Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, August 2015

Similar documents
DX Units. Ranging from 15 to 750 tons and 1,000 to 300,000+ CFM

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

INTRODUCTION. Heat Pipe Technology, Inc. The Heat Pipe Principle. Recent Heat Pipe Development

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Benefits Offered by Passive Dehumidification Wheel Speed Control

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Dehumidifying with Dedicated Outdoor Air

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

100% Outdoor Air Dehumidification Methods

Energy Recovery Ventilation

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

DES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY

Armstrong Cool-Fog Systems

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

Appendix 13. Categories of Cooling and Heating systems

Section 4 of 6 DOAS Core Technologies

Heat Recovery Units. Heat Recovery 1

Achieving Dry Outside Air in an Energy-Efficient Manner

Two essential attributes of mechanical systems intended to

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

DADANCO Technical Paper

Trane CDQ Desiccant Dehumidification

Heat pump and energy recovery systems

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

HEALTHCARE SURGERY VENTILATION HUMIDITY CONTROL

CHAPTER 4. HVAC DELIVERY SYSTEMS

Munters Heat Exchangers

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks

Dehumidification: Energy Efficiency Comparisons

Adding More Fan Power Can Be a Good Thing

EP SERIES PACKAGED ENERGY RECOVERY SYSTEM ENERGY EFFICIENT AIR COMFORT

HEAT RECOVERY & POWERED VENTS

REFRIGERANT AND WATER HEAT PIPES D E H U M I D I F I C A T I O N

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Redesign of Bennett Hall HVAC System

DERV / ERV DEHUMIDIFICATION & ENERGY RECOVERY V E N T I L A T O R U N I T S I N N O V AT I O N W I T H S T Y L E

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative

ASCENDANT CONVENTIONAL COOLING, ACTIVE DESICCANT DEHUMIDIFICATION SYSTEM ASCENDANT LOW DEW POINT EFFICIENT & EFFECTIVE

ENERGY RECOVERY HEAT PIPE HEAT EXCHANGERS

Principles of Active Desiccant Operation. Presented by Tom Peterson, CEO and Founder. Climate by Design International

HONORABLE MENTION: COMMERCIAL BUILDINGS, EXISTING

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Dehumidification System Enhancements

Chilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.

Daikin Blueprint: Delivering Hot Water with a Chiller

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Department of Mechanical Engineering ME 322 Mechanical Engineering Thermodynamics

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Direct and indirect evaporative cooling

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

Psychrometric Engineering Applications

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Are uncontrollable humidity problems costing you a bundle?

INTELLIGENT SOLUTIONS FOR ADIABATIC COOLING IN DATA CENTERS

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

Pthey are comfortable. In regions with hot

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

BOOK 2 SPECIFICATIONS

A according to their application as (1) process-to-process, (2)

CONTROLLED CHILLED BEAM PUMP MODULE

Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

ENGINEERING AND CONSTRUCTION BULLETIN

ASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES

7. MECHANICAL SYSTEM DESIGN

Green Maintenance Needed to Keep HVAC Systems Green

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

Breathe Easy With. Out. Out 54 FINE HOMEBUILDING. COPYRIGHT 2014 by The Taunton Press, Inc. Copying and distribution of this article is not permitted.

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

Designing Energy Efficient Outdoor Air Systems

Liquid Desiccant Technology Delivers Energy Cost Reductions and Indoor Air Quality Improvements. White Paper

PoolPak MPK Series. PoolPak.com. Environmental Control Systems REDUCED FOOTPRINT & WEIGHT COMPARED TO EARLIER GENERATIONS

BOOK 2 SPECIFICATIONS

Efficient energy recovery in AHU. DOHA, Qatar Timo Schreck Enventus AB, Sweden

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

4-Pipe VAV vs. Active Chilled Beams for Labs

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

Chapter 14, Problem 27.

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series.

Transcription:

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, August 2015 Advised by Heat Pipe Technology

Background: HVAC systems are often designed to supply a constant discharge air temperature from an air handling system to maintain comfort in the space. Some HVAC systems, especially those that have strict space humidity requirements, should be controlled for a constant discharge air dew point temperature (or maximum discharge air dew point) in addition to controlling to a set discharge dry bulb temperature. Wrap-around heat pipe systems, especially controllable wrap-around heat pipe systems, can be an effective tool to help meet these strict space humidity requirements. Wrap-around heat pipe systems are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil. The upstream precool heat pipe shifts the excess sensible cooling capacity off the cooling coil while the downstream heat pipe provides reheat. Wrap-around heat pipes are passive devices that are driven by the difference in thermal energy between the entering hot air and the cold air leaving the cooling coil. This thermal energy affects a phase change of the refrigerant in the tubes which drives the flow of refrigerant between the two heat pipe sections. As warm air enters the precool heat pipe, refrigerant changes phase from liquid to vapor extracting heat from the air stream thus lowering the air temperature. Refrigerant then flows naturally to the reheat section where it condenses and releases the energy it absorbed from the precool section to the airstream in the form of sensible heat. The Challenge: HVAC systems with strict space humidity requirements typically need to provide air with a dew point that is lower than the dry bulb temperature. Operating rooms and many other applications fall under this category. For this article, let s consider another example:

A space with chilled beams is being served by a dedicated outdoor air system (DOAS). A typical DOAS unit uses an air-to-air heat exchanger to transfer energy between the supply and exhaust air streams, followed by a preheat coil, a cooling coil and supply fan(s). The chilled beams in this example require 55 degree air (the supply air dry bulb set point, SASP) with a maximum dew point of 48 degrees (the supply air dew point set point, SADP). In the typical DOAS system, the chilled water coil will cool the air down to the SADP (48 degrees) to remove the necessary moisture. However, reheat is then required to bring the dry bulb temperature up to 55 degrees, as 48 degrees is too cold for the space. By introducing a wraparound heat pipe, the heat pipe can be selected to help precool the incoming air, relieving sensible load from the cooling coil, then reheat the air from 48 degrees to 55 degrees, which is exactly what the space requires. Since the wrap-around heat pipe system is a passive device, there is no means to control the amount of reheat applied to the supply air stream. The heat pipe can only reheat with as much energy as is extracted from the air on the precool side. Therefore, if a heat pipe system is selected for a hot day, the heat pipe will underperform on a cool day when the entering heat energy is lower and supply colder air than is needed to the space. If a heat pipe system is selected for a cool day, the heat pipe will overperform on a hot day when the entering heat energy is higher, and supply warmer air than is needed to the space. The Solution: Enter the controllable wrap-around heat pipe. By installing solenoid valves on the refrigerant circuits of the wrap-around heat pipe, the building management system (BMS) can control the amount of refrigerant flow in individual circuits between the precool and reheat heat pipes, and thus effectively control the amount of reheat being applied to the airstream. In our example, if we select the heat pipe to supply 55 dry bulb/48 dew point air with a 65 degree entering air temperature, for any entering air temperature above 65 degrees, the BMS will stage the solenoid valves closed to prevent overheating of the discharge air. What about other entering outdoor

air/humidity scenarios? How would the system be controlled then? The following psychrometric charts portray all possible air condition scenarios and explain how each should most effectively be handled. Note: The air-to-air heat exchanger is assumed to transfer total enthalpy for ease of illustration; however the same principles could be applied to a sensible-only energy recovery device. OADP: Entering outdoor air dew point temperature OAT: Entering outdoor air dry bulb temperature SADP: Supply air dew point set point SASP: Supply air dry bulb set point RAT: Return air dry bulb temperature from the space to the DOAS 1. Cold and dry (OAT < SADP): This is normal heating mode, and the air-to-air heat exchanger and hot water coil will work to reach the supply air dry bulb set point temperature. The heat pipe will do nothing under these conditions.

2. Cool and dry (OAT < SASP and OAT > SADP and OADP < SADP): This case is for when the outdoor air temperature is between the supply air dew point and dry bulb temperatures, and the air is sufficiently dry to not require dehumidification. As in case 1, the air-to-air heat exchanger and hot water coil will work to reach the supply air dry bulb set point temperature. The heat pipe will do nothing under these conditions.

3. Warm and dry (OAT < RAT and OAT > SASP and OADP < SADP): This case sees the outdoor air temperature between the supply air set point and the return air temperature. Because the dew point is sufficiently low, dehumidification is not required, the heat pipe and air-toair heat exchanger can be turned off, and the cooling coil brings the entering air down to the supply air set point.

4. Cool to warm, but humid (OAT< RAT and OAT > SADP and OADP > SADP): The outdoor air temperature is between the return air temperature and the supply air dew point set point, but contrary to cases 2 and 3, the entering dew point temperature is sufficiently high to require dehumidification. In this scenario, cooling mode is enabled, but the air-to-air heat exchanger operates to bring the entering air temperature as close as possible to the return air temperature to maximize reheat effectiveness. Though this increases the cooling load, the additional reheat savings will outweigh that additional cooling penalty. The cooling coil will work to cool/dehumidify, and the heat pipe can be staged to meet the supply air dry bulb set point.

5. Hot and dry (If OAT > RAT and OADP < SADP): The outdoor air temperature is greater than the return air temperature, but because the outdoor air dew point is below the supply air dew point set point, dehumidification is not required. Cooling mode is enabled and the airto-air heat exchanger precools outdoor air. The heat pipe can be staged off and the cooling coil is used to cool down the air to the supply air dry bulb set point.

6. Hot and humid (If OAT > RAT and OADP > SADP): This scenario is for a typical summer day, when full cooling mode is enabled. The air-to-air heat exchanger precools outdoor air and the heat pipe/cooling coil work to cool/dehumidify/reheat supply air. Stage heat pipe solenoid valves closed as required to maintain supply air dry bulb set point. Conclusions: With proper application and control of wrap-around heat pipe systems, the example illustrated can be expanded to nearly any system with strict space humidity requirements. Even more common systems where humidity requirements aren t as strict can be accomplished the same way by simply raising the dew point line that separates Cases 1-2-3 from Cases 4-5-6. Although the example did not include mention of humidification requirements, the system can be used in conjunction with a humidification system to effectively raise the humidity in the airstream and space as required. Furthermore, it is worth noting that the larger the outdoor air (ventilation) requirement for the particular air handling system, the more effective the controllable wrap-around heat pipe system will be, as less return air means less opportunity to condition the air by mixing.

About Flow Tech, Inc.: Flow Tech, Inc. s mission is to provide the highest quality and most energy-efficient HVAC systems and products that directly affect how buildings operate. Serving the commercial, healthcare, education, research, pharmaceutical, and water and wastewater markets, we strive to maintain the utmost professional and educated team offering sales, support and on-call, 24/7 service. We are a full-service heating, ventilating and air conditioning (HVAC) equipment manufacturer s representative celebrating over 25 years of business and serving CT, Western Massachusetts and counties in New York. We pride ourselves in offering: The premier source of new VFD applications, retrofits and servicing all brands of existing VFDs The finest critical airflow control solution in the market providing a safe and energy efficient environment for the occupants to work. The highest quality custom built air handlers providing a dependable means for building owners to provide conditioned air to occupants. Multiple technologies of heat recovery allowing owners to run their buildings at peak efficiencies. A service department that is educated and experienced and provides a level of service that goes above and beyond customer expectations Our product lines include ABB variable frequency drives, Air Enterprises, Air Monitor Corporation, Aircuity, Heat Pipe Technology, M.K. Plastics, Phoenix Controls, Steril-Aire, TAMCO, Thermowheel, ToxAlert, Twin City Fans and VAW. Learn more at www.flowtechinc.com. About Heat Pipe Technology: HEAT PIPE TECHNOLOGY, INC. (HPT) is the innovation leader in energy recovery and dehumidification systems for commercial applications around the globe. Employing the very latest in passive heat transfer technology, HPT designs and supplies the core systems to the world's leading commercial air handling equipment manufacturers. Heat Pipe Technology, Inc. is recognized worldwide for our innovation and expertise. Our heat pipes are made right here in Tampa, Florida; they save energy and dramatically reduce heating and cooling costs. With a network of more than 70 representatives and licensees in North and South America, Europe, The Middle East, Asia, and Australia, HPT is a true global operator. Learn more at www.heatpipe.com.