the reference option. Fig. 6 also shows that none of the non-sprinkler options can provide equivalent life safety to the reference option. However, one non-sprinkler option is very close to the reference option : the one that has voice alarms, closes the stair vents and has a lower population density (VA/NSV/LP without sprinklers). This option has a higher relative deaths value of 1.19 when compared to the reference option. But when compared to the 2.6 that represents the current level of risk before upgrades (A/SV/LP without sprinklers), it achieves almost the same reduction in risk as intended by the reference design : from 2.6 to 1.19 rather than 2.6 to 1. The use of voice alarms plus a lower population density allows this option to achieve almost the same result as the reference option with sprinklers but with a higher population density. The cost of installing sprinklers was estimated to be $575,, whereas the cost of installing voice alarms was only $73,. If funding to install the sprinklers is a problem, this option could be an attractive one to consider as a possible solution that could achieve most of the intended reduction in life risk, but with a capital cost of about $5, less. However, no consideration for property loss is included in this comparison which could be an important factor for heritage buildings. Sprinklers Installed No Sprinklers 3.5 3.16 Relative Deaths 3. 2.5 2. 1.5 1. 1. 2.31.78 1.8 1.12.89 2.6 (current) 1.56 1.19 2.52 1.76.5. A/NSV/HP A/NSV/LP A/SV/HP A/SV/LP A = Alarm NSV = No Stair Vent HP = High Population Density VA = Voice Alarm SV = Stair Vent Present LP = Low Population Density.25 VA/NSV/HP.19 VA/NSV/LP.28 VA/SV/HP.19 VA/SV/LP Fig. 6: Relative expected deaths for 16 design options shown in Table 1 25

REFERENCES 1. D. Yung, G.V. Hadjisophocleous and G. Proulx, Modelling Concepts of the Risk-Cost Assessment Model FiRECAM and Its application to a Canadian Government Office Building, Presented at the 5th International Symposium on Fire Safety Science, 3-7 March 1997, Melbourne, Australia (1997). 2. D. Yung, G.V. Hadjisophocleous, G. Proulx, and B.R. Kyle, Cost-Effective Fire-Safety Upgrade Options for a Canadian Government Office Building, Proceedings of the International Conference on Performance-Based Codes and Fire Safety Design Methods, 24-26 September 1996, Ottawa, Canada (1996). 3. D. Yung and V.R. Beck, Building Fire Safety Risk Analysis, SFPE Handbook of Fire Protection Engineering, National Fire Protection Association, Quincy, MA, pp. 5-95 to 5-11 (1995). 4. V.R. Beck, and D. Yung, The Development of a Risk-Cost Assessment Model for the Evaluation of Fire Safety in Buildings, Proceedings of the 4th International Symposium on Fire Safety Science, 13-17 June 1994, Ottawa, Canada, pp. 817-828 (1994). 5. A. Hokugo, D. Yung and G.V. Hadjisophocleous, Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment, Proceedings of the 4th International Symposium on Fire Safety Science, 13-17 July 1994, Ottawa, Canada, pp. 85-815 (1994). 6. G.V. Hadjisophocleous and D. Yung, Parametric Study of the NRCC Fire Risk-Cost Assessment Model for Apartment and Office Buildings, Proceedings of the 4th International Symposium on Fire Safety Science, 13-17 July 1994, Ottawa, Canada, pp. 829-84 (1994). 7. H. Takeda and D. Yung, Simplified Fire Growth Models for Risk-Cost Assessment in Apartment Buildings, Journal of Fire Protection Engineering, Vol. 4, No. 2, pp. 53-66 (1992). 8. G.V. Hadjisophocleous and D. Yung, A Model for Calculating the Probabilities of Smoke Hazard from Fires in Multi-Storey Buildings, Journal of Fire Protection Engineering, Vol. 4, No. 2, pp. 67-8 (1992). 9. G. Proulx and G.V. Hadjisophocleous, Occupant Response Model: A Sub-Model for the NRCC Risk-Cost Assessment Model, Proceedings of the 4th International Symposium on Fire Safety Science, 13-17 July 1994, Ottawa, Canada, pp. 841-852 (1994). 1. J. Gaskin and D. Yung, Canadian and U.S.A. Fire Statistics for Use in the Risk-Cost Assessment Model, IRC Internal Report No. 637, January 1993, National Research Council of Canada, Ottawa, Canada (1993). 11. V.R. Beck, D. Yung, Y. He and K. Sumathipala, Experimental Validation of a Fire Growth Model, Proceedings of Interflam 96, 26-28 March 1996, Cambridge, England, pp. 653-662 (1996). 12. D. Yung and J. Ryan, Full-Scale Fire Tests to Validate NRC s Fire Growth Model - Open Office Arrangement, IRC Internal Report No. 717, June 1996, National Research Council of Canada, Ottawa, Canada (1996). 13. G.V. Hadjisophocleous, G. Proulx and Q. Liu, Occupant Evacuation Model for Apartment and Office Buildings, IRC Internal Report No. 741, May 1997, National Research Council of Canada, Ottawa, Canada (1997). 14. G. Proulx, Evacuation Time and Movement in Apartment Buildings, Fire Safety Journal, Vol. 24, pp. 229-246 (1995). 15. G. Proulx, A. Kaufman and J. Pineau, Evacuation Time and Movement in Office Buildings, IRC Internal Report No. 711, March 1996, National Research Council of Canada, Ottawa, Canada (1996). 26