FloCat MFE Electromagnetic Flow Meter PRODUCT MANUAL

Similar documents
User Guide OI/FEX100HART EN Rev. A. WaterMaster FEX100 HART Field Device Specification

S/601 Controller Installation Manual

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

FLOW CONTROLLER TYPE S/601

SCHMIDT LED Measured Value Display MD Instructions for Use

EasyTronic III MANUAL SERVICE

Browser Manual ProMinent ProMtrac Cooling Tower Water Treatment Controller

Analog Room Pressure Monitor RPC Series

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

RPM1600 Series Room Pressure Monitors

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

SITRANS F. Ultrasonic Flowmeters FST030. Function Manual. Answers for industry. 04/2017. Edition

EXPERT TRI-STAR. Temperature controller. User s Manual

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Deltapilot S FMB70. Functional Safety Manual. Level and Pressure Measurement with Output Signal ma

PF1000 CONTROLLER. for the. Heateflex Corporation 405 E. Santa Clara St. Arcadia, CA TEL: (626) ; FAX: (626)

TD80 LEVEL GAUGING & OVERFILL PREVENTION SYSTEM PRODUCT MANUAL SUPPLEMENT. TPM 005 Revision 0.0

SCAN200E USER S MANUAL

FIL-SPL Flow-through heater for central heating USER MANUAL

2012 Toolbar & NH3 Operators Manual

CU-02 with Senaco Plus

User Guide IM/AX4CO4 Rev. K. AX413, AX430, AX433, AX436 & AX438 Single and dual input analyzers for high level conductivity

Electromagnetic water meter type MAG 8000

Halton SAFE / 7.14 user guide and installation instructions

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

Operation manual. Rooftop Packaged Unit

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 Electromagnetic Flowmeter

Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual. Version Date - June Part Number

No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic,

Application Manual Loop Water Controller

DC200 Digital Dispenser Operating Manual

Instruction Manual December 2001 ENACOCU02

Dryer Controller M720

F4 Process Controller Installation and Operation Guide

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table)

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S

DIGITAL METERS Large Display Temperature Meters Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

2-wire Passive Intelligent Loop (LED) Display Meter

DATA SHEET CS8100 CS8100_IT_EN_DS049REV02_IS

Fire Control Panel FS5100

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

Dryer Moisture Systems Inc. Dryer Master M 2. Product Manual

Sensor Control Panel

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Cerabar S PMC71, PMP71, PMP75

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

Magnetic Stirring Systems with Heat

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

1Byone Products Inc. USER MANUAL 400 Watt Low Lying Fog Machine Model No.: O00QL-0045

Instruction Manual August sitrans CU 02

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

FIRERAY 5000 range USER GUIDE

2-wire Passive Intelligent Loop (LED) Display Meter

XR401. Comfort Control TCONT401AN21MA. Owner s Manual. your local dealer (distributor) For more information contact. Tyler, Texas 75711

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

User Manual. Dryer Controller M720

PowerRouter application guideline

I/A Series 716C 1/16 DIN Temperature Controller

Product Manual SZ1145

Rosemount 3051S MultiVariable Transmitter

INSTRUCTION MANUAL FOR TOUCH PANEL MONITORING UNIT CMT-220-K

MODEL 4300-PG CENTRAL ACCESS PANEL FOR EC-GOLD TRANSMITTERS. User Manual

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

Air Comfort. Installation instructions (English) A

User manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort

AutomationDirect PM24. Microprocessor - Based Process/Temperature Limit Controller. Operator s Manual. Technical Support.

Digital Programmable

USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

Sierra Series 900 Single & Dual Channel System. Instruction Manual

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Fume Hood Operating Display Panel

Product waste disposal - Protection of the environment:

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power.

Model 9010 and 9020 Monitoring Systems

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide

Installation Guide. ECL Comfort 210, application A Table of Contents

Water Tank Level Monitor

MC200. Users Instructions. HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: Fax:

Temperature Controller CC24-7 UNIBOX USER S MANUAL Legion Dr. Mason, MI USA October 2010 Ph. (517) Fax (517)

User Guide ems25plus. Page 1. Normal operation. Product interface

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Product Manual SZ1144

QD-ENG-68 Controller for Thermoelectric Thermal Management

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

RF SCOUT PLUS INSTRUCTION MANUAL. Dielectric, LLC 22 Tower Rd. Raymond, ME Phone: January 2015, Rev B 1

General The Dryer Programmer for Windows Computers

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

SYSTEM ENHANCEMENT MODULE

Sierra Model 951 Digital Flo-Box. Instruction Manual Part Number IM-951 Revision A 09-05

Condensing Boiler RS100 Controller Training Program

RS Pro Infrared Temperature Sensor

Transcription:

FloCat MFE Electromagnetic Flow Meter PRODUCT MANUAL

Flocat Electromagnetic Flowmeter Operation Manual Table of Contents Part 1. 3-line Display on Transmitter 2 Main Interface. 2 Part 2. Programming Guide... 4 (1) Setting flow... 6 (2) Setting 4-20mA.. 7 (3) Setting Pulse Output... 7 (4) Setting Flow Total...... 8 (5) Setting Alarm output of channel 1. 9 (6) Setting Alarm output of channel 2. 9 (7) Setting Alarm... 10 (8) Setting Output of External Control... 10 (9) Setting Empty Alarm. 11 (10) Setting Sensor.. 11 (11) Setting Test Mode 12 (12) Setting Circuit Board... 12 (13) Setting Display and Communication... 12 (14) Others.. 13 Part 2. Troubleshooting Guide... 14 (1) No display on transmitter.. 14 (2) Flow data not displayed on transmitter..... 15 (3) Flow measurement incorrect..... 16 (4) Other errors... 17 Appendix 1. Chart Flow and Pulse spans for various sizes.. 18 1

Part 1. 3-line Display on Transmitter The standard transmitter has a three-line LCD display for viewing flow data and a four-button keypad for programming the meter. (Explosion proof transmitters have the same three-line LCD display but use four magnetic operating keys). Main Interface Percentage bar Flow rate % of range Alarm On indicator & Alarms Display Flow Total, Flow velocity, Alarms, Flow rate % of range in sequence Current flow rate Flow rate unit (user can change unit) Key 2 Key 4 Key 1 Key 3 (1) Alarm Indicator and Alarms If Alarm is turned on, a bell icon is displayed on the screen, indicating that the alarm feature is enabled. The following types of alarms are available and can be displayed on the line below the Alarm indicator. (Note that only Emp-Pipe and Coil alarms are turned on by default) Alarm identification displayed "Fwd" "Rev" "Cut" "High" "Low" "Anlg" "Pulse" "EROM"(eeprom error) "Copy" "Emp-Pipe" "Coil" Explanation Forward flow alarm Reverse flow alarm Alarm when flow velocity in mm/s below which all outputs are set to zero Alarm when flow excess high limit. Alarm when flow excess low limit. Alarm when current output exceeds limit Alarm when pulse output exceeds limit Alarm when the initial default parameter is lost Copy initial default parameter Alarm when pipe is empty Alarm when excitation coil occurs 2

(2) Press Key 1 to view the following items on the 3 rd line in sequence: > Forward flow total value < Reverse flow total value * Net flow total value (e.g. * 10364 L) V Current flow velocity Q current flow rate % Flow rate percent of range (3) Press Key 3 to reset Flow total value. This task can only be done when the parameter of "Reset Total" is set to "Yes" through the parameter configuration menu (see Part 2 for how). If Reset Total is not changed into Yes, pressing on the main interface will result in display of CtrEn=0, which means reset is not successful. (4) Press Key 2 to enter login screen as shown below: Enter the password as provided. The correct password will bring you into the programming interface. See Part 2 for the parameter settings. 3

Part 2. Programming Guide This section describes how to navigate the menu and configure the parameters according to user s application. Note: Only user with authorization can perform the following tasks. Security setting: Note: the password of level 1 and level 2 is all a 5-digit security code. Correct password brings you to the parameter setting menu. The first level of password is '02041', permitting user to set the parameters; the second level of password is '04121', permitting technician to set the parameters. To enter password: After getting into the login screen, press key to the digit you want to enter, and then press either or key to reach the desired digit. Continue until all digits have been set, and press switch. If a correct password is entered, the parameter setting menu will be displayed and you will be able to navigate the menu on the next page and perform programming tasks. Otherwise you will be brought back to the main interface. 4

Configuration Menu Overview Press Moves Return to Flow Span Page one Page two Flow Span Current High Pulse Scale Total Unit (Remark 2) Alarm1 Status Alarm2 Status High Alarm Span Input Empty pipe Set Sensor Id Test Mode Hardware Fact1 Flow Decimal Reset! Debug reset Flow Unit (Remark 1) Current Low Pulse Span Reset Total Alarm1 Enable Alarm2 Enable Low Alarm TotalClear Input Empty pipe Value Sensor Tag Test Out Hardware Fact2 Write protect Debug Fwd/Tot Flow Damping Flow Direct Pulse Value Total password Alarm1 Coil Alarm2 Coil H/L ALM HYS FlowHold Input Idle Time Nominal Size Test Flow Header Length Debug Rev/Tot Dead Time Flow Span2 Pulse Idle Stat Alarm1 Forward Alarm2 Forward Alarm Enable FlowCut Input Velocity High Sensor Fact1 Test Percent Net address Debug Setcon Dead Time Current Alarm1 Alarm2 Input Sensor Test Switch Value Reverce Reverce IdleState Fact2 Frequency Flow Percent Current Direct1 Alarm1 LowCut Alarm2 LowCut Auto Zero Test Current Velocity Cutoff 4-20mA Full1 Alarm1 Empty Alarm2 Empty Fact Copy Test Velocity 4-20mA Zero1 Alarm1 High Alarm2 High Test Alarm Current Direct2 Alarm1 Low Alarm2 Low 4-20mA Full2 4-20mA Zero2 Alarm1 PulseHigh Alarm2 PulseHigh 5

How to Navigate Menu and Set Parameters: Press and keypads (M or E key for explosion-proof transmitter) to cycle through the units till the desired one is found, then press or keypad ( + or key for explosion-proof transmitter) to change the value. Once the desired value is set, press (E for explosion-proof transmitter) to confirm. (1) Setting Flow Item R/W Data Range Unit Default Explanation Flow Span W Flow Unit 100 Flow range (Corresponding to max value of 4-20mA output) Flow Unit W (see Remark 1) m^3/h Flow Damping W 0~7 s 3.2 Nominal time constant Dead Time W 0~7 s 0.8 The amount of time the meter will ignore abnormal flow readings and hold the last valid reading Dead Time Switch W 0~100(%) 30 If the flow fluctuates more than a set percentage of the flow range, the flow meter will ignore the fluctuation for the duration of the Dead Time Flow Percent R Flowrate percentage Velocity Cutoff W 0~255 ft/s 0.1 Velocity Cutoff. Flow velocity in ft/s below which all outputs are set to zero Remark 1: The available Flow Unit options include Ltr/S, Ltr/M, Ltr/H, MLtr/D, M^3/S, M^3/M, M^3/H, M^3/D, Ft^3/S, Ft^3/M, Ft^3/H, Ft^3/D, Gal/S, Gal/M, Gal/H, MGal/D, In^3/S, In^3/M, In^3/H, In^3/D, aft/h, aft/d, ain/h, ain/d, Bbl/M, Bbl/H, and Bbl/D. Display of Flow Unit: (Ltr = Liter; M^3 = Meter^3; Ft = foot ; Gal = gallon; In = inch; aft = acre-foot; ain = acre-inch; Bbl = Barrel. S = second; M = Minute; H = Hour; D = Day) Flow Unit Ltr/S Flow Unit Ltr/M Flow Unit Ltr/H Flow Unit MLtr/D Flow Unit M^3/S Flow Unit M^3/M Flow Unit M^3/H Flow Unit M^3/D Flow Unit Ft^3/S Flow Unit Ft^3/M Flow Unit Ft^3/H Flow Unit Ft^3/D Flow Unit Gal/S Flow Unit Gal/M Flow Unit Gal/H Flow Unit MGal/D Flow Unit In^3/S Flow Unit In^3/M Flow Unit In^3/H Flow Unit In^3/D Flow Unit aft/h Flow Unit aft/d Flow Unit ain/h Flow Unit ain/d Flow Unit Bbl/M Flow Unit Bbl/H Flow Unit Bbl/D 6

(2) Setting 4~20mA Item R/W Data Range Unit Default Explanation Current High W 0~20 ma 20 Output current in ma for 100% flow range Current Low W 0~4 ma 4 Output current in ma for 0% flow range Flow Direct W [-]/[+] + + is forward direction; - is reverse Flow Span2 W (%) 100(%) Full scale flow range for second analogue range as percentage of main flow range **SPECIAL ORDER** Current Value R ma Present electric current output Current Direct1 W [-]/[+] + Direction of channel1 current output 4-20mA Full1 W 0 Calibration function. Revised value of channel1 electric current output at full scale 4-20mA Zero1 W 0 Calibration function. Revised value of channel1 electric current output at zero Current Direct2 W [-]/[+] + Direction of channel2 electric current output **SPECIAL ORDER** 4-20mA Full2 W 0 Calibration function. Revised value of channel2 electric current output at full scale **SPECIAL ORDER** 4-20mA Zero2 W 0 Calibration function. Revised value of channel2 electric current output at zero **SPECIAL ORDER** Note: IC1+ is standard for electromagnetic flowmeter. IC2+ is optional item and should be specially indicated at the time of ordering. The value [+] of Current Direct means forward direction of flow and [-] means reverse direction of flow. Flow direction could be changed by changing the value of Flow Direct. (3) Setting Pulse Output Item R/W Data Range Unit Default Explain Pulse Scale W 1 Number of pulses per Total Unit Pulse Span W 0~2000 Hz 800 Max output frequency in Hz. The recommended span is 800 ~ 1000 Hz. Higher values may affect performance of the flowmeter. Over 3000Hz will cause a system reset Pulse Value R Hz Present output frequency in Hz Pulse Idle Stat W High/Low Low State when there is no pulse output Pulse Mode W High/Low Indicates if above or below 4 Hz 7

Note: The unit of pulse output is the same as Total Unit. 1 Pulse means 1 Total Unit by default. For example, if Total Unit is m^3, 1 Pulse means 1 m^3. Please refer to Appendix 1 for the pulse settings for the different sizes of flowmeter. For example, for DN25, the max flow (i.e. Flow Span) is 6 m3/h, Total Unit is ml, then the max pulse (i.e. Pulse Span) = Flow Span x Flow Scale = 6m3/h x 0.1 = 6000000ml/3600s x 0.1 = 166.6666667 ml/s = 166.6666667 Hz. Forward Total Flow is output through FOUTA, and reverse Total Flow is output through FOUTB. (4) Setting Flow Total Item R/W Data Range Unit Default Explanation Total Unit W (see Remark 2) m^3 Reset Total W Yes/No No Selecting Yes enables totalizer reset by pressing the key Total Password W 12345 Modify Total values in the following options: (1)Total Integer[+]: the integer portion of forward Total. (2)Total Decimal[+]: the decimal portion of forward Total. (3)Total Integer[-]: the integer portion of reverse Total. (4)Total Decimal[-]: the decimal portion of reverse Total. Note: After setting the Reset Total to Yes, the next step is to exit the programming menu, go back to the main interface and press the key to reset the total. The Alarm code ClrEn=0 will be displayed if the above steps aren t completed. Remark 2: The available Total Unit options include Ltr, hltr, M^3, In^3, Ft^3, Yd^3, Gal, Kgal, Bbl, aft, and ain. Display of Total Unit: (hltr = 100xLitre; Kgal = 1000xGallon; Yd^3 = Yard^3) Flow Unit Ltr/S Flow Unit Ltr/M Flow Unit Ltr/H Flow Unit MLtr/D Flow Unit M^3/S Flow Unit M^3/M Flow Unit M^3/H Flow Unit M^3/D Flow Unit Ft^3/S Flow Unit Ft^3/M Flow Unit Ft^3/H Flow Unit Ft^3/D Flow Unit Gal/S Flow Unit Gal/M Flow Unit Gal/H Flow Unit MGal/D Flow Unit In^3/S Flow Unit In^3/M Flow Unit In^3/H Flow Unit In^3/D Flow Unit aft/h Flow Unit aft/d Flow Unit ain/h Flow Unit ain/d Flow Unit Bbl/M Flow Unit Bbl/H Flow Unit Bbl/D 8

(5) Setting Alarm Output of Channel 1 Item R/W Data Range Unit Default Explanation Alarm1 Status W High/Low High Idle state for alarm output Alarm1 Enable W Yes/No Yes No=Alarm output disabled; Yes=Alarm output enabled Alarm1 Coil W Yes/No Yes Alarm occurs for excitation coil Alarm1 Forward W Yes/No No Alarm occurs for forward flow Alarm1 Reverse W Yes/No No Alarm occurs for reverse flow Alarm1 LowCut W Yes/No No Alarm occurs for Cutoff Alarm1 Empty W Yes/No Yes Alarm occurs for empty pipe Alarm1 High W Yes/No No Alarm occurs for Flow High Alarm1 Low W Yes/No No Alarm occurs for Flow Low Alarm1 PulseHigh W Yes/No No Alarm occurs for exceeding Pulse range Note: Terminal ALARM 1 outputs a constant voltage to show the current alarm status of the flowmeter. The initial status could be set through Alarm 1 Status. (6) Setting Alarm output of Channel 2. (SPECIAL ORDER) Item R/W Data Range Unit Default Explanation Alarm2 Status W High/Low High Idle state for alarm output Alarm2 Enable W Yes/No Yes No=Alarm output disabled; Yes=Alarm output enabled Alarm2 Coil W Yes/No Yes Alarm occurs for excitation coil Alarm2 Forward W Yes/No No Alarm occurs for forward flow Alarm2 Reverse W Yes/No No Alarm occurs for reverse flow Alarm2 LowCut W Yes/No No Alarm occurs for Cutoff Alarm2 Empty W Yes/No Yes Alarm occurs for empty pipe Alarm2 High W Yes/No No Alarm occurs for Flow High Alarm2 Low W Yes/No No Alarm occurs for Flow Low Alarm2 PulseHigh W Yes/No No Alarm occurs for exceeding Pulse range Note: Terminal ALARM 2 outputs a constant voltage to show the current alarm status of the flowmeter. The initial status could be set through Alarm 2 Status. Alarm 2 is not available on explosion-proof transmitters. For regular transmitters, Alarm 2 is disabled by default, unless user specifies it in the order. 9

(7) Setting Alarm The settings are used for both Alarm 1 and Alarm 2 (if enabled). Item R/W Data Range Unit Default Explanation High Alarm W 0~200(%) 110 High flow alarm trip point as % of the range Low Alarm W 0~200(%) 0 Low flow alarm trip point as % of the range H/L ALM HYS W 0~200(%) 10 Setting hysteresis/sluggish length/width of automatic range transformation. Alarm Enable W Yes/No Yes Turn on/off alarm. Yes means to make alarm indicator available. Alarm identification "Fwd" "Rev" "Cut" "High" "Low" "Anlg" "Pulse" "EROM"(eeprom error) "Copy" "Emp-Pipe" "Coil" Explanation Forward flow alarm Reverse flow alarm Alarm when flow velocity is lower than velocity cutoff setting Alarm when flow exceeds high limit Alarm when flow exceeds low limit Alarm when current output exceeds limit Alarm when pulse output exceeds limit Alarm when the initial default parameter is lost Copy initial default parameter Alarm when pipe is empty Alarm when excitation coil error occurs (8) Setting Output of External Control Item R/W Data Range Unit Default Explanation Span Input W Yes/No Yes Switch to the second flow range **SPECIAL ORDER** TotalClear Input W Yes/No No Reset totalizer FlowHold Input W Yes/No No Hold flowmeter output value FlowCut Input W Yes/No No Set flow rate output to zero Input IdleState W High/Low Low (EXTI/P+ act on short circuit),high (EXTI/P- act on open circuit) Configure external control status Note: EXTI/P+ and EXTI/P- works as an external output channel and connects with control system. When Input IdleState is Low, EXTI/P+ and EXTI/P- supply low potential. When Input IdleState is High, EXTI/P+ and EXTI/P- supply high potential. The flowmeter has four kinds 10

of options for control as shown in the above list. If ONE of Span Input, TotalClear Input, FlowHold Input, or FlowCut Input is Yes, the other three will be automatically set to No. (9) Setting Empty Alarm Item R/W Data Range Unit Default Explanation Empty Pipe Set W 0~20000 KΩ 1000 Set resistance limit of Empty sensor Empty Pipe Value R KΩ Display Empty Pipe sensor real time resistance value Idle Time W 0~255 Min 5 Idle time in minutes. Idle Time is the sampling time period for empty pipe detection. Velocity High W 0~20.000 m/s 6 The max flow rate measured by flowmeter Notes: (i) Empty Pipe Value is the resistance between two electrodes in sensor. When resistance exceeds the value of Empty Pipe Set, the value of flow rate will be displayed as 0, and flowmeter will return to the status of empty pipe. (ii) When flow rate exceeds the value of Velocity High, the displayed flow rate will be 0. (10) Setting Sensor Item R/W Data range Unit Default Explanation Sensor Id W 0~99999999 11111111 Serial No Sensor Tag W 0~255 1 Tag No (legacy setting, not on all units) Nominal Size W 0~3000(>0) mm 100 Nominal Diameter in mm Sensor Fact1 W (>0) 1 Slope Sensor Fact2 W 0 Offset in mm/s at zero Auto Zero W 0~2 0 Velocity zero set Fact Copy W 0~19 0 Creates back-up copy of sensor parameters Notes: (i) Each flowmeter has its own Sensor Id (Identity) which is also used as address of HART communication. (ii) When setting the value of Fact Copy to be 19, all the parameters may get multiple backup, which may take a few seconds. During this period, please don t cut off the power supply. Pressing the keypads of transmitter does not have effect. When the keypads become responsive, it means the backup is completed. (iii) Auto Zero: After installing the flowmeter on a pipeline, please make Auto Zero Adjustment before using it to measure flow, by following the steps below: 11

Step 1: Let the liquid fill full of the pipeline, and the flow velocity be zero. Step 2: switch the menu of Sensor Id to Auto Zero ; Step 3: change the value of Auto Zero from 0 to 1, and then wait for 1 minute without any operations on transmitter and pipeline. The value will come back to 0 after one minute to indicate that the Auto Zero Adjustment is completed. (11) Setting Test Mode Item R/W Data range Unit Default Explanation Test Mode W Yes/No No If Yes, the transmitter is in Test Mode Test Out W No No Data output (MUST NOT BE SWITCHED FROM NO) Test Flow W Flow Unit 100 Simulate input flow Test Percent R 0 Show Flowrate as a percentage Test Frequency R ma 0 Show Pulse Output frequency Test Current R 0 Show Output frequency Test Velocity R 0 Show flow velocity in sensor Test Alarm R 0 Show currently active alarms Note: When Test Mode is set to be Yes, the flowmeter enter simulation status of measurement. If there isn t any action on the keypads of transmitter for more than 15 minutes when the interface is in status of test mode, the transmitter will quit and return to the main menu of the interface. (12) Setting Circuit Board Item R/W Data range Unit Default Explanation Hardware Fact1 W 1 Correction coefficient 1 of circuit board Hardware Fact2 W 0 Correction coefficient 2 of circuit board Note: This menu is for the factory only. It s forbidden for customers to change these parameters by themselves. (13) Setting Display Item R/W Data range Unit Default Explanation Flow Decimal W 0~7 3 Decimal digits 12

(14) Others Item R/W Data range Unit Default Explanation Reset! W Yes/No No If the value is changed to Yes, the transmitter will be rebooted without changes to parameters. Notes: 1. R means that the field is read only; W means that the field is writable/editable 2. The value 'Yes' means that the option is selected; 'No' means that the option is not selected. 3. Use the keypads on transmitter to cycle through the menu and set the parameters accordingly. 4. If there isn t any action on the keypads of transmitter for more than 30 minutes when the flowmeter is in the parameter setting mode, the transmitter will quit and return to the main menu. 13

Part 3. Troubleshooting Guide The FloCat MFE Electromagnetic Flowmeter is designed for many years of optimal performance and requires little maintenance. However, if a malfunction occurs, we recommend you try resolving the issue by referring to the following guide. If you need further assistance, please contact your vendor. (1) No Display on Transmitter No display on transmitter Open wire connection box of transmitter to check if water entered box. Replace transmitter Check if cable connections are correct and reliable. Correctly connect cable again according to the installation manual. Check if fuse is broken. Replace with the same type of fuse. Issue still exists Contact the vendor. 14

(2) Flow Data not Displayed on Transmitter Flow data not displayed Connect wires again to ensure the connections are correct and reliable. Check if sensor CD1 and CD2 are switched off. Check if contact of wire connection terminal is reliable. Check if sensor CD1 or CD2 are switched on with earth DND, or its insulation resistance less than 20MΩ. Check if sensor signal wire SIG or SIG2 are switched on with the earth. In most cases, it is because water entered wire and caused wire insulation malfunctioning. 1. Open wire connection box of sensor, and dry wire with an air blower. Then refill box with the special sealing glue. 2. If issue still exists after step 1, contact the vendor. Correctly connect wires according to the installation manual. Check if signal wire connections are correct and reliable. Check if electrodes are contaminated. (If resistance between SIG1 and SIG2 is infinitely great when the pipeline is full of fluid, electrodes are contaminated.) Try removing deposits with soft cloth or soft brush. Do not damage the electrode or lining. If deposits cannot be cleaned by above method, remove sensor from pipeline. Then clean electrode by soft cloth or soft brush. Do not damage on electrode and lining. Issue still exists 15 Contact the vendor.

(3) Flow Measurement Incorrect Flow measurement incorrect Check if transmitter parameters are set correctly following nameplate. Set correct parameters according to nameplate. Check if pipeline is full of fluid. 1. Change installation location of flowmeter to make sensor tube full of fluid. 2. Vertically install flowmeter, and make flow from low to high. Check if fluid contains plenty of air bubble. Install air bubble expunction machine at upstream of flowmeter. Check if deposits exist in sensor tube. Remove deposits from tube with soft brush, especially those on electrode. Do not damage electrode or lining. Check if flowmeter is near motor, transformer, or other electrical equipment. Relocate flowmeter to a place far away these equipment, or make adequate shield for flowmeter. Check if ground connection is reliable. To ensure reliable ground connection, use copper wire with diameter is not less than 4mm. Issue still exists Contact the vendor. 16

(4) Other Errors Errors Empty pipe error Note: Only Emp-pipe and Coil alarm are enabled by default. To see other alarm information, user must turn on them according to their needs. Please refer to the Programming Guide Setting Alarm output of Channel 1 (or 2) for how-to. Recommended Actions 1. Check if pipeline is full of fluid. 2. Connect SIG1 and SIG2 to SIG GND to see if errors can be excluded. 3. Check if signal wires are correctly connected. 4. Check if electrodes contaminated. 5. If flow exists, check if resistance between SIG1 and earth, or between SIG2 and earth is less than 50kΩ. Analog output error PLS frequency error Other error 1. If analog output is out of range, refer to the Programming Guide to set the value of the Current range. 2. Switch off current output cable, check the Current Value in the setting and the current value between output terminals IC+ and IC- to see if they are equal. 3. If flow is full of the range and current output is up to full scale, check if current output circuit resistance is less than 750Ω. 1. If frequency output is out of range, refer to the Programming Guide to set the value of the Pulse Span. 2. If PLS frequency output is incorrect, use the test function to test output frequency to exclude output connection errors. Reset the parameters and see if error disappears. 17

Appendix 1: Size Flow Span (m3/h) Pulse Scale Unit Volume/unit Total Unit Pulse Span (Hz) DN2.5 0.055 1 1 ml/l ml 15.27777778 DN4 0.15 1 1 ml/l ml 41.66666667 DN5 0.24 1 1 ml/l ml 66.66666667 DN6 0.35 1 1 ml/l ml 97.22222222 DN8 0.6 1 1 ml/l ml 166.6666667 DN10 1 1 1 ml/l ml 277.7777778 DN12 1.4 1 1 ml/l ml 388.8888889 DN15 2 1 1 ml/l ml 555.5555556 DN20 4 1 1 ml/l ml 1111.111111 DN25 6 0.1 10 ml/l ml 166.6666667 DN32 10 0.1 10 ml/l ml 277.7777778 DN40 15 0.1 10 ml/l ml 416.6666667 DN50 25 0.1 10 ml/l ml 694.4444444 DN65 40 0.1 10 ml/l ml 1111.111111 DN80 60 0.01 100 ml/l ml 166.6666667 DN100 100 0.01 100 ml/l ml 277.7777778 DN125 150 0.01 100 ml/l ml 416.6666667 DN150 200 0.01 100 ml/l ml 555.5555556 DN200 300 0.01 100 ml/l ml 833.3333333 DN250 600 1 1 l/l l 166.6666667 DN300 900 1 1 l/l l 250 DN350 1200 1 1 l/l l 333.3333333 DN400 1600 1 1 l/l l 444.4444444 DN450 2000 1 1 l/l l 555.5555556 18

DN500 3000 1 1 l/l l 833.3333333 DN600 4000 1 1 l/l l 1111.111111 DN700 5000 0.1 10 l/l l 138.8888889 DN750 6000 0.1 10 l/l l 166.6666667 DN800 7000 0.1 10 l/l l 194.4444444 DN900 9000 0.1 10 l/l l 250 DN1000 10000 0.1 10 l/l l 277.7777778 DN1100 12000 0.1 10 l/l l 333.3333333 DN1200 12000 0.1 10 l/l l 333.3333333 DN1400 12000 0.1 10 l/l l 333.3333333 DN1600 12000 0.1 10 l/l l 333.3333333 DN1800 12000 0.1 10 l/l l 333.3333333 DN2000 12000 0.1 10 l/l l 333.3333333 19