Installation Manual. Wiegand Interface Unit Two-State (WIU-2) North America T F Asia T F

Similar documents
Installation Manual. Wiegand Interface Unit Four-State (WIU-4) North America T F Asia T F

Transition 500-PIV Series Multi-Technology Readers Installation Manual

TruVision Bullet IR Camera Pocket Guide

TruVision Bullet IR Camera Pocket Guide

KM300 Carbon Monoxide Detection System Installation Manual

RMS/RPX Reader. User Manual

Model SWH-3000 Proximity Multi-Frequency 125KHz & 13.56MHz (Fixed) Reader Installation Guide. Version A0 Part Number UM-102 September 2005

Model SWH-4000 Multi-Technology Mullion 125 KHz and MHz (Flex) Reader Installation Guide. Version A0 Part Number UM-104 September 2005

TruVision IR Turret Camera TVT-2202/TVT-4202 Installation Guide

R Series Remote Annunciators and Expander Installation and Operation Guide

FTP-1000 Touchpad/Display Installation Manual

IFS Fiber Module Installation & Operation Instructions

IFS Fiber Module Installation & Operation Instructions

IFS Fiber Module Installation & Operation Instructions

INSTALLATION GUIDE. AXIS A1001 Network Door Controller

VT1101M VT1102M IFS Fiber Module Installation & Operation Instructions

IFS Fiber Module Installation & Operation Instructions

IFS Fiber Module Installation & Operation Instructions

IFS Fiber Module Installation & Operation Instructions

KFP-CF Series Operation Manual

IFS Fiber Module Installation & Operation Instructions

ATS1235 Advanced Wireless DGP on 868 MHz AM Installation Sheet

IFS SFP Tranceivers User Manual

TruPortal Wireless Locks Quick Reference

IFS Fiber Module Installation & Operation

UNC100 Integra Manual

FEC403EN Installation Manual

Advisor Advanced User Guide

RCR-REX Request-to-Exit Dual Technology Motion Sensor Installation Guide

3M Benchtop Air Ionizer 963E. User s Guide

4100U City and Relay Cards Installation Instructions

SIGA-CC1 Single Input Signal Module Installation Sheet

HP Power Distribution Unit with Power Monitoring (Models S124 and S132) User Guide

safety & regulatory information

HARDwired Installation/ Owner s Manual

NetworX NX-548E Receiver Installation Instructions

Networked Access Control Panel. Installation Guide

GE Security. Challenger V8 & V9. User Manual

IR Speed Dome. Quick Guide UD.6L0201B1357A01

VS-AXESS-4DLX Installation Manual

DS-K2600 Series. Access Controller. Quick Start Guide UD01216B-A

Figure 1. These Installation Instructions -1- K4866 4/00 OmniProx Reader Model Series OP-10/20/30/40

KT-100 Door Controller

GE Security. ATS1250/ door DGP / 4-lift DGP. Installation guide

KTD-348 Crosspoint 32 Matrix Video Switcher

1X-F Series Installation Manual

Operation and Maintenance Manual

ZP2 Series Operation Manual

Rev D 3/20/17

R-Series Remote Annunciators and Expanders Installation and Operation Guide

Installation Instructions

The system should also be capable of recording events automatically on any compatible DVR and should be able to retrieve recordings based on events.

UC-331-UCX Dual Path Communication Module. Quick Start Guide

(EN) RevC AS610-AS630 Outdoor Siren Installation Sheet.pdf. Remark: Rev. Date: Modif. no.

ATS125x/1260 Four- Door/Four-Lift DGP Programming Guide

/9308 External Battery Chargers Installation Instructions

POINTEK CLS 100 OINTEK CLS 100 CAPACITANCE LIQUIDS/SOLIDS. Instruction Manual March 2001

PDU Power Distribution Unit for IP-NINJAR. User s Guide Ver

ARCHITECTURAL DOOR HARDWARE KEY PADS & CARD READERS CATALOG

Product Manual. TZ Analog Sensors. TZ Sensors 8115CF 8116CF 8117CF 8118CF. Date: January 2015 Document Number: _B

Installation Guide for models:

NX-181xx NetworX Voice keypad with touch buttons User Manual

Table of contents. Metra WBC-WBI RFID ISO Module - Technical Manual. Page 2

Network Camera. Quick Guide DC-T1233WHX. Powered by

Booster Power Supply Manual

Independent Zone Control (I.Z.C.)

Long Range Radio Alarm Transmitter

GETTING STARTED GUIDE NI TC, ±78 mv, 24 Bit, 75 S/s Aggregate

C-Bus Four Channel Analogue Output Unit Installation Instructions

Series. Access Power Controllers. Installation Guide

User Guide. Luxxor. 35 LED Light Source Fax: Tremont Street, Rochester, New York gradientlens.

GETTING STARTED GUIDE NI RTD, 0 Ω to 400 Ω, 24 Bit, 400 S/s Aggregate, PT100

Installation Guide for models:

Long Range Radio Alarm Transmitter

International ECO Door Controller Installation Guide

SAFETY INFORMATION AND WARNINGS

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

GETTING STARTED GUIDE NI DIO, 5 V/TTL, Bidirectional, 7 μs

Remote Booster Power Supply Technical Reference Manual

Access Control Solutions

CV-350 TCP/IP Access Control System. System Overview

C-Bus 2 Channel Bus Coupler with Remote LED Facility Installation Instructions

Limitations of the Alarm System or Device

Greentrol Automation, Inc.

UBC Technical Guidelines Section Edition Access Control Page 1 of 5

Premier External TD. Installation Manual INS352-3

METEOROLOGICAL INSTRUMENTS

SEE DISCLAIMER ON REVERSE

ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.

WSD-E WHEEL DETECTOR QUICK REFERENCE GUIDE JUNE 2016 DOCUMENT NO. SIG-QG VERSION A

APC BC300 Series 40kW 208/450/480V User Guide

GETTING STARTED GUIDE NI DI, 30 V, Sourcing, 7 μs

Controllers. Centralization of Access Control Devices Made Easy. Installer Guide

Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design SBS-H2. Hydrogen Gas Detector Kit

VX SERIES Wireless Thermostat with Occupancy Sensor

Planning Elevator Relay Groups Programming Millenium for Windows Software

Approvals, Safety Instructions, and Statutory Information

COMSPHERE 48 Vdc CENTRAL OFFICE POWER UNIT

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

TX3 Series TX3-CX-1. Installation Manual

Transcription:

North America T 888 437 3287 F 561 998 6224 Asia T 65 639 19314 F 65 639 19306 Wiegand Interface Unit Two-State (WIU-2) Installation Manual Australia T 61 3 9239 1200 F 61 3 9239 1299 Canada T 800 267 6317 F 613 737 5517 EMEA T 48 58 326 22 40 F 48 58 326 22 41 Latin America T 503 885 5700 F 561 994 6572 Email: rs-bctsupport@fs.utc.com Web site: www.utcfireandsecurity.com 2011 UTC Fire & Security. All rights reserved. UTC Fire & Security, 9 Farm Springs Road, Farmington, CT 06034-4065, USA 460579001G, June 2011

Copyright Disclaimer Trademarks and patents Intended use FCC compliance 2011 UTC Fire & Security. All Rights Reserved. This document may not be copied in whole or in part or otherwise reproduced without prior written consent from UTC Fire & Security, except where specifically permitted under US and international copyright law. The information in this document is subject to change without notice. UTC Fire & Security assumes no responsibility for inaccuracies or omissions and specifically disclaims any liabilities, losses, or risks, personal or otherwise, incurred as a consequence, directly or indirectly, of the use or application of any of the contents of this document. For the latest documentation, contact your local supplier or visit us online at www.utcfireandsecurity.com. This publication may contain examples of screen captures and reports used in daily operations. Examples may include fictitious names of individuals and companies. Any similarity to names and addresses of actual businesses or persons is entirely coincidental. The Wiegand Interface Unit Two-State (WIU-2) name and logo are trademarks of UTC Fire & Security. Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products. Use this product only for the purpose it was designed for; refer to the data sheet and user documentation for details. For the latest product information, contact your local supplier or visit us online at www.utcfireandsecurity.com. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. You are cautioned that any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. Regulatory 2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: www.recyclethis.info. Manufacturer Contact information UTC Fire & Security HQ and regulatory responsibility: UTC Fire & Security, 9 Farm Springs Road, Farmington, CT 06034-4065, USA For contact information see our Web site: www.utcfireandsecurity.com

i Contents Introduction..........................................1 Safety...............................................2 Radio interference...................................2 Electrostatic discharge (ESD) precaution.................2 Product features.......................................3 System requirements...................................4 Technical specifications................................5 Parts list.............................................6 Installation overview...................................6 Mounting the WIU-2....................................7 Configuring the WIU-2..................................8 J1: Reader interface connector........................10 J2: Controller interface connector......................11 J3: Two-state reporting connector.....................11 J5: Reserved......................................11 J6: HID reader supervision...........................11 Connecting the WIU-2.................................12 Wiring diagrams...................................13 Testing the WIU-2.....................................15 Troubleshooting the WIU-2.............................16 Regulatory approvals.................................16 UL..............................................16 CE..............................................17

ii Wiegand Interfact Unit Two State (WIU-2) Installation Manual Figures Figure 1. Mounting instructions...7 Figure 2. WIU-2 connectors and jumpers...9 Figure 3. Sample WIU-2 configuration...12 Figure 4. WIU-2 to M5 8RP Interface...13 Figure 5. WIU-2 to M2000PX or M2000PXN Interface...14

Introduction 1 Introduction The Wiegand Interface Unit - Two State (WIU-2) board is installed between a controller and an access control reader. When users present their credential (card, key fob, fingerprint, etc.) to the reader, the WIU-2 converts Wiegand badge identification (BID) data into the F/2F protocol and sends it to the controller. The access control system then grants or denies access to the secure location. The Wiegand Interface Unit-Two State (WIU-2) board features a Wiegand data converter, which can accommodate both conventional and proprietary Wiegand reader protocols, and includes a 2 Amp relay for door strike control (entrance/exit) activity. With the WIU-2 card, any organization can quickly add a wide range of Magnetic Stripe, Wiegand, Proximity, Mifare, and Biometric readers to any UTC Fire & Security access control system. To minimize installation efforts, the door contact and request-to-exit (REX) input circuitry connects directly to the WIU-2 to avoid the high cost of home-running cables back to the controller.

2 Wiegand Interface Unit Two State (WIU-2) Installation Manual Safety Radio interference WARNING: This is an FCC Class A product. In a domestic environment, this product may cause radio interference, in which case, the user may be required to take adequate measures. Electrostatic discharge (ESD) precaution WARNING: Circuit board components are vulnerable to damage by electrostatic discharge. ESD can cause immediate or subtle damage to sensitive electronic parts. An electrostatic charge can build up on the human body and then discharge when you touch a board. A discharge can be produced when walking across a carpet and touching a board, for example. Before handling any board, make sure you dissipate your body s charge by touching ground. This discharges any static electricity build-up.

Product features 3 Product features The WIU-2 is designed to provide the following functions: Supports a wide range of Magnetic Stripe, Wiegand, Proximity, Mifare, and Biometric readers that employ Wiegand data formats Converts both traditional and custom Wiegand BID formats to F/2F supervised protocol Centralizes wiring connections for remote access control readers, door strike hardware, door contact, and request-to-exit (REX) circuitry Includes a heavy-duty 2 Amp door strike relay Supports up to 24 VAC or 30 VDC door strikes Connector compatible with popular 2-state interface adapters Note: The WIU-2 does not support keypad reader output formats.

4 Wiegand Interface Unit Two State (WIU-2) Installation Manual System requirements For UL compliant installation notes, refer to UL Listed Installations on page 16 Host software Controllers Readers Wiegand data formats Secure Perfect Edition 3.0 or later Picture Perfect 1.7 or later FCWnx M5PX with 2RP or 8RP M5PXN with 2RP or 8RP M5PXNplus with 2RP or 8RP M2000PX M2000PXN M2000PXNplus M3000PXNplus with 2RP or 8RP Formats up to 40 bits 26-bit 32-bit 35-bit Corporate 1000 37-bit 40-bit formats

Technical specifications 5 Technical specifications For UL compliant installation notes, refer to UL on page 16. Operating temp. range -32 o F to +150 o F (-35 o C to +66 o C) Relative humidity Physical dimensions (HxWxD) Index of protection Input voltage range Power consumption Cable specifications a Maximum cabling distance WIU-2 to controller: b WIU-2 to Reader: c Door strike relay d 5% to 95% (non-condensing) 3.25" (82.55 mm) x 1.85" (46.99 mm) x 0.644" (16.35 mm) IP00 9 to 16 VDC 25 ma @ 12 VDC (no reader attached) Belden 8725 or equivalent, 20 AWG minimum 1000 ft (304.8 m) @ 12 VDC with 20 AWG cable 250 ft (76.2 m) @ 12 VDC with 20 AWG cable 2.0 A @ 30 VDC maximum Agency approvals FCC Class A part 15 CE UL 294 a. UTC Fire & Security recommends using shielded cable for all installations. b. WIU-2 to Controller: The maximum cabling distance of 1,000 ft (304.8 meters) is influenced by wire gauge, reader power requirements, and the 12 VDC level from the controller. c. WIU-2 to Reader: The maximum cabling distance of 250 ft (76.20 meters) is influenced by wire gauge, reader power requirements, minimum input voltage at the reader when using the 12 VDC from the WIU-2 (originally from the controller), and the cabling between the WIU-2 and controller. d. The life of the relay decreases as the current switched by the contacts is increased. Use low current door strikes to maximize the relay life. Use an external relay for high current or high traffic applications.

6 Wiegand Interface Unit Two State (WIU-2) Installation Manual Parts list WIU-2 Hardware Kit Installation Manual Refer to the UTC Fire & Security product catalog for part numbers and ordering information. Installation overview The following is the general sequence of steps to follow when installing the Wiegand Interface Unit-2. Each step is explained in further detail in the sections that follow: 1. Mount the WIU-2. Refer to Mounting the WIU-2 on page 7. Note: The WIU-2 must be mounted indoors, in a protective enclosure or standard 1-gang electrical box (installer supplied) as shown in Figure 1. 2. Configure the WIU-2. Refer to Configuring the WIU-2 on page 8. 3. Connect the WIU-2. Refer to Connecting the WIU-2 on page 12. 4. Test the WIU-2. Refer to Testing the WIU-2 on page 15.

Mounting the WIU-2 7 Mounting the WIU-2 Figure 1. Mounting instructions 1. To mount the WIU-2 board in the single gang electrical box, first remove the electrical box cover and clean it with the alcohol wipes provided in the mounting hardware kit. 2. Apply the four standoffs, provided in the mounting hardware kit, to the four corners of the WIU-2 board, as shown in Figure 1. 3. Remove the adhesive liner on the standoffs and attach the WIU-2 board to the electrical box cover, making sure the WIU-2 board does not interfere with or touch the sides of the electrical box.

8 Wiegand Interface Unit Two State (WIU-2) Installation Manual Configuring the WIU-2 The following connectors and jumpers make up the Wiegand Interface Unit-2: J1: Reader Interface Connector J2: Controller Interface Connector J3: 2-State Reporting Connector J5: Reserved J6: HID Reader Supervision

Configuring the WIU-2 9 Figure 2. WIU-2 connectors and jumpers J2 J6 J3 J1

10 Wiegand Interface Unit Two State (WIU-2) Installation Manual J1: Reader interface connector The 10 pin connector J1 is the reader interface connector. J1 is used to connect a Wiegand output device to the WIU- 2. Table 1. PIN J1: Reader interface connector Description 1 Door ground (return) 2 Door input 3 REX ground (return) 4 REX input 5 Wiegand Data 1 6 Wiegand Data 0 7 Door DO/LED control Used to control door strike and activate green LED 8 Beeper Signal switches to ground to activate the beeper 9 Ground 10 12 VDC fused power, 250 ma maximum.

Configuring the WIU-2 11 J2: Controller interface connector The 7-pin connector J2 is the controller interface connector. J2 is used to connect controller power and data signals to the WIU-2. Table 2. J2: Controller interface connector PIN Description 1 12 VDC power for WIU-2 2 Ground 3 Door DO/LED control Used to control door strike and activate green LED 4 Reader F/2F Data 5 Strike NC 6 Strike Common 7 Strike NO J3: Two-state reporting connector The 2-pin connector J3 is the 2-state reporting connector. By default, this connector is jumpered to enable 2-state reporting. Remove the jumper to disable 2-state reporting. J5: Reserved The 2-pin connector J5 is reserved. J6: HID reader supervision The 2-pin connector J6 is the HID reader supervision connector. By default, this connector is not jumpered and HID reader supervision is disabled. Place a jumper over this connector to enable HID reader supervision.

12 Wiegand Interface Unit Two State (WIU-2) Installation Manual Connecting the WIU-2 Connect the WIU-2 between the controller and access control reader as indicated in Figure 3. It is important to ensure all connections are made prior to applying power. Figure 3. Sample WIU-2 configuration Typical controller (M5 shown) WIU-2 Typical Wiegand reader

Connecting the WIU-2 13 Wiring diagrams Figure 4. WIU-2 to M5 8RP Interface

14 Micro/ SianaiName Pin P~-2000, +12VDC 1 P~N-2000 Ground 2 M200(). P~NPius Data.J4-J7 I Door IXlllleaeler L 0! f-x.. lnstjjii1n5817 Blocking Diede as shown. Locate awcy from ""'der an secure side of door. ~.,... Pin Sianal Name 1 +12VOC 2 Ground 3 DaorOO WIU- 4 Datil J2... r- Cable Shield 5 Strike Rela - NC r- Use 20 AWG shielded cable,..---- 6 Strike Rela - common 1 +--- 7 ~Yikl! Rea -N I I ~ See strike manufacture~_--:-----< ) installation instructions for conductor size AWG Connect protection deoice J w~ 2.:--: :~o Jl ~Q.!!I' ~~... ~cable splice to Reader pigtail Signal Name Pin Pigtail Wire Color Sianal Name +12VOC 10 Red 12VOC Ground 9 Black Ground Beeoer B 7 Oren e Door 00!Green LED Centro DataO 6 Green DataO I In Ugh!,..., Vel low Beeoer I Wjlfl across strike =--. I Data 1 5 l strlke ~ I EKitDI(Re>l+l ~~~.J.L _j EKit 01 Return IReK-1 3 f---.. - Door Dl (DC+) 2 Door Dl Return DC- 1 4'SJ Door or E>cit Dl's J Drain Wire T-SlO< Reader Figure 5. WIU-2 to M2000PX or M2000PXN Interface Wiegand Interface Unit Two State (WIU-2) Installation Manual ~Strike PowerSuppl ~ 2 ProYide cunrent restriction deoice, less t11an 2 Amps through Controller Relay ~ l.j~ Normally Open oraosed Use plenum roted cable for applications where ooble is to be run aboye thefolse!suspended ceiling! in the air circulation space. 531.004001A

Testing the WIU-2 15 Testing the WIU-2 1. Verify the reader (J1) and controller (J2) connections are properly wired. 2. Verify that jumpers J3, J5, and J6 are set properly. 3. If a communications error occurs, when connected to a supervised HID reader, verify that jumper J6 has been removed. 4. If an incorrect badge ID (BID) displays on the host, check for crossed lines between the WIU-2 and the reader. See Figure 4, WIU-2 to M5 8RP Interface, on page 13. or Figure 5, WIU-2 to M2000PX or M2000PXN Interface, on page 14., as appropriate. 5. Do not jumper or short DO/LED (located on J2-pin3) to the Pin light (located on connector J1-pin7). For proper LED and pin light operation, wire as shown in Figure 4 and Figure 5 using diode provided.

16 Wiegand Interface Unit Two State (WIU-2) Installation Manual Troubleshooting the WIU-2 If the operation of a component is in doubt, substitute a known good component and retry the system. Always verify wiring against the wiring diagrams before powering up the system. Regulatory approvals UL UL Listed Installations The following are the results of the UL evaluation of the WIU-2 readers: Operating temperature range: +32 o F to +120 o F (+0 o C to +49 o C) Relative humidity: 85% For UL Listed installations, the WIU-2 must be mounted within the protected area of a protective enclosure.

Regulatory approvals 17 CE MANUFACTURERS DECLARATION OF CONFORMITY For Product identification: Model/type : WIU-2 BOM revision level : A Category (description) : Interface Board Brand : Manufacturer: UTC Fire & Security, Americas Corp., Inc 3211 Progress Dr. Lincolnton, NC 28092 USA EU Representative: Concerning A sample of the product has been tested by: Test report reference UTC Fire & Security B.V. Kelvinstraat 7 6003 DH Weert The Netherlands RTTE EMC Safety Radio PSE 12955 Bellamy Brothers Blvd. Dade City, FL 33525 PSE 12955 Bellamy Brothers Blvd. Dade City, FL 33525 07F260I 03F246C Applied standards EN50130-4(1995) +A1(1998) +A2(2003) EN 55022 (2006) Equipment class identifier (RF products falling under the scope of R&TTE) x Not Applicable None (class 1 product) (class 2 product) Means of conformity We declare under our sole responsibility that this product is in conformity with Directive 1999/5/EC (R&TTE), 2004/108/EC (EMC), 2006/95/EC (LVD), and 93/68/EEC (Marking) based on test results using harmonized standards in accordance with the Directives mentioned Signature of representative/manufacturer: Rafael Martinez Compliance Leader, Access 791 Park of Commerce Blvd, Suite 100 Boca Raton, Fl 33487 Place : Boca Raton Date : 11 June 2011 Page 1 of 2

18 Wiegand Interface Unit Two State (WIU-2) Installation Manual Model listing (list of all product variants or models for which this declaration is valid) Model BOM revision level WIU-2 2-state Wiegand Interface Unit, 430187001 A Signature of representative/manufacturer: Rafael Martinez Compliance Leader, Access 791 Park of Commerce Blvd, Suite 100 Boca Raton, Fl 33487 Place : Boca Raton Date : 11 June 2011 Page 2 of 2