MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

Similar documents
Dehumidification: Energy Efficiency Comparisons

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

The Ed Roberts Campus Berkeley, CA

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Heat Pumps and Public Swimming Pools, a Perfect Match

100% Outdoor Air Dehumidification Methods

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, August 2015

Achieving Dry Outside Air in an Energy-Efficient Manner

Sivu 2/8 Rate data Description Suomi Shut off times total 0.0 h/day Weekends with shut off times yes Daytime rate of heat pump Time for daytime rate 5

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Humidity Control & Psychrometrics

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Performance of Solar Water Heating Systems in the United States

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Optimisation of cooling coil performance during operation stage for improved humidity control

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Variable Refrigerant Flow (VRF) Systems

Economic Analysis of Solar Assisted Chemical Heat Pump Dryer

Free cooling on RTAF Chiller. Integrated option

Munters Heat Exchangers

System Using Exhaust Heat from Residential GHPs

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

Designing Energy Efficient Outdoor Air Systems

Energy Recovery Ventilation

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Auburn University Basketball Arena:

A/C Cooling Load calculation and measurement

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

PRODUCT SERIES. VPR Series VPRX Series VPRE Series VPRP Series VPRC Series

Comfort and health-indoor air quality

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

Air Conditioning Clinic

On Balance: Heat Rejection Control a Packaged Solution

SOLAR HOT WATER AND HEAT PUMP BOOSTER ENERGY CALCULATION METHODOLOGY

Natatorium Economizer Vs. Conventional Dehumidifier

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

Dehumidification System Enhancements

Active desiccant integration with packaged rooftop HVAC equipment

Adding More Fan Power Can Be a Good Thing

Liquid Desiccant Technology Delivers Energy Cost Reductions and Indoor Air Quality Improvements. White Paper

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

Laboratory Evaluation of Hybrid and Advanced Water Heaters: Performance Overview in Hot Humid Climate

December 6, 2018 Optimizing Solutions through Superior Dehumidification Technology SM

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Design and Operation of a Conditioning Energy Recovery Ventilator (CERV) for Passive Houses

Identification of Aberrant Railroad Wayside WILD and THD Detectors: Using Industry-wide Railroad Data. June 10, 2014

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Benefits Offered by Passive Dehumidification Wheel Speed Control

GRAIN STORAGE AERATION PRESENTED BY: BRENT BLOEMENDAAL AERATION EXPERT

Acknowledgement: Ralph Prahl, Prahl & Associates, contributed critical review and analysis

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Redesign of Bennett Hall HVAC System

Dehumidifying with Dedicated Outdoor Air

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc.

Available online at ScienceDirect. Energy Procedia 52 (2014 ) Vishal Vadabhat, Rangan Banerjee

Dedicated Outdoor Air Systems: AHRI 920, ISMRE & ASHRAE 90.1

ENERGY MANAGEMENT IN MILK POWDER PLANTS

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

NET ENERGY WATER LOOPS A clear path to net zero energy buildings

Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING

announcements 4/10/08

Comparison of Heating Efficiency of a Heat Pump to Electric Heating Panels

Cooling Load Analysis and Computation Worksheet

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Air Conditioning Clinic

Optimizing Electric Humidifier Operation with an Air Side Economizer

Special Topics on Residential HVAC

HEALTHCARE SURGERY VENTILATION HUMIDITY CONTROL

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative

To Keep Docs Cool, Dry and Happy

DADANCO Technical Paper

Chapter 14, Problem 27.

ACHIEVING ENERGY-EFFICIENT DATA CENTER COOLING: DOES REDUCING FAN SPEED ALWAYS RESULT IN ENERGY SAVINGS?

Psychrometric Engineering Applications

WLAC Facilities Committee Meeting. September 18, 2017

Trane CDQ Desiccant Dehumidification

Product Release Summary

Time-Based Scheduling of Residential Ventilation

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Annual environmental performance evaluation of light and heat in daylight harvesting systems using Radiance and NewHASP

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

MASTER PLAN KICK-OFF Open House #1A, April 28, 2015

Cooling Options for Geothermal and Concentrating Solar Power Plants

CHAPTER 4. HVAC DELIVERY SYSTEMS

Desiccant Dehumidification in Air Conditioning for a Large Commercial Building

Innovative Technologies [and Design Concepts] in Commercial Foodservice

Principles of Active Desiccant Operation. Presented by Tom Peterson, CEO and Founder. Climate by Design International

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Transcription:

MSP WRAP-ARUND MULTIPLE SMALL PLATE DEHUMIDIFICATIN TECHNLGY VS. CNVENTINAL DEHUMIDIFICATIN IN DEDICATED UTDR AIR SYSTEMS (DAS) ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ A white paper presented by Walter Stark, President of MSP Technology (wstark@msptechnology.com) MSP s wrap-around plate technology offers superior efficiency removing moisture from outdoor air. MSP Wrap around plate technology MSP s wrap-around multiple small plate is the system of using air-to-air plate heat exchangers to precool and then reheat air in the dehumidification process. A conventional dehumidification system, does no precooling and Figure 1- MSP Dehumidification with precooling & reheating A T1 T2 T3 T4 PRE-CL C L RE-HEAT SA Wrap-around plate precools (T1-T2) Saving significant energy (T2-T3) reheats using waste heat from the refrigeration system. Compared with Conventional dehumidification, MSP s wrap-around plate systems have lower operating costs. The MSP wrap-around plate dehumidification technology offers significant precooling, which reduces the load and energy consumption of the cooling coil, thus saving operating costs. MSP uses nearly one square foot of plate heat transfer surface per cfm of air, which accounts for MSP s superior performance. In the example below, close to 4,500 square feet of heat transfer surface is used. Comparison of MSP with a hot gas system MSP (Fig. 1, left) uses cold air leaving the process (T3) to precool outdoor air. A single continuous airstream (T1) is pre-cooled (T2) before passing through a cooling coil (T3), and then reheated (T4). Hot gas reheat systems (Fig. 2, below right) do not have a pre-cooling feature and thus have increased Btu, compressor horsepower and electrical load. Hot gas reheat systems have to expend more energy for cooling. Decoupling MSP improves the overall efficiency of a DAS working with a decoupled building heating and cooling system. Decoupling leaves the building s air conditioning system to control its temperature, while the outdoor (DAS) unit controls the building s humidity. Neither function can overpower the other. They work separately, yet in harmony. Air delivered by the DAS is at a dew-point that is equal to (neutral) or lower than the building s dew-point. Zone temperature control remains the job of the building temperature control system. Heat, when added to cold and dehumidified outdoor air, increases the load in zones that are already in a cooling mode. This is true of both systems. However, systems employing wrap-around reheat, such as MSP, have an added feature; Precooling dramatically reduces the dehumidification load Figure 2- Conventional Dehumidification with no precooling & hot gas reheating No precooling uses more energy and thereby neutralizes the effect of supplying temperatures that may be higher than zone set-point. Usually, the effect on the zone sensible load is small enough to ignore. If not, post-cooling at the DAS unit can be employed for the few hours surrounding peak design dry-bulb temperature. DAS equipment with MSP Dehumidification Technology, is designed to maintain supply air dew-point, while dry-bulb temperature floats naturally, in relation to outdoor air temperature. Warm hours of the day will result in higher supply air temperature. Nevertheless, each uninvited Btu of reheat is matched to a welcome Btu of energy-saving precooling. Btu s of reheating that exceed zone temperature have their energy-saving (precooling) counterpart. T1 T2 A C L T3 H G R E H E A T T4 SA

The effect of climate on overall performance Design conditions often serve as basis for judging overall performance. But design conditions occur for only a fraction of the time. This is especially true of applications with extended hours of operation such as hospitals, hotels, barracks, assisted living, and dry storage, because lower nighttime temperatures bring the average down. The performance of the MSP DAS actually improves at lower dry-bulb temperatures, which occur for most of hours in a dehumidification season. To understand the benefit of MSP in a DAS application, we will evaluate the energy consumption of both systems using Atlanta, GA as an example. Performance analysis using Atlanta GA Table 1 (below), illustrates the performance of MSP and conventional dehumidification in Atlanta, GA, using conditions representing the average dry-bulb and dew-point temperatures (73.2 F/63.1 F). These values were derived from TMY3 data and include only hours when the outdoor dew-point is greater than 50 F. These values are supported in the data analysis section below. Table 1 - MSP vs. hot gas reheat performance at 4,500-cfm in Atlanta, GA SYSTEM T1 (db/dp) T2 (db/dp) T3 (db/dp) T4 (db/dp) Btuh MSP (FIG 1) 73.2 F/63.1 F 62.5 F/58.0 F 50.0 F/50.0 F 70.2 F/50.0 F 118,900 CNVENTINAL (FIG 2) 73.2 F/63.1 F 50.0 F/50.0 F 70.2 F/50.0 F 217,000 Figure 3 (below) shows details of the MSP psychrometric performance shown in Table 1 (above). Inlet conditions are the average of annual dry-bulb and dew-point temperatures during active dehumidification hours, when the dew-point greater than 50 F. Figure 3 MSP Psychrometric Analysis

Figure 4 (below) shows the psychrometric chart profile, based on table 1 (above). Figure 4- MSP Psychrometric Chart Reheating GRAINS/PUND DRY-BULB TEMPERATURE NTE: Chart shows MSP DAS profile. Conventional DAS profile is similar. utdoor air travels directly from T1 to T3, with no precooling and T3 to T4 is hot gas reheat. Data analysis Atlanta, GA This analysis uses TMY3 data provided by the United States National Solar Radiation Data Base. Table 2 (below), confirms that the maximum average outdoor temperature for any month in Atlanta, GA does not exceed 80 F while ASHRAE tables, for 0.4%, put the design outdoor temperature at 93.9 F. It is important to consider that the average outdoor temperature entering the DAS is significantly lower than design outdoor temperature. Table 2 - Average monthly dry-bulb temperatures & associated hours, using TMY3 climate data in Atlanta, GA MNTH Jan Feb Mar Apr May Jun Jul Aug Sep ct Nov Dec DRY-BULB ( F) 39.1 46.3 56.8 63.0 69.5 76.6 78.9 79.8 72.5 60.8 53.5 45.9 HURS 744 672 744 720 744 720 744 744 720 744 720 744 Total hours: 8,760 Table 3 (below), illustrates the monthly average dry-bulb and dew-point temperatures that occur when the outdoor dew-point is greater than 50 F, which is a typical set-point for a DAS system. Table 3 - Average monthly dry-bulb & dew-point temperatures & hours when outdoor dew-point is greater than 50 F in Atlanta, GA MNTH Jan Feb Mar Apr May Jun Jul Aug Sep ct Nov Dec DRY-BULB ( F) 57.2 57.9 67.2 66.1 70.8 77.9 78.9 79.8 72.6 66.2 64.2 60.2 DEW-PINT ( F) 55.0 55.4 55.2 57.3 59.9 64.4 67.7 69.3 62.7 59.8 57.7 55.6 HURS 53 84 168 301 601 627 744 744 697 345 164 91 Total hours: 4,619

Hot gas reheat has diminishing returns The formula for calculating the energy available for hot gas reheat is: EVAPRATR BTUH + (CMPRESSR KW X 3,414) = AVAILABLE REHEAT ENERGY BTUH From this formula we know that energy available for reheating decreases with evaporator Btuh. We also know that as evaporator load decreases, reheat requirement increases. To increase the reheat capability of the refrigeration system under low evaporator load conditions, the compressor KW must increase. This can be accomplished by raising the refrigeration system condensing temperature, but the net result of this measure is equal to electric resistance heat. It would be better to avoid the wear and tear on the compressor and simply use the winter heating source, which is generally equal to, or lower than, the cost for electric resistance heat. Hot gas reheat with a building in cooling mode Building zones with higher cooling loads require lower supply air temperature, while zones with lower cooling loads require higher supply air temperature. Thus, a conventional DAS system employing hot gas reheat and serving multiple zones, can only truly satisfy one zone. The remaining zones must compensate with additional cooling to overcome excess hot gas reheat. This is clearly wasteful. Undesired heating in zones will respond with undesired cooling in the same zones. To avoid over-cooling some zones, a higher supply air temperature is required for all zones. MSP reheat with a building in cooling mode MSP reheat is efficient reheat because it has an energy-saving precooling counterpart. Even when it is overheating some zones, it is doing so efficiently with no energy waste. The MSP DAS dehumidification solution offers a very efficient means for controlling supply air dew-point temperature. In this system the supply air dry-bulb temperature floats relative to outdoor dry-bulb temperature. Sensible cooling is shifted to the individual zone temperature controls which can now be very effective and very efficient dealing largely with sensible heat (temperature change) rather than latent heat (humidity change). The influence of climate, application and utility rates, on RI To get a true picture of the energy use of different DAS solutions, we must move beyond evaluation of performance under one design condition. For a complete evaluation, we need to analyze annual performance under a full range of climates, applications and utility rates. Climates: As we move toward coastal areas and closer to the equator, annual hours of exposure to high humidity and temperature increase. These areas can benefit significantly from MSP Technology because of longer season which equates to more equipment run-time and fast return on investment. Application: Many dehumidification applications have 24-7 operation. These include hospitals, hotels, barracks, dry storage and many more. Places with extended hours of operation are excellent candidates for MSP because longer run-time means faster return on investment. In chilled water applications, compressors and refrigeration components are eliminated, making MSP chilled water dehumidification an especially good application for improving RI. Utility rates: Locations with high utility costs can benefit significantly from using MSP with wrap-around reheat because savings on high utility rates result in faster return on investment. Fan power Fan power energy is higher with the MSP solution due to added pressure drop through the heat exchangers. The added fan power, in the Atlanta, GA example is estimated at ~2000 kwh during 4619 active dehumidification hours. Dehumidification savings for this period far outweigh fan power cost. When system is inactive, an optional bypass damper opens, eliminating pressure drop through the entire dehumidifier section. With this feature, the benefit during inactive hours can offset the added cost during active hours.

Conclusion When MSP wrap-around plate technology is used to treat outdoor air in a DAS application, the combined DAS and building systems operate more efficiently than conventional dehumidification systems. With nearly one square foot of aluminum heat transfer surface per cfm of processed air, the MSP solution offers superior performance. In chilled water applications compressors and refrigeration components are eliminated, making chilled water dehumidification an especially good application. The amount of hot gas reheat energy used in a conventional DAS system would be roughly equal to the amount of thermal energy savings achieved by an equivalent MSP DAS system. MSP offers custom and standard models of High Efficiency Chilled Water, Packaged and Split Dehumidification Systems. We hope that we have stimulated some thought. Please send your comments to: wstark@msptechnology.com