TECHNICAL DATA. Viking Technical Data may be found on Pip Cap: Brass UNS-C31400 or UNS-C31600

Similar documents
quick response Sprinkler 105a October 25, 2010

standard response large orifice dry

DRY VERTICAL SIDEWALL SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. 2. LISTINGS AND APPROVALS NOTE: Viking Dry Vertical Sidewall Sprinklers are NOT listed or approved. Sprinkler 103a.

standard response dry horizontal sidewall sprinklers

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

standard response/ quick response extended coverage

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

quick response ordinary hazard dry hsw sprinklers (8.0K) (VK275, VK277, & VK279)

standard response dry horizontal sidewall sprinklers

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK3311 (K4.2) TECHNICAL DATA

QUICK RESPONSE DRY CONCEALED PENDENT SPRINKLER VK194 TECHNICAL DATA

quick response sprinkler vk194 Sprinkler 104j January 1, 2011

TECHNICAL DATA OBSOLETE

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

December 14, 2015 Page 1 of 7 TECHNICAL DATA

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

microfast quick response Pendent sprinkler VK302 (K5.6)

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

quick response horizontal sidewall sprinkler vk360 (K8.0)

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

micromatic Standard response Horizontal Sidewall sprinkler

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

microfast and microfasthp quick conventional sprinklers

Standard response. elo sprinklers

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

TECHNICAL DATA. Page 1 of 6

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

TECHNICAL DATA. Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed.

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK120 (K8.0) TECHNICAL DATA

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

standard response elo upright and pendent sprinklers (storage-density/area)

QUICK RESPONSE FUSIBLE ELEMENT HSW SPRINKLERS VK308 AND HP VK320 (PART NOS AND 13955) TECHNICAL DATA

micromatic Standard response Horizontal Sidewall sprinkler

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

MICROMATIC STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK104 (K5.6) TECHNICAL DATA

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

TECHNICAL DATA. MicrofastHP QUICK RESPONSE FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK318 (K5.6)

standard/quick response extended coverage light and ordinary hazard elo sprinklers

micromatic standard response stainless steel sprinklers

TECHNICAL DATA. The Web site may include a more recent Frame Casting: Brass UNS-C84400

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

standard response Fusible Link Upright sprinkler VK204 (K8.0)

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

MICROMATIC STANDARD RESPONSE PENDENT SPRINKLER VK102 (K5.6) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

MicrofastHP QUICK RESPONSE HORIZONTAL SIDEWALL HIGH PRESSURE SPRINKLER VK319 (K5.6) TECHNICAL DATA

micromatic standard response Upright sprinkler VK100 (K5.6)

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) TECHNICAL DATA

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK470 (K3.0) TECHNICAL DATA

TECHNICAL DATA. Refer to Approval Chart 1 and Design Criteria for culus Listing requirements that must be followed.

TECHNICAL DATA vk470 (K3.0)

standard response elo upright sprinkler

STANDARD RESPONSE DRY PENDENT ELO SPRINKLERS TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS

Microfast quick response Fusible element hsw sprinkler

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK479 (K3.0) TECHNICAL DATA

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

MICROFAST SR/QR EXTENDED COVERAGE HSW SPRINKLER VK605 (K5.6) TECHNICAL DATA

microfast sr/qr extended coverage pendent sprinkler

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

standard response fusible link sidewall sprinkler VK112 (K5.6)

freedom residential pendent sprinkler vk466 (K5.2)

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK486 (K4.0) TECHNICAL DATA

TECHNICAL DATA. Page 1 of 5

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

standard response/qr extended coverage concealed pendent sprinklers vk614 & vk616

microfast quick response extended coverage hsw sprinkler vk606

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart.

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

HORIZON QUICK RESPONSE FLUSH PENDENT SPRINKLERS TECHNICAL DATA

STANDARD/quick. Sprinkler 42o. August 8, 2011

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

standard/quick response sprinklers (vk302 & vk352) 3. technical data Specifications: Available since Sprinkler 41g May 1, 2009

QUICK RESPONSE EXTENDED COVERAGE CONCEALED HSW SPRINKLER VK630 (K8.0) TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

mirage Quick response concealed pendent sprinkler vk464 (K8.0)

freedom residential horizontal sidewall sprinkler Vk450 (k4.2)

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK460 (K5.8) TECHNICAL DATA

MicrofastHP EC/QREC FUSIBLE ELEMENT HSW HIGH PRESSURE SPRINKLER VK613 (K5.6) TECHNICAL DATA

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

Transcription:

1. DESCRIPTION Viking Standard Response Dry Pendent Sprinklers are thermosensitive spray sprinklers suitable for use in areas subject to freezing. The sprinklers are designed for dry systems and preaction systems where it is necessary to prevent water or condensation from entering the drop nipple before sprinkler operation. They may also be installed in spaces subject to freezing and supplied from a wet system in an adjacent heated area. Viking Standard Response Dry Pendent Sprinklers are available in various finishes and temperature ratings to meet design requirements. The special Polyester coating has been investigated for installation in corrosive atmospheres. NOTE: When installed in some corrosive environments, the Polyester finish may change color. This natural discoloration over time is not in itself an indication of corrosion and should not be treated as such. All sprinklers installed in corrosive environments should be replaced or tested as described in NFPA 25 on a more frequent basis. 2. LISTINGS AND APPROVALS CE Certified: Standard EN 12259-1, EC-certificate of conformity 1725-CPD-H0009. 3. TECHNICAL DATA Specifications: Available since 2011. Minimum Operating Pressure: 0.35 bar* (5 psi) Maximum Working Pressure: 12 bar (175 psi) Factory tested pneumatically to 6.89 bar (100 psi) Thread size: 25 mm BSP or 1 NPT Nominal K-Factor: 80.6 metric** (5.6 U.S.) for all approved lengths. Glass-bulb fluid temperature rated to -55 C (-65 F) *The minimum operating pressure for CE Approvals ONLY is 0.35 bar (5 psi). **Metric K-factor measurement shown is when pressure is measured in bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. Material Standards: Frame Casting: Brass UNS-C84400 Deflector: Brass UNS-C26000 Bulb: Glass, nominal 5 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Compression Screw: Brass UNS-C36000 Viking Technical Data may be found on Pip Cap: Brass UNS-C31400 or UNS-C31600 The Viking Corporation s Web site at Pip Cap Adapter: Brass UNS-C36000 http://www.vikinggroupinc.com. Orifice: Copper UNS-C21000 The Web site may include a more recent Tube: ERW Hydraulic Steel Tube edition of this Technical Data Page. Barrel End and Threads: QM Brass Support (Internal): Stainless Steel UNS-S30400 Barrel: Steel Pipe UNS-G10260, Electrodeposited Epoxy Base finish Sleeve (for Adjustable Standard style only): Brass UNS-C26000 or UNS-C26800 Escutcheon Materials: Adjustable Standard Dry Escutcheons: Brass UNS-C26000 or UNS-C26800 Recessed Dry Escutcheons: Cold Rolled Steel UNS-G10080 Ordering Information: (Also refer to the current Viking price list.) Order Standard Response Dry Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish, the appropriate suffix for the temperature rating, and then the suffix for the length ( A dimension) to sprinkler base part number. Order in a specific length noted as the A dimension (see Figures 3 through 5). The A dimension is the distance from the face of the fitting (tee) to the desired finished surface of the ceiling. Replaces Form No. F_101811.Rev October 18, 2011 (Added P65 Warning.)

These sprinklers are listed and approved in lengths from 38.1 to 1,156 mm (1-1/2 to 45-1/2 ) for the adjustable standard style, 76.2 to 1,194 mm (3 to 47 ) for the plain barrel style, and 82.5 to 1,207 mm (3-1/4 to 47-1/2 ) for the adjustable recessed style. Lengths exceeding the standard lengths are available, with no approvals, on a made-to-order basis: Recessed Dry Pendent up to 1,664 mm (65-1/2 ). Adjustable Standard Dry Pendent up to 1,613 mm (63-1/2 ). Plain Barrel Dry Pendent up to 1,651 mm (65 ). Contact the manufacturer for more information. Finish Suffix: Brass = A, Chrome-Enloy = F, and White Polyester = M-/W Temperature Suffix: 68 C (155 F) = B, 79 C (175 F) = D, 93 C (200 F) = E, 141 C (286 F) = G For example, sprinkler VK1550 with 25 mm BSP Threads, a Chrome finish and a 68 C (155 F) temperature rating, and A length of 254 mm (10 ) = Part No. 17391FB10. Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the Sprinkler Accessories section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 07297W/B (available since 1991) B. Wrench for recessed sprinklers: Part No. 07565W/B (available since 1991) A ½ ratchet is required (not available from Viking). Sprinkler Guard: Chrome, with no listings or approvals, for installation on dry pendent sprinklers manufactured after May 1994 only (Part No. 08954). Replacement Escutcheons: A. Adjustable Standard Dry Escutcheon: Base Part No. 17442 B. Recessed Dry Escutcheon Cup: Base Part No. 05459A 4. INSTALLATION Refer to appropriate Installation Standards. Figure 1: Standard Sprinkler Wrench 07297W/B 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the internal parts to open the waterway. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Standard Response Dry Pendent Sprinkler is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking s current list price schedule or contact Viking directly.

Sprinkler Temperature Classification TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Nominal Temperature Rating 1 Maximum Ambient Ceiling Temperature 2 Bulb Color Ordinary 68 C (155 F) 38 C (100 F) Red Intermediate 79 C (175 F) 65 C (150 F) Yellow Intermediate 93 C (200 F) 65 C (150 F) Green High 141 C (286 F) 107 C (225 F) Blue Sprinkler Finishes: Brass, Chrome-Enloy (patents pending), and White Polyester Corrosion-Resistant Coating 3,4 : White Polyester in all temperature ratings 1 The sprinkler temperature rating is stamped on the deflector. Footnotes 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The Polyester coating is NOT corrosion proof. Prior to installation, verify through the end-user that the coating is compatible with or suitable for the proposed environment. Polyester coating is applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester coatings. 4 When installed in some corrosive environments, the Polyester finish may change color. This natural discoloration over time is not in itself an indication of corrosion and should not be treated as such. All sprinklers installed in corrosive environments should be replaced or tested as described in NFPA 25 on a more frequent basis. Figure 2: Wrench 07565W/B for Adjustable Recessed Dry Pendent Sprinklers

Sprinkler Base SIN Style Part No. 1 Approval Chart Standard Response Standard Orifice Dry Pendent Sprinklers Maximum 12 bar (175 PSI) WWP Thread Size Nominal K-Factor 2 Order Length Increment Listings and Approvals 4 NPT BSP U.S. metric 3 Inches mm culus NYC VdS LPCB 5 17391 VK1550 Adjustable -- 25 mm -- 80.6 1/2 12.7 -- -- -- -- A1 -- 17390 VK1550 Standard 1 -- 5.6 -- 1/2 12.7 -- -- -- -- A1 -- 17387 VK1590 Adjustable -- 25 mm -- 80.6 1/4 6.35 -- -- -- -- B2 -- 17386 VK1590 Recessed 1 -- 5.6 -- 1/4 6.35 -- -- -- -- B2 -- 17389 VK1510 Plain -- 25 mm -- 80.6 1/2 12.7 -- -- -- -- A3 -- 17388 VK1510 Barrel 1 -- 5.6 -- 1/2 12.7 -- -- -- -- A3 -- Approved Temperature Ratings A - 68 C (155 F), 79 C (175 F), 93 C (200 F), and 141 C (286 F) B - 68 C (155 F), 79 C (175 F), and 93 C (200 F) Approved Finishes and A Dimensions 1 - Chrome-Enloy with A dimensions 38.1 mm to 1,156 mm (1-1/2 to 45-1/2 ) 2 - Chrome-Enloy or White Polyester with A dimensions 82.5 to 1,207 mm (3-1/4 to 47-1/2 ) 3 - Chrome-Enloy or Brass with A dimensions 76.2 mm to 1,194 mm (3 to 47 ) Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 K-Factor applies for standard lengths ( A Dimensions indicated above). 3 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 4 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 5 Certified, Standard EN 12259-1, EC-certificate of conformity 1725-CPD-H0009. NOTE: When using CPVC fittings with Viking dry sprinklers, use only new Nibco Model 5012-S-Bl tees. When selecting other CPVC fittings, contact Viking Technical Services. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page DRY1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Figure 3: Adjustable Standard Dry Pendent Sprinkler Figure 4: Adjustable Recessed Dry Pendent Sprinkler Figure 5: Plain Barrel Dry Pendent Sprinkler

Figure 6: Dry Pendent Sprinkler Required Minimum Barrel Length Based on Ambient Temperature in the Protected Area (Adjustable Standard Dry Pendent Sprinkler is shown) Figure 7: Dry Sprinkler Seal (Adjustable Standard Dry Pendent Sprinkler is Shown) Replaces Form No. F_101811.Rev October 18, 2011 (Added P65 Warning.)