40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

Similar documents
38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

40 RM/RMS Packaged Air-Handling Units

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

50BY, BL. Ÿà Õ µ µ Èß ËÕߪ Õ» å Single-Package Cooling Units 50BY, BL 50BY, BL

Vertical Concealed Fan Coil. FCVC Series MANUAL INSTALLATION, OPERATION, & MAINTENANCE

AHU INSTALLATION & OPERATION MANUAL

Installation Instructions

INSTALLATION, START-UP AND SERVICE INSTRUCTIONS

Installation, Start-Up and Service Instructions

KCC Centrifugal Fan Air Cooled Condensers

SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

Installation, Operation, and Maintenance Manual

SeasonMaker Hi-Line Fan-coil Units Model HSS S10 & S12

Installation, Start-Up and Service Instructions

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

SECTION AIR HANDLING UNIT

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

User s Information Manual

Horizontal & Horizontal Quiet Blower Coils

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Installation & Maintenance Data IM Contents

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Air Handler Unit. Installation & Operations Manual. Table of Contents. Bulletin No. H-IM-AH August 2002 Part Number 4346B001

Installation Instructions

VERTICAL HIGH OUTPUT VHC-IOM INSTALLATION AND MAINTENANCE INSTRUCTIONS VHC INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE TECHNICIAN

Vertical Stack Fan Coil Units Models: TVA, TVE, TVS

Installation Instructions Part No , Part No Part No

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

USER'S MANUAL PGE Single Package Rooftop

Verde GSE PCA Bridge and Ground Mount Units 30/45/60/90/120 Tons. Installation and Maintenance Manual

Installation, Start-Up and Service Instructions

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

INSTALLER S GUIDE WARNING: TWE-IN-2A 18-GE02D1-3. Convertible 1 ½ - 5 Ton Air Handlers WARNING HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

MIST MAX MODEL MM800. Important: Installation and Operation Manual

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Installation Instructions

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Installation Instructions

Installation, Operation, and Maintenance Information

40TCQ Vertical Ducted Fan Coil Unit for Variable Refrigerant Flow (VRF) Heat Pump or Heat Recovery System

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

DR-180 Through the Wall Exhaust Fan PRODUCT MANUAL & INSTALLATION GUIDE

Installation Instructions

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Installation, Operation, and Maintenance Information

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

38XTZ ABZ 007, 008, 016, 020 and ALZ 011 and 014. Split system air-cooled air conditioners. Models 38XTZ 016 to 024 MASTER LINK I

T-Series Air Conditioner T53 Model

Multi-position, Upflow, Horizontal Left, or Horizontal Right, Modular Air Handlers

T-Series Air Conditioner T20 Model

Installation, Start Up and Service Instructions

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

Installation, Operating & Maintenance Instructions. Air Handler Models: AH & AV

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

Installation Instructions

Installation Instructions

VSA/VSB & KSA/KSB Series Air Doors

Installation Instructions

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL

Installer s Guide Convertible Air Handlers 1-1/2 5 Ton

HOSHIZAKI ICE DISPENSING BIN/ WATER DISPENSER MODEL DM-90A SERVICE MANUAL

MODEL MC-UL592 MC-UL594 POWER SOURCE. 230V - 240V ~ 50 Hz MAX INPUT 1400 W 1500 W NOMINAL INPUT DIMENSIONS (W x L x H)

INSTALLATION and OPERATION BALL WASHER MODEL NO: BW-022

FILTERS MANIFOLD CABINET REFRIGERANT CONNECTION LOCATION

T-Series Air Conditioner T15 Model

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Ameristar SUBMITTAL M4AH4E26B1A00AA. 2.0 Ton Multi-position Air Handler M4AH4E26B1A00AA TAG:

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

READ AND SAVE THESE INSTRUCTIONS. Air Boss Model T5200 Custom Packaged Electronic Air Cleaner. TRION

50VZ/PZ 38VZ/PZ+40PZ. Vertical Air-Cooled Split-System Cooling Units and Heat Pumps. Installation, operation and maintenance instructions

BACK BAR REFRIGERATION Installation, Operation and Maintenance Instructions

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

Ceiling Concealed Fan-Coil Unit

LOW STATIC HYDRONIC DUCTED UNIT

Installation, Operation and Service Instructions

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

Enviro KES INSTALLATON MANUAL

Transcription:

Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging and Unpacking 4 Location, Mounting & Isolation 4 Space Requirement And Service Clearance 4 Piping Connection 5 Condensate Drain 5 Duct Connection 5 Filter 6 Unit Access 6 Wiring 6 Configuration 6 Start-Up 7 Service 7 Check List 7 Alignment of Pulley 7 Adjusting Belt Tension 7 Maintenance 8 Wiring Diagram 9-10 TABLE 1 PHYSICAL DATA Model : 40LM 120 150 200 Power Source V Ph Hz 230 1 50 415 3 50 Min/Max Voltage V 207 253 390 440 Operating Weight kg 120 200 230 Coil Type Copper Tube Aluminium Fin Face Area m² 0.61 1.01 1.36 No. of Rows 4 Fin Type Lanced Sine Wave Plate Fins Fins/inch 14 12 Fan Type Centrifugal Forward Curved Quantity 2 1 Drive Direct Drive Belt Drive Air Flow Range l/s 1000 1820 1700 2600 2000 3400 Fan Motor Type PSC TEFC Quantity 1 Output kw 1.83 2.2 3.0 Speed rpm 1325 1500 Connection Type BSP MPT Supply mm 25.4 38.1 50.8 Return mm 25.4 38.1 50.8 Drain mm 19.05 NPT MPT Dimension Height mm 480 1487 1541 Width mm 1600 1346 1651 Depth mm 680 710 764 Note : For 40LM150 & 40LM200; Motor, filter media and drive packages are field supplied. A United Technologies Company 1

DIMENSION ALL DIMENSION IS IN MM FIG.1 40LM120 DIMENSIONAL DRAWING 2

DIMENSION 40LM 150/200 Model No A B C D E F G H J K L 40LM150 1346 1487 644 208 1413 553 660 1270 1161 224 1.5 40LM200 1651 1541 698 235 1713 606 714 1575 1215 276 2.0 FIG.2 40LM150 & 200 DIMENSIONAL DRAWING 3

SAFETY CONSIDERATIONS Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should instali, repair or service air conditioning equipment. When working on air conditioning equipment observe precautions in the literature and labels attached to the unit and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available for all brazing operations. Note: Units are designed for indoor use, do not expose the unit to the outdoor weather. Place in indoor space where refrigerant piping, electrical wiring and duct connections are conveniently applied. SPACE REQUIREMENT AND SERVICE CLEARANCE Do not restrict service areas. Refer Fig.3 and Table 2 for minimum recommended clearance space. (a) For Horizontal Application WARNING!!! Before performing service or maintenance operations on system, turn off main power switches to indoor unit and outdoor unit. Electrical shock could cause personal injury. PRELIMINARY SURVEY: Following is a check list which should be checked before the installation is started. The installer should be familiar with each of the following requirements before the actual installation. a) Space requirement and clearance b) Ceiling or mounting strength c) Piping connections d) Condensate drain connection e) Power supply and wiring f) Air duct connections RIGGING AND UNPACKING Carton / crate should not be removed from unit until reaching final location to avoid damage. Inspect unit for shipping damage and file claim with transportation agency if necessary, check nameplate voltage against available power supply. For special installation, consult local building and electrical codes. LOCATION, MOUNTING & ISOLATION Unit could be installed either horizontally above a ceiling or vertically in a mechanical room. 40LM150/200 are convertible either horizontally or vertically. 40LM120 can only be installed horizontally. For horizontal discharge application, suspend horizontally using the factory-provided holes located at the top side flanges of unit. (Refer Fig.1 & Fig.2 for holes position). Make sure the ceiling or floor is strong enough to support unit operating weight and proper isolation installed. Where vibrations cause noise, insert isolation pads between unit and floor. (b) For Vertical Application (40LM150/200 only) FIG.3 UNIT CLEARING & MOUNTING Table 2. Unit Clearance MODEL A B C D 40LM150 400 500 500 600 40LM200 500 600 500 700 Note: Clearance space beneath the unit may be levied provided the ceiling offers sufficient access to the unit for servicing and maintenance works. Select and adjust vibration isolators and suspension rods so that unit is uniformly suspended. See Table 1 for the approximate unit weight and ensuring that the ceiling strength is sufficient enough to support it. Ductwork to be installed and insulated in accordance with Carrier System Design Manual and applicable codes, use flexible connections to minimize duct to unit alignment problems plus vibration and noise transmission. 4

PIPING CONNECTION Refer to table 1 for connection s types and sizes. Install piping in accordance with all applicable codes. When all joints are completed, perform hydrostatic test for leaks. Vent all coils at this time. Check unit piping for signs of leakage. If leaks are found, notify Carrier representative before initiating any repairs. Release trapped air from system. Following the hydrostatic test, insulate all piping to prevent sweating. To ensure compliance with building codes, restore the structure s original fire resistance rating by sealing all holes with material carrying the same fire rating as structure. DUCT CONNECTION See Fig.1 & Fig. 2 for connection size. SUPPLY DUCT CONNECTION Connect the flanged discharged openings to the supply duct utilizing a canvas connection to prevent vibration. It is important that this connection be properly fabricated to prevent high friction losses and air noise. RETURN DUCT CONNECTION Attach flanges on the return air openings and connect return and outside air duct thru a canvas connection. CONDENSATE DRAIN During installation, suspend unit level. Plug the other drain pipe with the factory supplied condensate plug. Observe all local sanitary codes and provide plugged tees for cleaning. See Fig.4. Min. 50mm Trap piping Unit 100mm or higher Drain Plug for cleaning FIG.4 CONDENSATE DRAINAGE For drain piping, observe the following items: i) Size of drain line must be equal to or larger than connection size. ii) Provide a trap which should be cleanable. iii) Provide insulation to prevent water condensation near the unit or indoor piping. Note: In most application, it is recommended that an auxiliary drain pan be used. It should be a water tight pan installed beneath the coil section to catch overflow condensate due to clogged condensate drain. The auxiliary condensate pan drain should be a minimum 12.7mm nominal pipe size, discharging at a point which can be readily observed. Condensate drains should not be directly connected to a plumbing drainage system nor be made common to the unit condensate drain. 5

FILTER (40LM120 only) Filter is supplied with the standard unit. The unit is designed such that a filter in a rectangular frame (collapsible type) of dimension shown below may be inserted or removed at the back of the unit with ease by removing the side angles (see Fig.5). Throwaway filter of the right dimensions may be purchased from Carrier. AIR FLOW 25 MM DRAIN PAN FAN DECK FRONT SIDE PANEL Fig. 5 Filter Access Note: Filter size for 40LM120 is 1344mm x 398mm x 12mm. FILTER (40LM150/200) Filter is field supplied and not factory fitted with the standard unit. The filter sizes are: Model Filter size Quantity 40LM150 635mm x 406mm x 25mm 4 pcs 40LM200 635mm x 406mm x 25mm 2 pcs 508mm x 406mm x 25mm 4 pcs To insert / remove the filters, follow the procedures below: 1. Remove opposite header s side panel at the coil section. 2. Slide in/out the filter media on the provided filter track. 3. Re-install the side panel. UNIT ACCESS (40LM120 only) All internal parts of the unit should be accessible by removing access panel at the base of the unit. Do not remove the base pan which is connected with the drain pipe unless necessary. To remove the access panel, follow the procedures below (Refer to Fig.6). 1. Remove the screws from the fan deck & side panel. 2. Pull down the access panel as shown in Fig.6 (approximate 25mm) 3. Slide out the access panel. To reinstall access panel, reverse the procedures. Finally, slot the access panel in place with screw from side thru the holes in the deck & side panel. ACCESS PANEL FIG.6 MOUNTING ACCESS PANEL WIRING Beware! When making wiring connections or working on unit be sure that electrical disconnect is open, locked & tagged. Follow local codes describing conduit and shielding requirements. The unit may be operated at either one of its three fan speeds. Refer wiring diagram (Fig.9 & 10) to relate colour & number of wire to the respective speed required. REMEMBER that although power is supplied to only one of the speeds, the remaining wires are live and must be isolated from unit body. CONFIGURATION * FLANGE FOR SLOT IN ACCESS PANEL * IMPORTANT: Slot the flange in the slot provided before screwing into the access panel. The unit is factory installed with coil connections located on the left hand side when viewed in direction of air flow. The control box is fixed on the left hand side when viewed in direction of air flow. 6

START-UP BEFORE STARTING UNIT - Check the following:- (1) No water leaks in system. (2) Correct field wiring and tight connections. (3) Panels and covers to be tightly fitted. (4) Check 40LM unit for correct fan operation and condensate drainage must be confirmed and unit level adjusted if necessary for proper drainage. SERVICE Ensure that electrical disconnect is open, locked and tagged while working on unit. MOTOR & BLOWER REMOVAL : (40LM120 only) 1. Remove access panel by following the steps described previously. 2. Disconnect motor wires from terminal block in junction box at the side of the unit. 3. If capacitor is to be removed, detach if from the control box by removing the capacitor bracket. 4. Removed the bolts on the left & right hand sides of fan discharge. 5. Slide the inner fan deck, motor & blower out at the bottom. 6. Dismantle the end plate at the left by unscrewing the screw on fan deck & scroll. 7. Release the blower by unscrewing the screw on blower & motor shaft. 8. Repeat step 5 & 6. 9. Dismantle the rest of the screws on fan deck. 10.To dismantle the motor, loosen the bolts on the motor bracket. CHECK LIST Before completing the installation, re-check the following: i) Make sure units are firmly installed. ii) Pulley, V belt alignment. Fan motor installation. iii) Check for any loosen parts which may cause vibration and noise. iv) No water leaks. v) Correct field wiring. vi) Slope for drain pipe and correct trap setting. vii)panels and covers are fastened correctly. ALIGNMENT OF PULLEY (40LM150/200) Position motor pulley and fan pulley in straight line. Fit straight edge to side of both pulleys to check alignment (Fig.7). Misalignment causes excessive power consumption and shorter life of belts. ADJUSTING BELT TENSION (40LM150/200) Refer to Fig.8. Adjust belts so that they can be depressed 15mm with one finger midway between two pulleys. New belts are likely to stretch during operation so adjust again. Refer Carrier General Maintenance Guidelines for proper belt tension. To reinstall blower, reverse the above procedures. Ensure that the fan deck insulation is not turn and exposing the internal panel surface. If this happens, replace the insulation. To install motor, reverse the above procedures, ensure all screws are tightened securely and blower wheel is centered and can be turned freely by hand before switching on supply. FIG.7 PULLEY ALIGNMENT DRAIN CHECK If water drips from unit either drain pipe, drain line or trap may be clogged. Also drain pipe plug on opposite side of unit may have fallen loose, replace them. Check drain pan water level by removing access panel, remove particles obstructing flow from drain pan or drain line. Drain pan may also be removed from suspended unit. To do this, first remove the access panel as illustrated previously. FIG.8 BELT TENSION FILTER CHECK They should be checked periodically. Do not attempt to clean or reuse disposable filters, replace them. 7

MAINTENANCE Proper maintenance prevents trouble and extends unit life. Check unit periodically. DRAIN CHECK If water drips from unit either drain pipe, drain line or trap may be clogged. Also drain-pipe plug on opposite side of unit may have fallen loose, replace them. FILTER CHECK Check twice a month, and wash if clogged. Clogged filter increases air-resistance and decreases air flow. Soak filters in detergent solution. Rinse and allow them to dry before reinstalling. V-BELT (40LM150/200) Loose belt causes excessive belt slipping and wear. Check for proper tension and adjust as required. Replace excessively worn belts. COIL Keep clean. Never operate unit without a filter or panel. Check inlet side of coil and brush out or vacuum if coil is clogged with dirt. BEARINGS (40LM150/200) Hermetic permanently lubricated bearings are used. The bearings are maintenance-free for the first five years under normal operating condition. If abnormal sounds are detected, change to new one. PANEL Fasten panels tightly to the unit so that there is no air leakage. 8

WIRING DIAGRAM FIG.9 40LM120 WIRING DIAGRAM 9

WIRING DIAGRAM FIG.10 40LM150 & 200 WIRING DIAGRAM 10

MEMO 11

Carrier International Sdn. Bhd. Malaysia Carrier International Sdn. Bhd. (3385-T) Lot 4, Jalan P/6, 43650 Bandar Baru Bangi, Selangor, Malaysia. Tel: 03-825 8001 Telex: MA 31610/MA 31614 Fax: 03-825 3578 40LM REV 1 05 2010 40LM500-039 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. 12