Slip resistance testing of GRP flooring surfaces for Anglia Composites Ltd

Similar documents
Slips: framing the issue

Slips and falls. OHS Exchange FDF - Willis. better information, fewer accidents. 22 nd September

Ceram Guide to Slip Resistance Tests

SAFETY ACTION NOTICE By arrangement with the NHSScotland Property and Environment Forum

Slips, trips and falls. National Metalforming Centre - February Steve Thorpe - HSL

SAIME. KaleidoSeries. 300x300,300x600,600x600&450x900mm Mat(R10CP4),Roc(R12P5)&Lappato. Bianco Beige Avorio. Cappucino Cenere Fango.

Flooring accessories in public buildings. Creating inclusive environments for the ageing population, with a focus on stair safety. A discussion paper

Infrastructure Technology

Slip Resistance Tests on Coated Panels. Duram. for. Date: 4th August Your Reference Number: Document Reference Number:

EC DECLARATION OF CONFORMITY. The manufacturer or his nominated representative established in the community;

CERTIFICATION OF EXPLOSIVES UNDER G.B. STATUTORY INSTRUMENT No. 2714

Australian/New Zealand Standard

Web:

SLIP RESISTANCE TESTING OF ENDURO-MESH PANEL

SAFETY TECH. RRL Pendulum Test >36 (wet test) EN Class DS Bacterial resistance

Global Safe Technologies (Australia) Pty Ltd

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA

TEST METHODS. Physico-chemical characteristics Slip resistance 1 Test methods

HOTEL MOTEL ENGINEER ASSOCIATION

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

CERTIFICATION OF EXPLOSIVES UNDER G.B. STATUTORY INSTRUMENT 2016 No 315

MGN 453 (M) Maritime and Coastguard Agency Logo MARINE GUIDANCE NOTE

Slipping properties of ceramic tiles / Quantification of slip resistance

Loss Prevention Standard

This document is a preview generated by EVS

BSc MBA EngD DMS PGCE CEng CSci CEnv FIMMM MIET MCMI. Confined Spaces. Mining. Rope Cableways

Furenflex RWV Advanced Liner

ANSI NFSI B101.0 Walkway Auditing Standard. Brent Johnson Traction Auditing LLC

Building Standards Division. Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems

SUMMARY. On completion of all of the five tests, general body concentrations of ozone gas within the room monitored were less than 0.01 ppm.

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

The Legal Obligations of Employers to Maintain all Electrical Installations in a Safe Condition

Ultrasonic Clamp-On Flow Meter Testing

Successful Installation. of PHOTOLUMINESCENT EXIT PATH MARKING SYSTEMS

Your specialist partner for total electrical compliance. Electrical Testing

Evaluation of Slip Potentials on Bilecik Beige Marble with Pendulum Method

REASONS FOR SPECIFICATION REASONS FOR SPECIFICATION. Polysafe Ultima - heavy-duty safety flooring with enhanced slip resistance

Introduction. Products conforming with a European Council Directive. CE marked construction products. Other regulations

Loss Prevention Standard

BS 476: Part 6: 1989+A1:2009

MARKET LEADERS IN LARGE SCALE COMMERCIAL CLEANING SERVICES

July 17, Dear Mr. Fields:

General Workplace Safety Checklist

Advanced Fire Rated Ductwork Solutions

Guide to Gate Safety Legislation & the Machinery Directive

EMERGENCY PREPAREDNESS & RESPONSE PROCEDURE

Testing coated fabrics

Guide to Gate Safety Legislation & the Machinery Directive. In Association with:

BS EN ISO : 2010

Cumberland Comprehensive Plan Town Council adopted August 2003, State adopted June 2004 TABLE OF CONTENTS

BEFORE THE CHRISTCHURCH REPLACEMENT DISTRICT PLAN HEARINGS PANEL

BS EN ISO : 2010

Appendix H. BGS BR211 Radon Report

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

Printing Ink Market in Russia to Market Size, Development, and Forecasts

Health & Safety Induction. Faculty of Engineering Dr Julie Etches Faculty Safety Manager & Advisor

AGT 1 Confined Space. Authorised Gas Tester 1. Scienco Limited. Authorised Gas Tester 1 1

NOTIFIED BODY NO: 0519 CERTIFICATE NO: ENB/B/035/17 Issue 7

Using Height Access Poles for Safe Testing Of Fire Detection Systems

Designed for possibilities. Made for people. Kitchens: floors and walls guide. Transforming spaces in kitchens, front and back of house. altro.co.

Electrical Safety Policy and Management System

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

Sliding Gates White Paper 1 Sliding Gate Safety Third Edition

Project Briefing Document. Section 3 Electrical Services design guide and specifications

New Approach vs Standards and Regulation: how it all works

Overhead Line Insulators

Loss Prevention Standard

Hardware for Sliding Doors & Folding Doors

Dangerous Assumptions

Cooker Fire Mitigation Device Assessment for Cheshire Fire and Rescue Service

Guide to Membership Assessments

Fire Risk Assessment

Fire Safety Management Audit Specification August 2017

Guide to interpreting Markings for Single Axis Fire Doors Hinges

Loudspeaker Test. Report

Remote Monitoring of Offshore Structures using Acoustic Emission.

Process Safety - Market Requirements. V.P.Raman Mott MacDonald Pvt. Ltd.

Fire Risk Assessment

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

Library of Birmingham integrated with The REP

Safety. Rubber Footwear. for professional use

SIGMADEK, LTD. FIRE TEST REPORT

MANSION A HAND-PICKED COLLECTION FOR LUXURY LIVING

Consumer unit replacement in domestic and similar premises

Charcon British Standard kerb

SAFETY ACTION NOTICE By arrangement with NSS Health Facilities Scotland

Slip resistance according to Goldilocks

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

Operating Instructions

Fire protection of cantilevered external steel balconies in multistorey flats - a case study.

HYGIENE SLUICE & GATES

Section 2 - Applications - General. Section 2A - FD30 Strebord 35+, 38+, 44 & Superpan with MDF & Wood Frames

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

The new fire regulations - more demands on the employer? The Regulatory Reform (Fire Safety) Order 2005

BS EN ISO : 2010

CENTRAL HOUSING GROUP LTD. General Property Standards Guide

Legal Requirements. There is no general legal requirement to install sprinklers. in places of work

Transcription:

Slip resistance testing of GRP flooring surfaces for Anglia Composites Ltd Author: Mark Liddle Report Number: ERG/18/05 HSL: HSE s Health and Safety Laboratory Enabling a Better Working World

Slip resistance testing of GRP flooring surfaces for Anglia Composites Ltd Report approved for issue by: Kevin Hallas BSc (Hons) Date of Issue: 5 th January 2018 Lead Author: Mark Liddle, BSc (Hons) Customer: Keith Bareham Technical Reviewer(s): Dave Riley BSc(Hons) FIEHF Editorial Reviewer: Dave Riley BSc(Hons) FIEHF Project number: PE08508 Disclaimer: This report and the work it describes were undertaken by the Health and Safety Laboratory under contract to Anglia Composites Limited. Its contents, including any opinions and/or conclusion expressed or recommendations made, do not necessarily reflect policy or views of the Health and Safety Executive. Crown copyright 2018 Page 1 of 12

EXECUTIVE SUMMARY This report presents the results of laboratory based slip resistance testing of four GRP flooring samples supplied by Anglia Composites Limited, at the request of Mr. Keith Bareham. Testing was carried out by Mr. Mark Liddle on the 23 rd January 2018. Slip resistance assessments were undertaken in accordance with the United Kingdom Slip Resistance Group (UKSRG) Guidelines, Issue 5, 2016, and BS 7976-2:2002+A1:2013 where appropriate, as recommended by the Health and Safety Executive. Measurements of the floor surface Pendulum Test Value (PTV) were made using a calibrated Munro Stanley pendulum instrument, with Slider 96 test rubber. Testing was carried out in three directions across the floor surface, with test direction 2 at 90 to test direction 1, and test direction 3 at 45 to directions 1 and 2. The results generated for all four flooring samples suggest that they would present a low slip potential in both dry and water contaminated conditions. The suitability of flooring should be determined by means of a risk assessment, which should take into account the level and type of pedestrian activity, the user demographic, the type of footwear, the type and prevalence of contamination, and the presence of any slopes. Page 2 of 12

CONTENTS 1 INTRODUCTION... 4 2 METHOD... 5 2.1 Evaluation of results... 5 3 RESULTS... 6 4 CONCLUSIONS... 10 5 REFERENCES... 11 6 APPENDIX... 12 Page 3 of 12

1 INTRODUCTION Slip, trip or falls remain a significant contributor to the risk of injury or ill health at work. Recent statistics for Great Britain show that almost 60% of specified injuries to employees were due to a slip, trip or fall on the same level, or a fall from height (HSE, 2016). This report presents the results of slip resistance testing of four GRP flooring samples supplied by Anglia Composites Ltd. Testing was carried out by Mr. Mark Liddle on the 23 rd January 2018. Page 4 of 12

2 METHOD Four different samples of GRP flooring were supplied by Anglia Composites Limited for testing, the details of which are presented in Table 1. Photographs of each sample are presented in section 3. HSL I.D. FAL/18/1 FAL/18/2 FAL/18/3 FAL/18/4 Table 1 Floor surfaces supplied for testing Sample details GRP grating with aggregate on walking surface GRP plate with aggregate on walking surface GRP stair tread and nosing with aggregate on walking surface GRP insert strips with aggregate on walking surface Slip resistance assessments were undertaken in accordance with the United Kingdom Slip Resistance Group Guidelines, Issue 5.0 (UKSRG, 2016) and BS 7976-2:2002+A1:2013 where appropriate, as recommended by the Health and Safety Executive (HSE) (HSE, 2012). Measurements of the floor surface Pendulum Test Value (PTV) were made using a calibrated Munro Stanley pendulum instrument (TE507). The test rubber used was Slider 96, which is considered to be representative of a shoe sole with moderate slip resistance. The test rubber was conditioned in accordance with the requirements of the UKSRG Guidelines prior to testing each surface. Testing was carried out in three directions across the surface, with test direction 2 at 90 to test direction 1, and test direction 3 at 45 to directions 1 and 2. Measurements were carried out in the clean, dry condition, and under the water contaminated condition. The GRP insert strips were approximately 52 mm wide and so multiple strips were positioned side by side to create a test area large enough to accommodate the pendulum footprint. Verification of the pendulum was undertaken immediately prior to testing to ensure the reliability of the pendulum data. Details of the verification procedure and results are given in Appendix A. 2.1 EVALUATION OF RESULTS The pendulum test results were interpreted in accordance with the classification system for slip potential used by the UKSRG, which is based on research undertaken by the Building Research Establishment (Pye and Harrison, 2003). Table 2 presents the UKSRG slip potential classifications and how they relate to PTV. Table 2 Slip potential classifications on a level surface PTV Slip Potential 0 24 High 25 35 Moderate 36 + Low The classifications shown in Table 2 apply to normal walking on a level surface. Sloped surfaces and activities such as rushing, turning, pushing or pulling, are likely to require a higher level of friction than normal walking. Other factors, such as the level and type of pedestrian activity and user demographic (such as age and physical ability) also have an influence and an assessment of the slip risk should be conducted in all situations. Page 5 of 12

3 RESULTS HSL Sample I.D. FAL/18/1 Sample details Table 3 Pendulum test results for FAL/18/1 GRP grating with aggregate on walking surface Slider Test Condition Test Direction PTV Slip Potential on level 1 84 Low Clean, dry 2 88 Low 96 3 82 Low 1 79 Low Water contaminated 2 78 Low 3 74 Low Page 6 of 12

HSL Sample I.D. FAL/18/2 Sample details Table 4 Pendulum test results for FAL/18/2 GRP plate with aggregate on walking surface Slider Test Condition Test Direction PTV Slip Potential on level 1 71 Low Clean, dry 2 68 Low 96 3 73 Low 1 67 Low Water contaminated 2 67 Low 3 73 Low Page 7 of 12

HSL Sample I.D. FAL/18/3 Sample details Table 5 Pendulum test results for FAL/18/3 GRP stair tread and nosing with aggregate on walking surface Slider Condition Test Direction PTV Slip Potential on level 1 66 Low Clean, dry 2 67 Low 96 3 68 Low 1 63 Low Water contaminated 2 62 Low 3 63 Low Note: Testing was undertaken on the black tread area, as opposed to on the nosing. Page 8 of 12

HSL Sample I.D. FAL/18/4 Sample details Table 6 Pendulum test results for FAL/18/4 GRP insert strips with aggregate on walking surface Slider Condition Test Direction PTV Slip Potential on level 1 78 Low Clean, dry 2 77 Low 96 3 77 Low 1 75 Low Water contaminated 2 74 Low 3 69 Low Note: Multiple strips were positioned side by side (as shown above) to create a large enough test area to accommodate the pendulum footprint. Page 9 of 12

4 CONCLUSIONS The results of the testing suggest that all four samples will present a low slip potential in the clean, dry and water contaminated conditions. It should be noted that low slip potential presented by the GRP insert strips (FAL/18/4) is based on results generated when the strips are placed side by side with minimal gaps, to maximise contact with the pendulum slider. This however may not reflect how the strips will be used. If there is spacing between the GRP strips large enough for a pedestrians foot to make contact with the substrate to which they are attached, the slip potential of the walking surface will be influenced by the slip resistance of the substrate. The suitability of flooring should be determined by means of a risk assessment, which should take into account the level and type of pedestrian activity, the user demographic, the type of footwear, the type and prevalence of contamination, and the presence of any slopes. Page 10 of 12

5 REFERENCES British Standards Institution, (2002), BS7976-2:2002+A1:2013, Pendulum Testers Part 2: Method of Operation, British Standards Institution, London. Houlihan, R., (2008) Novel slip characteristics of conglomerate tiles, HSE Research Report RR653. HSE, (2012), Assessing the slip resistance of Flooring, A technical information sheet, http://www.hse.gov.uk/pubns/geis2.htm, Health and Safety Executive, last accessed 3/5/2017. HSE, (2016), Kinds of Accident in Great Britain 2016, http://www.hse.gov.uk/statistics/causinj/kindsof-accident.pdf, Health and Safety Executive, last accessed: 28/04/2016. Pye, P.W., and Harrison, H.W., (2003), BRE Building Elements: Floors and flooring - performance, diagnosis, maintenance, repair and the avoidance of defects. BRE Report 460, 2003. United Kingdom Slip Resistance Group (UKSRG), (2016), The Assessment of Floor Slip Resistance - The UK Slip Resistance Group Guidelines, Issue 5.0 October 2016, The United Kingdom Slip Resistance Group. Page 11 of 12

APPENDIX A: VERIFICATION TESTS 6 APPENDIX Verification of the pendulum was carried out according to the UKSRG Guidelines by making measurements on three surfaces in the water contaminated condition: 1. A 3M 216X 3 m Pink Lapping Film surface (PLF). 2. A float glass surface. 3. A Pavigrés vitrified ceramic tile (HSL ID FAL/17/62, PTV = 35). The PTV range required to meet the verification requirements for each surface and the results are shown in Table A.1. Table A.1 Verification conditions and the required PTV range Surface Test Condition PTV Verification Range Measured PTV Pink Lapping Film Water contaminated 59-64 62 Float Glass Water contaminated 5-10 6 Pavigrés Ceramic Tile Water contaminated 32-36 36 Page 12 of 12

HSL: HSE s Health and Safety Laboratory is one of the world's leading providers of health and safety solutions to industry, government and professional bodies. The main focus of our work is on understanding and reducing health and safety risks. We provide health and safety expert advice and consultancy, research, specialist training and products. At HSL, we have been developing health and safety solutions for over 100 years. Our long history means that we're well placed to understand the changing health and safety landscape, and anticipate future issues. We employ over 450 scientific, medical and technical specialists, including occupational health and risk management experts to help our clients manage a wide range of issues in workplace health and safety. ISO 9001 ISO 14001 OHSAS 18001 Health and Safety Laboratory Harpur Hill Buxton Derbyshire SK17 9JN UK www.hsl.gov.uk T : +44 (0) 1298 218000 E: hslinfo@hsl.gsi.gov.uk Page 13 of 12