MANUAL RESET ALARM RELEASE BOX

Similar documents
WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE

INSTRUCTION MANUAL. AlarmGard Chain Operator (Model FCA) AlarmGard Crank Operator (Model FKA)

AUTO RESET ALARM RELEASE BOX MODEL AR-C INSTRUCTION MANUAL

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

Hand Chain (Model FCF) &

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

INSTALLATION & MAINTENANCE CORNELL FIREGARD CHAIN & ES ECO #1515 REVISION # 0000 FIREGARD CRANK OPERATORS BY: RICKM DATE: 3/23/2011

M O D E L S FIREGARD BV EXTENDED PERFORMANCE RELEASE DEVICE

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

RELEASE DEVICE CONTROLS

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

OWNER S MANUAL. Extended Performance Release Device. Models: Firefly III Plus, Firefly III Plus with Voiceboard

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

SP-1000X. Panic Device Power Controller Installation Guide. Rev

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL. FT-EPB Series. Single Motor

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

Model 17A00 Expansion Enclosure

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

Multiple Input and Output Modules

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Installation Guide for models:

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

INSTALLATIONN GUIDE & OPERATION MANUAL

F220-B6PS/M. Installation Guide. Addressable Detector Bases

Installation Guide for models:

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

Series. Access Power Controllers. Installation Guide

PSN-1000 & PSN 1000(E) Installation Manual

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

TS93 EMR WITH SMOKE DETECTOR

Conventional Smoke Detectors KFAPO

AL600ULX Series. Power Supply/Charger. Installation Guide

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

8600 EMR SERIES. INSPK NO Rev.06/ INS NO. GENERAL DESCRIPTION

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL. FST-EPB Series. Single Motor

RM-1 Series. Remote Microphones. (RM-1, RM-1SA) Document Revision B RM-1 RM-1SA. RM-1 on ADP-4 dress panel. RM-1SA in a CAB-RM or CAB-RMR

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

Conventional Releasing Control Panel

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

D7053. Installation Instructions Multiplex Input/Output Module

Remote NAC Power Supply D7038

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

FMR Installation Instructions. Addressable Fire System Controller

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL600ULADA. NAC Power Extender. Installation Guide

FireNET Plus Wiring Instructions

TS93 EMF SERIES. INSPK NO Rev.03/10

AND ARCHITECT SPECIFICATIONS

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

SECTION OVERHEAD COILING FIRE DOORS 641 SERIES OVERHEAD COILING COUNTER FIRE DOORS

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

DH100ACDCI Ionization Air Duct Smoke Detector

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Multiplex Eight Input Remote Modules

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

DS160/161 Request To Exit PIR sensors Installation Instructions

Addressable NAC Output Module D327A

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

EVO192 v3.0 Fire and Burglary What s New

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

MR-2602 Two Zone Fire Alarm Control Panel

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

IDP-Zone-6 Six Zone Interface Module

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Duct smoke housing, 2-wire D340/D340P

FireNET Fire Alarm Control Panel Installation Manual

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

SECTION OVERHEAD COILING FIRE DOORS FIREKING FIRE DOOR SERIES, MODEL 635

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

Signature Series Auto-Sync Output Module (CC1S)

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual

Operation & Maintenance Manual

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

Transcription:

MANUAL RESET ALARM RELEASE BOX (For 100~240VAC or 24VAC or 24VDC) INSTRUCTION MANUAL

WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device systems, maximum fire protection is provided when installed in accordance with factory specifications. 2. Installation and testing to factory specifications shall be performed by factory authorized personnel for proper operation in accordance with all of the latest National fire Protection Association (NFPA), Underwriters Laboratories (UL), National electrical Code (NEC), local, state, county, district and/or other applicable building and fire standards, guidelines, regulations and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). 3. To be performed by factory authorized personnel only. 4. Clear fire door opening and prohibit all traffic through door opening during testing of system! Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release mechanism before connecting to a fire door. INTRODUCTION The releasing device is a failsafe constantly energized solenoid mechanism. It is designed for use on rolling doors, single-slide and center-parting level and inclined track doors, which use gravity or spring tension to close during alarm release. Inside the mechanism, contact relays receive the alarm signal from the fire alarm control panel. When the unit receives the signal, the power to the solenoid is cut, releasing the fire door mechanism and hence close the fire door. The alarm signal can be Form C dry contact or 24VDC/VAC. Any interruption of power will release the solenoid mechanism. The release has a 10 second delay upon power failure and alarm, closed door detection capabilities, Form C relay outputs for the status of release box and 24VDC power output for door close warning. 1

SPECIFICATION Input Power Rating: 100~240VAC, 0.5A; 24VAC, 1.5A; 24VDC, 1.6A Alarm Dry Contact Rating: Lower Limit Microswitch Rating: 12.2 ohms max line impedance 12.2 ohms max line impedance Door Close Warning Power: 24VDC @Max. 0.5A Status Dry Contact: Frequency: Release Pull: Fuse: Rating: 24VDC/VAC, 0.5A Max. Resistive Load 50Hz or 60Hz 50 lbs (22.7kgs) F1: 2A@250V, Fast-Act Type *Input voltage [standby/full load* current]: 100~240VAC [0.15~0.1A/0.5~0.25A], 24VAC [0.6/1.5A] or 24VDC [0.2/1.6A] *Full load current only required for optional warning device(s). 24V input power can be 24VDC or 24VAC from power supply listed for fire, with regulated outputs. 18-gauge wire recommended. For Indoor Dry location use only. Close warning power is provided for less than a minute or from when alarm occurs until door reaches close limit. Any fire Listed audible device may be used. And not for connection to strobes or any other type of device that requires synchronization. Note: Door Close Warning Output is only functional when the box has input power. INSTALLATION WARNING Disconnect power supply before servicing. - For Indoor Dry location use only. All wiring must satisfy the most current version of NFPA72 National Fire Alarm Code and the National Electric Code. - 18-gauge wire is recommended. 2

INSTRUCTION & DRAWING 1. Actual configuration may differ. Must pull straight cable minimum 18 inches before turning (This unit may be rotated 90 degrees CW for a vertical pull.). See door manufacturer recommendations and NFPA 80 for use of this product with specific door. Must connect to fire alarm control panel or local smoke detector. 2. To be performed by factory authorized personnel only. 3. The release device shall be mounted on a vertical surface with chain end link exiting side of enclosure as illustrated on figure 1. The unit may be rotated 90 degrees CW for a direct vertical pull. AR-D Release Device Figure 1 4. Release device and associated hardware (if required) [sash chain or 1/16 cable, eyebolts, fusible links, turnbuckles] shall be installed as per door manufacturers recommendations (figure 1 typical installation configuration). Note should be taken that the end link direction of pull is perpendicular to the enclosure side. An eyebolt installed at a distance of 18 to 24 inches from the release device should adequately redirect sash chain pull as illustrated in figure 1. Please also see figure 2 for illustration. 3

Mounting Release Latch Connect release cable and fusible link if desired. Figure 2 "Set-Tie" Cable Lever "ARMED" (RELEASE) Remove Tag WARNING Disconnect power supply before servicing. 5. ELECTRICAL CONNECTIONS Installation of all wiring and connections shall be performed in accordance with, but not limited to, the latest NFPA, U.L. and N.E.C. standards. In addition, all installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material, wiring gauge related to power capacity requirements and circuit length and wiring methods. 6. Verify voltage rating of release device to power source being utilized. 7. Connect release cable and fusible link (if desired) as shown in Figure 2. 8. Connect power and alarm connection to the unit. 9. Remove the Set-Tie cable after power and alarm connection. Set-Tie cable mechanically secures release latch and must be removed to allow proper emergency operation of release device after installation is completed. NOTE: A trouble sounder will be activated if power is present, the latch is engaged, but the Set-Tie has not been removed and/or the lever is in the DIS-ARMED position. 4

WIRING WARNING Disconnect power supply before servicing. WIRE ROUTING Power Wiring 24VDC/VAC AR-D1 Alarm Dry Contact (N/C) Lower Limit Wiring Closing Warning Wiring (24VDC) Release Status Dry Contact Resistive Load Power Wiring Ground Release Plunger Power Strip TB1 + - POWER 12VDC 4142 3132323335363738 + - 100~240VAC L N 12VDC, 0.2A Max. Transient Voltage Surge Suppressors G AC Power Y Close Limit R Latch Released R Release Dis-Armed Alarm Release Test Button Note: Non-supervised. 5

TERMINAL CONNECTIONS WARNING Disconnect power supply before servicing. TB1 L N Input power 100-240VAC* See Note.6 CN2 41 42 31 32 33 35 (+) 36 (-) 37 38 Power 12VDC + - Input 24VDC/VAC Release dry contact *Note 4 *Note 6 Alarm Dry Contact (N/C) Max. Short circuit current 6mA, 14.7VDC. *Note 1 Door closing warning 24VDC, 0.5A Max. Regulated *Note 3 Lower Limit Microswitch (N/C) 3mA, 14.7VDC *Note 2 * Wirings on CN2 (35,36) and Power 12VDC (+,-) are limited to be connected within 20 feet in conduit. 12VDC output power, 0.2A Max. Special Application (See Page 10 for connection details) Compatibility ID: SD4W-1 *Note 5 * Notes: 1. Terminal 31&32 Building fire alarm panel needs to provide dry contact (N/C) connection or connect wiring to (N/C) 4-wire Class B initiating device loop with 12.2 ohms max line impedance. 2. Terminal 32&33 Use this connection to notify release device the status of the door. Field installation of microswitch/proximity sensor on the door or connection to an extra limit switch in the door operator is necessary to use terminal 32&33. When the door is already in its close position, a closed contact (N/C) can cause the release device not to release (12.2 ohms max line impedance). Power failure will still cause the solenoid to let go, hence resetting is necessary. 6

3. Terminal 35&36 This connection provides 24VDC, 0.5A power with 18AWG wire for maximum of 20 ft., when release device has been released. This can be used to provide power for warning devices. The warning power is provided for less than a minute or from when alarm occurs until door reaches close limit. The wiring connections are enclosed within conduit or equivalently protected against mechanical injury. 4. Terminal 37&38 These terminal connections will provide the status of this release device. When release device is in the standby mode, connection is open (N/O). When release device have been activated or released, connection would be in closed (N/C) state (12.2 ohms max line impedance). 5. Power 12VDC (+,-) 12VDC output power, 0.2A Max. In serial connection max. 4 detectors can be connected. 6. See connection chart for power inputs. Connection Chart Line In Low Voltage Alarm Connection Type Term: L & N Term: 41 & 42 (High Voltage) (24VDC or 24VAC) Must connect one or both power supplies Connect Dry Contact Signal Connect 24VDC or 24VAC 100-240VAC (Voltage supplied by FACP or an UL listed power supply) Power Alarm Signal Connect Alarm Signal (100~240VAC) 100-240VAC Do Not Connect Connect Alarm Signal Power Alarm Signal Do Not Connect 24VDC or 24VAC (24VDC/AC) (Voltage supplied by FACP) *Note: FACP Fire Alarm Control Panel. 7 Alarm Connection Term: 31&32 (Dry Contact) Connect FACP* Alarm Dry Contact (12.2 ohms max line impedance) Jump (Wire size min 18AWG) Jump (Wire size min 18AWG)

WIRING DIAGRAM 8

LIGHTS INDICATION AC Power Close Limit Latch Released Release Dis-Armed Alarm Release Test Button Release Status Light Normal Abnormal AC Power Close Limit Latch Released Release Dis-Armed Green LED G Power on Power off Yellow LED Y Door Not at Close Limit Door at Close Limit Red LED R Not Released Released Red LED R Armed Not Armed 9

CONNECTIONS OF INITIATING DEVICES AND ACCESSORIES Normally Close 4-wire Class B initial devices: A maximum of 4 4-Wire smoke detectors may be installed with this device. Field wiring shall consist of 18 AWG wiring. When using 4-wire smoke detectors with this device, electrical supervision can be provided by connecting a UL/ULC listed EOL relay. The suitable models of smoke detector for connecting to Loop SD4W-1. Manufacturer Model System Sensor 4W-B, 4WT-B, 4WTA-B, 4WTR-B, 4WTAR-B, 4WITAR-B, C4W-BA, C4WT-BA, C4WTA-BA, C4WTR-BA, C4WTAR-BA, BEAM1224 Use one model only for smoke detector circuit connections. Loop SD4W-1 wiring connections: 10

TESTING 1. Simulate an alarm condition and see if the solenoid disengages and releases the fire door. 2. Reset and simulate power failure to verify solenoid disengages, latch releases and fire door closes. RESETTING 1. Make sure power and alarm connection is normal. 2. Push the release latch all the way back into the slot. 3. Verify the solenoid is holding. Note: If the power or the alarm is not normal, solenoid will not hold. Hence the release latch will not stay in the slot. MAINTENANCE INSTRUCTIONS WARNING Disconnect power supply before servicing. Check the following items at the intervals listed: CHECK LIST DESCRIPTION EVERY 3 MONTHS EVERY 6 MONTHS Fasteners Check & tighten as required EVERY 12 MONTHS Drop-test Inspect door, drop-test for proper operation and full closure per NFPA-80 Inspect and service whenever a malfunction either door or release device is observed or suspected. Before servicing, always disconnect power supply to the release device. Replace fuses only with those of the same type and rating. All replacement parts must be obtained from the door manufacturer per NFPA-80. Testing of the release device is independent of, and shall in no way be interpreted as an alternative method of, testing of the fire alarm system, and/or any other system component employed on the fire door or counter fire door installation. TESTING SHALL BE PERFORMED AND WITHNESSED FOR PROPER OPERATION. 11