Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT

Similar documents
Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant

EarthLinked SC Series Compressor Unit R-407C Quik-Start Instructions

EarthLinked SCW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked HC Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked CC Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked Freeze Protection Kit Model FP-1872 Installation Manual

AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH

EarthLinked Model DSH-1872 Desuperheater Kit

AVS Air Handlers Installation Manual for Classic SC, SD, and SDH

EarthLinked AVN Series Air Handlers Installation Manual

EarthLinked AFN Series Air Handlers Installation Manual

EarthLinked SD(A) Series

Heat Recovery Module Installation Manual for

EarthLinked STORAGE WATER HEATER / HYDRONIC BUFFER TANK MODELS GSTE-60, GSTE-80 & GSTE-119

AVS Air Handlers Prime PSC, PSD, PSDH and Classic SC, SD, and SDH

EarthLinked Series PHXTI Pool Heat Exchangers Installation Manual

MASS. MARITIME ACADEMY

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Prime Series PSC Geothermal Heating and Cooling System

Temperature Control Kit Model HHK/CWK-1872

Classic Series SC Geothermal Heating and Cooling System

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

Prime Series PSDH Geothermal Heating and Cooling System

Classic Series SD Geothermal Heating and Cooling System

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X

INSTALLATION MODULE XARIOS RANGE. UTC Climate, Controls & Security PROPRIETARY Rev B 29th mai 2013

Sporlan Valve Division Parker Hannifan/CIC Group

EARTHLINKED GEOTHERMAL RENEWABLE ENERGY SYSTEMS MAINTENANCE GUIDE

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

RCM Refrigerant Module

Service Step by Step Trouble-Shooting Check-List

R Series Cooling Modules

Installation Manual BCS2000/3000

USING THE P-T CARD AS A SERVICE TOOL

R.A.S.E.R.S System. Installation Guide

Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS

Residential Piping and Long Line Guideline

R Series Cooling Modules

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

Ocean Breeze Split System. General Installation Manual. Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida Tel:

Condensing Unit Installation and Operating Instructions

Installation Manual BCS 1000/1500

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

R Series Cooling Manual

Prime Series PSDH Geothermal Heating and Cooling System

Condensing Unit Installation and Operating Instructions

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE LIST OF SECTIONS LIST OF FIGURES

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

R4H4. Product Specifications

OPERATING INSTRUCTIONS

PROJ. NO SECTION REFRIGERANT PIPING

Otherwise, you can continue reading the file on the following pages.

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold

Air Cooled Condenser Installation and Operating Instructions

R4H4. Product Specifications

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

Refrigeration/Troubleshooting Manual

Determining Real Time Performance of Residential AC Systems. Presented at the RESNET Conference San Antonio, TX February 28, 2006

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

Digital Refrigerant System Analyzer. MAXMIN Psi kpa Bar MPa C F R TIME P T UNITS

INSTRUCTIONS! DO NOT DISCARD!

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

INSTALLATION AND MAINTENANCE INSTRUCTIONS 2SCU13 Series Split System Air Conditioner WARNING

RSMSD Technical Guide

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

WineZone Ceiling Mount Ductless Split 15

PRODUCT GUIDE EARTHLINKED TECHNOLOGIES GEOTHERMAL RENEWABLE ENERGY SYSTEMS SIMPLE. EFFICIENT. EFFECTIVE.

Warm Case Troubleshooting Guide 9/18/2014

MODEL URS-1: FACTORY RETROFIT PROGRAM

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

The Refrigeration Cycle

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION

APPLICATION & SERVICE GUIDE

Technical Standards for the Air Conditioning and Heat Pump Professional BPI STANDARDS

MANUAL J/S Summary One summary sheet for each system

The Refrigeration Cycle

HSXA15 HSXB15. IMPORTANT Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A.

HVAC Service Technicians Training Center

YCIV Hz & Hz

XC13. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A.

TSA WARNING. Service Literature TSA SERIES UNITS. 6, 7.5, 10, 12.5, 15 & 20 ton

Public Services Building 155 N First Avenue Hillsboro, OR March 2012

OPERATING INSTRUCTIONS

ACU Split System Air Conditioners

Installation, Operation, and Maintenance Information

Transcription:

EarthLinked TXV Kit Installation Manual for Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT CONTENTS PAGE Pre-Installation 3 Hydronic Water Module Conversion 4 System Start-Up 21 TXV HWM-410-KIT (01/13) Copyright 2013 Earthlinked Technologies, Inc.

Disclaimer Proper installation and servicing of this EarthLinked Kit is essential to the Heating and Cooling Systems reliable performance. All EarthLinked systems and kits must be installed and serviced by an authorized, trained technician who has successfully completed the training class and passed the final examination. Installation and service must be made in accordance with the instructions set forth in this manual. Failure to provide installation and service by an authorized, trained installer in a manner consistent with this manual will nullify the limited warranty coverage for the system. EarthLinked Technologies shall not be liable for any defect, unsatisfactory performance, damage or loss, whether direct or consequential, relative to the design, manufacture, construction, application or installation of the field specified components. Earthlinked Technologies, Inc. 4151 South Pipkin Road Lakeland, Florida 33811 tel. 863-701-0096 fax 863-701-7796 info@earthlinked.com www.earthlinked.com CSI # 23 80 00 TXV HWM-410-KIT (01/13) Page 2

1. Pre-Installation Upon receipt of the TXV Kit carefully check the model number against the bill of lading. The TXV Kit is designed to improve performance of an R-410A EarthLinked air heating and cooling system utilizing an HWM or Non-ETI Hydronic Water Module to provide chilled water. The TXV Kit must be matched with the appropriately sized SC or SD series compressor unit and the hydronic water module. See Figure 1 below for correctly matched components. R-410A COMPONENT MATCHING TABLE COMPRESSOR UNIT NOMINAL CAPACITY, BTUH TXV KIT MODEL HYDRONIC WATER MODULE MODEL -024 (24,000) TXV-024CH HWM-1836-036 (36,000) TXV-036CH HWM-1836-048 (48,000) TXV-048CH HWM-4248-060 (60,000) TXV-060CH HWM-6072-068 (68,000) TXV-072CH HWM-6072 Figure 1. R410A Component Matching Table There are two steps to the field installation of the TXV Kit: 1. Hydronic Water Module conversion 2. System Start-Up TXV HWM-410-KIT (01/13) Page 3

2. Hydronic Water Module Conversion The TXV ASSEMBLY is illustrated in Figure 2. Familiarize yourself with the tube connections TO DISTRIBUTOR and FROM COMPRESSOR UNIT. Also note the EQUALIZER CONNECTION and the BULB TEMPERATURE SENSOR. These will be addressed in Figures 3.a. through 3p. Figure 2. TXV/CAV Assembly TXV HWM-410-KIT (01/13) Page 4

Remove the cabinet door of the HWM Hydronic Water Module and follow the illustrations of Figure 3a. through Figure 3p. to install the TXV assembly. Figure 3a. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 5

NOTE: The mounted TXV/CAV assembly projects 6 from the cabinet. Provide 13 clearance on the right side of the cabinet to access the TXV/CAV assembly. Figure 3b. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 6

Figure 3c. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 7

Figure 3d. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 8

Figure 3e. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 9

Figure 3f. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 10

Figure 3g. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 11

Figure 3h. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 12

Figure 3i. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 13

Figure 3j. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 14

Figure 3k. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 15

Figure 3l. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 16

Figure 3m. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 17

Figure 3n. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 18

Figure 3o. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 19

Figure 3p. Hydronic Water Module Conversion TXV HWM-410-KIT (01/13) Page 20

3. System Start-Up Evacuation/Charging SC and SD Models Refer to Figure 4 and the following description: Evacuation and Initial Charge 1. Carefully vent the nitrogen charge from the compressor unit. 2. After installing and nitrogen brazing the HVAC system components and compressor unit service valves, turn the Service Valves to Full Open and pressurize the HVAC components to 150 psig with dry nitrogen and a trace of refrigerant. Valve off the nitrogen Tank from the HVAC system components and check joints with a sensitive Electronic Leak Detector to ensure they are sealed. Repair any leaks and re-test as appropriate. TXV HWM-410-KIT (01/13) Page 21

3. After venting the pressurized system, connect the Gage Block, Refrigerant Container and Hoses as shown in Figure 4. LP and HP valves are fully open. Both Service Valves are fully opened. 4. As illustrated in Figure 4, connect a good quality Digital Micron Gage to the Liquid Line Service Valve Access Port with an Isolation Hose/Valve. Connect a quality Vacuum Pump (at least 6 CFM capacity) to the Gage Block. 5. Connect the Refrigerant Hose from the Refrigerant Container to the Charging Port. 6. Initiate the system evacuation. Evacuate the system down to 230 MICRONS as read on the digital micron gage. After 230 microns has been achieved, turn off the LP and HP valves and turn OFF the vacuum pump. Reading the digital micron gage, the system pressure must not exceed 280 MICRONS WITHIN 5 MINUTES. If pressure rises to greater than 280 microns, open LP and HP valves, crack the refrigerant valve and allow just enough refrigerant into the system until 20 inches of Hg vacuum is read on the LP gage. Close the refrigerant valve, and initiate the evacuation process again and until the above conditions are met. TXV HWM-410-KIT (01/13) Page 22

Figure 4. Typical Evacuation & Initial Charge Set-up for SC and SD Compressor Models (SC model shown). 7. Close the LP and HP valves on the gage block. Disconnect the vacuum pump and the utility hose from the gage block. Isolate/protect the Digital Micron Gage from the liquid Earth Loop Service Valve until the initial refrigerant charge is complete. 8. Open the refrigerant container valve and inject liquid refrigerant into the charging port as shown in Figure 4. TXV HWM-410-KIT (01/13) Page 23

Item 9. Charge with liquid refrigerant until 3 pounds of refrigerant per ton of system capacity, has entered the system. Liquid entering the system at the charging port goes directly to the system earth loops. It does not go to the compressor. Should the pressures equalize and prevent the intended charge from entering completely, terminate the process of initial charging. Note and document the amount of refrigerant. 10. When the initial refrigerant charge (see step 9 above) has entered the system, close the refrigerant container valve and disconnect the refrigerant hose from the charging port. Note and document the amount of refrigerant. 11. The system has now been initially charged. Disconnect the Digital Micron Gage. Final Charge It is critical to control the conditions under which the compressor unit operates while final charging the system. Final charging must be done in HEAT mode. Hydronic Systems Comp. Unit If heating is provided through the hydronic water module, HWM, as listed in Figure 5, the circulating water in the primary circuit (see Figures 6 and 7) for the hydronic system is to be maintained in the 95 F to 105 F range. Air Htg. Hydroni c Htg. Air Clg Domestic Wtr. Htg. System Functions 1. SC Yes 2 2 Radiant panel hydronic heating and air Yes cooling (chilled water handler) 2. SC Yes 2 Yes 2 Yes 1 cooling (chilled water handler); and domestic hot water by field installed Radiant panel hydronic heating and air desuperheater 3. SD Yes 2 Yes 2 Yes 1 cooling (chilled water handler); and Radiant panel hydronic heating and air domestic hot water by desuperheater 1 Includes Desuperheater Model DSH-1872 to supplement water heating. 2 Hydronic (radiant floor) water heating provided with separately purchased Series HWM Hydronic Water Module. Figure 5. Systems with Hydronic Heat Exchangers TXV HWM-410-KIT (01/13) Page 24

Figure 6. Primary Circuit with Hydronic Water Module (HWM) Figure 7. Primary Circuit with Compressor Unit Heat Exchanger TXV HWM-410-KIT (01/13) Page 25

Final charging is done in the HEAT mode as follows, with the charging set up described in Figure 8: 1. Continue measuring the refrigerant charge weight as shown in Figure 8. 2. Be sure that circulating water is to be held between 95 F and 105 F. 3. Close the HP valve. Then turn the system on in the HEAT mode. 4. Initiate final charging by opening the refrigerant container valve and the gage manifold LP valve to allow liquid refrigerant to enter the system SLOWLY as shown in Figure 8. The ACC will not allow liquid refrigerant to enter the compressor. 5. Adding liquid refrigerant will raise the liquid level in the ACC. Continue to add liquid refrigerant to the system until the liquid level has reached the middle sight glass, as shown in Figure 9. 6. When the liquid level is at the middle sight glass, as shown in Figure 9, turn the refrigerant container valve OFF. 7. When the system has run for 20 minutes (in HEAT mode), read the evaporating temperature and condensing temperature. The evaporating temperature can be read by attaching a thermocouple lead to the Earth Loop Vapor Line with electrical tape, then wrapped with ½ thick insulation. The condensing temperature can be read by attaching a thermocouple lead to the Air Handler/CC/HWM liquid line coming into the compressor unit with electrical tape, then wrapped with ½ thick insulation. Use an accurate temperature indicator. In Figure 10, locate the evaporating temperature on the horizontal axis. The corresponding condensing temperature reading should fall between the upper and lower parallel lines in Figure 10. If condensing temperature is above acceptable range, the circulating water flow is low. If condensing temperature is below the acceptable range, circulating water flow is too high. Adjust circulating water flow as appropriate. TXV HWM-410-KIT (01/13) Page 26

Figure 8. Typical Final Charge Set-up for SC and SD Compressor Units (SC Model shown). 8. Check the suction saturation temperature to verify that it is within ±3 F for the measured suction pressure. The suction temperature should be approximately 15 to 20 F lower than the local earth temperature. TXV HWM-410-KIT (01/13) Page 27

Figure 9. Charge at Middle Sight Glass Figure 10. EarthLinked Performance Parameters TXV HWM-410-KIT (01/13) Page 28

9. If the system is to operate in Heat Only mode, write the final refrigerant charge on the Warranty registration Card and on the inside of the compressor unit on the electrical diagram for future reference. This is the full system charge. For Heat Only Operation, do not adjust the Thermostat Expansion Valve (TXV) or the Cooling Assist Valve (CAV). These valves have been factory set and are not to be adjusted by the installer. The system is fully operational and needs no further adjustment. 10. If the system is to operate in Heat/Cool or Cool Only mode: While the system is still operating in HEAT mode, add refrigerant to the system to bring the liquid refrigerant level up to the top sight glass on the ACC. See Figure 11. Document the total weight of the refrigerant charge to the system. Figure 11. Charge at Top Sight Glass 11. The following additional steps in the system start-up process are required if the system is to operate in Heat/Cool or Cool Only modes. These following steps require that the system be run in COOL mode. TXV HWM-410-KIT (01/13) Page 29

Cooling Mode Start-Up Process These following steps are to be followed if the system is to be run in Heat/Cool or Cool Only. The process flow chart for these steps is illustrated in Figure 17. Be sure the cooling mode for the system is enabled. Start the system in COOL mode and run system until the suction pressure stabilizes. 1. Determine what the liquid refrigerant level is in the ACC by viewing it through the sight glasses. If the liquid level is at or above the lowest sight glass, wait 10 minutes and check it again. The liquid level should be dropping with time. Repeat the 10 minute cycle observations until the liquid is below the lowest sight glass or until 2 hours pass. After 2 hours, if the liquid level has not dropped below the lowest sight glass, call ETI Technical services at 1-863-701-0096. 2. When the liquid refrigerant level drops below the ACC lowest sight glass, observe the INLINE sight glass (not the ACC sight glasses) for the status of the refrigerant flow. There are three possibilities: A. INLINE sight glass is CLEAR: As illustrated in Figure 12, a clear sight glass means the refrigerant flow is liquid. Remove 1 pound of refrigerant from the system, wait 10 minutes, and observe again. Continue this until bubbles appear in the sight glass. Figure 12. Clear-Inline Sight Glass B. INLINE sight glass has MANY BUBBLES: This is illustrated in Figure 13. Wait 10 minutes and observe the sight glass again. If many bubbles are still present, repeat the 10 minute wait cycle until the bubbles become few, or you have waited 2 hours. After a 2 hour wait, and many bubbles still exist in the sight glass, the process is done. No further adjustment in cool mode is required, and the system is operational. Figure 13. Many Bubbles-Inline Sight Glass TXV HWM-410-KIT (01/13) Page 30

C. INLINE sight glass has FEW BUBBLES: This is illustrated in Figure 14. When this condition exists, the next steps are to check the superheat and adjust the TXV as necessary. Figure 14. Few Bubbles-Inline Sight Glass 3. The TXV is to be adjusted to provide 10ºF to 15ºF superheat while running in cooling mode. The first step is to utilize the access port and LP gage in Figure 15 to measure suction pressure. Next, apply a thermocouple at the compressor suction port as shown in Figure 15 by attaching the thermocouple lead with electrical tape, and wrapping with ½ thick insulation. Figure 15. Superheat Measurements for SC and SD Compressor Units (SC Model shown). TXV HWM-410-KIT (01/13) Page 31

4. Using an accurate temperature indicator, read the suction temperature at the compressor suction port. Read the suction pressure at the access port on the LP gage. 5. Enter the Pressure-Temperature Table in Figure 16 and for the suction pressure read on the LP gage, determine the saturation temperature (evaporating temperature) from the chart, interpolating if necessary. SATURATION TEMPERATURE ( F) SUCTION PRESSURE (psig) SATURATION TEMPERATURE ( F) SUCTION PRESSURE (psig) -20 26.1 70 199.2-15 30.8 75 216.1-10 35.9 80 234.0-5 41.5 85 253.0 0 47.5 90 273.0 5 54.1 95 294.1 10 61.2 100 316.4 15 68.8 105 339.9 20 77.1 110 364.6 25 86.0 115 390.5 30 95.5 120 417.7 35 105.7 125 446.3 40 116.6 130 476.3 45 128.3 135 507.6 50 140.8 140 540.5 55 154.1 145 574.8 60 168.2 150 610.6 65 183.2 Figure 16. Pressure-Temperature for R-410A 6. To determine the degrees of Superheat, subtract the saturation temperature from the suction temperature read at the compressor suction port thermocouple. The difference in the temperatures is the superheat. (Superheat, F) = (Suction Temp., F) - (Saturation temp., F) 7. If superheat is greater than 20 F, decrease the superheat by adjusting the setting on the TXV in the counter clockwise direction. 8. See Figure 17 and follow the guidelines to bring the superheat into the 10 0 F to 15 0 F range. When superheat is adjusted to within this range, the system is fully operational and needs no further adjustment. 9. Document the net weight of the refrigerant charge in the system. Net weight is equal to the final refrigerant charge minus refrigerant removed from the system. Write it down on the Warranty Registration Card and inside the compressor unit on the electrical diagram, for future reference. This is the full system charge. TXV HWM-410-KIT (01/13) Page 32

Figure 17. Cooling Mode Start-Up Process TXV HWM-410-KIT (01/13) Page 33