Wiring Diagrams. 9AB4-12 Air-Cooled Remote Condenser INDEX OPERATING SEQUENCE ACCESSORIES LEGEND AND NOTES FOR FIG. 1-6

Similar documents
AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.

Wiring Diagrams DIAGRAM INDEX

Wiring Diagrams. 38ARZ ARS ARD Air-Cooled Condensing Units 50/60 Hz

Wiring Diagrams Units Produced After April 20, 2009

SINGLE-PACKAGE ROOFTOP HEAT PUMP UNITS INDEX. VOLTAGE (3 Ph, 60 Hz) ACCESSORIES

E1 Electrical Fundamentals. # 4 - Symbols and Wiring Diagrams

wiring diagrams AIR-COOLED CONDENSING UNITS SPLIT-SYTEM HEAT PUMP UNIT UNITS PRODUCED AFTER SEPTEMBER 1996 DIAGRAM INDEX

Installation Instructions

INSTALLATION INSTRUCTIONS Low Ambient Kit NASA201LA, NASA401LA

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Air Conditioners and Heat Pumps Using R-22 Refrigerant

Product Data PH13(N,P)R FEATURES AND BENEFITS. SPLIT SYSTEM HEAT PUMP For Use With R Refrigerant 1---1/2 TO 5 TONS ( )

Installation Instructions

Installation Instructions

ACNF Series Ceiling-Mount Air Handlers 1½ to 2½ Tons

38TKB Air Conditioning Unit Installation and Start-Up Instructions

Split-System Residential Air Conditioners and Heat Pumps Service Manual

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

Installation Instructions

Installation, Start-Up and Service Instructions

Product Data. Features/Benefits. 40QA Cooling Only and Heat Pump Ceiling Suspended Fan Coil. 1 1 / 2 to 5 Nominal Tons

AllStyle Coil Company, LP 7037 Brittmore Houston, TX Phone Fax

Product Data. Features/Benefits. 40QKB024,036 40QKE024,036,048 Cooling Only and Heat Pump In-Ceiling Cassettes. 2to4NominalTons

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

Installation Instructions / User s Manual NAXA00101DB Communicating Daughter Board

FAST-STAT Black. Red. Gray. Purple. Orange. Orange. Black. Black. Compressor Stage 1 Heat Control. Transformer Transformer L1 L2

This parts list is current as of the above revision date. See for the current revision.

Refrigeration / Air Conditioning Systems Circuit Drawings. Student Resource Package No: NR 24

Installation, Operation, and Troubleshooting Instructions

INSTALLATION INSTRUCTIONS

Installation Instructions

Wiring Diagrams DIAGRAM INDEX 208/230PW,XL;380PW;380/415PW;460PW;575PW XL;380/415XL;460XL;575XL ,070

User s Information and Installation Instructions

Product Data PA13 AIR CONDITIONER 1 AND 3 PHASE 1-1/2-5 TONS ( ) FEATURES AND BENEFITS AVAILABLE SIZES:

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons

ICM 275. Replacement Description

Split system air conditioner. *S4BE - 018KB, 024KB, 030KB, 036KB (1.5, 2, 2.5, & 3 Ton) Series

INSTALLATION INSTRUCTIONS

Residential Split System Air Conditioners and Heat Pumps Using R-22 Refrigerant

Commercial High-Efficiency Condensing Units

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492)

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

LRP14HP/LRP14DF/LRP14AC/LRP14GE/LRP16GE/LRP16HP SERIES UNITS

MODELS W1LC220, 260 AND 320 STYLE B

User s Information/Installation Instructions

Reach-In Refrigerators and Freezers Service Manual

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

Commercial High-Efficiency Condensing Units

Installation Instructions

SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN - NOTICE -

INSTALLATION INSTRUCTIONS

Heat Pump Defrost Board Replacement Kit

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

Installation Instructions

Installation, Start-Up and Service Instructions

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

Installation Instructions HEAT COOL FAN POWER

DIGI3U. Zoning Systems. Installation Guide. That s all we do. Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications

MR3CCUHV Temperature/Defrost Control

AE October 1965 Reformatted October Hot Gas Bypass Control Systems

User s Information/Installation Instructions

SERVICE MANUAL FOR 6537 & 6538 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Air Conditioning Operation and Troubleshooting Matt Dunham

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

Installation Instructions

4TTB3030D1000B 208/230/1/60 4TTB3036D1000B 208/230/1/ RECIP /230/1/ RECIP YES YES

Installation Instructions

User s Information and Installation Instructions

IOM 410. Installation Operation Maintenance Information. UNIT COOLERS Super-Flo (SD Models) Easy-Flo (EF Models) Table of Contents

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

208/230/1/60 5/8 5/8 5/8 5/8 5/8 20 CLIMATUFF /230/1/

24 VAC SYSTEM CONTROL KIT

T8090A/Q682B Heating, Cooling, and Heating-Cooling Thermostat, Wallplate and Subbase

Z24 Wireless Zone Controller Professional Installation Guide

LOW PROFILE UNIT COOLER

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

Installation, Start-Up and Service Instructions

WCH5**4. Product Specifications

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

4TTB3060D1000B 208/230/1/60 35 SCROLL /230/1/ /8

INSTALLATION AND MAINTENANCE INSTRUCTIONS. MCE4 Series. Electric Cooling Package Unit. Save these instructions for future reference

Installation Instructions

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioners

Installation, Start-Up and Service Instructions

Product Data. Features/Benefits. 50ZP Single-Package Electric Cooling Units. 2 to 5 Nominal Tons

Installation Instructions

AHG**-0B Series Hydronic Air Handling Units

UNIT INFORMATION. Corp L7. Gauge Manifold Attachment... Page 30 Parts Arrangement... Page 8

PAJ3. Product Specifications

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTR6024-SF-1B. Split System Cooling 4TTR6024A1000B CAUTION CAUTION WARNING

Air-Cooled Split Systems Models ACU 075 to to 300 MBH 60 Hz, R-22 Refrigerant

Product Data. Features/Benefits All in one package high cooling efficiency, installation convenience, ease of accessibility for timesaving

PACKAGE AIR CONDITIONER

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

208/230/1/ CLIMATUFF /230/1/ YES NO NO PROPELLER 23-1 DIRECT / /230/1/ SPINE FIN

Product Data. 38CKD (60 Hz) 13 SEER Air Conditioner Sizes FEATURES AND BENEFITS AVAILABLE SIZES:

Transcription:

9AB4-12 Air-ooled Remote ondenser Wiring Diagrams INDEX UNIT 9AB DRAWING TYPE DRAWING NUMBER FIG. NO. 4,6 Label Diagram 9AB6-10816 1 8,12 Label Diagram 9AB12-10816 2 AESSORIES OMPONENT PART NO. FIG. NO. ontrol Box 50BA-900---344 3 ondensing Pressure Fan ontrol 09AB-900-001 09AB-900-032* 4 Motormaster III ontrol 32LT-900---301 5-7 Winter Start ontrol 38AE-900---021 8 Winter Start ontrol with Defrost Thermostat, ontrol Box, 9 and Liquid Line Solenoid Wind Baffle Details 10 *The 09AB-900-032 package includes 3 09AB-900-001 kits. LEGEND AND NOTES FOR FIG. 1-6 LEGEND ommon AP apacitor Equipment Ground FR Fan Motor Relay L Lead NE National Electrical ode QT Quadruple Terminal W1 Heat Stage 1 W2 Heat Stage 2 Field Splice Terminal Block onnection Marked Terminal Unmarked Terminal Factory Wiring Field Wiring NOTES: 1. Wiring for field power supply must be rated at 60 minimum. Use copper or copper-clad aluminum conductors only. 2. Replacement of factory wires must be with 90 (194 F) appliance wiring material or its equivalent. 3. Factory wiring is in accordance with NE. Field modifications or additions must be in compliance with all applicable codes. 4. Fan motors are inherently thermally protected. No overloads required. UNIT VOLTS PHASE HERTZ FAN FLA* 9AB4 200/230 1 60 2.3 Amps 9AB6 200/230 1 60 2.3 Amps 9AB8 200/230 1 60 4.6 Amps 9AB12 200/230 1 60 4.6 Amps *FLA Full Load Amps. 5. Maximum base unit fuse size 15 amps. OPERATING SEQUENE The 9AB unit uses single-pole contactors. Even when the fan is not running, power can still be applied to the fan motor. Open unit disconnect before servicing unit. NOTE: The 9AB condensing unit may be used with different compressor and evaporator combinations. The variation in combinations may affect the sequence of operation. When matched with 50BZ units, the 9AB sequence of operation is as follows: On a call for cooling, the thermostat closes and energizes terminals Y1 and W1 on the 50BZ unit low voltage terminal strip. The fan motor contactor (FR) is energized with 24 v through terminals W1 and. The fan will continue to run until the thermostat is satisfied. At that time, the thermostat will open W1, and the fan will stop immediately. On twostage units, a thermostat call for second stage cooling energizes W2 and the second 9AB condenser unit. When a 2-fan 9AB8 or 9AB12 unit is used on one refrigeration circuit of a 50BZ012,014 or 016 unit, then both condenser fans must be controlled from one contactor. This may be accomplished by using an accessory control box (part no. 50BA-900---344). For proper part load control, install a condensing pressure fan control (part no. 09AB-900- --001) on one fan for each circuit. If the condenser-fan motor overheats due to motor overload, or lack of cooling air, the internal fan protector will open the circuit internally in the motor, and the fan still stop. If a safety control in the unit opens, the 9AB condenser fan will not be affected and the fan will continue to run as long as the thermostat is closed. If the condenser is equipped with the Motormaster low ambient kit, the condenser-fan motor speed is controlled in response to the saturated condensing temperature. For outdoor temperatures down to 20 F, the controller maintains the condensing temperature at 100 F. Winter Start control accessory used with Motormaster control will bypass the lowpressure switch for 3 minutes on compressor start-up to allow system pressures to stabilize. On 9AB8 and 12 units the second condenser fan should be equipped with accessory fan cycling head pressure control. This control opens the power to the second condenser fan at outdoor temperatures below 60 F. If evaporator defrost thermostat is used, it will open if frost begins to form on the evaporator coil. This will stop the compressor but the outdoor fan will continue to run. In addition, a field-supplied selenoid valve (located at indoor unit, see Fig. 9 for wiring) wired in parallel with the compressor contactor coil, shuts off the liquid line to prevent refrigerant from returning to the compressor during the off cycle. The solenoid valve is recommended for all installations and is mandatory if piping length is more than 75 ft (22.9 m), or if liquid line diameter exceeds 5 8-inch. If two liquid line solenoid valves are used (units over 7 1 2 tons), add accessory relay-transformer package 38AE-900-001. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 4 P 111 atalog No. 530-966 Printed in U.S.A. Form 9AB-4W Pg 1 12-97 Replaces: 9AB-3W Tab 4a 4a

-INSTALLED AESSORIES ontrol Box (50BA-900---344) The 9AB units are not furnished with a relay or contactor to start the fan. One may be furnished in the indoor unit. A field-supplied relay or contactor installed in the 9AB control box or the accessory control box may be used. The accessory control box is a water tight box with two contactors which is mounted on the side of the 9AB condenser. This box uses 24 volt ac power from the indoor unit to control the 9AB unit. See Fig. 3 for typical wiring with a 9AB 8 or 12 (wiring is similar for 9AB 4 or 6, but only one contactor is used). The accessory control box can also be used to control two 9AB units used with one 50BZ unit. Winter Start (38AE-900-021) If units matched with 9AB condenser are equipped with a 27 psig low-pressure switch (i.e., 50BZ units), a 3-minute low-pressure switch bypass is recommended for operation below 50 F. See Fig. 8 for winter start control wiring. Evaporator Defrost Thermostat (50BB-900--- 001) The evaporator defrost thermostat is recommended for use with Winter Start control. Thermostat is installed on the evaporator coil. See Fig. 9 for proper wiring of defrost thermostat. ondensing Pressure Fan ontrol (09AB-900-001,032) This thermostat control is used with unit sizes 8 and 12 with two condenser fans. The control allows operation to 50 F by stopping the second condenser fan when the ambient temperature is below 60 F. Size 8 and 12 units with Motormaster control must have the control installed. See Fig. 4 for proper wiring. Motormaster ontrol (39LT-900-301) The accessory low-ambient Motormaster control kit contains a fan speed control device activated by a temperature sensor. The accessory controls condenser-fan motor speed in response to the saturated condensing temperature. For outdoor temperatures down to 20 F, it maintains the condensing temperature at 100 ± 10 F. The Motormaster control consists of a solid-state circuit on a printed circuit board encased in aluminum. The control must be fastened to a panel in the unit, and the sensor assembly (Fig. 7) mounted to a return bend on the unit condenser coil. Parts necessary for mounting control and sensor are included in the kit. Motormaster Pre-Installation onsiderations VERIFY WIRING Power wiring must comply with NE (National Electrical ode) and all local requirements. onfirm that supply voltage meets minimum voltage specified on the unit s rating plate and that it matches the voltage rating of the low-ambient kit. WINTER START If the indoor unit has a low-pressure switch, the unit should be modified for winter start control before installing the Motormaster control. ONDENSING PRESSURE FAN ONTROL The 9AB8 and 12 size units require accessory condensing pressure fan control installed on the second condenser fan when Motormaster control is applied to the first condenser fan. WIND BAFFLES The 9AB units are furnished with a wind baffle for the discharge. A similar baffle on the inlet is required with Motormaster control installation to prevent wind crosscurrents from causing abnormal operation as the fan is modulated. Fabricate and install inlet baffles per dimensions in Fig. 10. Motormaster ontrol Installation After completing the pre-installation checks, proceed as follows: DISONNET UNIT To prevent electric shock, open and tag all disconnects before modifying the condenser. 1. Mount ontrol Assembly. a. See Fig. 5 for the mounting location of the Motormaster low-ambient control on the side of the unit. b. Using the template supplied in accessory installation instructions, drill pilot holes for mounting the lowambient control. Use extreme caution to avoid drilling into any of the condenser tubes or return bends. c. Fasten control to unit with 4 No. 10 sheet metal screws and star lockwashers (provided in kit). NOTE: Lockwashers are required to ensure electrical ground with condenser unit. 2. Mount Sensor Assembly. The sensor assembly is fragile. Handle with care. a. See Fig. 5 to determine where to locate sensor on coil return bend. Recommended location is indicated by shaded return bend. As shown in Fig. 7, fasten sensor to return bend with the supplied screw, plate washers, and nut. See Table 1 for sensor temperature vs. resistance values. b. Remove the coil cover from the unit. Run a piece of flexible conduit from the bottom of Motormaster control to a hole drilled in the coil cover. Route sensor wire from Motormaster control through conduit to specified sensor location. c. oil and secure excess wire inside the unit near the sensor or next to the low ambient control; provide additional protection against abrasion or movement of the wire if necessary. Table 1 Sensor (Thermistor) Temperature vs Resistance TEMPERATURE NOMINAL RESISTANE F (Ohms) 60 16 7750 70 21 5900 77 25 5000 80 27 4650 90 32 3650 100 38 2875 110 43 2275 120 49 1850 3. Install ontrol Power Wiring. Wire the Motormaster control to the unit power circuit as shown in Fig. 6. Wire Motormaster control in series with fan motor. Power wiring must comply with all local and national requirements. 2

4. Verify Operation. Turn on the unit power and set the thermostat below the ambient room temperature. If the unit is equipped with a Time Guard II circuit (50BZ), wait at least 5 minutes. After the compressor starts, the fan speed is modulated according to the condensing temperature and then maintained until the set point is achieved. If fan motor does not start, verify the following conditions and correct as necessary: ondensing unit power is on. Power is present at fan motor relay contacts. Sensor wire connections inside the low-ambient control are tight. If the preceding conditions are met and fan motor still does not start, perform corrective procedures or replace components as follows: Jumper the power wires (-to-) in the Motormaster control. If the motor does not run, check motor wiring and run capacitor. Replace capacitor and motor if necessary. If the motor runs, ensure the fan motor is wired in series with the control. Refer to Fig. 6. If the fan motor runs when connected to the single-phase voltage supply but does not run when connected in series with the Motormaster control, AND the return bend where the sensor is mounted is warm, short the sensor leads (BLUto-). If the motor runs, replace the sensor. If the motor does not run, replace the control and sensor assembly. 3

OUTDOOR FAN MOTOR RUN APAITORS 200/230-1-60 ONTROL BOX TO BLDG GROUND L1 DISONNET PER NE Fig. 1 Schematic Diagram, Units 9AB4, 6 OUTDOOR FAN MOTOR TO BLDG GROUND 200/230--1-60 L1 (STAGE 1) L1 (STAGE 2) FROM INDOOR DISONNET PER NE RUN APAITORS ONTROL BOX Fig. 2 Schematic Diagram, Units 9AB8, 12 4

OUTDOOR FAN MOTOR TO BLDG GROUND FR1 L1 FR2 DISONNET PER NE RUN APAITORS FR1 FR2 W1 W2 24V ONTROL FROM INDOOR UNIT AESSORY ONTROL BOX ONTROL BOX Fig. 3 Field Wiring with Accessory ontrol Box 2 1 FAN MOTORS ARE INHERENTLY THERMALLY PROTETED (NO OVERLOADS REQUI) TO BLDG GROUND FR1 L1 FR2 DISONNET PER NE RUN APAITORS FR1 FR2 W1 24V ONTROL FROM INDOOR UNIT ONDENSING PROESSOR FAN ONTROL AESSORY ONTROL BOX W2 Fig. 4 Wiring Diagram; Accessory ondensing Pressure Fan ontrol, Units 9AB8 and 12 5

Fig. 5 Motormaster ontrol Location and Sensor Location OUTDOOR FAN MOTOR DISONNET PER NE L1 FR AP 1QT 1 AP 2QT 1 2 2 BLU MOTORMASTER ONTROL SENSOR Fig. 6 Motormaster ontrol Wiring Diagram Fig. 7 Sensor Mounting Detail 6

T TDR LPS LEGEND LPS Low-Pressure Switch ontactor oil TDR Time Delay Relay T Time Delay Relay oil Factory Wiring Field Wiring Fig.8 Wiring for Winter Start ontrol (Indoor Unit Wiring Modification) THERMOSTAT NE LASS II ONT OOL OFF AUTO T1 TB2 R G W1 Y1 X ORN LOGI 3 2 1 TDR1 ORN 2 X R1 LOGI 1 LO1 3 BLU LPS1 HPS1 BLU BLU 1 1 2 BLU 1 R 2 FR AESSORY RELAY BOX DT T TDR WINTER START LLS* 1 ompressor ontactor (In 50BZ) LO1 ycle-lo ontrol (In 50BZ) ONT ontinuous Fan R ontrol Relay (In 50BZ) DT Defrost Thermostat (Accessory) FR Fan Relay (Accessory) HPS1 High-Pressure Switch (In 50BZ) LLS Liquid Line Solenoid (Accessory) LEGND LPS1 Low-Pressure Switch (In 50BZ) NE National Electrical ode R1 Resistor T Timer TB2 Low-Voltage Terminal Block (In 50BZ) T Thermostat ooling TDR1 Time Guard Time Delay (In 50BZ) TDR Winter Start ontrol (Accessory) *Solenoid valve is field-supplied. Resistor may be internal to LO on some models. Fig. 9 Wiring for 9AB Unit with 50BZ Using Winter Start, Evaporator Defrost Thermostat, ontrol Box, and Liquid Line Solenoid Valve 7

ITEM 1 BAFFLES ITEM 3 ITEM 2 WIND BAFFLE LOATION 12 3/4" 7 1/2" DIAM 2 HOLES 22/32" 11 5/32" 1/2" 3/4" 7/32" DIAM 5 HOLES 30 18 9/16" 7 1/2" 1 3/16" 9/32" DIAM 2 HOLES MAKE ONE AS SHOWN AND ONE OPPOSITE HAND ITEM 1 (16 GA) 7/32" DIAM "F" HOLES 3/4" 6" 6" 27" 6" 6" 1 1/2" 9/32" DIAM 5 HOLES ITEM 2 (16 GA) 1" 30 7 1/2" 7 1/2" 10 5/8" 37 1/16" 10 1/8" 1 3/16" B D E A E E E ITEM 3 (18 GA) 1/2" DIMENSIONS (in.) UNIT SIZE A B D E F 9AB4 29 1 8 2 9 16 6 13 9AB6 38 1 2 7 1 4 6 13 9AB8 57 2 1 4 6 4 1 2 6 18 9AB12 75 1 2 6 7 8 6 13 3 4 6 18 NOTE: All 9AB units are shipped with one wind deflector assembly for the discharge air side of unit. When the 32LT Motormaster control is installed, field fabricate another identical wind deflector assembly and install on air inlet side of unit. Fig. 10 Wind Baffle Details opyright 1997 arrier orporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 4 P 111 atalog No. 530-966 Printed in U.S.A. Form 9AB-4W Pg 8 12-97 Replaces: 9AB-3W Tab 4a 4a