SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING GPX Builders Series Fire Protective

Similar documents
SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING GPX Builders Series Temperature Rise Door Framing

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING GPX Builders Series Fire Protective

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING SuperLite TM I-XL minute SuperLite TM I-XL IGU minute PART 1 GENERAL

PART 1 GENERAL 1.01 SUMMARY

PART 1 GENERAL 1.01 SUMMARY

PART 1 GENERAL 1.01 SUMMARY

PART 1 GENERAL 1.01 SUMMARY

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING SuperClear 45-HS (patent pending)

SECTION FIRE-RATED GLASS AND FRAME

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

ARCHITECTURAL SPECIFICATIONS

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 10 - SPECIALTIES

1. Items known commercially as finish hardware or builders hardware, required for swing, sliding, or folding doors.

SECTION DOOR HARDWARE

1. Portable fire extinguishers. 2. Fire-protection cabinets for portable fire extinguishers.

ARBOR SERIES DIVISION FLEXIBLE WOOD VENEER WALLCOVERING

University of Rochester October 17, 2008 Brooks Landing Business Center

DIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY

ARBOR SERIES WOOD WALLCOVERINGS

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents

DIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY

SECTION DOOR HARDWARE

Fire Rated Door Assemblies: Compliant Designs

Architectural Specification Sheet

Architect s Specification Guideline:


B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

SECTION INTRUSION DETECTION SYSTEM

DIVISION 10 SPECIALTIES

UNIVERSITY OF ROCHESTER DESIGN STANDARDS FEBRUARY 2005MARCH 2007

Hands On Training for Fire Door Products and Fire Door Assemblies

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011

SECTION FIRE EXTINGUISHER CABINETS

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

B. Shop Drawings: For fire protection cabinets. Include plans, elevations, sections, details, and attachments to other work.

SECTION INCLINE WHEELCHAIR LIFTS. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

Questions related to specific materials, methods, and services will be addressed at the conclusion of the presentation.

SPECIFICATION: ARGONITE Engineered Fire Suppression System

An ASSA ABLOY Group brand Series. Architectural Door Closers

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

SECTION CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

DESIGN & CONSTRUCTION GUIDELINES

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION INTEGRATED DOOR ASSEMBLIES

SECTION AIR COILS

c. Oko-Tex (European environmental health standard)

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

Engineering Specifications

SECTION INTERIOR LIGHTING

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

SECTION AIR DUCT ACCESSORIES

NFPA 80 Overview January 21, 2016

About the Instructor & Presenter:

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

B. Shop Drawings: Details of electrified door hardware, including wiring diagrams.

UFGS (June 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

C. Thresholds, weatherstripping, seals and door gaskets. A. ANSI/ICC A117.1 Standard for Accessibility and Usable Buildings and Facilities; 1998

Fire-Rated Glazing Changes in 2012 International Building Code (IBC)

1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for detention furniture.

SECTION FINISH HARDWARE

SECTION ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM

SECTION FM-200 FIRE SUPPRESSION SYSTEM

.2 Section Waste Management and Disposal..4 Section Electrical General Requirements.

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

SECTION XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

WALLCOVERINGS WALLCOVERINGS

UBC Technical Guidelines Section Edition Door Hardware Page 1 of 7

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

SECTION SECURITY TESTING AND COMMISSIONING

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

DOOR HARDWARE SECTION DESIGN REQUIREMENTS GENERAL INFORMATION

DIVISION LOW VOLTAGE DE-ICING / SNOW MELTING SYSTEM IN EXISTING ASPHALT/CONCRETE

FM-200 In-Cabinet Series

2. Interior doors shall be not less than 18 gauge steel.

Objectives. To review updated IBC and fire test requirements when designing for life safety.

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION NURSE CALL SYSTEM

SECTION AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER

A. Curtains: Provide curtain fabrics with the following characteristics:

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

A. Section Masonry Assemblies: Anchor placement in masonry.

EMERGENCY DRENCH SHOWER

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

FIRE & LIFE SAFTEY STANDARD

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI

B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator.

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

Transcription:

Welcome to the SAFTIFIRST TM Guide Specification System prepared as an aid to specifiers in preparing written construction documents. For specification assistance with specific product applications, please contact SAFTIFIRST TM. To download an electronic copy, please visit www.safti.com. PART 1 GENERAL 1.01 SUMMARY SPECIFICATION SECTION 08 8810: FIRE RATED GLASS & FRAMING GPX Builders Series Fire Protective A. Section Includes: Fire protective framing system. 1. GPX Builders Series Fire Protective 20-45 minute fire protective doors and openings for interior and exterior applications. 2. Applications of fire protective framing includes: a. Vision lites in fire protective doors, fire protective openings, fire protective sidelites, borrowed lites, and transoms with fire rating requirements as specified. B. Related Sections: 1. Section 01 3323: Shop Drawings, Product Data and Samples. 2. Section 08 1110: Steel Doors and Frames. 3. Section 08 1113: Hollow Metal Doors and Frames 4. Section 08 5130: Steel Windows. 5. Section 08 7100: Finish Hardware. 6. Section 08 8000: Glazing. 1.02 REFERENCES A. American Society for Testing and Materials (ASTM): 1. ASTM E152: Methods of Fire Tests of Door Assemblies. 2. ASTM E163: Methods for Fire Tests of Window Assemblies. 3. ASTM E2074: Standard Test Method for Fire Tests of Door Assemblies, including Positive Pressure Testing of Side-hinged and Pivoted Swinging Door Assemblies. 4. ASTM E2010-1: Standard Test for Positive Pressure of Fire Tests of Window Assemblies. B. National Fire Protection Association (NFPA): 1. NFPA 80: Fire Doors and Windows. 2. NFPA 252: Fire Tests of Door Assemblies. 3. NFPA 257: Fire Tests of Window Assemblies. C. Underwriters Laboratories, Inc. (UL): 1. UL 9: Standard for Safety of Fire Tests of Window Assemblies. 2. UL 10 B: Standard for Safety of Fire Tests of Door Assemblies. 3. UL 10 C: Standard for Safety of Positive Pressure Fire Tests of Door Assemblies. D. Standard Council of Canada (ULC): 1. ULC Standard CAN4-S104: Fire Tests of Door Assemblies. 2. ULC Standard CAN4-S106: Fire Tests of Window Assemblies.

E. Consumer Product Safety Commission (CPSC): 1. CPSC 16 CFR 1201: Safety Standard for Architectural Glazing Materials. F. American National Standards Institute (ANSI): 1. ANSI Z97.1: Safety Glazing Materials Used in Buildings - Safety Performance Specifications and Methods of Test. G. Glass Association of North America (GANA) 1. GANA Glazing Manual. 2. FGMA Sealant Manual. H. [American Recovery and Reinvestment Act 1. Section 1605, Title XVI Buy American Provision] I. [Insert building code used by Authority Having Jurisdiction] 1.03 SYSTEM DESCRIPTION A. Performance Requirements: 1. Fire Rating: must meet 20 or 45 minutes for fire protective doors and openings as specified. 2. Window Certifications: Window assemblies with ratings of less than 60 minutes may be tested in accordance with ASTM E2010-01, NFPA 80, NFPA 257, UL 9, CAN4-S106. 3. Door Certifications: Doors shall be tested in accordance with ASTM E2074-00, NFPA 80, NFPA 252, UL 10C, 10C, or CAN4-S104. 4. Testing Laboratory: Fire test must be conducted by a nationally recognized independent testing laboratory. 5. Glazing: Must use fire protective glazing less than 60 minutes up to the max. size tested. All glazing used in doors, sidelites and other hazardous locations must meet CPSC Cat. I or II impact safety. 6. Max. Door Opening Sizes: must meet maximum sizes of 54 in. x 120 in. for single doors and 108 in. x 120 in. for pair doors. No intermediate rails required. For max. door sizes, continuous hinges may be required. B. Listings and Labels: 1. Fire rated framing system shall be under current follow-up service by a nationally recognized independent testing laboratory approved by OSHA and maintain a current listing or certification. Assemblies shall be labeled in accordance with limits of listings. 1.04 SUBMITTALS A. Submit listed submittals in accordance with Conditions of the Contract and Division 1 Submittal Procedure Section. 1. Shop Drawings: Submit shop drawings showing layout, profiles and product components. 2. Samples: Submit samples for finishes, colors and textures. 3. Technical Information: Submit latest edition of manufacturer s product data. 2

1.05 DELIVERY, STORAGE AND HANDLING A. General: Comply with Division 1 Product Requirements Sections. B. Ordering: Comply with manufacturer s ordering instructions and lead-time requirements to avoid construction delays. C. Delivery: Deliver materials to specified destinations in manufacturer s or distributor s packaging undamaged, complete with installation instructions. D. Storage and Protection: Store off ground, under cover, protected from weather and construction activities and at temperature conditions recommended by manufacturer. 1.06 FABRICATION DIMENSIONS A. Field Measurements: Verify actual measurements for openings by field measurements before fabrication. Show recorded measurements on shop drawings. Coordinate field measurements and fabrication schedule with construction progress to avoid construction delays. 1.07 WARRANTY A. Project Warranty: Refer to Conditions of the Contract for project warranty provisions. B. Manufacturer s Warranty: Submit, for Owner s acceptance, manufacturer s standard warranty document. Manufacturer s warranty is not intended to limit other rights that the Owner may have under the Contract Documents. PART 2 PRODUCTS 2.01 MANUFACTURERS (FIRE PROTECTIVE DOOR) (FIRE PROTECTIVE OPENING) A. Manufacturer of Framing System: GPX Builders Series Fire Protective Framing as distributed by SAFTI FIRST TM Fire Rated Glazing Solutions. 1. Contact: 100 N Hill Drive, Suite 12, Brisbane, CA 94005; Telephone 888/653-3333; Fax 888.653.4444; email info@safti.com; Web site www.safti.com B. Manufacturer of Glazing Material: (SuperLite TM I) (SuperLite TM I IGU) (SuperLite TM I-XL) (SuperLite TM I-XL IGU) (SuperLite TM I-W) (SuperLite TM II-XL 45 ) (SuperLite TM II-XL 45 IGU) (SuperLite X-45/60/90) as manufactured and distributed by SAFTI FIRST TM Fire Rated Glazing Solutions. (PYRAN Platinum) (PYRAN Platinum IGU) (PYRAN Platinum F) (PYRAN Platinum F IGU) (PYRAN Platinum L) (PYRAN Platinum L IGU) as manufactured by SCHOTT Technical Glass Solutions and distributed by SAFTI FIRST TM Fire Rated Glazing Solutions. 1. Contact: 100 N Hill Drive, Suite 12, Brisbane, CA 94005; Telephone 888.653. 3333; Fax 888.653.4444; email info@safti.com; Web site www.safti.com 3

C. Fire rated glass and framing must be provided by a single-source, US manufacturer. Distributors of fire rated glass and framing are not to be considered as manufacturers. Materials for the project should be shipped together in the same shipment on the same truck. D. Substitutions: No substitutions allowed. 2.02 MATERIALS FRAMING A. Fire protective framing system for 20-45 minute doors and openings. B. Properties: 1. Constructed in accordance with the individual manufacturer s listings or in accordance with HMMA 861-06 and HMMA 850. 2. Maximum door opening sizes are 54 in. x 120 in. for single doors and 108 in. x 120 in. for pair doors. No intermediate rails required. For max. door sizes, continuous hinges may be required. 3. Standard door profile includes 5 in. rail and 2 in. frame. Narrow door profile includes 3-3/4 in. rail and 1-1/8 in frame. 4. 10 in. ADA compliant bottom rail (can be modified with AHJ approval). 5. 4 to 5 in. door depth 2.03 MATERIALS GLASS A. Assemblies shall be glazed with SuperLite TM glazing products. B. Properties: 1. Fire protective glazing less than 60 minutes up to the max. size tested. 2. Individual Lites shall be permanently identified with a listing mark. 3. Glazing material installed in Hazardous Locations (subject to human impact) shall be certified to meet the applicable requirements for fire rated assemblies referenced in ANSI Z97.1 Standard for Safety Glazing Materials Used In Buildings and/or CPSC 16 CFR 1201 Safety Standard for Architectural Glazing Materials. 4. Visible daylight transmission: Varies by glazing type. Refer to SuperLite TM product data for more information. 5. STC rating: Varies by glazing type. Refer to SuperLite TM product data for more information. C. Logo: Each piece of fire rated glazing shall be labeled with a permanent logo. 2.03 FABRICATION A. Assemblies shall be furnished [knocked down for field assembly and will be glazed in the field] [assembled (should configurations and job site conditions allow)] [unitized (should configurations and job site conditions allow)]. B. Door assemblies shall be factory prepared for field mounting of hardware. 4

C. Fabrication Dimensions: Fabricate to approved dimensions. The general contractor shall guarantee dimensions within required tolerance. Obtain approved shop drawings prior to fabrication. 2.04 FINISHES A. Available with high performance Coraflon fluoropolymer finishes by PPG or other custom finishes including stainless steel. 2.05 DOOR HARDWARE FOR SINGLE AND PAIR DOORS A. Hardware shall be supplied with the fire door. Hardware selection shall be from door manufacturer s standard recommended hardware groups as specified below. B. Provide high traffic areas of areas requiring a door motion force of greater than 15 lbs. with power assisted hardware for use with manufacturer s frame system. C. Standard operating hardware for standard profile single and pair doors. Please call manufacturer for narrow profile door hardware and custom hardware options (including but not limited to concealed rods, concealed closers, electric strike, etc.) Quantity Item Description Manufacturer Finish 4 Hinges Ball Bearing Heavy Duty Butt Hinges 1 Panic Device Heavy Duty Touch Bar Panic with Surface vertical Rods 1 Closing Device Heavy-duty Surface Applied Closer PBB4B81 Monarch F-25-V LCN 4040XP US26D US26D Aluminum 1 Auto Door Bottoms 420APKL Pemko PART 3 EXECUTION 3.01 MANUFACTURER S INSTRUCTIONS A. Compliance: Comply with manufacturer s product data including product technical bulletins and installation instructions. 3.02 EXAMINATION 5

A. Site Verification of Conditions: Verify substrate conditions, have been previously installed under other sections, and are acceptable for product installation in accordance with manufacturer s instructions. Openings shall be plumb, square and within allowable tolerances. The Architect/Engineer shall be notified of any conditions that jeopardize the integrity of the proposed fire wall/door framing system. Do not proceed until such conditions are corrected. 3.03 INSTALLATION A. Fire door/window installation shall be by a licensed contractor and in strict accordance with the approved shop drawings. 3.04 CLEANING AND PROTECTION A. Protect glass from contact with contaminating substances resulting from construction operations. Remove such substances by method approved by manufacturer. B. Wash glass on both faces not more than four days prior to date schedule for inspections intended to establish date of Substantial Completion. Wash glass by method recommended by glass manufacturer. C. Remove temporary coverings and protection of adjacent work areas. D. Remove construction debris from project site and legally dispose of debris. END OF SECTION In the interest of continuous improvement of its product line, SAFTIFIRST TM reserves the right to modify its products composition, colors, textures, sizes, and other physical and performance attributes and these guide specifications at any time. SAFTIFIRST TM makes no expressed or implied warranties regarding content, errors, or omissions in the information presented. Specifications modified or rewritten not in conformance with manufacturer s standard processes, products, and procedures may void warranties and related remedies. 6