ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat

Similar documents
SAS803WHL-7 Thermostat for floor heating

ONX908MTW-0/24V MULTI STAGE THERMOSTAT

Eswa DC-1. Thermostat for Floor Heating

ONX908FCT-4B/220V/RC FAN COIL THERMOSTAT

SAS908WHB-3-RF/B WIRELESS THERMOSTAT

Smart Temp. Model

SAS6000UTK-7 UNIVERSAL THERMOSTAT

T6865 Series Large LCD Digital Thermostat 24 VAC 2-pipe fan coil control

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

1F Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

ET10 Series Stand-alone LCD Fan Coil Thermostat

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings

T6590 Series FAN-COIL CONTROLLER

1F Non-Programmable Electronic Digital Multi-Stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

SAS6000UTK-7-WIFI OPERATING INSTRUCTION

T6590 Series FAN-COIL CONTROLLER FEATURES APPLICATIONS PRODUCT DATA

INSTALLATION & USER MANUAL

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Touch Screen Thermostat. MTSC/SUPER, MTSC24/SUPER Series. MTS/SUPER, MTS24/SUPER Series. Owner s manual and technician settings

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

Touch Screen Thermostat. MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series. MTS/SUPER/CO2, MTS24/SUPER/CO2 Series. Owner s manual and technician settings

Networkable Fan Coil Controller Specification and Installation Instructions

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

OPERATING INSTRUCTIONS

Operator: SaVe these instructions forfuture use

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

ETAF Series VDC Fan output LCD Fan Coil Thermostat

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

Single Zone LCD Thermostat Operating Instructions

XE99 SERIES FAN-COIL THERMOSTATS 2-PIPE & 4-PIPE FAN-COIL CONTROL FEATURES APPLICATION PRODUCT SPECIFICATION SHEET

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

T600MEP-2 Programmable Economizer Thermostat

- Data Brochure Universal Reset Module 422

B-40/B-41 Modulating Temperature Controller

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

Operator: Save these instructions for future use!

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

Room Temperature Controller

INSTRUCTION MANUAL ECO RANGE FAR INFRARED HEATER

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

T6861 Series Large LCD Digital Thermostat Two stage Cool Control. Product specification sheet. Features. Application.

VENSTAR T1070 FAN COIL THERMOSTAT PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

DPC-1 Programmable digital thermostat with communication Versión 2.0. Technical Information. Ref: N

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

Smart Temp. ApolloP/n Installation Manual. Version 1.0

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

QUICK INSTALLATION GUIDE

Emerson Blue Easy Set 1H/1C

- Data Brochure Universal Reset Module 423

IF79 CAUTION CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS. Installation Instructions for. Heating & Air Conditioning

GreenCon On/Off Room Thermostat

GreenCon On/Off Room Thermostat

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions

Comfort System T-21-P Touchscreen Thermostat Installation Manual

Digi-Sense TC9000 Advanced PID and On/Off Temperature Controller with Thermocouple Input

Phone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction.

HTW-% Series Large LCD Digital Thermostat 110VAC/220 VAC 2-pipe/4-pipe fan coil control. Features

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

Operator: Save these instructions for future use

Installation Instructions

OVEN INDUSTRIES, INC.

ATP21W02 CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS REMOVING OLD THERMOSTAT 2 THERMOSTAT DETAILS

Heat Link. Technical Guide

CONTENTS. Installation Guide. VT7200 Series

TDU Series LCD Thermostat For EFCB and EVCB Controllers. Models. Features. Functions. Onboard Sensors. Model # Temp RH CO2 Color.

TEC210x-2 Series Networked Thermostats

- Data Brochure tekmarnet 4 Thermostat 542e

ARO Series. Description. Features. Modbus CO2 VOC. Networkable* ARO AROB24TGVH AROB24TGH. room controller. (AROB series only) or network

CommStat 4 Controller

Operator: Save these instructions for future use!

T170 Thermostat. Installation and Maintenance Manual. 24 VAC/ VAC 3-Speed Fan Control (Continuous or Cycling) or Staged Fan Control

TB7300 Series Communicating Fan Coil Thermostats 24 VAC/FOR COMMERCIAL AND LODGING HVAC APPLICATIONS

Installation, Start-Up, and Operating Instructions

Operator: Save these instructions for future use!

ELECTRONIC COMMUNICATING THERMOSTAT

Product Manual SZ1022/SZ1031/SZ1035/

TEC2100 Series Networked Thermostats

T-32-TS Touchscreen Thermostat. Installation Manual

Fan Coil Thermostat. Specification & Installation Instructions TFC54F3Y1. Technical Data

TH146-N-2H1C. 1. Introduction. 2. Installation. 1.1 Applications. 2.1 Control Module (CT280-2H1C) 1.2 Supplied Parts. 1.

- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions

RC-2000 Thermostat Installation Instructions

Operator: Save these instructions for future use!

RC-122BZ Two Stage Heat/Cool 2 Stage Heat / 2 Stage Cool Thermostat Installation Instructions

T6862 Series Large LCD Digital Thermostat Time Programmable 2-pipe/4-pipe fan coil control

Safety & Installation Instructions

T6572A, T6573A,B, T6992A,B, T6993B Digital Fan-Coil Thermostats XE88/XE100 SERIES

NCU Mounting Details

Programmable Thermostat

Model: PRT-TS / PRT-NTS


TIREE FAN COIL CONTROLLER - T6580

ETN24-P/PD-FC-SUPER2. Owner's Manual - Installation and Operating Instructions

MC200. Users Instructions. HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: Fax:

45 Commerce Ave., Unit #2 South Burlington, VT tel: fax:

TER Active Room Temperature Sensor (Controller),

Transcription:

ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat Installation and operation instructions The ONX908PIT-V1-S1-F1 modulating digital thermostats are designed to provide Proportional-Integral (PI) modulating control in 2-pipe or 4-pipe fan coil units, zoned commercial heating, Ventilating and various heating and cooling applications. This thermostat provides modulating analog 0-10V or 4-20mA control. Other available feature includes energy savings card key input, auto-detection of temperature sensor (remote sensor or internal sensor), and optional Celsius or Fahrenheit operation. SPECIFICATION: Input Voltage 24Vac, 50/60 Hz (Digital Thermostat) 24Vac-250Vac; 50/60Hz (Fan) Output Voltage Modulating output 4 to 20mA or 0-10VDC On/Off output for fan 5A 250VAC Room temperature setting range 5 to 35 (41 to 95 ) Accuracy. ±0.1 or ±0.2 Dimensions 115mm 90mm 28mm Color.. White FEATURE: Large LCD display The screen displays the set temperature, the room temperature simultaneously Permanent user setting and program setting retention during power loss, Special energy saving mode-external input from window contact or hotel card-key overrides the temperature setting to installer defined heating and cooling temperatures 0-10Vdc or 4-20mA heat and cool outputs Fan switch with on and auto Fahrenheit or Celsius display capability IMPORTANT SAFETY INFORMATION: Always turn off power at the main power source by unscrewing fuse or switching circuit breaker to the off position before installing, removing, cleaning, or servicing this thermostat. Read all of the information in this manual before installing this thermostat. Only a professional contractor should install this thermostat. All wiring must conform to local and national building and electrical codes and ordinances. Use this thermostat only as described in this manual. 1

KEYBOARD, DISPLAY AND SWITCH DESCRIOPTION (7) (8) (9) (1) (2) (3) (4) (5) (16) (10) (11) (6) (15) (14) (12) (13) Figure 1 Figure 2 (1) Power Button (2) System Button (3) Fan Button (4) Setback Button (5) Raise Temperature setting button (6) Lower Temperature setting button (7) Bar Graph Shows approximate Power Output of Modulation Output (8) Indicates the Portion of Modulating Output (9) Setting temperature (10) Shows temperature display in or (11) indicates when thermostat is in setback mode. (Energy saving mode) indicates when thermostat is in normal operation. (Comfort mode) (12) Indicates different fan speed (13) Shows when card key is vacant (14) Indicates system icon (15) indicates when there is a call for On/Off heating (16) Shows Current Read temperature 2

INSTALL THE THERMOSTAT ATTACH THERMOSTAT BASE TO WALL Screw for mounting thermostat to wall Base Control panel Figure 3 Fixing screw 1. Remove 2 screws from the bottom of thermostat. Gently pull the control panel straight off the base. Forcing or prying on the thermostat will cause damage to the unit. 2. Connect wires beneath terminal screws on power supply module using appropriate wiring schematic. See figure 4 3. Push power base into wall. 4. Using two mounting screws mount the power base to the wall. Place a level against bottom of base, adjust until level, and then tighten screws. (Leveling is for appearance only and will not affect thermostat operation.) 5. Replace control panel on the power base and fix power base and control panel by removed two screws in item 1 WIRING DIAGRAM NLOccupancy 24VAC Switch DC0~10V Or 4~20MA Modulating Output AOUT+ AGND- External Sensor Heating Relay ON OFF Med Fan 1 2 3 4 5 6 7 8 9 10 11 12 13 Figure 4 3

Occupancy Switch C 24VAC R DC0~10V Or 4~20MA Modulating Output AOUT+ AGND- External Sensor Heating Relay ON OFF Med Fan 1 2 3 4 5 6 7 8 9 10 11 12 13 Figure 5 OPERATION Control Output 1: Terminal 12 and 13. The main output of the thermostat is modulating PI analog (4~20mA or 0-10Vdc). This signal uses a variable ma signal for the control of analog damper actuator and analog valve actuator in cooling or heating. (User can select On/Off output by terminal 7 and 9 to control heating system. See configuration menu item 12) Output 2:On/off output from terminal 7 and 8. This output can be used as the main output for heating system or act as the second heating output. (See configuration menu item 12). If it is selected as the second heating output, it will activate the second stage heating when the setting temperature is 1 plus P-band value higher than room temperature. System Button Pushing system button to select among heat mode, cool mode and auto mode. Heat mode: Thermostat operates only for heating Cool mode: Thermostat operates only for cooling Auto mode: Thermostat operates in automatic change over Automatic change over function is available only when external sensor installed in terminal 3 and 4. In automatic changeover, the thermostat detects when the system switches between heat mode and cool mode by comparing the air supply temperature with the ambient temperature. If the thermostat is in heat mode, it switches to cool mode when the air supply is cooler than ambient by 5 (9 ) or more. If it is in cool mode, it switches to heat mode when the air supply is warmer than ambient by 5 (9 ) or more. Fan Button Set fan button to Med or Auto Auto is the most commonly selected setting and runs the fan only when the heating or cooling system is on. Fan runs continuously in medium speed for increased air circulation. Setback Button Holding the setback button for 5 seconds, the thermostat can shift from comfort mode to setback (energy saving). Factory default setting for setback mode in heating is 18 and for cooling is 25. Shows indicate you are now in comfort mode while shows indicate you are now in setback mode. Every time 4

you change the setting in comfort mode, the new setpoint will be memorized as the setpoint of the comfort mode. You can change the setback setting in configuration menu item 5 and 6 Energy Saving Mode Energy Saving mode is activated by a special input from a card key, occupancy switch or window contact switch. If the signal via input terminals 4 and 5 is calling for energy saving mode. Then the thermostat will control to user/installer defined setback setpoints for increased energy savings. The display will show symbol to indicate when this mode is active. Shows energy saving mode is activated by input signal. During energy saving mode, setpoint cannot be changed. The setback setpoint can be change in configuration item No.6 and No.7. Factory default setting for heating is 18, for cooling is 25. For example, if the user setpoint is 21 and the energy Savings Mode setpoint for cooling (unoccupied cooling setpoint) has been set to 28, then the thermostat will control to 28 when the input signal activated the Energy Saving mode.. The energy saving mode input can be configured within the configuration menu item 13 to be Card activated either a short circuit (default) or open circuit signals. 4 5 Dip Switch: A two-way DIP switch allows selection of modulating analog output between 4 to 20mA and 0~10V. Open the thermostat, you will find the JP6 in the rear board. Following figure showing you how to select 0~10V output and 4~20mA output via change the dip switch position. 0~10V 0~10V 4~20mA 4~20mA 0~10V output 4~20mA output Note: The configuration menu item 15 should match with the Dip Switch Position CONFIGURATION Configuration Menu The configuration menu allows you to set certain thermostat operating characteristics to your system or personal requirements. Switch off the thermostat. Hold button (4) for 5 seconds to enter the configuration menu. The display will show the first item in the configuration menu 1. Press button (4) to shift to the next menu item. Use to select. To exit the menu, pressing button (1) to switch off the thermostat. If no buttons are pressed within 20 seconds the thermostat will exit the menu. To revert to factory default setting, push (2) button for 3 seconds. Display will show DEF blinking 3 times and return to Menu item 1 indicates all the configuration setting has reverted to factory default setting. The configuration menu chart summarizes the configuration options. An explanation of each option as follows: 1) Select ºF or ºC Readout Changes the display readout to Centigrade or Fahrenheit as required. 2) Select temperature recalibrates Adjustment 3 LO to 3 HI You can adjust the room temperature display up to 3 higher or lower. Your thermostat was accurately 5

Item Press buttons Displayed(factory default) Press to select Description 1 (4) For 5 second FC ( ) / Select ºF or ºC Readout 2 (4) CL (0) -3 --- +3 Select temperature display adjustment higher or lower 3 (4) CH (35 /95 ) 18 (64 ) 35 (95 Select maximum setpoint ) 4 (4) CC (5 /41 ) 5 (41 ) 20 (68 ) Select minimum setpoint 5 (4) UC (25 /77 ) 25 (77 )-30 (90 ) Select setback point for cooling 6 (4) UH (18 /65 ) 10 (50 )- 18 (65 ) Select setback point for heating 7 (4) PH (2) 0-10 Select P-band 8 (4) LP (5) 1-10 Integral action time 9 (4) FH (100) (50-100) Maximum integral part 10 (4) FL (0) (0-50) Minimum of integral part 11 (4) bl (1) 1/2/3 Select display backlight mode 12 (4) HF (h1) h1/of/h2 Heating output type option 13 (4) En (AC) OU/AC Active temperature sensor OU:Return air temperature sensor active AC:Room temperature sensor active AU: Mix temperature sensor active 13 (4) rc (SC) SC/OC/OO Activate energy saving mode option 14 (4) U (I) U: 0 10 VAC output I: 4-20 MA output Choose the control mode between 0~10VAC output to 4~20MA output 15 Press Power Button return to close calibrated at the factory but you have the option to change the display temperature to match your previous thermostat. The current or adjusted room temperature will be displayed on the right side of the display. 3) Select maximum temperature set point This feature provides a maximum set point temperature. The default setting is 35 (95 ), It can be changed between 18 (64 ) to 35 (95 ) 4) Select minimum temperature set point. This feature provides a minimum set point temperature. The default setting is 5 (41 ), It can be changed between 5 (41 ) to 20 (68 ) 5) Select energy saving setpoint for heating This feature provides energy saving setpoint temperature for heating. The default setting is 16, It can be changed between 10 to 18 6) Select energy saving setpoint for cooling This feature allows you to set energy saving setpoint temperature for cooling. The default setting is 25, It can be changed between 25 to 30 7) Select P-band 6

The proportional band is the amount of change required by the ambient temperature for the output to go from 0 to 100%. It can be adjust from 0~10. Factory default setting is 2. For example if the P-band is set in 2 in the heat mode, with a 25 set point and an ambient temperature of 25, the modulating output is 0%; at 24 the output is 50%; and at 23 the output is 100%. The intergral gain implies that the longer the error between the ambient and the set point temperatures exists, the more the output will change to eliminate the error. The integral portion of the algorithm eliminates the temperature offset from the set point. Heat mode (P-band: 2 ) When the ambient temperature is below the set point the output is somewhere between 0~100% % of Output 0-10V or 4-20mA 100% 50% 0% Figure 5-3 -2-1 Set point +1 +2 +3 Cool mode(p-band: 2 ) When the ambient temperature is above the set point the output is somewhere between 0 and 100% % of Output 0-10V or 4-20mA 100% 50% 0% Figure 6-3 -2-1 Set point +1 +2 +3 8) Select integral action time This feature allows you to set the integral action time for the integral to run from 0 to 100%. The value required depends on the reaction time of the control loop. If the time is chosen too short, the control loop will become instable and oscillate. If the time is chosen too long, the control loop will become sluggish. 9) Select maximum integral portion This feature allows you to set the maximum modulating output. For example, if you set the maximum integral portion to 80%, the maximum modulating output will be 8V or 16.8mA. 10) Select minimum integral portion This feature allows you to set the minimum modulating output. For example, if you set the maximum 7

integral portion to 20%, the maximum modulating output will be 2V or 7.2mA. 11) Display backlight option Select 1 the light will be on when any button of the thermostat is touched. Select 2 the display will keep the light on continuously. Select 3 the display will keep the light off continuously Factory default is 1 12) Heating type option h1: Only proportional output for heating control is available, terminal 12 and 13 (See Figure 4) is used as 0-10V or 4-20mA modulating output to control heating or cooling OF: Only On/Off output for heating control is available. Terminal 7 and 8 (Figure 4) is the On/Off output to control heating. Terminal 12 and 13 is used as 0-10V or 4-20mA modulating output to control only cooling. h2: 2 stage heating active. Terminal 12 and 13 (See Figure 4) is used as 0-10V or 4-20mA modulating output to control 1 st stage heating. Terminal 7 and 8 (Figure 4) is the On/Off output to control 2 nd stage heating. 13) Select active temperature sensor This feature provides two active temperature sensor option. Select OU means return air temperature sensor active Select AC means room temperature sensor active Select AU means mix temperature sensor active for seasonal changeover 14) Activate energy saving mode option This feature allows you to select the way to activate the energy saving mode. Select OC to activate the energy mode by open circuit Select SC to activate the energy mode by close circuit Select 00 to cancel the energy mode 15) Shift between 0~10VAC output to 4~20MA output This feature allows you to select the way to shift the mode between 0~10VAC output to 4~20MA output. NOTE: Do not forget to change the position of the dip switch so that it can match with output option. (See dip switch in Operation Chapter) CUSTOMER ASSISTANCE After reading this guide, if you have any question about the operation of your thermostat, please contact your installer or Energy Utility company or service provider. 8