SUBMITTAL DATA: PVA-A36AA7 & PUZ-HA36NHA5 36,000 BTU/H AIR HANDLER HEAT PUMP SYSTEM. Job Name: System Reference:

Similar documents
SUBMITTAL DATA: PVA-A42AA7 & PUZ-A42NKA7(-BS) 42,000 BTU/H AIR HANDLER HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A42NKA7

SUBMITTAL DATA: PVA-A36AA7 & PUY-A36NKA7(-BS) 36,000 BTU/H AIR HANDLER AIR-CONDITIONING SYSTEM. Job Name: System Reference: Outdoor Unit: PUY-A36NKA7

SUBMITTAL DATA: PEAD-A42AA7 & PUZ-A42NKA7(-BS) 42,000 BTU/H HORIZONTAL-DUCTED HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A42NKA7

SUBMITTAL DATA: PEAD-A24AA7 & PUY-A24NHA7(-BS) 24,000 BTU/H HORIZONTAL-DUCTED AIR-CONDITIONING SYSTEM. Job Name: System Reference:

SUBMITTAL DATA: PEAD-A30AA7 & PUZ-A30NHA7(-BS) 30,000 BTU/H HORIZONTAL-DUCTED HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A30NHA7

SUBMITTAL DATA: PEAD-A12AA7 & PUZ-A12NKA7(-BS) 12,000 BTU/H HORIZONTAL-DUCTED HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A12NKA7

SUBMITTAL DATA: PCA-A24KA7 & PUZ-A24NHA7(-BS) 24,000 BTU/H CEILING-SUSPENDED HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A24NHA7

SUBMITTAL DATA: PLA-A36EA7 & PUZ-A36NKA7(-BS) 36,000 BTU/H CEILING-CASSETTE HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A36NKA7

SUBMITTAL DATA: PLA-A24EA7 & PUZ-A24NHA7(-BS) 24,000 BTU/H CEILING-CASSETTE HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUY-A24NHA7

SUBMITTAL DATA: PLA-A12EA7 & PUZ-A12NKA7(-BS) 12,000 BTU/H CEILING-CASSETTE HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A12NKA7

SUBMITTAL DATA: MSY-GL24NA & MUY-GL24NA 24,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM. System Reference:

SUBMITTAL DATA: MSY-GL12NA & MUY-GL12NA 12,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM. System Reference:

SUBMITTAL DATA: SLZ-KA09NA & SUZ-KA09NA 9,000 BTU/H CEILING-CASSETTE HEAT-PUMP SYSTEMS. Cooling 4. Heating

M-SERIES SUBMITTAL DATA: SEZ-KD15NA4** & SUZ-KA15NA. Job Name: Location: Date: Submitted to: For Reference Approval Construction

SUBMITTAL DATA: SLZ-KA09NA... 9,000 BTU/H CEILING-CASSETTE INDOOR UNIT FOR MXZ-B MULTI-ZONE HEAT-PUMP SYSTEMS

SUBMITTAL DATA: MSZ-FH06NA & MUZ-FH06NA 6,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM. Electrical Power Requirements. Indoor / Outdoor A 1 / 11

1. INDOOR UNITS... MSZ-FH-3 2. OUTDOOR UNITS... MSZ-FH-4 3. SYSTEM... MSZ-FH-5

M-SERIES PRODUCT CATALOG

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System

The Hyper-Heat Advantage

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To

Power Input (Max) 1,500 W Dehumidification 1.7 pt/hr HSPF 10.5 COP 4.2 Compressor Type DC Inverter Driven 2-Stage Rotary Heating at 17 F FLA 8.

Submitted to: For Reference Approval Construction

Innovative Ductless Mini Split Solution Submittal Data: GUHD24ND3FO/GKH24D3FI Job Name Location Date

Ductless Split Systems Concealed Duct Heat Pumps

18-2 AWG / 300V THHN Operating Range MCA 2.0A Cooling (Max) 118 F (48 C) MOCP/Breaker Size 15A (Min) 0 F (-18 C)

Submittal Data: UMAT48HP230V1AF. Job Name Location Date. Submitted To

15A 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

P-Series Full-line Catalog. Commercial-grade Applications. Smart, Efficient INVERTER-driven Ductless and Ducted Comfort Systems.

Product Data. 38GJQ MULTI-ZONE DUCTLESS SYSTEM MATCHED WITH 40GRQ / 40GJB / 40GJC / 40GJD / 40GJF Indoor Units Sizes 18, 24, 30, 36, 42, 48 and 56

P-Series Full-line Catalog. Commercial-grade Applications. Smart, Efficient INVERTER-driven Ductless and Ducted Comfort Systems.

PUHZ-SHW140YHA PUHZ-SHW230YKA

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

15A Operating Range Communication Wire Size 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

Market District Commons. Black Oak Engineering. Daikin Ductless Heat Pump Split Systems N/A N/A M001. Plans. Fujitsu ductless heat pump systems

Ductless Split Systems Wall-mounted, Single Zone Heat Pump

ZONED COMFORT SOLUTIONS

High Efficiency, Powerful Heating and Cooling HEAT PUMP PEH-7, 8, 10 AIR COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS. Series

SUBMITTAL M4MCW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

SUBMITTAL M4MCW1509A-SUB-1C. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

SUBMITTAL M4MHW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MHW1509A1N0A M4THS1509A11NA TAG:

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Samsung 360 Cassette, Single Zone, Split System

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

Project ID: 9217 Project name: Fuller Lake Arena Address: Fuller Lake, BC V0R 1K5 Project Type: Sports Complex / Civic Center

Residential and Light Commercial Ductless Systems Catalog

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

Ductless Split Systems Ceiling Cassette Heat Pumps

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

Rooftop Units 60HZ. PACKAGED HEAT PUMPS 13HPP / rhp13 PRODUCT SPECIFICATIONS 13 HPP 36 A P - 1 A RHP 13 A 36 T - 1 A MODEL NUMBER IDENTIFICATION

P-Series Full-line Catalog. Commercial-grade Applications. Smart, Efficient INVERTER-driven Ductless and Ducted Comfort Systems.

SUBMITTAL DATA - OUTDOOR UNIT VEP075N432G VRF HEAT PUMP

Condensing Units & Air Handlers

Ductless Split Systems Wall-mounted, Multizone Heat Pump

DUCTLESS FULL LINE CATALOG

Submittal Sheet AIR-CON MULTI-SPLIT II. High-Wall Cassette Duct Floor and Ceiling AMTCM4H4R18

Cold Remedies. SamsungHVAC.com. Product Registration Required Conditions Apply

13 SEER CONDENSING UNITS & AIR HANDLERS

TECHNICAL & SERVICE MANUAL

Engineering Data Book

TECHNICAL SPECIFICATIONS

Single Zone Air Conditioner SVC MANUAL (Exploded View)

Product Data INDUSTRY LEADING FEATURES / BENEFITS

P-SERIES PRODUCT CATALOGUE AIR CONDITIONER & HEAT PUMP

ELECTRICAL QUANTITY WEIGHT (LB)

SUBMITTAL M4MLW1809A-SUB-1A. Specifications 18 SERIES. Single Zone Mini-Split Inverter System M4MLW1809A1N0A M4TLS1809A11NA TAG:

TECHNICAL SPECIFICATIONS

Engineering Data Book

Digital Inverter 4 series 8 & 10HP

SUBMITTAL AG015KSVAJH/AA Samsung DVM Heat Pump Chiller. Submitted to Reference Approval Construction Unit Designation Schedule #

R4H4. Product Specifications

TECHNICAL SPECIFICATIONS

Product Data INDUSTRY LEADING FEATURES / BENEFITS

Lennox 8 Series Single Zone - R-410A

DESIGN & TECHNICAL MANUAL

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Engineering Data Book

INVERTER-driven. Split-ductless and ducted Comfort Systems M Series Full Line Catalog.

BCE4 PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER WITH VARIABLE SPEED APPLICATION INSTALLATION CABINET COMPONENTS CONTROLS WARRANTY

VARIABLE REFRIGERANT FLOW (VRF) FULL LINE CATALOG

Air Conditioning & Heating. Ductless Product Catalog

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

Product Data. Features/Benefits. 40QKB024,036 40QKE024,036,048 Cooling Only and Heat Pump In-Ceiling Cassettes. 2to4NominalTons

DESIGN & TECHNICAL MANUAL

Engineering Data Book

Ductless Split Systems. J Series. The Next Generation of Ductless Split Systems

A single answer for multiple zones.

Heating & Cooling Products

N4H4. Product Specifications

NEW DAIKIN FTQ SERIES HEATING AND COOLING SYSTEMS. MULTI-POSITIONAL AIR HANDLER Up to 16 SEER / Up to 10.4 HSPF / Up to 12.5 EER

R4H4. Product Specifications

1 TECHNICAL CHANGES. MUZ-A09NA MUZ-A09NA - 1 MUZ-A09NA - U1 MUZ-A09NA - U2 1. Refrigerant system diagram has been changed.

P-SERIES PRODUCT CATALOGUE AIR CONDITIONER & HEAT PUMP

Engineering Data Book

PAD3. Product Specifications. 13 SEER PACKAGE AIR CONDITIONER, 2 to 5 TONS Single Phase, 208/230 V, 60 Hz REFRIGERATION CIRCUIT

Transcription:

P-SERIES SUBMITTAL DATA: & 36,000 BTU/H AIR HANDLER HEAT PUMP SYSTEM Job Name: System Reference: Date: : : INDOOR UNIT FEATURES Ducted air handler provides a solution to cool and heat large zones Highly efficient totally enclosed ECM motor Selectable external static pressure: 0.30, 0.50 and 0.80 in.wg with 3 fan speeds at each static setting 1 inch R4.2 fiberglass free insulation reduces condensation and boosts efficiency Positive pressure cabinet with air leakage of less than 1.0% at 1.0 in. w.g. Unique blow through design allows simple coil cleaning when the blower is removed Multi-position installation: horizontal (left or right), vertical (up or down). For downflow configurations, the CMA-1 is recommended for proper management of condensate to prevent water blow-off in certain conditions Optional electric heat kit for additional heat capacity Optional humidifier control and ERV control OUTDOOR UNIT FEATURES Variable speed INVERTER-driven compressor High heating capacity: flash injection circuit maintains 100% heating capacity at 5 F outdoor temperature Wide heating range: heating performance down to -13 F (average of 80% heating capacity) High speed heating at start up: Hyper-Heating INVERTER reduces the time for heating at start up by about half compared to standard models Suction accumulator pre-charged with refrigerant volume for piping length up to 100 ft. Twinning of two indoor units possible with the 36 kbtu/h model High pressure/temperature protection

SPECIFICATIONS: & Model Number Cooling*1 Heating at 47 F*2 Heating at 17 F *3 Heating at 5 F *4 Efficiency Electrical Maximum Capacity Btu/h 36,000 Rated Capacity Btu/h 33,000 Minimum Capacity Btu/h 18,000 Maximum Power Input W 3,040 Rated Power Input W 2,640 Moisture Removal Pints/h 7.4 Sensible Heat Factor 0.74 Power Factor % 87.6 Maximum Capacity Btu/h 40,000 Rated Capacity Btu/h 38,000 Minimum Capacity Btu/h 18,000 Maximum Power Input W 3,360 Rated Power Input W 3,040 Power Factor % 88.7 Maximum Capacity Btu/h 38,000 Rated Capacity Btu/h 29,000 Maximum Power Input W 5,400 Rated Power Input W 3,230 Maximum Capacity Btu/h 38,000 Maximum Power Input W 6,100 SEER 17.8 EER *1 12.5 HSPF (IV) 11.0 COP at 47 F *2 3.66 COP at 17 F in Maximum Capacity 2.06 COP at 5 F in Maximum Capacity 1.82 ENERGY STAR Certified (ENERGY STAR products are thirdparty certified by an EPA-recognized Certification Body) Voltage, Phase, Frequency Yes 208 / 230V, 1-phase, 60 Hz Guaranteed Voltage Range V AC 198 253 Voltage: Indoor - Outdoor, S1-S2 V AC 208V / 230

SPECIFICATIONS: & Model Number Operating Temperature Range Voltage: Indoor - Outdoor, S2-S3 V DC 24 Voltage: Indoor - Remote controller V DC 12 Recommended Fuse/Breaker Size A 30 Recommended Wire Size (Indoor - Outdoor) AWG 14 MCA A 5.50 Fan Motor Full Load Amperage A 4.40 Fan Motor Output W 430 Airflow Rate, Dry CFM 788-956-1125 Airflow Rate, Wet CFM n/a External Static Pressure in.wg 0.30-0.50-0.80 Sound Pressure Level db(a) 30-34-38 Drain Pipe Size In. (mm) 3/4 FPT (19.05) Condensate Lift Mechanism, Maximum Distance Heat Exchanger Type External Finish Color Unit Dimensions // Grille Dimensions Ft. (m) n/a Plate fin coil Galvanized steel cabinet-powder coated Slate Gray W: In. (mm) 25 (635) D: In. (mm) 21-5/8 (548) H: In. (mm) 59-1/2 (1511) Unit Weight Lbs. (kg) 172 (78) Cooling Intake Air Temp (Maximum / Minimum) F 90 DB, 73 WB / 66 DB, 59 WB Heating Intake Air Temp (Maximum / Minimum) F 82 DB / 50 DB MCA A 28 MOCP A 40 Fan Motor Full Load Amperage A 0.4+0.4 Fan Motor Output W 86+86 Airflow Rate CFM 3,530 Refrigerant Control Defrost Method Heat Exchanger Type Electronic Expansion Valve Reverse Cycle Cross fin

SPECIFICATIONS: & Model Number Operating Temperature Range Refrigerant Piping Sound Pressure Level, Cooling*1 db(a) 52 Sound Pressure Level, Heating*2 db(a) 53 Compressor Type INVERTER-Driven Twin Rotary Compressor Model ANB33FJEMT Compressor Rated Load Amps A 18 Compressor Locked Rotor Amps A 27.5 Compressor Oil Type // Charge oz. FV50S // 45 External Finish Color Ivory Munsell 3Y 7.8/1.1 Base Pan Heater n/a W: In. (mm) 37-3/8 (950) Unit Dimensions D: In. (mm) 13 + 1-3/16 (330 + 30) H: In. (mm) 53-1/8 (1,350) W: In. (mm) 40-15/16 (1,040) Package Dimensions D: In. (mm) 17-11/16 (450) H: In. (mm) 56-11/16 (1,440) Unit Weight Lbs. (kg) 265 (120) Package Weight Lbs. (kg) 289 (131) Cooling Intake Air Temp (Maximum / Minimum) F 115 DB / 0* DB Heating Intake Air Temp (Maximum / Minimum) F 70 DB, 59 WB / -13 DB, -13 WB Thermal Lock-out / Re-start Temperatures** F n/a Type R410A Charge Lbs, oz 12 Gas Pipe Size O.D. (Flared) In.(mm) 5/8 (15.88) Liquid Pipe Size O.D. (Flared) In.(mm) 3/8 (9.52) Maximum Piping Length Ft. (m) 245 (75) Maximum Height Difference Ft. (m) 100 (30) Maximum Number of Bends 15

SPECIFICATIONS: & AHRI Rated Conditions (Rated data is determined at a fixed compressor speed) *1 Cooling (Indoor // Outdoor) F 80 F DB, 67 F WB // 95 F DB, 75 F WB *2 Heating at 47 F (Indoor // Outdoor) F 70 F DB, 60 F WB // 47 F DB, 43 F WB *3 Heating at 17 F (Indoor // Outdoor) F 70 F DB, 60 F WB // 17 F DB, 15 F WB Conditions *4 Heating at 5 F (Indoor // Outdoor) F 70 F DB, 60 F WB // -4 F DB, -5 F WB Notes *Wind baffles required to operate below 23 F DB in cooling mode. PUZ with wind baffle: 0 F - 115 F. **System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures Notes:

ACCESSORIES: Electric Heat Kit Electric Heat Kit Separate Power Terminal Block Kit 3-Pole Disconnect Switch (30A/600V/UL) [fits 2" X 4" utility box] Drain Pan Level Sensor (Control for indoor unit shut off to prevent drain pan overflow) MaxiBlue Advanced Blue Diamond Mini-Condensation pump w/ Reservoir & Sensor (110V) up to 48,000 Btu/h [recommended] MaxiBlue Advanced Blue Diamond Mini-Condensation pump w/ Reservoir & Sensor (208/230V) up to 48,000 Btu/h [recommended] EH10-MPA-L EH15-MPAS-L SPTB1 TAZ-MS303 DPLS2 X87-711 - 110 X87-721 - 208/230 Extension Cord for Blue Diamond Pump C13-103 MegaBlue Blue Diamond Condensate Pump (110-230V) up to 170,000 Btu/h X87-835 Remote Sensor (Extensible) Connector Cable for Remote Display Connector for CN32 (Remote ON/OFF) Connector for CN24 (Back up Heating) Connector for CN30 (LLC) Remote Operation Adapter (with wire terminals for remote ON/OFF and operation status/ error) External Fan / Heater Control Relay Adapter Backlit, Wall-mounted, Wireless Wireless Adapter BACnet and Modbus Interface Wall-mounted, Wired Wired Remote Controller PAC-SE41TS-E PAC-725AD-E(10pcs) PAC-SE55RA-E PAC-SE56RA-E PAC-SE57RA-E PAC-SF40RM-E *1 CN24RELAY-KIT-CM3 MHK1 PAC-USWHS002-WF-1 PAC-UKPRC001-CN-1 PAC-YT53CRAU-J PAR-33MAA-J T-STAT Interface PAC-US444CN-1 *2 Signal Receiver Wireless Remote Controller Wireless Signal Receiver Wire for Remote ON/OFF with CN32 connector Lockdown Bracket for Wireless, Hand-held, Remote Controllers *1 Unable to use with wireless remote controller *2 Unable to use with the electric heat time delay PAR-SA9CA-E PAR-FL32MA-E PAR-FA32MA-E PAC-715AD RCMKP1CB

ACCESSORIES: Twinning Distribution Pipe (50:50) MSDD-50TR-E Air Outlet Guide PAC-SG59SG-E (two pieces are required) Front Wind Baffle WB-PA5 (two pieces are required) Hail Guard HG-A3 Drain Socket PAC-SG61DS-E Centralized Drain Pan PAC-SH97DP-E Control/Service Tool PAC-SK52ST Wall Mounting Bracket (Powder-coated Steel) QCWB2000M-1 Wall Mounting Bracket (316 Series Stainless Steel) QSWBSS M-NET Control Adapter for Building Management System PAC-SF83MA-E M-NET Control Adapter for Building Management System PAC-SJ19MA-E Mounting Pad 24" x 42" x 3" ULTRILITE2 3-1/4 inch Mounting Base - Pair (Plastic) DSD-400N MiniSplit Mounting Stand-Dual Fan Models - 12" QSMS1202M MiniSplit Mounting Stand-Dual Fan Models - 18" QSMS1802M MiniSplit Mounting Stand-Dual Fan Models - 24" QSMS2402M 3/8 x 5/8 x 10' / 1/2" Lineset (Twin-Tube Insulation) MPLS385812T-10 3/8 x 5/8 x 15' / 1/2" Lineset (Twin-Tube Insulation) MPLS385812T-15 3/8 x 5/8 x 30' / 1/2" Lineset (Twin-Tube Insulation) MPLS385812T-30 3/8 x 5/8 x 50' / 1/2" Lineset (Twin-Tube Insulation) MPLS385812T-50 3/8 x 5/8 x 65' / 1/2" Lineset (Twin-Tube Insulation) MPLS385812T-65 3/8 x 5/8 x 100' / 1/2" Lineset (Twin-Tube Insulation) MPLS385812T-100

DIMENSIONS: & INDOOR UNIT PVA-A12, 18, 24, 30, 36, 42AA7 Left side 2-ø4.6 Burring ring Holes for electric heat installation 1 Refrigerant piping brazing flare connection(gas) 2 Refrigerant piping brazing flare connection(liquid) ø26 Knockout Hole Secondary drain pipe (Indoor /Outdoor (Emergency ddraining) unit connection) Primary P drain pipe (Gravity drain) 77.8(3-1/8) (Horizontal left) 66(2-5/8) ø26 Knockout Hole (Indoor / Outdoor unit connection) G 70(2-13/16) H 55(2-3/16) Top 8(3/8) 43(1-3/4) 8(3/8) 92(3-5/8) 30(1-3/16) Secondary drain pipe (Emergency ddraining) 55(2-3/16) 3 Air filter Bottom B(Duct) 28.8(1-3/16) C 76(3) Air outlet Air inlet A ø26 Knockout Hole (Remote controller t transmission) Terminal block (Remote controller t transmission) Terminal block (Indoor / Outdoor unit connection) Control bbox 43(1-3/4) Primary drain pipe (Gravity drain) Secondary drain pipe (Emergency ddraining) (Horizontal Right) Primary drain pipe (Gravity drain) D 525.5(20-3/4) 8(3/8) F 55(2-3/16) 13.2(9/16) E 24(15/16) 548(21-5/8) 117.4 (4-5/8) 402(15-7/8) (Duct) Model 3 Nominal Filter sisize Duct Connection J 36.8(1-1/2) 508X508X25.4 477X402 P PVA-A30AA4 (20X20X1) (18-13/16X15-7/8) Model A B C D E F G H J 1 Gas pipe 2 Liquid pipe Unit: mm (in.) Model A B C D E F G H J P VA-A36AA4 Gas Pipe 508X609.6X25.4 Liquid Pipe 579X402 PVA-A12AA7 534 477 382.6 266.5 1378 737 953.5 792 461 (20X24X1) (22-13/16X15-7/8) P VA-A30AA4 P VA-A42AA4 432 (17) 376 (14-13/16) 281 (11-1/8) 224 (8-7/8) 1275 (50-1/4) 680 (26-13/16) 823 (32-7/16) 735.5 (29) 360 (14-3/16) Φ 12.7 (1/2) Φ 6.35 (1/4) PVA-A18AA7 (21) (18-13/16) (15-1/8) (10-1/2) (54-1/4) (29-1/16) (37-9/16) (31-3/16) (18-3/16) Ø15.88 Ø9.52 PVA-A24AA7 534 (21) 477 (18-13/16) 382.6 (15-1/8) 266.5 (10-1/2) 1378 (54-1/4) 737 (29-1/16) 953.5 (37-9/16) 792 (31-3/16) 461 (18-3/16) PVA-A30AA7 P VA-A36AA4 635 579 484.6 317.5 1511 798.5 1053 853.5 563 (5/8) (3/8) Φ 15.88 (5/8) Φ 9.52 (3/8) P VA-A42AA4 (25) (22-13/16) (19-1/8) (12-1/2) (59-1/2) (31-7/16) (41-1/2) (33-5/8) (22-3/16) 635 (25) 579 (22-13/16) 484.6 (19-1/8) 317.5 (12-1/2) 1511 (59-1/2) 798.5 (31-7/16) 1053 (41-1/2) 853.5 (33-5/8) 563 (22-3/16) PVA-A42AA7 50.8(2) 470(18-9/16) Note 1.Keep the se service space for maintenance at at the the front front.. Front Top ø26 Knockout Hole (Remote controller t transmission) Bottom Unit:mm(in.) Right side Model Nominal Filter Size Duct Connection PVA-A12AA7 508 x 406.4 x 25.4 376 x 402 PVA-A18AA7 (20 x 16 x 1) (14-13/16 x 15-7/8) PVA-A24AA7 508 x 508 x 25.4 477 x 402 PVA-A30AA7 (20 x 20 x 1) (18-13/16 x 15-7/8) 508 x 609.6 x 25.4 579 x 402 PVA-A42AA7 (20 x 24 x 1) (22-13/16 x 15-7/8) 17 2016 Mitsubishi Electric US, Inc.

DIMENSIONS: & OCH607 10 1 FREE SPACE (Around the unit) 2 SERVICE SPACE 3 FOUNDATION BOLTS 4 PIPING-WIRING DIRECTIONS The diagram below shows a basic example. Explanation of particular details are given in the installation manuals, etc. 10mm <3/8> 1000mm <39-3/8> FREE 150mm <5-29/32> 10mm <3/8> Example of Notes 10mm<3/8> Service space 1 Refrigerant GAS pipe connection (FLARE)[15.88<5/8> 2 Refrigerant LIQUID pipe connection (FLARE)[ 9.52<3/8> *1 Indication of STOP VALVE connection location. Dimensions of space needed for service access are shown in the below diagram. 500mm <19-11/16> 150mm <5-29/32> 500mm <19-11/16> Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts. (Bolts and washers must be purchased locally.) 30mm <1-3/16> <Foundation bolt height> FOUNDATION Piping and wiring connections can be made from 4 directions: front, right, rear and below. Rear Air Intake Side Air Intake Side Air Intake 1350<53-5/32> 635<25> 330<13> 30<1-3/16> Rear Air Intake 175<6-7/8> Air Discharge 600<23-5/8> 950<37-13/32> 322<12-11/16> Earth terminal 66<2-5/8> 2-U Shaped notched hole (Foundation Bolt M10<W3/8>) 175<6-7/8> 42<1-21/32> 2-12 o 36 Oval hole (Foundation Bolt M10<W3/8>) Unit : mm<inch> Terminal Block Left Power supply wiring Right Indoor/Outdoor wiring Service panel 19<3/4> 45<1-25/32> 56<2-7/32> 370<14-9/16> 417<16-13/32> 53<2-3/32> 28<1-3/32> 1076<42-3/8> 6 OUTLINES AND DIMENSIONS Air intake 371<14-19/32> 23<29/32> 1 2 * 1 443<17-7/16> * 1 447<17-19/32> Piping Knockout Hole Details Front trunking hole 40<1-9/16> Front piping hole Conduit hole (2-[27<1-1/16>Knockout) [92 <3-5/8> 92<3-5/8> 65<2-9/16> 45<1-25/32> 27<1-1/16> 55<2-3/16> 63 <2-1/2> 23<29/32> 73<2-7/8> Right piping hole 23<29/32> 27<1-1/16> 92<3-5/8> 73<2-7/8> 63<2-1/2> 75 <2-31/32> 40<1-9/16> 19<3/4> 55<2-3/16> Conduit hole (2-[27<1-1/16>Knockout) [92 <3-5/8> 92<3-5/8> Right trunking hole 45<1-25/32> 40<1-9/16> Conduit hole (2-[27<1-1/16>Knockout) 2-[22.2<7/8> Rear trunking hole 23<29/32> 73<2-7/8> 63<2-1/2> 27<1-1/16> 55<2-3/16> 92<3-5/8> 65<2-9/16> [92 <3-5/8> Rear piping hole When installing the conduit. Set the attachment to the inner side of each panel. 40<1-9/16> 74<2-19/32> 1/2 Conduit attachment 31<1-7/32> 81<3-3/16> 219<8-5/8> 30<1-3/16> 220 <8-21/32> 145 145 145 <5-23/32> <5-23/32> <5-23/32> 71<2-13/16> 71<2-13/16> Drain hole 5-[33<1-5/16> Front piping cover Rear piping cover Bottom piping hole 1340 Satellite Boulevard, Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com FORM# / - 201709