ADVANCE ELECTRIC THERMAL STORE

Similar documents
ADVANCE ECB ELECTRIC COMBINATION BOILER

SEALED THERMAL STORE

ADVANCE UNIVERSAL MULTI-FUEL THERMAL STORE

ADVANCE STAINLESS STEEL UNVENTED HOT WATER SYSTEMS

THERMflow Thermal Store Cylinders

CUBEflow Thermal Store Tank

Installation and Commissioning Manual

ENERSTORE. Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

Advance Stainless Steel Unvented Hot Water Cylinders for Heat Pump Systems. Installation and Commissioning Manual

Tristor MF. Installation Guide

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

CPC-150-ABIAB. Important Installation Notes.

New Zip AquaFlo. Stainless steel cylinders for mains pressure hot water

PANDORA HEAT BANKS OXFORD BROOKES, HARCOURT HILL. Operation and Maintenance. THERMAL INTEGRATION LTD. Tel: Internet:

Installation & User Instructions

Unvented Electric Water Heater 10/15 litre Undersink

S T O R E R A N G E C Y L I N D E R & G R A N T FEATURES: GRANT MONOWAVE UNVENTED DIRECT AND INDIRECT SINGLE-COIL CYLINDERS

Design, Installation & Servicing Instructions. A total hot water and heating thermal store that can also make the most of renewable energy

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

Installation and User Instructions HS10U, HS15U.

INTRODUCTION STORAGE PRIOR TO INSTALLATION. Expansion Vessel Hose. Part No High Flow Rate Inlet Control Set. Part No.

CPC-180-ABNAB. 180 litres, 535mm x 1550mm high

MEGAFLO HE Iss 1

ELECTRIC COMBINATION BOILER. (European Patent No: Design Right Protected.) TH12-450U MRK 2

TORRENT STAINLESS ONE NAME. EVERY SOLUTION. OPEN VENTED THERMAL STORE PROVIDING HEATING AND MAINS PRESSURE HOT WATER

Instructions for Use Installation and Servicing

Combined electric boiler and domestic hot water store

Assessment Schedule - TS.6

Cylinder Manual. Open Vented Cylinders Stainless Steel Water Heaters. Twin Coil TW180V TW210V TW250V TW300V Triple Coil TR250V TR300V

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

Manual Heatstream Installation & Maintenance

Design, Installation & Servicing Instructions. A total hot water and heating thermal store that can also make the most of renewable energy

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

STAINLESSLITE PLUS ONE NAME. EVERY SOLUTION. UNVENTED MAINS PRESSURE AND VENTED WATER STORAGE CYLINDERS

SMART SHOWERS ELITE SP P0985 READ ME THIS IS A HIGH PERFORMANCE HIGH SPECIFICATION PUMP AND HAS PRECISE INSTALLATION REQUIREMENTS

1845 Tech Manual.qxd 23/11/05 1:20 pm Page 2 EXCELSIOR UNVENTED WATER HEATERS INSTALLATION MANUAL. Design for living

STAINLESSLITE PLUS ONE NAME. EVERY SOLUTION. UNVENTED MAINS PRESSURE AND VENTED WATER STORAGE CYLINDERS

Contents. Commissioning 6 Operation 6 Routine Preventative Maintenance 6 Fault Finding 7 Spares Parts 8 Technical Support 9

Water Heating UK 14 th May 2016

Cistern-fed water heating

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

UNIQ HEAT BATTERIES REFERENCE MANUAL_V2.2. Version: 2018_07_19_v2.2

INSTALLATION & TECHNICAL MANUAL

STAINLESSLITE ONE NAME. EVERY SOLUTION. UNVENTED MAINS PRESSURE AND VENTED WATER STORAGE CYLINDERS

AquaFlo II. Issue 3 December Please read these instructions carefully before commencing installation of the AquaFlo unvented water heater

Technical and Installation manual All Models

Schuco SS-TC/SC Cylinders

hxi High Efficiency Heating Only 24hxi hxi High Efficiency Heating Only 30hxi hxi High Efficiency Heating Only 38hxi

Stored Water District Heating Interface Units. Heat Interface Units

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE:

INTERCYL. INTERNAL EXPANSION EXCELLENCE

Commissioning Pack. Heating and Hot Water Heat Pumps. IMPORTANT DOCUMENTS To Be Kept At All Times. With Equipment. Accredited Ecodan Installer:

HEATRAE SADIA. Installation and User Instructions for the UTC Undersink Vented Water Heater

Alpha CombiMax 350 and 600

Mains Pressure Hot Water from an existing vented copper cylinder... Allows the cold water tank to be removed, freeing loft space.

H o t Wa te r Syste m s. Ultrasteel. Unvented Hot Water Cylinders. Exceeding the Standard

H o t Wa te r Syste m s. Senator Electric Flow Boilers. Making Life Simpler

Broag Pressurisation equipment

AIRE. Thermostatic bath shower mixer. Installation and Operating Instructions INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER

Standard Assessment Procedure Instantaneous Waste Water Heat Recovery Systems Design Checklist for 'System A' Installation Configuration

Streamline Undersink. Fitting Instructions and User Guide

Amptec. Electric flow boiler

INSTALLATION & TECHNICAL MANUAL

Torrent ECO. The final piece in your heating and hot water system. Open vented thermal store providing heating and mains pressure hot water

Unvented Hot Water Criteria

Water Heating Systems

HOTFLO 10 / 15. Fitting Instructions and User Guide

CPC-150-ANA. 150 litres, 535mm x 1300mm high. Pandora Heat Bank. 100kW Plate Heat Exchanger with 22mm Thermostatic Mixing Valve.

Standard Assessment Procedure Instantaneous Waste Water Heat Recovery Systems Design Checklist for Configurations A, B & C

ZIP AQUAFLO II Unvented storage cylinders

Installation Instructions

Unvented Direct & Indirect Hot Water Cylinders (400L L)

TORRENT ECO ONE NAME. EVERY SOLUTION. OPEN VENTED THERMAL STORE PROVIDING HEATING AND MAINS PRESSURE HOT WATER

REGISTRATION EXAMINATION, JUNE 2015 LICENSED PLUMBER QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

Why Vaillant? Because the ecotec delivers day in, day out. Vaillant ecotec boiler range. The TECHNICAL Brochure

Multi-Elec COMPACTE BOILER

Quantum. Installation, User and Service Manual. Hot Spring

VENTED CYLINDER RANGE

SOLAR HEATING SYSTEMS

INSTANTANEOUS ELECTRIC SHOWER

Thermostatic bar mixer valve with adjustable head Installation guide

ADVANCED WATER COMPANY LTD COPPERFORM. Advanced Water Company Ltd. Unvented Hot Water Cylinders. Supplied By Advanced Water Company Ltd

Installation Manual EXCELSIOR Unvented Water Heater

Bosch Group. 15SBi / 24SBi. WALL MOUNTED BOILERS FOR CENTRAL HEATING and Indirect supply of domestic hot water

Megalife Vented Cistern Fed Water Heater Installation manual

Artisan Thermostatic Bath Filler

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION. For Super SXD, SX, SCI & SC

Bath Shower Mixer

TORRENT ECO INSTRUCTION MANUAL DESIGN, INSTALLATION & SERVICING ONE NAME. EVERY SOLUTION.

Plus. USER and INSTALLATION INSTRUCTIONS. 30,000-9kW for Heating and Hot Water

Renewable Range Cylinders providing a perfect partnership with renewable energy inputs SUPPLIERS TO THE MERCHANT TRADE FOR OVER 40 YEARS

Sanitary Water Tank INSTALLATION & SVC MANUAL

unvented indirect & sealed heating systems unvented direct system & electric space heating Hot and cold water supply to all outlets at mains pressure

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data Electrical Details Connection Details Dimensions Standing Losses

EnergyMasterHP. user guide. Cylinder for use with NIBE heat pump systems. v12 Nu-Heat 2017 UNDERFLOOR HEATING HEAT PUMPS SOLAR THERMAL

MERSEY sequential exposed thermostatic mixer shower

TORRENT STAINLESS INSTRUCTION MANUAL DESIGN, INSTALLATION & SERVICING ONE NAME. EVERY SOLUTION.

Transcription:

ISSUE 13 1118 INSTALLATION AND USER GUIDE ADVANCE ELECTRIC THERMAL STORE ADVANCE APPLIANCES LTD HOUSEHOLDER PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE.

2

INTRODUCTION Advance thermal stores meet the Hot Water Association Thermal Store Specification and Part G and Part L of the Building Regulations. Advance Electric Thermal Store Systems are perfect for installations where oil or gas is not available or preferred such as rural dwellings or modern apartments. No flues are required and the unit is quiet in operation. Off peak tariffs can be utilised and all units are fitted with two 3kW immersion heaters. The unit is designed to make use of off-peak tariffs. The top heater is for top-up during peak tariff times. If only one immersion heater is used for single tariff or low load preferences, please connect only the bottom heater. This is a hot water only thermal store. Mains pressure hot water is provided safely at 20 litres per minute provided an adequate service is connected to the unit. This enables power showering without a pump and fast bath filling. The unit can be fitted and left isolated from the filling point if it is not possible to fit an overflow. Please see page 4. The blending valve can be orientated to right or left hand hot water service. Loosen the compression nuts, move valve and re-tighten the nuts. SITING The unit can be positioned anywhere within the property, even below hot water outlets, on a flat even surface. Do not site in aggressive environments or areas subject to frost. Please note that the unit must be installed in a position where it can be serviced and maintained in the future. Please make sure all parts are accessible for future maintenance, ESPECIALLY immersion heaters. 200mm top access should be allowed for. Please also take into account the weight of the unit when full and ensure that the floor can take the load. PERFORMANCE 160 litre unit for single standard bath and shower up to 20 litres/minute. 3

INSTALLATION The unit must be installed to meet current best practice by a person competent to do so. Incoming mains of 22mm with a pressure of 2 bar or above is recommended for best performance. Lesser pressures/pipe diameters will compromise performance; this must be taken into account as the decision rests with the installer/householder. Incoming pressures of more than 3 bar must be controlled at 3 bar by a pressure reducing valve (Not supplied). Recommended flow rate from 18 to 20 litres per minute. Excessive flow rates may result in lower hot water temperatures. In hard water areas where concentrations exceed 200ppm a suitable scale reducer must be installed. The choice is left to the installer to suit local conditions. Chlorine levels must be below 200ppm. We recommend that the cold service to the ballcock in the cold section is turned off using the isolation valve fitted. Remove the plastic lever to prevent customer error. Make sure that the cold section has a 50mm depth of water. Cap the overflow connection with a 22mm compression end stop to prevent evaporation. If you wish to install the unit without an overflow (warning) pipe, order with the AA0300 isolation kit fitted. This kit is pre-plumbed and pre-wired to the unit and detects any rise in the water level of the cold section. If the level rises, it activates a float switch which energises (closes) a two port motorised valve to prevent further flow into the unit. The wiring enclosure should be connected to a 5A 230V AC protected and switched supply. Cap the overflow connection with a 22mm blank compression fitting. Where the isolation kit is fitted the unit is supplied with manual fill only. Turn on isolation valve to fill to marked point on sight glass then turn off. Check the level annually. If the overflow is connected it must be in line with current practice. A metal overflow should be fitted. Push fit or solvent weld are not recommended. Discharge must be to a safe point. We also recommend that the ball valve is isolated even if an overflow is fitted. Inhibitor must be added via the top of the store to manufacturers recommended dosage. 4

PIPEWORK In order to comply with Part L Building Regulations it is necessary to insulate any hot water (primary and secondary) pipework within one metre of the cylinder. Guidance is given in the Table 5 (Page 20) of the 2013 Domestic Heating Compliance guide. Insulation values for the most popular pipe sizes are reproduced below. Pipe outside diameter 15 22 28 35 COMMISSIONING 5 Maximum heat loss in W/m 7.89 9.12 10.07 11.08 ALL JOINTS MUST BE TESTED AS THEY CAN LOOSEN IN TRANSIT. The blending valve is set to 50 C. See manufacturer s leaflet if adjustment is required. The immersion heaters are rated at 3kW each, and should be set at 75 o C There is a thermal cut out on the thermostat. This may trip from time to time and need to be re-set. Use only approved replacements. The expansion vessel is charged at 3 bar and acts as a shock arrestor to prevent water hammer and takes up expansion in the internal heat exchanger. SERVICING This should be done every year. Fill in the form at the back of this publication - you may need it in case of warranty issues. Keep proof of servicing (receipts etc). Service the expansion vessel by inflating to 3 bar, check condition of ball and float valve and ensure store is inhibited with a proprietary brand of inhibitor. USING THE UNIT It is critical that the water level is checked if the unit doesn t have the cold service connected to the ballcock. About 50mm depth in the cold section is required. The transparent vent pipe acts as a sight glass to check water level without removing the top. Simply open the valve on the flexible hose to re-fill the unit.

USING THE UNIT (Continued) Do not allow water levels to drop below the immersion heater as it will fail if switched on in air. Please note that if you are using one immersion heater only, it must be the lower one otherwise performance will be compromised. The store temperature should be 75 C in the morning. WARRANTY Warranty is for ten years on the tank against failure due to manufacturing fault, and two years on components supplied and fitted to the heating manifold and thermal store. Conditions apply, the unit must be serviced annually and a record of service must be maintained. It must be in a frost free environment and must be used for public mains potable water only. It must be installed and used correctly in accordance with manufacturer s requirements and current best practice. Corrosion and scale are not covered. Chlorine/chloride levels must be below 200ppm. The store must be inhibited to correct dose. Scale is not covered Your statutory rights are not affected by the above. Please see www.advanceappliances.co.uk for full terms and conditions and to register your product. COMPONENT LIST Component Reference 3 kw immersion heater (high temp) AA 0005 Control thermostat for above (high temp) AA 0007 High limit thermostat for above AA 0006 Blending valve AA 0002 Expansion vessel 2 litre AA 0001 Float switch and motorised valve kit AA 0300 Only use authorised replacement components. 6

TECHNICAL DATA CAPACITY WEIGHT IMM HGT X HOT WATER HW COIL Narec Distributed Energy (NDE) tested an ETS160 thermal store manufactured by Advance Appliances Ltd. The test uses EN13203 tapping cycle no.s; which aligns with tap cycle M within the EU regulation No 812/2013 with regard to the energy labelling of water heaters, hot water storage tanks and packages of water heater and solar device. This report details the test method used, analysis results and presents the key test parameters used for energy labelling within EU regulation no. 812/2013, namely: Water heating function is M Water heating efficiency of 36.02%, placing it in band C predicted annual electricity consumption AEC = 1425 kwhor 5.13GJ/annum Thermostat temperature setting 75 C Measurement of the standing loss over a 48hr period showed this to be 136 Watts at the nominal operating setpoint of 75 C. DISPOSAL At the end of the life of the product please dispose of in line with any regulations ruling at the time. 7

ELECTRICAL SAFETY Incorrectly made electrical connections can result in overheating and risk of fire. When installing the product, please ensure the wiring is adequate to minimise risk of overheating. Please ensure you have: Used the correct type and cross sectional area cable to meet manufacturer and Wiring Regulation requirements. Stripped the insulation from the individual conductors, taking care to not damage the strands of the conductor wire, which would reduce the cross sectional area of the conductor. Ensured the conductors are tightly and securely connected to the controls or immersion heater. Ensured the bared conductors are correctly inserted into the terminals, to avoid bearing on the insulation sleeve or only partially clamping the conductors. Securely anchored the supply cable using the means provided to avoid exerting any external strain to the cable and hence to the terminals Checked to ensure the product is earthed correctly; the Live and Neutral connections are to the correct terminals, and the Residual Current Device (RCD) operates correctly. As part of the annual service checked the electrical connections to ensure the wires remain in good condition and terminations remain secure. Ensure any spare parts used during maintenance of the product are an authorised spare part and meet the manufacturers requirement. The Manufacturers wiring instructions must always be followed. 8

INSTALLER & COMMISSIONING ENGINEER DETAILS Name Customer Details... Address...... Tel No.... Installer Details Name... Address...... Tel No.... DATE... REGISTRATION DETAILS (where applicable for unvented systems) REG No.... ID SERIAL No. etc.... Commissioning Engineer Details Servicing Requirements 1. Check pressure reducing valve (if fitted) is 3.0 bar static and adjust if necessary. 2. Check flow rates are correct at 18 litres per minute. Clean filter in pressure reducing vale only if required. 3. Check inhibitor levels in system. 4. Check expansion vessel change is 3.0 bar - inflate as required after decommissioing the cold supply. 5. Check blending valve temperature is 55 C or lower. See manufacturer s installation instructions for any further requirements. 6. Inspect water level in sight glass and top up if necessary by opening isolation valve. Level should be about two thirds up the glass. Should further assistance or clarification be required contact Advance Advice on 01543 377723. Failure to carry out annual service/ maintenance requirements and log proof in service/maintenance records may invalidate warranty. Name... Address...... Tel No.... DATE... REGISTRATION DETAILS (where applicable for unvented systems) REG No.... ID SERIAL No. etc.... Appliance Details Model... Capacity Serial No.... General Installation Litres... Has a check been done for joint tightness and leaks? Yes No Has a check been done for electrical safety? Yes No 9

COMMISSIONING PROCEDURE INFORMATION PRIMARY SETTINGS IS THE PRIMARY SEALED OR OPEN VENTED SYSTEM Sealed Open IF SEALED THEN WHAT IS THE SYSTEM PRESSURE? Hot...Cold...BAR IF SEALED THEN WHAT IS THE CHARGE PRESSURE OF HEATING EXPANSION VESSEL?...BAR WHAT IS THE AVAILABLE BOILER* FLOW TEMPERATURE?... C WHAT IS THE BOILER* RETURN TEMPERATURE WHEN CYLINDER/STORE IS SATISFIED?... C ALL MAINS PRESSURE SYSTEMS WHAT IS INCOMING COLD WATER PRESSURE?...BAR HAS A WATER TREATMENT DEVICE BEEN FITTED? YES NO IF YES TO ABOVE THEN WHAT TYPE?... THERMAL STORE SYSTEMS ONLY IS THE STORE TREATED WITH INHIBITOR? YES NO (NOTE - FOR INDIRECT THERMAL STORES THE STORE MUST BE TREATED IN TYPE... ADDITION TO THE PRIMARY SYSTEM) CONCENTRATION... IS A 3 BAR PRESSURE REDUCING VALVE FITTED? YES NO IS THE FITTED SHOCK ARRESTOR FULLY CHARGED AT 3 BAR? YES NO IS THE OVERFLOW/WARNING PIPE INSTALLED IN LINE WITH BEST PRACTICE? YES NO IF OVERFLOW NOT FITTED IS ISOLATION KIT FITTED AND FUNCTIONAL? YES NO IS THE BLENDING VALVE SET AT 55 C? YES NO IS THE DHW FLOW CONTROLLED TO THE APPROPRIATE RATE? YES NO IF CYLINDER IS IT VENTED CORRECTLY? YES NO IS THE CYLINDER STAT SET TO 70 C TO 80 C? YES NO ALL PRODUCTS HAS THE SYSTEM BEEN EXPLAINED TO THE HOUSEHOLDER? YES NO HAS THE SYSTEMS LITERATURE BEEN LEFT WITH THE HOUSEHOLDER? YES NO * Boiler or Heat Pump ENGINEERS SIGNATURE... CUSTOMERS SIGNATURE... 10

11

HOT WATER ASSOCIATION CHARTER MEMBER Hot Water Association (HWA) Members undertake to offer their customers the following: To supply fit for purpose products clearly and honestly described To supply products that meet or exceed appropriate standards and building and water regulations To provide pre and post sales technical support To provide clear and concise warranty details to customers www.hwacharter.org UNIT 4 COPPICE SIDE IND EST BROWNHILLS WALSALL WS8 7EX TEL 01543 377723 For Terms and Conditions go to www.advanceappliances.co.uk