Danfoss gas detection unit Type GD Heavy Duty

Similar documents
Danfoss gas detection units

Danfoss gas detection units

Recalibrate the way you look at gas detection

Danfoss gas detection Controller unit

Gas Detection Unit (GDU) GDA, GDC, GDHC, GDHF, GDH

Multi-Gas-Controller MGC2

Gas Detection Sensor type GDA, GDC, GDHC, GDHF, GDH REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Sensor unit MC2 with analog output for Freon gases and refrigerants

Two-Channel Gas Controller

Gas Controller Module GC-06

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Oxygen (O2) Single-Point Gas Detection System

Nitrogen Dioxide Stand-Alone Detector - Analog, ModBus

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Gas detecting sensor Types GDA, GDC, GDHC, GDHF, GDH

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours

PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases

Carbon Monoxide (CO) Gas Detectors with (0)2-10 Vdc or (0)4-20 ma Output

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

Gas Central with built-in Gas Detector for Nitrogen Dioxide (NO 2

Dräger Polytron 8000 Stationary gas detector (EC)

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

Dräger Polytron 5700 IR Detection of flammable gases and vapours

Dräger Polytron 8310 IR Detection of flammable gases and vapour

Carbon Monoxide Transmitter

Dräger Polytron 5200 CAT Detection of flammable gases and vapours

Sensepoint. Fit For Purpose Flammable, toxic and Oxygen versions available High performance, low cost Suitable for new and retro fit applications

Ammonia Leak Detector Manual

User Manual. PolyGard Gas Controller MGC3. Two-Channel Analog Gas Controller Serial Number _E _0907. September 2007

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006

Carbon Monoxide CO Transmitter ADT-X3-1110

Combustible Gas Detection and Control System

OLCT 700 & 710. Certifications FIXED GAS DETECTION. Better detection. Better protection.

PolyGard 2-channel Gas Controller MGC-03

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

Remote alarm indicator and test combination MK2430

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

Carbon Monoxide (CO) Gas Detector March 15 GCO 300

Dräger X-am 7000 Multi-Gas Detection

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

P R O D U C T D ATA S H E E T

Dräger Polytron 5100 EC Detection of toxic gases and vapors

Dräger Polytron 8700 IR Detection of flammable gases and vapors

Dräger Polytron 8200 CAT Detection of flammable gases and vapors

Sensepoint. Fit For Purpose Flammable, toxic and oxygen versions available High performance, low cost Suitable for new and retro fit applications

Inc Series Digital Gas Detector/Controller. Operation Manual

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

YOUR PARTNER IN FIRE & GAS DETECTION

Snifter ATEX22 VERSION. User Manual. Distributor

Dräger Polytron 8310 Stationary gas detector (DSIR)

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen

QD6310. Fixed Gas Detector Operation Manual

Improve Performance and Reduce Maintenance Costs. Model Q45D. Dissolved Oxygen Monitor...

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

Gas detectors for Industrial Refrigeration: Safety, efficiency and peace of mind

Crowcon XgardIQ. Intelligent Gas Detector and Transmitter. Installation, operating and maintenance instructions M070030/SF

Product Manual SZ1144

Dräger Polytron 5200 CAT Detection of flammable gases and vapours

TOC-20 SERIES. Refrigerant Gas Monitor. Installation and Operation Manual Version 3 IGD OLIVER CH4 NO. Document Ref: T20-V3

MODEL 9010/9020 LCD CONTROL UNIT

MO n : 12JMC rév A

Product Manual SZ1145

REGARD. REGARD 4-20 AND Ex CHANNEL CARDS INSTALLATION AND OPERATING MANUAL (FOR ATEX VERSION CARDS)

SUPREMATouch Modular Fire & Gas Detection System

Stand Alone DYNAGARD SP Operation Manual

DIGITAL TEMPERATURE RELAY TR-100

SENSE Instruments CO., LTD. Data sheet Gas detector Page 1 / 5. Gas detector

FUNCTIONAL SAFETY MANUAL

Engineering Guideline. pac- Carriers Type Universal

APPLICATION DATA SHEET

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

CTT8 TEMPERATURE MONITOR DEVICE

Dräger Polytron 8100 EC Detection of toxic gases and oxygen

I/A Series 716C 1/16 DIN Temperature Controller

PolyGard Digital Gas Controller DGC-05 RS-485 Bus

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

P R O D U C T D ATA S H E E T

Air Check EX LEL Gas Monitor Instruction Manual

GAS PLUS ALARM SYSTEM

APPLICATION DATA SHEET

Touchpoint 1. The Touchpoint 1 controller provides 24 hour protection from flammable, toxic or Oxygen gas hazards.

Dräger Polytron 8700 IR Detection of flammable gases and vapors

Refrigeration and Air Conditioning Technical leaflet. Electronic controller EKC 201 and EKC 301

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

HART TOCSIN 903 SINGLE CHANNEL GAS DETECTOR USER INSTRUCTIONS. Oliver IGD Limited NEW WITH OPTIONAL. 4a Pepper Road Stockport SK7 5BW England

TER Active Room Temperature Sensor (Controller),

Dräger Polytron 8000 Stationary gas detector (EC)

SUPREMATouch. Modular Fire & Gas Detection System

Dräger Polytron 8100 EC Detection of toxic gases and vapors

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Gas Detection System TOX ALARM DG2000-Garage

POSITIONERS CONTROLS ELECTRO-PNEUMATIC INTELLIGENCE FOR DOUBLE & SINGLE ACTING PNEUMATIC ACTUATORS SERIES 6A. The High Performance Company CELEBRATING

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

Sintrol Snifter A2 EX. Manual. Version 1.2.3

ST-IAM Sensor Transmitter Integrated Area Monitor. Check / Calibration Procedure* 10 ASH (1)

SMART Gas Detector/Transmitter(4~20mA) with built-in LCD & explosion proof DA-500

Transcription:

Data sheet Danfoss gas detection unit Type GD Heavy Duty The Heavy Duty gas detection units are used for monitoring and warning of hazardous Ammonia gas concentrations. They are intended for ATEX/ IECEx applications and consists of a robust flameproof metal enclosure that can be kept closed after wiring, since programming (configuration) is performed by magnetic field to the display via a magnetic pen.depending on the application, they are available with an electrochemical, a semiconductor or a Pellistor sensor covering a wide range of ppm. The Heavy Duty gas detection units are intended as Stand-alone, or connected to a central system like Gas Detection Controller Unit, or a PLC. As stand-alone the on-board relay can be used for activation of alarm devices, while the Analog or RS85 Modbus connection to a central system allows additional centralized monitoring and alarm activation. The gas detection units come with a factory default, -step alarm set-up ready for use. The integrated software enables the user to configure two individual alarm ranges. Alarm, a pre-alarm indicating the gas level has passed a predefined threshold, and - if the gas level passes predefined threshold - the final alarm. Features Digital, factory configured and pre-calibrated gas detectors for plug-and-play installation (no adjustment required) Easy configuration via Display and Magnetic pen and intuitive user-interface; helps simplify operator handling and minimize risk of operational, settings and calibration errors Stand-alone (integrated relay) and/or flexible connection to central controller - by either Analog or RS85 open Modbus communications Wide selection of sensor types and detection ranges Display background color indicating alarm or communication fault by turning red Fieldbus wiring - connect and power up to 96 sensors, wire length max. 900 meters (95 ft) per segment; controller expansion modules permits additional segments and alarm relays Automatic self-diagnostics to ensure correct communication and operation. On board fault relay. Sensor seal cap to prevent premature exposure during installation Digital user interface ensures high sensor accuracy Reduced risk of false alarms due to temperature compensated sensors Password protected alarm settings allowing authorized access only LCD display with status LED Magnetic pen/on-board acknowledge button to reset alarms and to verify that no gas leaks are present Service alerts on unit, controller or both, readable via service tool Display Quick and precise calibration procedures - either by Plug & Play replacement sensors or calibration with gas. No potentiometers or multi-meters required For improved safety and to optimize the lifetime of the sensor, degenerated sensors with too low sensitivity (<0%) are rejected during calibration process. Conformity to Ex d EN60079-0, -, Ex d IEC 60079-0, -, EN 500, EN 6508-, -, -, EN 507 Certificate BVS 5 ATEX E 9 X, IECEx 6.008 X Enables regulatory compliance with EN 78:06, ISO 59:0, IIAR -07, and ASHRAE 5:06 AI757850en-0000 DKRCI.PD.S00.E.0

Contents Page Features... Working principle/operation.... Service and maintenance... Specifications... Electrical connection...5 Fieldbus loop...6 General info...7 Gas types and thresholds...7 Alarm scheme......................................................................................8 Ordering...9 AI757850en-0000 DKRCI.PD.S00.E.0

Working principle/operation One sensor is connected to the Heavy Duty sensor board via local bus. The Sensor board provides the power supply of the sensor and prepares the measured data for digital communication. The operation menu of the Heavy Duty software is accessed through the Display via a Magnetic pen, or the connected Gas Detection Controller, or via the dedicated GD Service tool (or PC tool). The Service tool (or PC tool) is plugged directly to the board of the unit by use of an adapter. These interfaces allow the unit configuration, setting of the unit alarm levels and calibration of the attached sensor. The service tool (or PC tool) can be used on all units across the Basic, Premium and Heavy Duty platforms. For Stand-alone units the alarm signals are handled by the unit software, which activates the integrated relay directly. For central controlled units the alarm signals are handled by the Gas Detection Controller (or a PLC) via the -0 ma (-0V) analog output or the RS85 open Modbus communication. For additional operational safety the changing of parameters is password protected allowing authorized access only. The factory default password can easily be customized. Service and maintenance The Heavy Duty gas detection units are calibrated either by replacing of sensor heads or by calibration with gas. Plug & Play replacement sensors are precalibrated and factory certified for quick and easy calibration procedure. The sensor is connected to the local bus via a plug connection enabling easy and simple exchange of sensor instead of a calibration. The internal X-change routine recognizes the exchanged sensor during the exchange process and restarts the measurement mode automatically. An LED indicates the correct procedure of the exchange operation. To ensure the proper functioning of the units and to prevent human errors, the sensor head can only be replaced by the same type and ppm range (exact replacement) that match the configuration. If a different sensor head is installed, the GD unit will show a communication error. As an alternative, calibration with gas can be performed via the service tool (or PC tool), calibration gas with correct concentration and the Danfoss calibration adapter. The Danfoss gas detection units have an integrated, digital calibration interface and procedure, which makes the calibration process easy, accurate, and time-saving. No potentiometers or multi-meters required for the calibration. The calibration procedure requires significantly less calibration gas per calibration compared to traditional routines. AI757850en-0000 DKRCI.PD.S00.E.0

Specifications Electrical Power supply Power consumption ( V DC) Control unit Digital filter Visual indications Analog output signal (active) Serial interface Fault relay Alarm relay LCD 6 8 V DC 90 ma, max. 0 ma Microprocessor with bit converter resolution Averaging in order to increase the EMC immunity LEDs for operation, alarm and communication Proportional, overload and short-circuit proof, load 500 Ω 0 ma = measuring range.0 < ma = underrange > 0. ma = overrange ma = fault >.8 ma = fault High Serial data bus Max. 0 V AC/DC, A Max. 0 V AC/DC, A x 6 characters, status LEDs, menu operating elements Sensor data Gas type Flammable gases Toxic gases HCFC, HFC, HFO Sensor element Pellistor Electro Chemical Semiconductor Measuring range 0-00 % LEL 0-000 ppm / 0-0000 ppm 0-5000 ppm Response time t₉₀ < 0 sec. NH₃ t₉₀ < 0 sec. for NH₃ t₉₀ > 0 sec. for NH₃ Sensor head housing Material CrNi Stahl:.0 Dimensions (d x H) 0 x 56 mm (.8 x.0 in.) Protection class Gas inlet IP6, with option splash-proof IP65 Thread External thread M0 x.5 Environmental conditions Humidity 5 to 90% r.h. Operating temperature P: -5 C to +60 C / EC: -5 C to +50 C / SC: -0 C to +50 C Physical characteristics Case / colour Aluminium pressure die-casting / light grey RAL 70, epoxy coating Dimensions (d x H) 95 x 8 mm Weight Ca.. kg Protection class Housing protection IP66 to IP68 (depending on the cable glands used) Mounting Wall mounting (sensor head downwards) Cable entry x ¾ in. (Ansi B.0.) Wire connection Spring-type terminal, 0.08 to.5 mm² AWG 8 - Wire length Max. load 500 Ω (= wire resistance + controller input resistance) ATEX marking IIG Ex d IIC T Gb, CE 058 Options: LCD display LCD Operation Power consumption Two lines, 6 characters each, background highlighted in two colours Menu driven via four magnetic buttons 5 V, 60 ma, 0. VA Status LED Colour / Mode Red / yellow / green (alarm fault operation - service) Protection class IP 65 AI757850en-0000 DKRCI.PD.S00.E.0

Electrical connection Danfoss 8H6_0-08 NPT ¾ in. 0 9 8 7 6 Sensor PX + V DC/AC 6 5 + V DC/AC Tool Tool Service Service LED LED Ackn. Button Ackn. Button Status Status Sensor head Sensor head 5 6 GND BUS_A BUS_B - 0 ma Output output 7 8 Fault relais energized in operating mode at No alarm - Default NPT ¾ in. 9 0 Alarm relais de-energized in operating mode at No alarm - Default (Configurable) Sensor Danfoss 8H_0-08 Heavy Duty PCB POWER ALARM FAILURE D CH %UEG 0,00 Status LEDs Ackn.-/Test Testbutton = Ackn. button On board LED is similar to the display LED: Green () is power on - Flashing if maintenance needed Yellow () is an indicator of Error. - when the sensor head is disconnected or not the expected type - AO is activated but nothing connected Red () on alarm On board Ackn. -/Test button: Test: The button must be pressed for 0 sec. - Alarm is simulated, stop on release Ackn.: Pressed while Alarm, the audible warning switches off and goes back on after 5 min. when the alarm situation is still active (also possible over ESC button (use the magnetic pen). AI757850en-0000 DKRCI.PD.S00.E.0 5

Fieldbus loop Each GD controller can handle up to 96 sensors and handle any mix of individual Gas detection units of the types Basic, Premium and Heavy Duty. The max. recommended loop wire length is 900 meter (95 ft) per segment. With additional segments (and additional controller expansion modules) the max recommended loop wire length is 700 meter (6 ft). The controller and the last GDU in each segment must be provided with a resistor of 560 Ohm. A Umin of 6 V DC must be secured at any spot in the loop. Below figure shows how to make proper connections between the controller and each GDU. Controller Controller Unit unit 560 R GDU Addr. 05 GDU Addr. 0 Danfoss 8H9_0-08 0 V DC V DC BUS_B BUS_A 0 V DC V DC GDU Addr. 0 GDU Addr. 0 GDU Addr. 0 U min = 6 V DC R Wire length max. 900 meter (95 ft) per segment. Wire length max. 900 meter (95 ft) per segment. More More segments segments with with additional additional expansion expansion modules modules max. 700 max. meter 700 meter (6 (6 ft). ft). Additional Additional power power limitations limitations must must be calculated. be calculated. R RIGHT Controller unit R = Terminating resistor 560 560 Ohm Ohm = GDU (Basic, Premium and/or and/or Heavy Heavy Duty) Duty) R R Controller unit WRONG Danfoss 8H_0-08 AI757850en-0000 DKRCI.PD.S00.E.0 6

General info Cable gland mounted Sensor head (SX) mounted bottom ESC Sensor Heavy Duty Gas types and thresholds Sensor Sensor Type ppm range Alarm Alarm Hysteresis Ammonia EC 000 Electrochemical 0-000 500 ppm 900 ppm 5 ppm Ammonia EC 5000 Electrochemical 0-5000 000 ppm 500 ppm 50 ppm Ammonia SC 0000 Semiconductor 0-0000 5000 ppm 9000 ppm 50 ppm Ammonia P LEL Pellistor 0-0000 (0-00% LEL) % LEL (0000 ppm) % LEL (0000 ppm) % LEL Hysteresis = 5% of Alarm (rounded up to the next higher integer) Alarm thresholds can have the same value, therefore the relays and LED can be triggered together. AI757850en-0000 DKRCI.PD.S00.E.0 7

Alarm scheme Status LED Blinking ( sec.) Fast blinking ( ( sec.) Very fast blinking (0. sec.) Power LED Failure (e.g. sensor head is is disconnected) Slow blinking, sensor warm up Fast blinking, sensor is is in in special mode (e.g. to to change parameters,...)...) Danfoss 8H7_0-08 Alarm Alarm If ackn. button pressed pressen after Alarm Alarm Ackn. Ackn. LED Red If ackn. button not pressed Ackn. Ackn. LED Red Alarm Alarm * Time delay set set in in config. Gas Alarm Alarm AI757850en-0000 DKRCI.PD.S00.E.0 8

Ordering Type Model Refrigerant Sensor ppm Alarm ppm Temp. Range [ C] GDA Temp. Range [ F] Code number Heavy Duty Ammonia Electrochemical 0-000 500/900-5 to +50 - to 8H60 Heavy Duty Ammonia Electrochemical 0-5000 000/500-5 to +50 - to 8H60 Heavy Duty Ammonia Semiconductor 0-0000 5000/9000-0 to +50 to 8H605 Heavy Duty Ammonia Pellistor 0-0000 0000-5 to +60 - to 0 8H609 Spare parts and accessories Description Code number Replacement sensor - Heavy Duty Ammonia EC 000 Replacement sensor - Heavy Duty Ammonia EC 5000 Replacement sensor - Heavy Duty Ammonia SC 0000 Replacement sensor - Heavy Duty Ammonia P LEL Controller unit Controller solution (controller + enclosure) Controller solution Uptime Warning module (wire break monitoring module) Controller expansion module Service tool PC Tool Calibration adapter Heavy duty Gateway for controller Magnetic pen 8H67 8H68 8H69 8H60 8H6 8H6 8H67 8H6 8H6 8H6 8H65 8H6 8H68 8H69 Accessories overview Controller unit Used for a centralized monitoring and warning. The input signals for the controller are collected via RS85 Modbus or analog communication. The controller can handle up to 96 digital sensors via Fieldbus and four () analog input. An additional 8 analog input is possible using seven (7) expansion modules (-0 ma signal interface). The total number of connected sensors should not exceed 8 sensors. The controller unit can be employed as pure analog controller, as analog/digital, or as digital controller. Configuration is menu-driven via the keypad. For fast and easy configuration, the PC Tool is recommended. Controller solution Controller unit placed in an enclosure ready to be connected to a power source. A separate UPS for the controller is available. Warning module (wire break monitoring module) The warning module is used for monitoring the circuiting to the warning/alarm devices on a centrally controlled gas detection system. Wire breaks or wire interruptions in the alarm device loop will be reported to the central control. Controller expansion module The gas detection Controller Expansion module is used for expansion of the cable coverage in terms of number of loops and the total wire length. Each Controller Unit can handle up to 7 Expansion modules allowing additional 7 segments with a total of 700 meters (6 ft.) wiring and a total of relays for alarm device circuits. Service tool For interface with units with no display (Basic, Basic+, Premium, Premium+). Acts as a portable display and can be connected to all Danfoss gas detection units. (Heavy Duty w. adapter). PC tool The PC tool is a menu-driven and standalone software used for easy addressing, parameter setting, calibration, and data logging of the Basic, Premium and Heavy Duty gas detection units, and the controller unit. Calibration adapter The calibration adapter is required for connecting the calibration gas container, via the flow regulator, to the sensor head on the gas detection units. (Two variants, One for Basic and Premium plastic head sensors; one for heavy duty and Premium remote metal head sensors.). Gateway for controller The gateway is an addition to the controller and used for communicating via Modbus TCP/IP. Magnetic pen The pen is used to operate the Heavy Duty unit display. The Heavy Duty enclosure does not permit direct touch. AI757850en-0000 DKRCI.PD.S00.E.0 9

AI757850en-0000 DKRCI.PD.S00.E.0 0