Advanced diagnostics embedded in a pressure transmitter can detect integrity issues

Similar documents
Advanced Diagnostics for HART Protocol Rosemount 3051S Scalable Pressure, Flow, and Level Solutions

Advanced HART Diagnostic Suite

The evolution of level switches and detectors

SAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS)

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA

Diagnostics with fieldbus

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

Failure Modes, Effects and Diagnostic Analysis

Certification Report of the ST 3000 Pressure Transmitter with HART 6

Failure Modes, Effects and Diagnostic Analysis

STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT Revision 4 September 2017

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

United Electric Controls One Series Safety Transmitter Safety Manual

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators

Rosemount 2140:SIS Level Detector

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No

100 & 120 Series Pressure and Temperature Switches Safety Manual

Certification Report of the ST3000 Pressure Transmitter

Functional Safety Solutions

Digital EPIC 2 Safety manual

Session Ten Achieving Compliance in Hardware Fault Tolerance

Proservo NMS5- / NMS7-

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

Rosemount 3051S Electronic Remote Sensors

Failure Modes, Effects and Diagnostic Analysis

430128A. B-Series Flow Meter SIL Safety Manual

Proof Testing Level Instruments

SAFETY INTEGRITY LEVEL MANUAL. IEC and IEC XP95 and Discovery SIL Approved Product Range

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK

Functional Safety Manual Oil Leak Detector NAR300 System

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

Failure Modes, Effects and Diagnostic Analysis

Introduction. Additional information. Additional instructions for IEC compliant devices. Measurement made easy

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors

Failure Modes, Effects and Diagnostic Analysis

ADIPEC 2013 Technical Conference Manuscript

Technical Report Proven In Use SITRANS P500

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

Rosemount High Density Temperature Measurement. Simplify Your Project

Process Safety - Market Requirements. V.P.Raman Mott MacDonald Pvt. Ltd.

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark

Mobrey Magnetic Level Switches

SLG 700 SmartLine Level Transmitters Guided Wave Radar Safety Manual 34-SL Revision 4.0 December 2017

New requirements for IEC best practice compliance

SCADA 101 Introduction to SCADA Systems - Sensors, Data and Screens

ACCURATE FAILURE METRICS FOR MECHANICAL INSTRUMENTS IN SAFETY APPLICATIONS

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

Failure Modes, Effects and Diagnostic Analysis

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System

Safety lnstrumentation Simplified

Safety Instrumented Systems

Rosemount 4500 Hygienic Pressure Transmitter. Start

USER APPROVAL OF SAFETY INSTRUMENTED SYSTEM DEVICES

Failure Modes, Effects and Diagnostic Analysis

InstrumentationTools.com

Failure Modes, Effects and Diagnostic Analysis

Integrated but separate

Numerical Standards Listing

Pressure Transmitter cerabar M PMC 41/45 cerabar M PMP 41/45/46/48 with Output Signal ma/hart

IEC PRODUCT APPROVALS VEERING OFF COURSE

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

Rosemount 3051CFP Integral Orifice Flowmeter

Failure Modes, Effects and Diagnostic Analysis

Safety Transmitter / Logic Solver Hybrids. Standards Certification Education & Training Publishing Conferences & Exhibits

Temperature Data Logging

Effective Alarm Management for Dynamic and Vessel Control Systems

Rosemount 3051CFC Compact Flowmeter

FUNCTIONAL SAFETY MANUAL

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

The SIL Concept in the process industry International standards IEC 61508/ 61511

EPSS Monitoring for Total Compliance

Rosemount 4500 Hygienic Pressure Transmitter Demonstrated best-in-class performance during SIP/CIP for process temperatures up to 400 F (204 C)

Rosemount 4500 Hygienic Pressure Transmitter

Datasheet: K-22 LO Sensor

Safety in the process industry

IEC Functional Safety Assessment

Safety instrumented systems

Smarter Field Instrumentation Life Cycle Management. Ray Rogowski Global Marketing PMC Instruments

TD80 LEVEL GAUGING & OVERFILL PREVENTION SYSTEM PRODUCT MANUAL SUPPLEMENT. TPM 005 Revision 0.0

Rosemount 8800D Series Vortex Flowmeter

WW HMI SCADA-04 Discover the new Situational Awareness Library in InTouch 2014

Rosemount 3051L Level Transmitter

Failure Rate Data, Safety System Modeling Concepts, and Fire & Gas Systems Moderator: Lori Dearman, Webinar Producer Thursday, May 16th, 2013

IEC61511 Standard Overview

Failure Modes, Effects and Diagnostic Analysis

Safety Instrumented Systems The Smart Approach

TrueAlarm Analog Sensing

Configuration Data Sheet

Segment design & and Bus Diagnostics

Foundation Fieldbus Usability from field Device Perspective. Hemal Desai Endress+Hauser India Pvt. Ltd 16 th October 2014 Automation 2014 Mumbai

THE STANDARD OF EXCELLENCE WDG-V SERIES COMBUSTION ANALYZERS

Rosemount 2088, 2090P, and 2090F Pressure Transmitters

Transcription:

Advanced diagnostics embedded in a pressure transmitter can detect integrity issues 7 February, 2012Erik Mathiason, Jessica Lo and Natalie Strehlke comments Pressure transmitters measure pressure, flow, or level and may be used to control or monitor changes in a process. To receive these measurements, an operator relies on successful communication between the transmitter and the host system. A pressure transmitter with advanced diagnostics technology can detect issues with the integrity of this connection and proactively alert the operator of the possibility of miscommunication This technology can also provide a means for early detection of abnormal situations in a process environment. Having comprehensive diagnostic coverage improves the transmitter s overall safety levels to the highest levels seen in the industry. Advanced Diagnostics technology enables the user to respond to changes in both the process and electrical loop, troubleshoot, and proactively prevent future shutdowns. Electrical Loop Integrity Most pressure transmitters communicate using the 4-20 ma analog signal. To allow more information to be introduced into traditional automation networks, the HART (Highway Addressable Remote Transducer) Protocol was created as a standard for sending and receiving digital information via existing analog wiring. HART technology has been used to introduce many new transmitter innovations by utilizing this digital signal. In order to accurately obtain all of the information that is being communicated by the transmitter, an operator relies on the integrity of the electrical loop.

Advanced Diagnostics embedded in the pressure transmitter provide detection capabilities for failure modes that could occur in the electrical loop, such as power supply failures and on-scale measurement failures. Power Advisory Diagnostics monitor transmitter terminal voltage and sends notifications of unwanted changes on the electrical loop. Characterization of the electrical loop is completed when the diagnostic is enabled. The transmitter then automatically drives the terminal voltage to its low (20 ma) voltage and high (4 ma) voltage outputs. The characterization constructs a linear line between the two points (similar to Figure 1 below), and sets high and low voltage deviation limits that are parallel to that line. Figure 1: Power Advisory Diagnostic Technology When a deviation outside the limit occurs a HART alert or analog alarm will be sent to the host system. Many abnormal events can compromise the integrity of an electrical loop. From rainstorms to faulty power supplies to corroded terminals, each one of these events can cause the control system to receive an incorrect 4-20 ma signal from the transmitter. An issue that can occur is condensation accumulating in the terminal compartment, a result of poor conduit sealing. With enough water in the compartment a short may occur, causing an incorrect output signal ( see example in Figure 2 below).

Figure 2: Examples of Electrical Loop Issues Detectable by Power Advisory Diagnostics Spike in Output Another issue that Power Advisory Diagnostics can detect is an unstable power supply. Power supplies that drift or spike in output often indicate that the power supply is faulty and unreliable. Also, if the supply voltage decreases the transmitter may not have enough power to reach a high alarm value. Power Advisory Diagnostics calculates the power supply input and compares it against the characterization that was recorded during setup. This ensures that the varying power supply is not compromising the electrical loop. Advanced Diagnostics can detect certain types of on-scale failures by monitoring the transmitter power consumption and the 4-20 ma output. Monitoring the transmitter power consumption is critical to ensure that it can drive the appropriate alarm action when required. The transmitter should not consume more than 3.6 ma of current so it can drive to low alarm. Additional diagnostics verify that the analog 4-20 ma loop accurately reflects the pressure value. The conditions described above could result in an analog on-scale failure or even a loss of HART communication. Safety Coverage One measure of safety coverage, as defined per IEC 61511 Functional Safety: Safety Instrumented Systems for the Process Industry Sector, is the Probability of Failure on Demand or PFD.

PFD is defined as the probability that the SIS loop or device (transmitter) will have a failure or be in a failure mode upon demand when needed during a hazardous situation. This is undesirable as it impacts the ability for the SIS loop to function properly and prevent a catastrophic event from occurring. The Probability of Failure on Demand of a transmitter is heavily influenced by the transmitter s dangerous undetected failures. Dangerous undetected failures are identified during a Failure Modes, Effects and Diagnostics Analysis (FMEDA), conducted by a third party. During this activity the circuitry is analyzed component by component and each assigned failure modes. Each failure mode is classified as safe detected, safe undetected, dangerous detected and dangerous undetected and then assigned a probability. The numbers are based on the type of component and a large database of historical failure rates. Dangerous undetected failures are the most concerning as they may result in the transmitter not being able to perform properly during a safety shutdown event. A typical example of a failure that can occur within an electrical loop is a brown out. This is where there is enough power for the transmitter to operate but not enough power for the transmitter to reach 20 ma or to go to high alarm. Process noise Process diagnostics is where the transmitter uses Statistical Process Monitoring to look at process noise and detect an abnormal process condition. The transmitter first generates a process noise baseline and will tell you if it has changed outside the limits you configure. A typical example of a failure in this area is plugged impulse lines (see Figure 3 below). Figure 3: Comprehensive Protection from the Process to the Host Many other failures can be detected as well including loss of agitation, change in aeration or solids, and pump cavitations. When you factor in the internally focused diagnostics, as well as electrical loop and process diagnostics, you can achieve the safest, most reliable transmitter for use in an SIS system.

In conclusion, Advanced Diagnostics embedded in a Rosemount 3051S Pressure Transmitter can provide a means to ensure the operator is receiving the correct data values from the transmitter. This comprehensive detection coverage increases the pressure transmitter s overall safety levels to the highest in the industry. Advanced Diagnostics technology enables the user to proactively respond to changes in both the process and electrical loop, troubleshoot, and prevent future shutdowns. Tech Specs The Rosemount 3051S Pressure Transmitter with advanced diagnostics technology claims to have the industry's highest diagnostic coverage with a Safe Failure Fraction of 96.7 percent and the lowest dangerous undetected failures, resulting in the lowest PFD transmitter on the market. To achieve this rating, a number of internal transmitter focused diagnostics were added, such as power consumption and ma output. This transmitter can detect external failures that occur in the electrical loop and process that may otherwise go undetected. Electrical loop diagnostics is where the transmitter learns the voltage characteristics of the loop and alerts the operator if something changes. Authors: [Erik Mathiason is Marketing Engineer, Pressure Diagnostics; Jessica Lo is Senior Engineer, Pressure Research and Development; Natalie Strehlke is Product Marketing Manager, Pressure Technology. All three are with Emerson Process Management.]