Performance of a Transcritical CO 2 Heat Pump for Simultaneous Water Cooling and Heating

Similar documents
Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Performance of CO2 Cycles with a Two-Stage Compressor

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Transcritical Carbon Dioxide Microchannel Heat Pump Water Heaters: Part II - System Simulation and Optimization

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Carbon Dioxide based Heat Pump Dryer in Food Industry

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

A study of Transient Performance of A Cascade Heat Pump System

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

POTENTIAL OF NON - AZEOTROPIC REFRIGERANT MIXTURE AS WORKING REFRIGERANT IN HOT WATER HEAT PUMPS. FJ Smit and JP Meyer

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Performance characteristics of low global warming potential R134a alternative refrigerants in ejector-expansion refrigeration system

Exploring the Performance Characteristics of CO2 Cycles in a Breadboard-Type Test Facility

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

(Refer Slide Time: 00:00:40 min)

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Dynamic Simulation of Liquid Chillers

Performance of an Improved Household Refrigerator/Freezer

Performance Study of Triple Concentric Pipe Heat Exchanger

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Performance investigation of Air-conditioning system using ejector as expansion device

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Development of Energy Efficient R-134a Automotive Air Conditioning System Using Internal Heat Exchanger

ENSC 388. Assignment #6

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

2. HEAT EXCHANGERS MESA

Refrigerant Mass and Oil Migration During Start-up Transient

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Enhancement of COP in Vapour Compression Refrigeration System

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Performance Measurement of R32 Vapor Injection Heat Pump System

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Homework Chapter2. Homework Chapter3

*Corresponding author;

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Experimental Studies of a Heat Pump with Microprocessor Control on an Animal Farm

SIMULATION OF A NEW TYPE GAS-FIRED AIR-COOLED AIR-CONDITIONER. Lin Wang, Xing Xu, Aihua Ma, Yonghui Guo and Xiwen Zhou

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

In the name of God. Jami Institute of Jami - Mehdi Rasti

Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions

Design optimisation of CO 2 gas cooler/condenser in a refrigeration system

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Shortcut Model for Predicting Refrigeration Cycle Performance

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

American International Journal of Research in Science, Technology, Engineering & Mathematics

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

Performance analysis of a vapour compression-absorption cascaded refrigeration system with undersized evaporator and condenser

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Transcription:

Performance of a Transcritical CO Heat Pump for Simultaneous Water Cooling and Heating J. Sarkar, Souvik Bhattacharyya, and M. Ramgopal Abstract This paper presents the experimental as well as the simulated performance studies on the transcritical CO heat pumps for simultaneous water cooling and heating; effects of water mass flow rates and water inlet s of both evaporator and gas cooler on the cooling and heating capacities, system COP and water outlets s are investigated. Study shows that both the water mass flow rate and inlet have significant effect on system performances. Test results show that the effect of evaporator water mass flow rate on the system performances and water outlet s is more pronounced (COP increases 0.6 for 1 kg/min) compared to the gas cooler water mass flow rate (COP increases 0.4 for 1 kg/min) and the effect of gas cooler water inlet is more significant (COP decreases 0.48 for given ranges) compared to the evaporator water inlet (COP increases 0.43 for given ranges). Comparisons of experimental values with simulated results show the maximum deviation of 5% for cooling capacity, 10% for heating capacity, 16% for system COP. This study offers useful guidelines for selecting appropriate water mass flow rate to obtain required system performance. Keywords CO heat pump, experiment, simulation, performance characteristics. I. INTRODUCTION ECENTLY, natural fluid CO has been shown to be a R promising alternative refrigerant particularly in heat pump applications due to gliding heat rejection in the gas cooler and performance related various advantages. Some of the current theoretical and experimental investigations on several heat pump applications of transcrtical CO cycle have been presented by Neksa [1] and Kim et al. []. Neksa et al. [3] and White et al. [4] experimentally investigated the effects of charge pressure, water inlet and outlet s on the CO heat pump water heater performances. Yarral et al. [5] experimentally investigated to effect of charge pressure on CO heat pump performance for simultaneous production of refrigeration and water heating to 90 o C for the food processing industry. Adriansyah [6] experimentally studied the effect of charge pressure for J. Sarkar is with the Department of Mechanical Engineering, Institute of Technology-BHU, Varanasi, India 1005 (corresponding author: Tel: 91-9919787557; Fax: 91-54-368157; E-mail: jahar_s@hotmail.com). Souvik Bhattacharyya is with the Department of Mechanical Engineering, Indian Institute of Technology, Kharagpur India 7130 (e-mail: souvik@mech.iitkgp.ernet.in). M. Ramgopal is with the Department of Mechanical Engineering, Indian Institute of Technology, Kharagpur India 7130. simultaneous air-conditioning and water heating. Stene [7] presented the effect of water inlet for combination of space and water heating. Cho et al. [8] studied the performance of the CO heat pump by varying the refrigerant charge amount at standard cooling condition to show the importance of refrigerant charge to achieve better performance. Kim et al. [9] have done experimental study on CO heat pump to study the effect of internal heat exchanger using water as secondary fluid for both sides with emphasizes only on heating. Sarkar et al. [10] numerically studied the effects of water inlet, compressor speed and heat exchanger inventory for simultaneous water cooling and heating applications. Yokoyama et al. [11] numerically studied the influence of ambient on performance of a CO heat pump water heating system. Cabello et al. [1] experimentally studied the effect of evaporating and gas cooler outlet on optimum gas cooler pressure, and through comparisons with available correlations, showed that Sarkar et al. correlation [13] matches best with the test data. However, effects of water mass flow rate on heat pump behaviours are scarce. In the present investigation, both simulation and experimental results on the working prototype of a transcritical CO heat pump system for simultaneous water cooling and heating are presented. The cooling and heating capacities, system COP and water outlets s have been studied for various water mass flow rates and water inlet s of both evaporator and gas cooler. Comparison of simulated and experimental results is presented as well. II. EXPERIMENTS OF A TRANSCRITICAL CO HEAT PUMP A. Description of test setup Test facility layout of transcritical CO heat pump for simultaneous water cooling and heating with instrumental positions is shown in Fig. 1. Stainless steel was chosen as the material for all system components. A Dorin CO compressor (model TCS113: placement =. m 3 /hr and capacity =.5 kw @ 900 rpm) was chosen for the experimental investigation. On the basis of minimum and maximum pressure ratios of 80/50 and 10/6 (bar/bar), respectively, a Swagelok integral bonnet needle valve (model SS-1RS4) was used as the expansion device, which can be used regulate flow rate and degree of superheat. The separator and receiver were 571

designed for a total volumetric capacity of 8 L and L, respectively. A condensing unit including a fan and a storage tank was employed for a maximum heat transfer rate of 6 kw to cool the warm water to its initial at the inlet to the gas cooler. A water bath with heater and pump was incorporated in the evaporator to supply water at constant and flow rate. The evaporator and the gas cooler are counter-flow tube-in-tube heat exchangers, where CO flows in the inner tube and water in the outer annulus (Table I). Measuring ranges of instruments with uncertainties are listed in Table II. Fig. 1 Test facility layout of the transcritical CO heat pump TABLE I DIMENSIONS OF GAS COOLER AND EVAPORATOR Heat exchangers Gas cooler Evaporator Configuration Coaxial, Single Coaxial, Single pass, 14 rows pass, 9 rows Inner tube OD/outer tube OD 6.35 mm/1 mm 9.5mm/16mm Total length of 14 m 7. m tubing B. Test procedure and test conditions In the experimental study, the effects of water inlet and mass flow rate in gas cooler, and water inlet and mass flow rate in evaporator were investigated by varying them using condensing unit for the gas cooler and heating unit for the evaporator. Constant suction pressure and charge pressure were maintained by simultaneous control of the total mass of CO in the system and degree of opening of the expansion device. The total refrigerant mass in the system was controlled by adding CO from a high pressure cylinder or by venting it through the safety valve. For certain test conditions, constant water flow rates for both evaporator and gas cooler were maintained by pumps, water inlet water to gas cooler was maintained by controlling fan speed and water inlet to evaporator was maintained by heater control. The compressor power input was measured by using a power meter, the refrigerant mass flow rate was measured by a Coriolis effect flow meter, the pressure of the refrigerant were monitored by using pressure transducers, pressure drop in the heat exchangers was measured by differential pressure transducer and refrigerant and water s at all required locations were measured by using T-type & K-type thermocouples. All the measurements have been done at steady state condition. The principal system performance parameters under steady state, namely, power input to the compressor, cooling capacity, heating capacity, system COP have been computed from the measured data. The uncertainties of cooling capacity, heating capacity and system COP, estimated by error analysis, are approximately ±5%, ±5% and ±6%, respectively. Parameters Pressure Pressure loss CO mass flow rate Water mass flow rate Temperature TABLE II RANGES AND UNCERTAINTIES OF MEASURING INSTRUMENTS Measuring instruments Ranges Accuracy Dial pressure 0-160 bar ±1.5% of gauge full range Differential 0-4 bar ±1.5% of pressure gauge full range Mass flow meter 0. 10 ±0.1% of kg/min full range Mass flow meter 0.5 0 ±0.5% of kg/min full range Thermocouples Calibrated ±0.5 (T-type, K-type) range: 0-150 o C III. SIMULATION OF TRANSCRITICAL CO HEAT PUMP The simulated carbon dioxide based heating and cooling system consists of compressor, expansion valve, evaporator and gas cooler. Water is taken as secondary fluid for both gas cooler and evaporator to give the useful cooling and heating outputs. Both these heat exchangers are of double-pipe counter flow type, where the refrigerant flows through the inner tube and water flows through the outer annular space. The layout and corresponding -entropy diagram with water flow lines is shown in Fig.. The entire system has been modeled based on energy balance of individual components yielding conservation equations presented below. The following assumptions have been made in the analysis: 1. Heat transfer with the ambient is negligible.. Only Single-phase heat transfer occurs for water (external fluid). 3. Compression process is adiabatic but not isentropic. 4. Pressure drop on waterside and in connecting pipes are negligible. 5. Changes in kinetic and potential energies are negligible. 6. Refrigerant is free from oil. 57

Fig. Temperature-entropy diagram of a transcritical CO heat pump A. Compressor model The refrigerant mass flow rate through the compressor is given by, & N mr = ρη 1 vv (1) s 60 The following correlations have been used for volumetric and isentropic efficiencies respectively for the semi-hermetic compressor, which have obtained based on regression of manufacturer test data, neglecting the effect of degree of superheat: P P ηv = 1.1636 0.188 + 0.0163 () Psuc Psuc η is,c P P = 0.61 + 0.0356 0.057 Psuc Psuc B. Gas cooler model P + 0.00 Psuc To consider the lengthwise property variation, gas cooler has been cretized into equal length segments along the refrigerant flow direction and momentum and energy conservation equations have been applied to each segment [9-10]. Employing LMTD expression, heat transfer in i th segment of the gas cooler is given by, i i i+ 1 i+ 1 ( Tgcr Tgcw ) ( Tgcr Tgcw ) i i Qgc = ( UA) (4) gc i i Tgcr T gcw ln i+ 1 i+ 1 Tgcr T gcw Additionally, energy balance in segment of gas cooler for both the fluids yield: Q = m( & h h ) = m & c ( T T ) (5) i i i + 1 i i + 1 gc r gcr gcr gcw pw gcw gcw 3 (3) The overall heat transfer coefficient for the segment of gas cooler has been calculated using the fundamental equation for overall heat transfer coefficient. To estimate the heat transfer coefficient of supercritical carbon dioxide for in-tube cooling in gas cooler, Pitla et al. [14] correlation, incorporating both bulk and wall properties due to large variation of fluid properties in the radial direction, has been used. The pressure drop for supercritical carbon dioxide in-tube cooling has been calculated by Petrov and Popov equation [15], neglecting inertia effect. The waterside heat transfer coefficient has been evaluated by the Gnielinski [16] equation for annular flow. All water properties are assumed to be dependent only, and polynomial expressions based on text book values have been used. C. Evaporator Model The evaporator consists of two zones: two-phase (boiling) zone and superheated zone. Similar to the gas cooler, both zones in the evaporator are divided into a finite number of equal-length segments along the refrigerant flow direction. Each segment is treated as one counter-flow heat exchanger and the outlet conditions of each segment should become inlet conditions for the next segment. For each segment LMTD method is used and properties are evaluated based on mean and pressure. Energy balance in each segment of the evaporator for the refrigerant ( CO ) and water, respectively, yields: i i+ 1 i i+ 1 i Qev = m( & r hevr hevr ) = m & evwcpw( Tevw Tevw ) (6) The overall heat transfer coefficient for each segment of the evaporator has been calculated in the same way as for the gas cooler. In this analysis, the recently developed Yoon et al. [17] correlation has been employed to estimate the boiling heat transfer coefficient. For superheated zone, Gnielinski [16] equation has been used to estimate convective heat transfer coefficient of carbon dioxide. Jung and Radermacher [18] correlation has been used for boiling pressure drop and Blasius correlation has been used for single phase pressure drop of carbon dioxide. The waterside heat transfer coefficient has been evaluated by Gnielinski [16] equation for annular flow for both two-phase and superheated sections. Using cretization, the heat exchanger is made equivalent to a number of counter flow heat exchangers arranged in series and the combined heat transfer of all the segments is the total heat transfer of the heat exchanger. Therefore, fast changing properties of CO have been modeled accurately in both evaporator and gas cooler. D. Expansion Device Model The expansion process is considered to be isenthalpic under the assumption that the heat exchange with its surroundings is negligible, yielding: h = h (7) 4 3 573

Input: Evaporator and gas cooler dimensions, V s, N, t evi t, m& evw m, P suc, P, gci & gcw Gauss: suction (t 1 ) Compressor model: m&, charge conditions r Input evaporator model & find t evw, o, h 4 Input gas cooler model & find t 3, t gcw, o, h 3 Expansion device model: h =h Yes Capacities, COP calculated Fig. 3 Flow-chart for the simulation model E. Numerical Procedure A computer code, incorporating the subroutine COPROP [10] for thermophysical and transport properties, has been developed to simulate the transcritical carbon dioxide system for simultaneous water cooling and heating at various operating conditions. Water inlet s and water mass flow rates for both heat exchangers, compressor data, evaporator and gas cooler dimensions, compressor suction pressure and charge pressure are the input data for the simulation. The flow chart of the simulation is shown in Fig. 3. Pressure drop and heat loss in connecting lines are not considered; therefore, the outlet state of one component becomes the inlet state of the next component. In the simulation, by assuming the suction, refrigerant mass flow rate and compressor outlet conditions are calculated by compressor model, and refrigerant conditions at evaporator inlet and at gas cooler outlet as well as water outlet s of both evaporator and gas cooler are calculated based on mathematical model of evaporator and gas cooler. The suction is adjusted by the iteration in order for the enthalpy of inlet (h 3 ) and outlet (h 4 ) of expansion valves to converge within a prescribed tolerance and performances such as cooling and heating capacities, compressor work and COP are calculated. Tolerance has been maintained in the range of 10 3 for simulation. No Update t 1 IV. RESULTS AND DISCUSSION The performance of the CO heat pump system in terms of cooling and heating capacities and system COP (cooling + heating capacities divided by compressor power) considering both cooling and heating as useful outputs are studied for the suction and charge pressure of 40 bar and 90 bar, respectively. Both the numerical and experimental results are presented to study the effect of water inlet s and mass flow rates on the performances and water outlet s. System COP 3.7 3.5.9.7 1 1.3 1.6 1.9..5 Water flow rate in evaporator (kg/min) Fig. 4 System performance variation with evaporator water flow rate Effects of water mass flow rate to evaporator on the performances and water outlet s for both gas cooler and evaporator are shown in Figs. 4 and 5, respectively, for evaporator water inlet of 9 o C, gas cooler water inlet of 33 o C and water mass flow rate of 1 kg/min. With increase in water mass flow rate to evaporator, the cooling capacity increases due to increase in water side heat transfer coefficient and both the heating capacity and compressor work increase modestly due to minor increase in the suction (increase in degree of superheat) and also charge. Water outlet of evaporator increases due to dual effect of increase in cooling capacity and water mass flow rate; whereas water outlet of gas cooler increases due to increase in heating capacity. 4.3 3.7.5 1.9 1.3 574

17 9 0.6 per 1 kg/min) compared to the effect of water mass flow rate in gas cooler (COP increases about 0.4 per 1 kg/min). 15 13 11 9 7 tgcw,o; Experimental 1 1.3 1.6 1.9..5 Water flow rate in evaporator (kg/min) Fig. 5 Water outlet variation with evaporator water flow rate system COP 3.6 3.4 3. 3.8.6 0.6 0.8 1 1. 1.4 1.6 Water flow rate in gas cooler (kg/min) Fig. 6 Variation of system performance with gas cooler water flow rate Effects of water mass flow rate to gas cooler on the performances and water outlet s for both gas cooler and evaporator are shown in Figs. 6 and 7, respectively, for gas cooler water inlet of 33 o C, evaporator water inlet of 9 o C and water mass flow rate of 1.5 kg/min. With increase in water mass flow rate in gas cooler, heating output increases modestly due to increase in water side heat transfer coefficient and refrigerant mass flow rate increases, which enhances the cooling capacity, although the effect on compressor work is insignificant and hence the system COP increases. Due the dual effect of increase in water mass flow rate and heating capacity, the water outlet of gas cooler decreases and evaporator water outlet decreases due to increase in cooling capacity with increase in water mass flow rate in gas cooler. Results show that the effect of water flow rate in evaporator is more pronounced on the performances (COP increases about 4.4 3.8 3..6 1.4 88 84 80 76 7 15 13 11 9 7 5 tgcw,o; Experimental 0.6 0.8 1 1. 1.4 1.6 Water flow rate in gas cooler (kg/min) 100 Fig. 7 Variation of water outlet s with gas cooler water flow rate System COP 3.5.9.7.5 5 7 9 31 33 35 Evaporator water inlet ( o C) Fig. 8 Variation of system performance with evaporator water inlet Figs. 8 and 9 exhibit the variations of performances and water outlet s with evaporator water inlet for mass flow rates of water in gas cooler and evaporator of 1 kg/min and 1.5 kg/min respectively, and water inlet to gas cooler of 33 o C. With the increase in water inlet to evaporator, suction as well as charge increases, which enhance both cooling and heating capacities; however compressor work increases insignificantly due to decrease in refrigerant mass flow rate and hence system COP increases. Water outlet of evaporator increases due to dual effect of increase in cooling capacity and water inlet ; whereas water outlet of gas cooler increases due to increase in heating capacity. 4.3 3.8.8.3 1.8 1.3 94 88 8 76 70 575

17 15 13 11 89 85 81 77 gas cooler increases and evaporator water outlet increases due to decrease in cooling capacity with increase in water inlet to gas cooler. Results show that the effect of water inlet to gas cooler on the system performances is more significant (COP decreases about 0.48 per 10 o C) compared to the effect of water inlet to evaporator (COP increases about 0.43 per 10 o C water inlet ). 18 9 9 7 tgcw,o; Experimental 5 7 9 31 33 35 Evaporator water inlet ( o C) Fig. 9 Water outlet variation with evaporator water inlet System COP 3.5.9.7.5 30 3 34 36 38 40 Gas cooler water inlet ( o C) Fig. 10 Variation of system performance with gas cooler water inlet Figs. 10 and 11 exhibit the variations of performances and water outlet s with water inlet to gas cooler for mass flow rates of water in gas cooler and evaporator of 1 kg/min and 1.5 kg/min respectively, and water inlet to evaporator of 9 o C. As the water inlet to gas cooler increases, the heating capacity decreases due to deterioration in heat transfer properties of CO in gas cooler and the refrigerant exit in gas cooler increases, which increases the vapor quality in evaporator inlet and hence cooling output also decreases, however, compressor work is nearly invariant due to negligible change in refrigerant mass flow rate and degree of superheat and hence system COP decreases significantly. Due the dual effect of increase in water inlet and decrease in heating capacity, the water outlet of 4.3 3.8.8.3 1.8 1.3 73 69 16 14 1 10 8 tgce,o; Experimental 30 3 34 36 38 40 Gas cooler water inlet ( o C) Fig. 11 Water outlet variation with gas cooler water inlet Results show that the test values of heating capacity is lower than the simulated values with maximum deviation of 5%, test values of heating capacity are lower than the simulated values with maximum deviation of 10% and experimental values of COP is lower than the simulated values with maximum deviation of 16%. Results show that the test values of water outlet to evaporator are higher than the simulated values with maximum deviation of 1% and that is lower in case of gas cooler with maximum deviation of 7.5%. It may be noted that the suction pressure is maintained constant by varying degree of superheat unlike to the previous studies [9-10] and the superheat values varied from 5 o C to 15 o C in the simulation and 8 o C to 0 o C in the test for given ranges. V. CONCLUSIONS Both simulation and experimental studies on a transcritical CO heat pump system for simultaneous water cooling and heating have been carried out to study the system performances and water outlet s for various mass flow rates and water inlet s for both evaporator and gas cooler. The cooling and heating capacities and COP increase with increase in water mass flow rate to both evaporator and gas cooler; however, effect is more pronounce in case of evaporator mass flow rate (COP increases by 0.6 per 1 kg/min, whereas 0.4 for gas cooler mass flow rate). 88 84 80 76 7 576

Evaporator and gas cooler water outlet s increase with increase in evaporator mass flow rate and decrease with increase in evaporator mass flow rate. Cooling and heating capacities and COP increase with increase in water inlet to evaporator, whereas trends are opposite with increase in gas cooler water inlet ; effect of gas cooler water inlet is more pronounce (COP increases by 0.48 per 10 o C, whereas 0.43 for gas cooler). With the increase in water inlet s to both evaporator and gas cooler, water outlet s of both evaporator and gas cooler increase. Comparison of simulated and experimental values showed the maximum deviation of 5% for cooling capacity, 10% for heating capacity, 16% for system COP, 1% and 7.5% for water outlet s of evaporator and gas cooler, respectively. The present study offers useful guidelines for suitable system design and will help choose suitable water mass flow rates for required system performance and water outlet s. ACKNOWLEDGMENT The financial support extended by Ministry of Human Resource and Development, Government of India is gratefully acknowledged. NOMENCLATURE c p specific heat capacity (kj/kgk) h specific enthalpy (kj/kg) m& mass flow rate (kg/min) N compressor speed (rpm) P pressure (bar) Q & heat rate (kw) t,t ( o C, K) UA heat conductance (W/K) V s suction volume (m 3 ) η efficiency ρ density (kg/m 3 ) Subscripts charge ev evaporator gc gas cooler i inlet o outlet r refrigerant suc suction w water [4] S. D. White, M. G. Yarrall, D. J. Cleland, and R. A. Hedley, Modelling the performance of a transcritical CO heat pump for high heating, Int. Journal of Refrigeration, vol. 5, no. 4, pp. 479-486, June 00. [5] M. G. Yarral, S. D. White, D. J. Cleland, R. D. S. Kallu, and R. A. Hedley, Performance of transcritical CO heat pump for simultaneous refrigeration and water heating, XX Int. Congress of Refrigeration, Sydney, 1999, Paper no. 651. [6] W. Adriansyah, Combined air conditioning and tap water heating plant using CO as refrigerant, Energy and Buildings, vol. 36, no. 7, pp. 690-695, July 004. [7] J. Stene, Residential CO heat pump system for combined space heating and hot water heating, Int. Journal of Refrigeration, vol. 8, no. 8, pp. 159-165, Dec. 005. [8] H. Cho, C. Ryu, Y. Kim, and H. Y. Kim, Effects of refrigerant charge amount on the performance of a transcritical CO heat pump, Int. Journal of Refrigeration, vol. 8, no. 8, pp. 166 173, Dec. 005. [9] S. G. Kim, Y. J. Kim, G. Lee, and M. S. Kim, The performance of a transcritical CO cycle with an internal heat exchanger for hot water heating, Int. Journal of Refrigeration, vol. 8, no. 7, pp. 1064 107, Nov. 005. [10] J. Sarkar, S. Bhattacharyya, and M. Ramgopal, Simulation of a transcritical CO heat pump cycle for simultaneous cooling and heating applications, Int. Journal of Refrigeration, vol. 9, no. 5, pp. 735-743, Aug. 006. [11] R. Yokoyama, T. Shimizu, K. Ito, and K. Takemura, Influence of ambient s on performance of a CO heat pump water heating system, Energy, vol. 3, no. 4, pp. 388-398, Apr. 007. [1] R. Cabello, D. Sa nchez, R. Llopis, and E. Torrella, Experimental evaluation of the energy efficiency of a CO refrigerating plant working in transcritical conditions, Applied Thermal Engineering, vol. 8, no. 13, pp. 1596-1604, Sep. 008. [13] J. Sarkar, S. Bhattacharyya, and M. RamGopal, Optimization of a transcritical CO heat pump cycle for simultaneous cooling and heating applications, Int. Journal of Refrigeration, vol. 7, no. 8, pp. 830-838, Dec. 004. [14] S. S. Pitla, E. A. Groll, and S. Ramadhyani, New correlation to predict the heat transfer coefficient during in-tube cooling of turbulent supercritical CO, Int. Journal of Refrigeration, vol. 5, no. 6, pp. 887-895, Sep. 00. [15] X. Fang, C. W. Bullard, and P. S. Hrnjak, Heat transfer and pressure drop of gas coolers, ASHRAE Transactions, vol. 107, pp. 55-66, 001. [16] V. Gnielinski, New equations for heat and mass transfer in turbulent pipe and channel flow, Int. Chemical Engineering, vol. 16, pp. 359 366, 1976. [17] S. H. Yoon, E. S. Cho, Y. W. Hwang, M. S. Kim, K Min, and Y. Kim, Characteristics of evaporative heat transfer and pressure drop of carbon dioxide and correlation development, Int. Journal of Refrigeration, vol. 7, no., pp. 111-119, Mar. 004. [18] D. S. Jung, and R. Radermacher, Prediction of pressure drop during horizontal annular flow boiling of pure and mixed refrigerants, Int. Journal of Heat Mass Tran., vol. 3, no. 1, 435 466, Dec. 1989. J. Sarkar received his M. Tech. and Ph.D. degrees in Mechanical Engineering from Indian Institute of Technology Kharagpur, India in 001 and 006, respectively. After, he joined the faculty of Institute of Technology, Banaras Hindu University, India and working as a Lecturer in Mechanical Engineering Department till date. Author has published 30 research papers in international journal and 0 in national and international conferences in several areas of Heat Transfer and Refrigeration. REFERENCES [1] P. Neksa, CO heat pump systems, Int. Journal of Refrigeration, vol. 5, no. 4, pp. 41-47, June 00. [] M. H. Kim, J. Pettersen, and C. W. Bullard, Fundamental process and system design issues in CO vapor compression systems, Progress in Energy and Combustion Science, vol. 30, no., pp. 119-174, 004. [3] P. Neksa, H. Rekstad, G. R. Zakeri, and P. A. Schiefloe, CO heat pump water heater: characteristics, system design & experimental results, Int. Journal of Refrigeration, vol. 1, no. 3, pp. 17-179, May 1998. 577