TOPAZ ADIABATIC COOLER

Similar documents
PAD. Adiabatic cooler. PAD series

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

TrilliumSeries Condenser 1 TRILLIUMSERIES CONDENSER 10 ECOFLEX CONTROLS 11 SELECTION AND PAYBACK ANALYSIS SOFTWARE 3 BENEFITS 8 MODES OF OPERATION

MH fluid cooler HYBRID DESIGN. HIGHER PERFORMANCE.

MH Fluid Cooler HYBRID DESIGN. HIGHER PERFORMANCE.

THE TRUSTED ADIABATIC COOLER AND CONDENSER

kw. technicalcatalogue

KELVIN Clim F497. Kelvin air conditioning

I.O.M. #116 7/10 INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE. Covers Models from 25 to 100 tons.

PRODUCT GUIDE SPECIFICATIONS

AQUASNAP JUNIOR 30RHV

39HX. High-efficiency dual-flow air handling unit PRODUCT SELECTION DATA. Plug & play unit (built-in control) Class A+ across entire range

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

Fibreglass reinforced polyester (FRP) water collection basin with sloping base and smooth internal finish with rounded corners for easy cleaning.

INFO. Compact V-SHAPE. Condenser GCDC for HFCs and propane Gas cooler GGDC for CO 2 Fluid cooler GFDC for water/glycol and other fluids.

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

Air Conditioning Inspections for Buildings Condensers

Condensing Units CUS 15-60

Main technical datas:

EXPAIR. Use. Precision air handling cabinets. Reducted footprint Dual-wall construction

VERSO Air Handling Units

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Blow through unit coolers LEX. Standard coolers for cooling & freezing rooms

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

COOLROW Close control air conditioners for In-Row installation Cooling Capacity: kw

Compact VERTICAL FLAT. Compact. Condensers GCHC/GCVC for HFCs, NH 3

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

Conditioning your ambient, maximising your comfort.

MLC Air Cooled Chillers MLC-FC Free Cooling Chillers MLC-AD Adiabatic Chillers

Colt CoolStream Adiabatic Cooling & Ventilation System

HYBRID ADIABATIC Cooling System

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

Air-Handling System Cooling Options

Daikin Applied UK Technically better... D-AHU Modular R. Air handling units. Compact air handling unit with heat recovery wheel

TrilliumSeries. Condenser

The Fine Line of Heat Rejection

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

Leadership, Innovation, Advanced Technology Synergise Here!

Adsolair 56/58. Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system

Adconair 76. Comfort air conditioning unit with counterflow plate heat exchanger. AIR VOLUME FLOW: 2,600 23,600 m³/h

Engineering Specifications for HXV Closed Circuit Hybrid Cooling Tower

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

DAIKIN Air Handling Unit Modular

Chillers, air and water cooled, featuring centrifugal compressors with magnetic levitation, from 200 to kw

Air cooled industrial chillers

Remote Air Cooled Condensers C2 Series

VERSO Air Handling Units

The plug & play fresh Air Solution

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

HEATING & COOLING COIL PRODUCTS

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Refrigeration dryers with Energy Saving Impulse Technology and Thermal Mass 0,3-27,0 m³/min Purifying your compressed air, increasing your efficiency.

Performance Data ADSORPTION CHILLER AGGREGATES & SYSTEM COMPONENTS

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

EHH SERIES DRAW THROUGH FAN COILS CFM

Product Catalog. DCHC Horizontal Concealed Chilled Water Fan Coil with DCBL Motor Airflow: 180~2380 m 3 /h

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

Closed Circuit Cooling Towers

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Air-Handling System Cooling Options


YCAL-SB Millennium AIR COOLED LIQUID CHILLER R407C REFRIGERANT. COOLING CAPACITIES 141 kw to 360 kw

System-CoolAC. Bharatividyapeeth College of Engineering, Deekshant Bharti Scholar, New Delhi, India

Outdoor Refrigeration Unit - ZX Range High Efficiency In Compact Design

OPERA MORE. Use. Range. Drycoolers Air-cooled condensers. for LESS. Capacity: up to 1100 kw. Water misting. Free cooling

UNICO TURBO FL FREE UNICO TURBO FL FREE HIGHEFFICIENCY INVERTER ACLASS FREECOOLING LOWNOISE. rcgroupairconditioning

Lenntech. Tel Fax

Precision air handling cabinets Ciatronic MICRO/EXPAIR

HRV-IP. Ceiling Type Heat Pump Heat Recovery Unit

GLIDER EVO FREE GLIDER EVO FREE GLYCOL FREECOOLING. rcgroupairconditioning

i-chiller 181 to 210 kw ic770 to ic780 ABOUT THE i-chiller RANGE RELIABILITY: ENERGY & PROCESS EFFICIENCY: EASE OF OPERATION & MAINTENANCE:

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

4,5 22,5 kw. technicalcatalogue. Air-conditioned server-racks for direct installation into the room T_CLSEVO_0113_GB

GENERAL INFORMATIONS

DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: , Fax#: ,

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW

EPCE00-10B. Powerful. air cooled. Hydronic systems EUWA*40-200K(A)X

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

NEOSYS. AIR TO WATER LIQUID CHILLER kw. AIR TO WATER HEAT PUMP kw. lennoxemea.com

TECHNICAL SPECIFICATIONS - CW-80T AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

AIRSYS-P-SC-CHILLROW-E1503V01.1 CHILLROW. Row Cooling Precision Air Conditioner. Cooling Capacity: 26.2kW~68.6kW

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

DUCTED UNITS EBH EDS INTEGRATED COMFORT SYSTEMS

GLIDER EVO GLIDER EVO. rcgroupairconditioning

Presenters. Brett Alexander. Mihir Kalyani. Troy Reineck

Efficient heating that won t cost the earth

NEXT DL NEXT DL. rcgroupairconditioning

kw COOLING kw HEATING

GP SERIES Packaged Chillers

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

CONDAIR EL. Electrode boiler steam humidifier Easy maintenance with replaceable cylinders. Humidification and Evaporative Cooling

Process glycol chillers

VEXTRA. acoustic comfort Saves up to. 40% floor space. Use. Range. Description. Drycoolers. Slim design and. Capacity up to kw.

TECHNICAL SPECIFICATIONS - CW-80T-TWIN AUSTRALIAN, EUROPEAN, SOUTH AFRICAN & UK

Transcription:

TOPAZ ADIABATIC COOLER CONTENT Page Principle and operation 2 General description and benefits 3 TECHNICAL DOCUMENTATION Manufacturing details Options 4 6 Drawings and dimensions 7 On site lay out 8 Technical description 9 10 DT_TOPAZ UK 05-12-13

TOPAZ Principle and operation Principle The TOPAZ adiabatic cooler is a heat exchanger; calories / heat are rejected to atmosphere. The TOPAZ adiabatic cooler is a combination of dry cooler with an adiabatic precooling section: this precooling section lowers ambient air temperature by evaporating water which is passed over the cooling / humidifying pads, specially designed for this purpose. Adiabatic cooler operation Air outlet Water inlet Water outlet Air inlet Dry coil Water make up Humidifying pad Water recirculation pump Dry mode The fluid is cooled in the dry tube coil by ambient air flow. The ambient air is drawn through the coils by fans mounted centrally on the top of the Cooler; the humidifying pads located in front of the coils are dry. The fan speed is controlled by an inverter depending on heat load to maintain the fluid outlet temperature. The warm air is then evacuated upwards. Adiabatic mode When cooling in dry mode is not effective and the ambient temperature reaches a predetermined set point, the pads are saturated with water from the sump. The ambient air is cooled by evaporation when passing through the pads. This precooled air then passes through the tube coils and cools the fluid. The water which has not been evaporated on the pads is collected in a stainless steel collector and then flows to sump. As an option, it can be re circulated with the make up water from the sump to be redistributed over the pads. The water saving is then significant and does not require water treatment, it is without risk of Legionella. 2/10 DT_ TOPAZ UK 05 12 13

TOPAZ General description and benefits Range TOPAZ is available in a range of 6 different duties. General description The TOPAZ adiabatic cooler range includes: Two vertical heat exchanger tube coils, Two cooling / humidifying pads for pre cooling by evaporation, Asynchronous motors: one per fan combined with Variation Speed Drive, A low noise axial fan set, A panel for power and control: Automation. The water distribution system for pre cooling is as follows: Water make up electro / solenoid valve, Motorised bleed off valve, One or two water recirculation pump(s). Benefits No drift, No water spray in airflow, Elimination of legionella risk, The coils are manufactured by Friterm or by Thermokar, participating to the HECOILS Eurovent Certita Certification Program. Data can be checked on www.eurovent certification.com, No external fouling of the tube coils : extended life expectancy, No thermal performance decrease, No water treatment required, Easy maintenance due to vertical H shape of the tube coils : full access through the central door, Low operating costs, Very low water consumption, Optimized power consumption, Made in France. 3/10 DT_ TOPAZ UK 05 12 13

TOPAZ Manufacturing details Tube coils In standard configuration, the coils are made of copper and the aluminium fins are epoxy coated. Tubes are expanded through the fins to ensure both optimized mechanical resistance and thermal conductivity. The tube thickness is 0.35 mm, and the fin pitch is 2.1 mm. The large fin pitch offers good resistance against scaling of the exchange surfaces. The coils are hydraulically tested to 22 Bar as standard. The coils are manufactured by Friterm or by Thermokar, participating to the HECOILS Eurovent Certita Certification Program. Data can be checked on www.eurovent certification.com Selected to simplify maintenance, the media pads are not directional. It is easy to disassemble the cooling / humidifying pads, without tools or special access requirements. Water distribution The precooling circuit is activated when the fluid outlet temperature is higher than the set point. This wet / dry set point is around 23 C in a continental climate, for a fluid outlet temperature of 27 C. Pre cooling by evaporation The evaporation section is used to precool the ambient inlet air. The cooling / humidifying media covers the whole air inlet section, on both sides of the unit. The design and the choice of materials have proven to give best efficiency and long operating life, both in urban and industrial environments. The cooling / humidifying pads are made of special cellulose, chemically treated to avoid moisture and to improve water absorbing characteristics. The water distribution channels are entirely enclosed on the top in X STEEL stainless steel and do not require any pressure to operate. They are located outside the airflow and distribute water evenly onto the pads, in full safety. Their U shape makes internal cleaning very easy, without any tools, handles are provided to aid removal. X STEEL stainless steel channels collect the water which has not been evaporated. The water is then evacuated or can be sent to the sump for recirculation by means of a pump. 4/10 DT_ TOPAZ UK 05 12 13

Collected water can be re circulated without any bacteriological risk (temperature is below the level for bacterial growth): the water consumption is then divided by a factor of 3. The water is sent to a covered stainless steel sump: a level switch and one or two pumps are added, according to the model. Permanent magnet motors (optional) The TOPAZ adiabatic cooler is a cutting edge technology and shows exceptional performance (efficiency over IE3). They are IP 55 insulation class, 380/ 400 V. This efficiency places the TOPAZ range at the peak of energy efficiency, especially as the motors are always controlled by the inverter. The system includes a drain valve that automatically opens to dump the water from the sump if the cooling section has been used during the previous 24 hours. A drying cycle is incorporated which will drain the sump completely and will dry the pads and other items which come into contact with water by running the fans at high speed. This function minimises bacteria growth potential and prolongs pad life. Motor fan sets The magnets create their own magnetic field without induced power. The motor runs cooler, is smaller and lighter and has maintenance and handling benefits. Also, a lower temperature means long lasting bearings (grease nipples directly on the motor), and insulation materials. These motors have a low carbon footprint => power savings. Efficiency comparison The motor fan sets draw the air through the pads, then through the tube coils. Asynchronous motors are directly coupled to axial fans. This combination offers both power efficiency and optimized sound level. The motor fan coupling is direct and requires no maintenance. The blades are made of aluminum, and the hub is made of steel, the blade angle adjustment is made stand still. As an option, sound attenuators can be provided to significantly reduce the sound levels. Efficiency % Permanent magnet motor Motor IE3 Motor IE2 Values for indication only Load % Control panel with automaton The TOPAZ range is totally «Plug and Play»: the Siemens automaton equipped with HMI (Human Machine Interaction) as a standard, allows frequency drive and precooling operation controls without opening the electrical panel: It has an external screen for full safe maintenance. 5/10 DT_ TOPAZ UK 05 12 13

Intelligent access The TOPAZ adiabatic cooler has been design with two main goals: thermal performance and ease of maintenance. Therefore, the following technical features are incorporated: H orientation of the tube coils offers an ideal geometry for complete access to the motors, fans and the internal finned tube coils, over the whole height of the cooler. So it can be operated safely, without the use of specifically trained operators. Here are some functions of the automaton: Integral control of the time chip, Memory saving in case of power failure, Liquid crystal display showing multiple lines of main parameters and alarms, Interface for the user in order to readjust settings, Analogue outlet for fan speed control with frequency drive, installed as standard, Digital monitoring including: pumps, drain valve, water / sump make up valve, drain and dry mode controls, Security password to protect all set data. TOPAZ is equipped with an automated roller shutter door without doorstep. The motor/fan set is removable and can be extracted from inside for maintenance. Accordingly, lifting equipment*, safety guards or walkways are not necessary to carry out maintenance. Communication modes are optional: Ethernet, Modbus, LON, or Bacnet. Frequency drive Installed as a standard across the whole range, there is one frequency drive per motor. Permanent magnet motor directly coupled to axial fan and regulated by the frequency drive offers the best efficiency. *As an option; a hydraulic lifting table allows removal of the motor/fan set in complete safety, without means of other lifting equipment. Also, easy handling of the humidifying pads is possible, without any lifting/ handling tools. Support and casing The floor and external sides of the unit are made of X STEEL stainless steel. 6/10 DT_ TOPAZ UK 05 12 13

TOPAZ Drawings and dimensions WATER INLET WATER OUTLET OVER FLOW DRAIN WATER MAKE UP TOPAZ range Models T2B T3A T3B T4A T4B T5B Nominal capacity 1 kw 410 520 600 700 810 1030 Motor-fans Qty / kw 2 x 6.5 3 x 6.5 3 x 6.5 4 x 6.5 4 x 6.5 5 x 6.5 Fan diameter mm 1400 Motor absorbed power kw 10 15 15 20 20 25 Water recirculation pump installed power Qty / kw 1 x 0.75 2 x 0.75 2 x 0.75 2 x 0.75 2 x 0.75 2 x 0.75 Inlet/outlet water connections DN 65 100 100 100 100 100 Make up water flow (max) 2 m3/h 0.5 0.7 0.7 1 1 1.2 Make up water connection (threaded male) inches (mm) 1" (26 x 34) Drain connection (threaded female) inches (mm) 1" 1/2 (40 x 49) Over flow connection inches (mm) 1" 1/2 (40 x 49) Overall dimensions L1 mm 3665 5275 5275 6890 6890 8500 Frame support dimensions L2 mm 3265 4875 4875 6490 6490 8100 Weight empty kg 2240 3160 3250 4080 4200 5000 Weight in operation kg 3250 4200 4395 5100 5360 6050 Sound level 3 dba 57 58 58 59 59 61 Notes : 1. Based on condensing temperature of 37 C/32 C and design ambient 32 C/21 C (dry / wet bulb) 2. Based on ambient conditions 31 C/21 C (dry/wet bulb) 3. Sound pressure level Lp at 15 m in free field, in most silent direction of the unit (+/- 2 dba). 7/10 DT_ TOPAZ UK 05 12 13

TOPAZ on site lay out In order to achieve optimum thermal performance, the TOPAZ adiabatic cooler must be installed according to the following criteria: Sufficient space left on both sides of the machine: minimum 1, 5 m (2 to 3 fans) and minimum 2 m (4 to 5 fans) as per the sketches below; this will ensure that air will enter the coils efficiently to cool the fluid. In the case of a multiple cooler installation, it is important to consider the main wind direction; in order to avoid recirculation. The air outlet should be free from any obstacle. 1500 Recommended separation distances for smaller units (1 to 2 fan units) 2000 Recommended separation distances for 3 to 5 fan units When TOPAZ units are located adjacent to buildings, walls or enclosures, the top of the fan discharge casing must be aligned with or higher than any adjacent structure. Special care must be taken to avoid recycling of warm saturated discharge air by drifting into any ventilation inlets located nearby. Consider and allow for future expansion. Design pipework with some flexibility to allow for vibration, expansion and contraction. The dimensions given are minimum recommendations only. For unusual requirements or detailed recommendations on location, please consult Jacir. 8/10 DT_ TOPAZ UK 05 12 13

Prescription TOPAZ High performance adiabatic cooler, JACIR brand, TOPAZ. Series will be designed to operate with a glycol content of. %. Thermal characteristics The dissipated power will be... kw, with a temperature range from... C to... C, an ambient air temperature of C, and a wet bulb temperature of... C. Glycol concentration will be...% Sound level characteristics The sound pressure level will not be greater than db(a) at meters, in free field, in the quietest direction. Tube coils Tube Coils will be made of copper tubing and aluminium fins, epoxy coated. Tubes will be seamless and expanded through the fins to secure a mechanical resistance and optimized thermal conductivity. The tubes thickness will be 0.35mm, and the fin pitch will be 2.1 mm. The coils will be tested hydraulically to 22 Bar. Thermal performances of the coils will have been Eurovent certified. The headers will be installed on one side of the unit to make the internal access easier by a large access door and will be equipped with an automated roller shutter door, without doorstep for ease of use. The coils will be vertically installed, in H configuration, in order to allow full access to the internal sides of the coils and to the mechanics. Pre cooling by evaporation The cooling/ humidifying pads will cover the whole air inlet section, on the two sides of the unit. The pads will be made of cellulose, chemically treated in order to avoid moisture and to improve its absorbing characteristics. The media pads are not directional, so that any side can be used. Removal of the pads is simple and does not require tools and lifting equipment. Water distribution Air precooling will be activated when the outlet temperature is higher than the set point. The water distribution channels are designed for easy cleaning and will be in stainless steel, without external pressure regulation, and out of air flow. They will distribute the water evenly on the pads, in full safety. In order to significantly reduce water consumption in adiabatic mode, the stainless steel headers will collect the non evaporated water. The water will be sent to a stainless steel sump, with an installed a level switch and one or two pumps. The system will include a drain valve, which will be automatically activated on a daily cycle. A full drain cycle, combined with full speed fan operation, will dry the parts in contact with the water. The equipment will be factory assembled. Motor fan sets The motor/ fan sets will be aligned in a single row at the top of the unit. They will draw the air through the pads and tube coils. The motor/ fan sets will be completely removable from inside the unit for maintenance. The axial fans will operate at low speed to combine optimized efficiency and low sound level performance. The blades will be aluminium and the hub will be made of steel. The blade angle is adjustable. The fan/ motor coupling will be direct, requiring no maintenance. 9/10 DT_ TOPAZ UK 05 12 13

Permanent magnet motors (optional) High efficiency permanent magnet motors, specially developed to minimise power consumption will be supplied with an inverter / frequency drive as standard. They will be IP 55 insulation class, 380/ 400 V, and fitted with greased bearings for continuous operation. Inverter / Frequency drive An inverter / frequency drive will be installed on the whole adiabatic cooler range as standard. Control panel with automaton Siemens automaton will control fan speed and will activate the pre cooling mode. The TOPAZ cooler will be delivered totally plug and play, different communication languages as an option, and will be equipped with HMI (Human Machine Interaction), external screen on the control panel for safe maintenance. Functions of the automaton will be as follows: Integral control of the chip with clock. Memory saved record in case of power failure Liquid Crystal Display, multiple lines for main parameters and alarms. Interface for the user in order to read settings. Analogue output for fan speed control with frequency drive, installed as standard. Digital monitoring including: pump, drain valve, and water make up valve for the sump Water collectors, drain control and dry operation Security password to protect all set data Following information will be available as standard: General default, pad humidification setting, drain valve position, water make up valve s position, and reading of frequency drive. Support frame and casing Support and casing will be rigid and strong, made of galvanized steel. All metallic parts in contact with water, as well as the internal floor will be in stainless steel. Internal access for unit maintenance and motor/ fan set removal will be via an automated roller shutter door and without any doorstep for ease of access. Access to the pump(s) will also be via the above. JACIR 11, rue jean Moulin F 77348 PONTAULT COMBAULT Cedex tel. : +33 (0)1 64 43 53 20 fax : +33 (0)1 64 43 53 21 www.jacir.fr - 10/10- contact@jacir.fr DT_ TOPAZ UK 16-09-13