O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS

Similar documents
Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS *

Model/Sprinkler Identification Numbers

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

Sprinkler Identification Numbers. TY3351 Horizontal TY3451 Vertical. Technical Data

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

* Temperature rating is FIGURE K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS

Sprinkler Identification Numbers

WRENCH FLATS NPT 1/2" 7/16" (11,1 mm) NOMINAL MAKE-IN. 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN.

Series TY-FRB 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Sprinkler Identification Number. Page 1 of 6 AUGUST 2018 TFP288. Worldwide Contacts.

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

Sprinkler Identification Numbers

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

Page 1 of 8 DECEMBER 2018 TFP408. Worldwide Contacts.

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response)

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

Model TY-FRFS, TY-FS Special, and TY-FS 57, 80, and 115 K-factor Upright and Pendent Flat Spray Sprinklers General Description

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Horizontal Sidewall Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

Submittal Packages Detailed with Items and Reviewers

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description

ESCUTCHEON PLATE SEATING 3/4" NPT SURFACE. 1-1/2" (38,1 mm) CROSS SECTION PENDENT RECESSED PENDENT

Model TY-FRFS, TY-FS Special, and TY-FS Flat Spray Sprinklers, Upright and Pendent 57, 80, and 115 K-factor General Description

Series TY-B & TY-FRB, 10 mm Orifice, ISO 7/1-R3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description

Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General Description

RAPID RESPONSE Series LFII Residential Sprinklers 5.6 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

Sprinkler Identification Number (SIN)

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

FIGURE 1 MODEL RFIII ECLH CONCEALED HSW SPRINKLER ASSEMBLY AND FEATURES. 5/16" (7,9 mm) MIN. 9/16" (14,3 mm) MAX.

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

G3/8" DIN ISO 228 THREAD SHOULDER AND DUST CAP MATING SURFACE. STYLE H ESCUTCHEON (SEPARATELY ORDERED) 85 mm DIA. (3-3/8")

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Sprinkler Identification Numbers

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

Sprinkler Identification Number (SIN) TY4234. Page 1 of 8 APRIL 2012 TFP Technical Services

MODEL: FA003U FA004U FA005P FA006P STANDARD SPRAY, STANDARD QUICK RESPONSE, 5 3 mm BULB TYPE, K5.6, 1/2" CONNECTING THREAD

Series LFII Residential Pendent Sprinklers 4.9 K-factor General Description

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

Automatic Sprinklers

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

Model WS TM 5.6 K-factor Specific Application Window Sprinklers, Horizontal and Pendent Vertical Sidewall General Description

The Series LFII (TY3596) Residential

Sprinkler Identification Number TY ECLH HSW, 8.0K, 3/4"NPT

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-Factor General Description

Automatic Sprinklers

UL LISTED. SPRINKLER HEADS IN STOCK: Pendent Upright Horizontal sidewall Concealed. RESPONSE Quick response Standard response

Worldwide Contacts.

5.6K Pendent, Upright, and Horizontal Sidewall Standard Response, Standard Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

11.2K * Pendent Extended Coverage, Light and Ordinary Hazard General Description. Model/Sprinkler Identification Numbers (SINs) Technical Data

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

Series LFII Residential Horizontal Sidewall Sprinklers 4.2 K-factor General Description

TECHNICAL DATA NOTICE

Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General Description

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description

esfr pendent sprinkler vk510 (k25.2)

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Standard Coverage, Model: RC-QR, K-Factor: 5.6, SIN: SS9561

Series LFII Residential Horizontal Sidewall Sprinklers 4.4 K-factor General Description

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

Commercial Flat Concealed Sprinkler, Pendent, Quick & Standard Response, Standard Coverage, Model: CN-QR, K-Factor: 5.

Transcription:

Worldwide Contacts www.tyco-fire.com Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description The Series TY-B, 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers described in this data sheet are automatic sprinklers of the standard response 5 mm frangible bulb type. They are standard spray sprinklers intended for use in fire sprinkler systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on NFPA requirements). Both the Pendent and Upright Sprinklers produce a hemispherical water distribution pattern below the deflector. Intermediate Level Sprinklers are primarily designed for use in rack storage sprinkler systems where their thermally sensitive elements must be shielded from the water spray of higher elevation sprinklers that could operate earlier during a fire. Intermediate Level Sprinklers are also used in other applications such as beneath open gridded catwalks. IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the INSTALLER WARNING that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. NOTICE The Series TY-B Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Sprinkler Identification Numbers TY3153 TY3251 TY4153 TY4251 Upright 5.6K, 1/2 in. Pendent 5.6K, 1/2 in. Upright 8.0K, 3/4 in. Pendent 8.0K, 3/4 in. Technical Data Approvals UL and C-UL Listed FM and NYC Approved (Refer to Table A for complete approval information including corrosion resistant status.) Maximum Working Pressure 175 psi (12,1 bar) Discharge Coefficient K = 5.6 GPM/psi ½ (80,6 LPM/bar ½ ) K = 8.0 GPM/psi ½ (115,2 LPM/bar ½ ) Temperature Ratings Refer to Table A Finishes Sprinkler: Refer to Table A Physical Characteristics Frame...Bronze Button.... Brass/Copper Sealing Assembly................ Beryllium Nickel w/teflon Bulb... Glass Compression Screw................ Bronze Deflector....Copper Shield...Plated Steel Page 1 of 6 AUGUST 2018 TFP351

Page 2 of 6 * Temperature rating is indicated on deflector, ** Pipe thread connections per ISO 7-1 can be shield, or adjacent to orifice seat on frame. provided on special request. SCREW O-RING 1/2" ** 7/16" (11,1 mm) NOMINAL MAKE-IN 2-3/8" (60,3 mm) 7/16" (11,1 mm) NOMINAL MAKE-IN * MODEL S2 2-3/16" (55,6 mm) (FACTORY ASSEMBLED) 1/2" ** (FIELD ASSEMBLED - SEE INSTALLATION SECTION) FIGURE 1 SERIES TY-B (TY3153) AND (TY3251) SPRINKLERS STANDARD RESPONSE INTERMEDIATE LEVEL SPRINKLERS, 5.6 K-FACTOR, 1/2 INCH * Temperature rating is indicated on deflector, ** Pipe thread connections per ISO 7-1 can be shield, or adjacent to orifice seat on frame. provided on special request. SCREW O-RING 3/4" ** 1/2" (12,7 mm) NOMINAL MAKE-IN 2-7/16" (61,9 mm) 1/2" (12,7 mm) NOMINAL MAKE-IN * MODEL S2 2-5/16" (58,7 mm) (FACTORY ASSEMBLED) 3/4" ** (FIELD ASSEMBLED - SEE INSTALLATION SECTION) FIGURE 2 SERIES TY-B (TY4153) AND (TY4253) SPRINKLERS STANDARD RESPONSE INTERMEDIATE LEVEL SPRINKLERS, 8.0 K-FACTOR, 3/4 INCH

Page 3 of 6 SPRINKLER FINISH (SEE NOTE 5) K TYPE TEMP. BULB LIQUID (TY3153) NATURAL BRASS** LEAD COATED WAX COATED** 1, 2, 3, 4 1, 2, 3, 4 N/A WAX OVER LEAD COATED** 5.6 1/2 in. 8.0 3/4 in. (TY3251) (TY4153) (TY4251) 286 F (141 C) Blue 360 F (182 C) Mauve 1, 2, 3, 4 1**, 2**, 3**, 4** 1, 2, 3, 4 286 F (141 C) Blue 1*, 2*, 3*, 4* 360 F (182 C) Mauve N/A 286 F (141 C) Blue 360 F (182 C) Mauve 1, 2, 3, 4 1, 2, 3, 4 N/A 1, 2, 3, 4 1**, 2**, 3**, 4** 1, 2, 3, 4 286 F (141 C) Blue 1*, 2*, 3*, 4* 360 F (182 C) Mauve N/A NOTES: 1. UL Listed. 2. C-UL Listed. 3. FM Approved. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers. *150 F (66 C) Maximum Ceiling Temperature. ** With Zinc Plated Shield. N/A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS Operation The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. Design Criteria The Series TY-B Pendent and Upright Intermediate Level Sprinklers are intended for fire protection systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM s Loss Prevention Data Sheets).

Page 4 of 6 Installation The Series TY-B, Upright and Pendent Intermediate Level Sprinklers must be installed in accordance with this section. General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135 F (57 C) to 3/32 in. (2,4 mm) for the 360 F (182 C) temperature ratings. A leak tight 1/2 in. sprinkler joint should be obtained with a torque of 7 to 14 b-ft (9,5 to 19,0 N m). A leak tight 3/4 in. sprinkler joint should be obtained with a torque of 10 to 20 lb-ft (13,4 to 26,8 N m). Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler. Upright Sprinklers The Series TY-B Intermediate Level Upright Sprinklers must be installed in accordance with the following instructions. Step 1. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (refer to Figure 3), except that an 8 in. or 10 in. adjustable Crescent wrench is to be used for wax coated sprinklers. With reference to Figure 1 or 2, the W-Type 6 Sprinkler Wrench or the Crescent wrench, as applicable, is to be applied to the wrench flats. Pendent Sprinklers The Series TY-B Intermediate Level Pendent Sprinklers must be installed in accordance with the following instructions. Step A. Thread the S2 Shield onto the sprinkler threads with the stamped markings toward the deflector and just to the end of the threads. The final assembly step is easier to accomplish if the Shield is not disengaged by continuing to turn the Shield past the threads. Step B. Roll the O-Ring over the sprinkler threads until it seats against the Shield. Step C. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step D. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (refer to Figure 3). With reference to Figure 1 or 2, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats. Step E. Rotate the S2 Shield clockwise (looking up) so that it slightly compresses the O-Ring between the Shield and sprinkler fitting. Wax Coated Sprinklers When installing wax coated sprinklers with the adjustable Crescent wrench, additional care needs to be exercised to prevent damage to the wax coating on the sprinkler wrench flats or frame arms and, consequently, exposure of bare metal to the corrosive environment. The jaws of the wrench should be opened sufficiently wide to pass over the wrench flats without damaging the wax coating. Before wrench tightening the sprinkler, the jaws of the wrench are to be adjusted to just contact the sprinkler wrenching flanges. After wrench tightening the sprinkler, loosen the wrench jaws before removing the wrench. After installation, the sprinkler wrench flats and frame arms must be inspected and the wax coating retouched (repaired) whenever the coating has been damaged and bare metal is exposed. The wax coating on the wrench flats can be retouched by gently applying a heated 1/8 in. diameter steel rod to the areas of wax that have been damaged, to smooth it back over areas where bare metal is exposed. NOTES Only retouching of the wax coating applied to the wrench flats and frame arms is permitted, and the retouching is to be performed only at the time of the initial sprinkler installation. The steel rod should be heated only to the point at which it can begin to melt the wax, and appropriate precautions need to be taken, when handling the heated rod, in order to prevent the installer from being burned. If attempts to retouch the wax coating with complete coverage are unsuccessful, additional wax can be ordered RECESS (END "B" USED FOR 3/4" MODELS) RECESS (END "A" USED FOR 1/2" MODELS) FIGURE 3 W-TYPE 6 SPRINKLER in the form of a wax stick (the end of which is color coded). Only the correct color coded wax is to be used, and retouching of wrench flats and frame arms is only permitted at the time of initial sprinkler installation. With the steel rod heated as previously described, touch the rod to the area requiring additional wax with the rod angled downward, and then touch the wax stick to the rod approximately onehalf inch away from the area requiring retouching. The wax will melt and run down onto the sprinkler.

Page 5 of 6 Care and Maintenance The Series TY-B, Upright and Pendent Intermediate Level Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated or otherwise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb (refer to Installation Section). The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The installing contractor or sprinkler manufacturer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national code. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Numbers (P/N). Upright Sprinkler Assemblies with Shield and Thread Connections Specify: Series TY-B (specify SIN), (specify K-factor), Upright Intermediate Level Sprinkler Standard Response, (specify) temperature rating, with (specify finish or coating), P/N (specify from Table B) Pendent Sprinkler Assemblies with (Shield Ordered Separately) and Thread Connections Specify: Series TY-B (Specify SIN), (specify K-factor), Pendent Sprinkler Standard Response, (specify) temperature rating, with (specify finish or coating), P/N (specify from Table C) Model S2 Pendent Shield & O-Ring Specify: S2 Pendent Shield & O-Ring for use with (specify 1/2 or 3/4 ) Series TY-B Pendent Sprinklers, P/N (specify) 1/2 in. S2 Pendent Shield & O-Ring...... P/N 56-070-9-332 3/4 in. S2 Pendent Shield & O-Ring...... P/N 56-070-9-342 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Wax Sticks (for retouching wrench damaged wax coating) Specify: (Specify color) color coded Wax Stick for retouching (specify) temperature rating temperature rated Series TY-B Sprinklers, P/N (specify) Black for 135 F (57 C)..P/N 56-065-1-135 Red for 155 F (68 C)...P/N 56-065-1-155 Yellow for 175 F (79 C)..P/N 56-065-1-175 Blue for 200 F (93 C) and 286 F (141 C)....P/N 56-065-1-286 NOTES Each wax stick is suitable for retouching up to twenty-five sprinklers. The wax used for 286 F (141 C) sprinklers is the same as for 200 F (93 C) sprinklers, and, therefore, the 286 F (141 C) sprinkler is limited to the same maximum ceiling temperature as the 200 F (93 C) sprinkler (i.e., 150 F (66 C).

Page 6 of 6 TFP351 Page 6 of 6 P/N 57 XXX X XXX SIN SPRINKLER TEMPERATURE RATING 533 5.6K (1/2 in. ) TY3153 1 NATURAL BRASS 135 135 F (57 C) 543 8.0K (3/ in. ) TY4153 7 LEAD COATED 155 155 F (68 C) 175 175 F (79 C) 200 200 F (93 C) 286 286 F (141 C) 360 360 F (182 C) TABLE B SERIES TY-B INTERMEDIATE LEVEL SPRINKLERS PART NUMBER SELECTION (Upright Shield Included With Sprinkler) P/N 57 XXX X XXX SIN 571 5.6K (1/2 in. ) TY3251 SPRINKLER 1 NATURAL BRASS TEMPERATURE RATING 135 135 F (57 C) 591 8.0K (3/4 in. ) TY4251 6 WAX COATED 286 F (141 C) MAXIMUM 155 155 F (68 C) 7 LEAD COATED 175 175 F (79 C) 8 WAX OVER LEAD 286 F (141 C) MAXIMUM 200 200 F (93 C) 286 286 F (141 C) 360 360 F (182 C) TABLE C SERIES TY-B SPRINKLERS PART NUMBER SELECTION (Model S2 Pendent Shield & O-Ring Must Be Separately Ordered) 1400 Pennbrook Parkway, Lansdale, PA 19446 Telephone +1-215-362-0700 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a registered trademark of DuPont