RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

Similar documents
SP-1000X. Panic Device Power Controller Installation Guide. Rev

Installation Guide for models:

Installation Guide for models:

Series. Access Power Controllers. Installation Guide

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

Access Power Controllers with Power Supplies

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

AL600ULX Series. Power Supply/Charger. Installation Guide

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

AL600ULADA. NAC Power Extender. Installation Guide

ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.

Rack Mount Series Installation Guide

AL800ULADA. NAC Power Extender. Installation Guide

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

CM-RQE70A PIR REQUEST TO EXIT DETECTOR

Model 17A00 Expansion Enclosure

CM-RQE70 PIR REQUEST TO EXIT DETECTOR

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

PDD-FT-3. Fire Panel Interface With EOL Trigger. Installation and Specifications Manual

Remote NAC Power Supply D7038

TECHNICAL DATA OBSOLETE

MODEL B2 INSTALLATION MANUAL

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

MANUAL RESET ALARM RELEASE

Booster Power Supply Manual

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

Battery charger modules

MANUAL RESET ALARM RELEASE BOX

Section 1: General Description. Section 2: Features. Section 3: Operation. CM-RQE70 PIR REQUEST TO EXIT DETECTOR Installation Instructions.

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

PDD-8PCI. Power Distribution Board With Supervised Interface. Installation and Specifications Manual

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

DS160/161 Request To Exit PIR sensors Installation Instructions

Public Safety DAS Annunciator Panel

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

DS160/DS161 Request To Exit PIR sensors Installation Instructions

more than just power! Altronix is the professional security industry s leading manufacturer

EVO192 v3.0 Fire and Burglary What s New

/ How To Order

MANUAL RESET ALARM RELEASE

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

NetworX NX-548E Receiver Installation Instructions

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

IP Access FACP Adapters. Installation Guide. Entrada2DMK - IP Access FACP Adapter Kit. Kit Includes: Entrada2DMR - IP Access FACP Receiver

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

DT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

MR-2602 Two Zone Fire Alarm Control Panel

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

RELEASE DEVICE CONTROLS

Remote Chexit Module (RCM) System. General Information

120 VOLT POTENTIAL PRESENT. MAKE SURE POWER INPUT TO UNIT IS TURNED OFF DURING INSTALLATION AND WIRING PROCEDURE.

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

KT-100 Door Controller

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

Installation, Operating and Maintenance Manual

RMS/RPX Reader. User Manual

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

Specification/ Data Sheet

Crypto-Lock. Model CC-8521B Updated 7/17. Access Control System. MONITEQ, Inc. INSTRUCTION MANUAL

DE5300 Delayed Egress System. General Information

Installation Instructions

Conventional Releasing Control Panel

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

HARDwired Installation/ Owner s Manual

INSTALLATIONN GUIDE & OPERATION MANUAL

RCR-REX Request-to-Exit Dual Technology Motion Sensor Installation Guide

Transcription:

RPSMLR2 RPSMLR2BB Panic Device Power Controller Installation Guide LISTED Rev. 102715

Overview: RPSMLR2BB, RPSMLR2 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the Motorized Latch Retraction (MLR) exit devices demand. Each lock output has an adjustable re-lock delay timer. It will control a pair of doors simultaneously or independently control two individual doors. It has a relay for each output to trigger external door opening mechanisms. In addition, one un-switched auxiliary voltage output is provided. A configurable FACP interface will remove power from the lock outputs when activated. LED status indicators are provided to monitor Input status, battery condition, AC power, FACP status. Intelligent logic provides protection against accidental shorting of lock outputs. Specifications: Agency Approval: UL 294 - Access Control Unit Power Supply. Evaluated to the following levels of UL 294 6th Ed: Destructive Attack - I, Line Security - I Endurance - IV, Stand-by Power - II ULC-S319 - Access Control Unit Power Supply. Class 1. Input: Input 115VAC 60Hz, 2.5 amp or 230VAC 50Hz, 1.5 amp. Two (2) Normally Open (N.O.) trigger inputs (Input1 and Input2). FACP Normally Closed (N.C.) input. Two (2) Normally Open (N.O.) latch status inputs. Outputs: Two (2) 19.8VDC-26.4VDC rated individually controlled lock outputs for applications with battery back-up. 24VDC-26.4VDC rated for applications without battery back-up (US applications only). Current rating 2 amp combined for 400ms, 200mA continuous supply current. One (1) 19.8VDC-26.4VDC @ 0.8A rated auxiliary output for applications with battery back-up, 24VDC-26.4VDC @ 0.8A rated for applications in US not requiring battery back-up. Not affected by FACP trigger. Two (2) delayed follower Normally Open relay outputs for triggering auto operators after 1 second time delay or after the latch switch trigger, selected via dip switch. The option, when disabled, will trigger the auto operators when the latch switch input closes and, when enabled, will trigger them after the 1 second time delay regardless of latch switch position. Outputs (cont d): Trouble relay output indicating low AC voltage trouble. Battery Backup: Battery leads included. Battery PTC rating: 6A. Maximum charge current 650mA. Built-in charger for sealed lead acid batteries. Automatic switch over to stand-by battery when AC fails. When 7AH batteries are used, battery capacity for emergency stand-by is 30 minutes. Visual Indicators: Green AC Power LED indicates AC presence. Red trigger input LEDs indicate panic device status /trouble (activated, short circuit). Green Fire Alarm Interface (FAI) LED indicates FACP interface is activated. Red Battery LED indicates low battery during AC failure. Green AC LED indicates loss of AC trouble. Enclosure Dimensions (H x W x D approx.): RPSMLR2: 12.5 x 7.5 x 3.25 (317.5mm x 190.5mm x 82.55mm) RPSMLR2BB: 13.5 x 13 x 3.25 (342.9mm x 330.2mm x 82.55mm) Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. For Canadian installations - shielded wiring of appropriate gauge must be used. Unit is to be serviced by authorized personnel and de-energized prior to opening. 1. Mount unit in desired location within protected premises (Maximum Wiring Distance, pg. 5). Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 8-9). Secure cabinet to earth ground. 2. Hard wire unit: Connect unswitched AC power (115VAC 60Hz or 230VAC 50Hz) to terminals marked [L, N]. Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground. Keep power-limited wiring separate from non power-limited wiring (115VAC 60Hz or 230VAC 50Hz Input, Battery Wires). Minimum 0.25 spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel. - 2 - A85374 Copyright Stanley Security, Inc. 2015

Connect earth ground to a ground lug or ground lead. Do not connect to a receptacle controlled by a switch. Unit is intended for permanent connection using metal enclosed system. A fixed product shall be connected with one of the applicable wiring systems in accordance with CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations. Note: RLSMPR2, RPSMLR2BB is intended to be permanently connected. 3. Measure aux. output voltage before connecting devices. This helps avoid potential damage. 4. For ULC applications all interconnecting devices must be ULC Listed. Connect panic hardware device # 1 to terminals marked [+ OUT1 -- ], connect panic hardware device # 2 to terminals marked [+ OUT2 -- ] (Fig. 1, pg. 5). Be sure to observe polarity. The panic hardware device operating voltage specifications must cover 19.8VDC to 26.4VDC range. 5. Set lock output release time by adjusting [OUT1] and [OUT2] potentiometers. Turn potentiometer clockwise to increase time or counter-clockwise to decrease time. Timing range is 1 second to 4 minutes. Note: When external control of door unlock time is desired, i.e., card reader, set time to minimum (completely counter-clockwise). 6. Connect Normally Open (N.O.) Dry Contacts from actuating devices such as an Access Control Panel, REX PIR, Keypad, etc. to terminals marked [GND, INP1] and [GND, INP2] (Fig. 1, pg. 5) (100 ohm line resistance maximum). 7. Connect auxiliary devices to be powered (Keypads, REX motion detectors, electronic timers, external relays ) to the appropriate auxiliary power output terminals (Fig. 1, pg. 5). Note: Operating voltage range of device should be 19.8VDC- 26.4VDC or wider for applicators with battery backup and 24VDC-26.4VDC for applications not requiring battery backup. 8. Connect Automatic Door Operators to terminals marked [ADO1, ADO2]. Connect latch switch contacts to terminals marked [GND, Lt1] and [GND, Lt2] (if used), set OPT1 and OPT2 dip switches to the ON position if no Lt contacts are used. Note: For UL/ULC applications all interconnecting devices must be UL/ULC Listed respectively. 9. To hookup the Fire Alarm Disconnect feature, wire the normally closed (NC) dry contact output from a Fire Alarm Control Panel to the terminals marked [FACP] and [GND] of RLSMPR2, RLSMPR2BB. The Fire 1 option and Fire 2 option dip switches [Fr1] and [Fr2] when in the ON position will cause the unit to re-lock the mechanism if it was previously un-locked when FACP trigger input is activated (open circuit). 10. For ULC applications batteries must be connected. Stand-by batteries must be lead acid. 7AH batteries will provide 30 minutes of backup time. Connect two (2) 12VDC batteries wired in series to the terminals marked [+ BAT -- ]. For Access Control applications in the U.S. batteries are optional, for Canadian applications batteries are required. When batteries are not used, loss of AC will result in the loss of output voltage. 11. Mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide the tamper switch bracket onto the edge of the enclosure approximately 2 from the right side (Fig. 3, pg. 7). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure. Note: Do not exceed voltage and current ratings of tamper switch. Please refer to tamper switch installation instructions. 12. Upon completion of wiring secure enclosure door with screws or cam lock (supplied). LED Diagnostics: LED LED Status Panic Device Power Controller Status Power - On Normal operating condition. Green (AC) Off Loss of AC. On Output 1 - Energized. INP1 - Red Trigger Input 1 Rapid Blink Output 1 - Over current. Off Output 1 - De-energized. On Output 2 - Energized. INP2 - Red Trigger Input 2 Rapid Blink Output 2 - Short Circuit. Off Output 2 - De-energized. FAI - Green On FACP Input triggered (alarm condition). Off FACP normal (non-alarm condition). BAT Trouble Off Bad battery or no battery. Red Slow Blink Battery low. AC Trouble Off AC normal. Green Slow blink AC low or missing. A85374 Copyright Stanley Security, Inc. 2015-3 -

Maintenance: Unit should be tested at least once a year for the proper operation as follows: FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup, remove wire from the terminal marked [FACP] on RLSMPR2, RLSMPR2BB. With the dip switches [Fr1] and [Fr2] in ON position, unlocked Panic Hardware Devices will re-lock. With dip switches [Fr1] and [Fr2] in the OFF position (Fig. 2, 3, pg. 6, 7), locked Panic Hardware Devices will not be affected. Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level. Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at battery terminal and at the board terminals marked [+ BAT -- ] to ensure there is no break in the battery connection wires. Note: Maximum charging current under discharge is 650mA. Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed. Caution: For continuous protection against risk of electric shock and fire hazard, replace input fuse with the same type and rating: 5 amp/250v. Do not expose to rain or moisture; indoor use only. Terminal Identification: Terminal Legend Function/Description + AUX 24VDC Auxiliary Output @ 0.8 amp. 19.8-26.4VDC for applications with battery back-up. + BAT 24VDC Stand-by Battery Connection (Two (2) 12VDC batteries wired in series). OUT 1 + Connect 24VDC Panic Hardware Device #1 OUT 2 + Connect 24VDC Panic Hardware Device #2. Normally Closed Dry Contact from Fire Alarm Control FACP / GND (100 ohm maximum wiring resistance). Normally Open Trigger input controls Output 1. May be held closed for extended unlocking INP1 / GND (100 ohm maximum wiring resistance). Normally Open Trigger input controls Output 2. May be held closed for extended unlocking INP2 / GND (100 ohm maximum wiring resistance). Dry form A contacts provide a signal for door opening mechanism. With dip switch [OPT1] in the ON position, door opening mechanism will be triggered ADO1 within 1 second after Input 1 signal. With dip switch [OPT1] in the OFF position, the door opening mechanism will be triggered after the latch switch contacts close indicating lock retraction. Dry form A contacts provide a signal for door opening mechanism. With dip switch [OPT2] in the ON position, door opening mechanism will be triggered ADO2 within 1 second after Input 2 signal. With dip switch [OPT2] in the OFF position, the door opening mechanism will be triggered after the latch switch contacts close indicating lock retraction. C, NO Indicates AC trouble condition. Normally Open, closed if AC is low or missing. Lt1, GND Dry normally open inputs for latch switch 1 connection. Lt2, GND Dry normally open inputs for latch switch 2 connection. - 4 - A85374 Copyright Stanley Security, Inc. 2015

Fig. 1 RPSMLR2 Power Supply Made in USA + OUT1 --- + OUT2 --- Risk of Fire, Replace Fuses As Marked Fire 1 Option Fire 2 Option INP1 INP2 FAI BAT AC Altronix Corp. Brookllyn, NY 11220 ADO1 GND Lt1 ADO2 GND Lt2 C NO -- AUX + Auxiliary 24VDC Device Latch Switch Automatic Door Operator Latch Switch Automatic Door Operator M M ON 5A 250V L G N --- BAT + AC Fr1 Fr2OPT1 OPT2 OUT1 Timer OUT2 Timer GND INP1 GND INP2 GND FACP 115VAC/ 230VAC Fire Alarm Control Panel IN2 IN1 --- + --- + 12VDC 12VDC Rechargeable Batteries Wiring Distance Table: Wire Gauge Distance 18 AWG Stranded 200 ft. 16 AWG Stranded 320 ft. 14 AWG Stranded 500 ft. 12 AWG Stranded 800 ft. A85374 Copyright Stanley Security, Inc. 2015-5 -

Fig. 2 - RLSMPR2 WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. Replace fuse with the same type and rating: Input Fuse is rated at 5A/250V, Battery PTC rated at 6A. 5A 250V Earth Ground Battery Outputs (non power-limited) L G N --- BAT + Fr1 Fr2OPT1 AC ON 115VAC Input 60Hz, 2.5 amp or 230VAC Input 50Hz, 1.5 amp (non power-limited) Fire 1 Option Fire 2 Option Risk of Fire, Replace Fuses As Marked RPSMLR2 Power Supply Made in USA OPT2 FACP and Access Control Trigger Inputs () OUT1 Timer OUT2 Timer GND INP1 GND INP2 GND FACP INP1 INP2 FAI BAT AC Altronix Corp. Brookllyn, NY 11220 + OUT1 --- + OUT2 --- Outputs ADO1 GND Lt1 ADO2 GND Lt2 C NO -- AUX + Outputs Dry Outputs Dry Aux. Output Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. - 6 - A85374 Copyright Stanley Security, Inc. 2015

Fig. 3 - RLSMPR2BB WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. Replace fuse with the same type and rating: Input Fuse is rated at 5A/250V, Battery PTC rated at 6A. Wire Strap (from Enclosure to Door) Earth Ground Battery Outputs (non power-limited) FACP and Access Control Trigger Inputs () 5A 250V L G N --- BAT + Fr1 Fr2OPT1 OPT2 OUT1 Timer OUT2 Timer GND INP1 GND INP2 GND FACP AC ON 115VAC Input 60Hz, 2.5 amp or 230VAC Input 50Hz, 1.5 amp (non power-limited) Fire 1 Option Fire 2 Option Risk of Fire, Replace Fuses As Marked INP1 INP2 FAI BAT AC Altronix Corp. Brookllyn, NY 11220 RPSMLR2 Power Supply Made in USA + OUT1 --- + OUT2 --- Outputs ADO1 GND Lt1 ADO2 GND Lt2 C NO -- AUX + Outputs Dry Outputs Dry Aux. Output Optional Rechargeable Stand-by Battery for UL294 Applications. Note: 12V batteries required for Canadian installations. Optional Rechargeable Stand-by Battery for UL294 Applications. Note: 12V batteries required for Canadian installations. Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 7AH Rechargeable batteries are the largest batteries that can fit in this enclosure (UL/ULC - Stand-by power only evaluated with 7AH batteries). A UL Listed external battery enclosure must be used if using 12AH, 40AH or 65AH batteries. A85374 Copyright Stanley Security, Inc. 2015-7 -

RPSMLR2 Enclosure Dimensions (H x W x D approximate): 12 x 7.5 x 3.25 (304.80mm x 190.50mm x 82.5mm) 7.50 (190.5mm) 3.25 (82.5mm) 1.25 (31.75mm) 0.50 (12.7mm) 6.50 (165.1mm) 1.50 (38.09mm) G 0.75 (19.04mm) 0.70 (17.78mm) 1.11 (28.19mm) 1.9 (19.04mm) G 0.75 (19.04mm) 0.18 (4.57mm) 0.40 (10.16mm) 3.45 (87.63mm) Double Knockout 1.125 (28.575mm) 0.875 (22.22mm) 12.00 (304.80mm) 0.25 (6.35mm) 1.25 (31.75mm) 0.45 (11.43mm) 0.00 (0.00mm) 0.00 (0.00mm) 0.60 (15.24mm) 0.25 (6.35mm) 6.05 (153.67mm) 3.45 (87.63mm) - 8 - A85374 Copyright Stanley Security, Inc. 2015

RPSMLR2BB Enclosure Dimensions (H x W x D approximate): 13.5 x 13 x 3.25 (342.9mm x 330.2mm x 82.55mm) 1.4 (35.56mm) 4.85 (123.19mm) 4.85 (123.19mm) 1.4 (35.56mm) 1.21 (30.73mm) 3.25 (82.55mm) 1.20 (30.48mm) 0.75 (19.05mm) 12.5 (317.5mm) 11.0 (279.4mm) 0.75 (19.05mm) 1.20 (30.48mm) 1.4 (35.56mm) 0.18 (4.57mm) 0.527 (13.38mm) 0.9375 (23.813mm) 1.4 (35.56mm) Designated AC Knock Out 0.40 (10.16mm) 5.1 (129.54mm) 5.1 (129.54mm) Double Knockout 1.125 (28.575mm) 0.875 (22.22mm) 5.1 (129.54mm) 6.5625 (166.6875mm) 0.9375 (23.813mm) 1.347 (34.21mm) 3.25 (82.55mm) 3.25 (82.55mm) 3.25 (82.55mm) 1.00 (25.4mm) 1.00 (25.4mm) 1.00 (25.4mm) A85374 Copyright Stanley Security, Inc. 2015-9 -

Notes: - 10 - A85374 Copyright Stanley Security, Inc. 2015

Notes: - 11 - A85374 Copyright Stanley Security, Inc. 2015

Notes: Stanley Security is not responsible for any typographical errors. Product specifications are subject to change without notice. Stanley Security, 1-855-365-2407 website: www.stanleysecurity.com/precision - Made in U.S.A. IIRPSMLR2 / RPSMLR2BB A20P - 12 - A85374 Copyright Stanley Security, Inc. 2015