ASTM E 662 Rate of Smoke Generation of OXIFREE TM198"

Similar documents
ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"

CAN/ULC-S109 Flame Resistance of "Argo" Fabric

CAN/ULC-S109 Flame Resistance of "Xanadu" Material

ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC # TESTED: MARCH 27, 2009

CAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"

CAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"

CAN/ULC-S102 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

IMO Resolution MSC 61(67): Annex 1: Part 2

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

ASTM D Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet

NF X : Parts 1, 2, 3, 4 & 5

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

Public Comment No. 1-NFPA [ Section No ]

FUNDERMAX GMBH FIRE TEST REPORT

CAN/ULC-S102.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate"

~ 0."0... DESCRI PT ION OF TEST SAM PLE

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

FRANCE M & F RANKING ACCORDING TO NF F

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

Review Fire Test Report

STilE/DIVISION OF SHAW DESCRI.P TION 0 FT E STSAMP L E

We Identify and S.T.O.P. Your Noise Problems

GUARDIAN FIRE TESTING LABORATORIES, INC.

Heat and Smoke Release of a Ceiling-Installed Speaker

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

SIGMADEK, LTD. FIRE TEST REPORT

BS EN ISO : 2010

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

SHAW CONTRACT DESCRIPTION OF TEST SAMPLE

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

BCTC CARPET TECHNICAL CENTRE

BS EN ISO : 2010

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products

Public Comment No. 2-NFPA [ Section No ]

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

C-01 FIRE DECKS AND BULKHEADS

BS EN : 2001 & IEC :2000

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

EN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015

Contact person Date Reference Page Richard Johansson P (2) Fire Research

ZH Low Smoke 0-Halogen Flameretardant Identification Sleeves

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

Report of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC)

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES

CMZH Low Smoke 0-Halogen Flame- Retardant Mass Transit Tag

BS EN ISO : 2010

Inc. PACE 1 of 2. Testing Laboratory. AA TCC Test Method Electrostatic Propensity of Carpets TEST M ET"ODCON D UCTED

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

Fire Testing of Foams

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Abrasion Resistance of Fluoropolymer and polyester Coatings

Classification of Fire Performance of Wall and Ceiling Lining Materials

Report VNLF Test Report

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

Web Pages for Construction and Traveler Information Condition Reporting System 511 Phone Power. Data Processing and Response Formulation

BS 476: Part 6: 1989+A1:2009

Full Service Central Station Fire Alarm Listing Evaluation

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

/Mar/2014 Rev A

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor

STilE/DIVISION OF SHAW DESCRIPTION OF TEST SAMPLE

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

Analysis Report

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC

The Fire Resistance Performance Of Timber Or Mineral Composite Based Insulated Doorsets When Fitted With D & E Architectural Hardware Spring Hinges

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

Copper LAN cable. This specification describes the general requirements for AMP NETCONNECT* copper LAN cable.

Acoustical Surfaces, Inc.

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

TEST REPORT ON. TESTED FOR: Central States Manufacturing, Inc. 302 Jane Place Lowell, AR Phone: (800) Fax: (800)

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

STilE/DIVISION OF SHAW

Hazard Analysis, Mitigation, and Operating Procedures for (Laser name) Laser

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

Report of Surface Burning Characteristics Test on Acoustical Panel

ISO/TS TECHNICAL SPECIFICATION. Fire detection and alarm systems Part 9: Test fires for fire detectors

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798

Construction Heat CH-02 (up to 400,000 BTU) Record of Training Curriculum Document

NBS Smoke Density Chamber

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

Üntel is ready for CPR

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

Transcription:

ELECTRONIC COPY ASTM E 662 Rate of Smoke Generation of OXIFREE TM198" A Report To: Oxifree Global LLC 22955 State Highway 249, Suite 6 Tomball, TX 77375 USA Phone: (281) 251-7171 E-mail: ed.hall@oxifree.com Attention: Ed Hall Submitted By: Fire Testing Report No. 12-002-080(A) 3 pages + appendix Date: February 16, 2012

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198" Page 2 of 3 ACCREDITATION To ISO/IEC 17025 for a defined Scope of Testing by the International Accreditation Service SPECIFICATIONS OF ORDER Determine rate of smoke generation according to ASTM E 662, as per your Purchase Order No. 0110250 dated February 12, 2012. IDENTIFICATION Protective organic coating material, approximately 12 mm in thickness and identified as "Oxifree TM198". ( sample identification number 12-002-S0080) TEST RESULTS Specific Optical Density 300 250 200 150 100 50 ASTM E 662-09 FLAMING MODE 0 0 4 8 12 16 20 Time (minutes) Relative Room Humidity: 23% Test Duration: 20 min. Chamber Wall Temp: 35 C Flaming Mode Test #1 #2 #3 Average Specified Maxima Specific Optical Density at 1.5 minutes 9 69 17 32 100 Specific Optical Density at 4.0 minutes 52 206 157 138 200 Maximum Specific Optical Density 107 210 190 169 - Maximum Corrected Optical Density 107 191 179 159 -

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198" Page 3 of 3 TEST RESULTS (continued) Specific Optical Density ASTM E 662-09 300 NON-FLAMING MODE 250 200 150 100 50 0 0 4 8 12 16 20 Time (minutes) Relative Room Humidity: 23% Test Duration: 20 min. Chamber Wall Temp: 35 C Non-Flaming Mode Test #1 #2 #3 Average Specified Maxima Specific Optical Density at 1.5 minutes 2 3 2 2 100 Specific Optical Density at 4.0 minutes 12 13 13 13 200 Maximum Specific Optical Density 176 182 215 191 - Maximum Corrected Optical Density 174 182 212 189 - Observations In the flaming mode, sample melts and ignition was observed at the point of flame increasing to full ignition within 30 seconds of the test. Flaming dripping of the molten material was observed with visible smoke production. In the non-flaming mode, melting of the material was ovserved followed by visible smoke production. COMMENTS There are no current, specific Federal Railroad Administration requirements cited for coating materials when tested for rate of smoke generation using the ASTM E 662 test procedure. Therefore, the criterion cited in this report are for general requirements and are listed for reference purposes only. Note: This is an electronic copy of the report. Signatures are on file with the original report. Mel Garces, Fire Testing. Ian Smith, Fire Testing. Note: This report and service are covered under Canada Inc. Standard Terms and Conditions of Contract which may be found on the website (www.exova.com), or by calling 1-866-263-9268.

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198" APPENDIX (1 Page) Summaries of Test Procedures

ASTM E 662-09 This method of test covers a procedure for measuring the smoke generated by solid materials and assemblies in thickness up to and including 1 inch (25.4 mm). Measurement is made of the attenuation of a light beam by smoke (suspended solid or liquid particles) accumulating within a closed chamber due to nonflaming pyrolytic decomposition and flaming combustion. Results are expressed in terms of specific optical density (Ds), which is derived from a geometrical factor and the measured optical density (absorbance). As specified, the test samples are pre-dried for 24 hours at 60 C. Section 9.1 of ASTM E 662-09 states to then condition the specimens to "equilibrium (constant weight)" but does not specify a definition or procedure with respect to establishing the "constant weight". Therefore, prior to testing, the specimens are then conditioned for a minimum period of 24 hours at 50 ± 5% relative humidity and 23 ± 3 C. Three specimens, 3" square, are exposed to each mode of combustion. Prior to test initiation, the chamber wall temperature is established in the range of 33 to 37 C. The % light transmittance during the course of the combustion is recorded. These data are used to express the quantity of smoke in the form of Specific Optical Density based on the following formula, which assumes the applicability of Bouguer's law: Ds = (V/AL) log(100/t) = G log(100/t) = 132 log(100/t) Where: Ds = Specific Optical Density T = % Transmittance V = Chamber Volume (18 ft³) A = Exposed Area of the Sample (0.0456 ft²) L = Length of Light Path in Chamber (3.0 ft) G = Geometric Factor Among the parameters normally reported are: Ds 1.5 - specific optical density after 1.5 minutes Ds 4.0 - specific optical density after 4.0 minutes Dm Dm (corr) - maximum specific optical density at any time during the 20 minute test - Dm corrected for incidental deposits on the optical surfaces Transit authorities generally specify a maximum Ds 1.5 of 100 and a maximum Ds 4.0 of 200 in either flaming or non-flaming test mode.