DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION

Similar documents
SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

.2 Section Waste Management and Disposal.

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller:

SECTION ROTARY-SCREW WATER CHILLERS

Construction Standards Page

SECTION AIR COOLED WATER CHILLERS

MAC N-407 Air-Cooled Chiller

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

CONTENTS. B. System Design and Performance Requirements

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

MACH N-407 Heat Pump Air-Cooled Chiller

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

C. Samples for Initial Selection: For units with factory-applied color finishes.

SECTION CHILLERS

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

1.2 REFERENCES - comply with the following codes and standards:

Modified by MSU Physical Plant / Engineering and Architectural Services

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

AIR COOLED PACKAGED CHILLER

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil.

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Liebert CSU3000 Chiller

SECTION FAN COIL UNITS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

HVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT

HVAC Service Technicians Training Center

MAC-120HE-03 Air-Cooled Chiller

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

Multi-Institutional Academic Health Science & Research Center Evansville, IN

SECTION WATER-SOURCE UNITARY HEAT PUMPS

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

Call us today! (800)

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

Call us today! (800)

SECTION AIR-SOURCE UNITARY HEAT PUMPS

30GT FLOTRONIC AIR-COOLED CHILLERS

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

30GN FLOTRONIC II AIR-COOLED CHILLERS

Product Chillers A P P L I C AT I O N S

Evaporative Cooling Equipment Installer / Contractor Pre Start-Up Checklist

SECTION COOLING TOWERS

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

MAXIMUM SERIES. Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 70 F chilled water.

SECTION CENTRIFUGAL WATER CHILLERS

Call us today! (800)

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

SECTION AIR COOLED WATER CHILLER

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

SECTION DOMESTIC WATER PUMPS

Michigan State University Construction Standards. COOLING TOWERS Page SECTION COOLING TOWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Temptek Auxiliary Equipment

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw)

SECTION STEAM CONDENSATE PUMPS

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS)

Laboratory Enclosed Rotary Screw Air Compressor System with Air Treatment Center Package

SECTION STEAM CONDENSATE PUMPS

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

SECTION ROOFTOP REPLACEMENT AIR UNITS

DESIGN GUIDELINES SECTION HVAC

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

1.1 This section applies to air handling units for HVAC Systems.

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

072, 090, 120, 180 & 240 MODELS C SERIES CONDENSING UNITS P SERIES HEAT PUMPS

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Revitalize Building Mechanical Systems (4619)

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

INSTALLATION INSTRUCTIONS

Advance Release September 2009

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

Transcription:

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. Design and specify refrigeration systems and equipment in accordance with "Energy Conservation Standards" stipulated in Section 15010, Basic Mechanical Requirements. 2. Specify refrigerants that are CFC free, meet the requirements for ARI 700. Refrigerants shall have an Ozone Depletion Potential (ODP) less than or equal to 0.05. 3. Specify that isolation valves shall be provided by manufacturer in order to allow servicing of major components (e.g., compressor, receiver, condenser, filter-dryer, expansion valve) with no loss of refrigerant; the filter dryer shall have a three-valve arrangement with bypass. 4. Review with DPS Project Manager the equipment-mounted gauges desired for diagnosis and service. 5. Specify that Contractor needs to label the amount of refrigerant in the system in pounds, as required by IMC. 6. Provide Refrigeration Room Ventialtion in accordance with the current IMC and ASHRAE Standard 15. 7. Specifically, DO NOT require that self-contained breathing apparatus (SCBA) to be provided. ASHRAE Standard 15-2001 does not require SCBA. 8. Provide low ambient controls and crankcas heaters for air cooled chillers. B. DX Condensers: 1. For units requiring operation down to -30 o F, provide low ambient control package to allow start-up and positive head pressure control. C. Controls: all equipment controllers and system controllers must use BACnet protocol to integrate into the building automation system. Refer to Section 15975 Integrated Building Automation System (IBAS). Provide all necessary hardware and software to connect control panels or controllers to DPS Integrated Building Automation System. Refer to Section 15975 Integrated Building Automation System (IBAS) for interface requirements. D. Demolition: specify that all refrigerant be removed, recovered and reclaimed prior to demolition of any equipment containing refrigerant, such as rooftop units, split-system condensing units, air conditioning units and chillers. Specify that Contractor notifies DPS HVAC shop supervisor prior to commencing demolition work. DPS personnel will either remove refrigerant from equipment or direct contractor to remove refrigerant. All handling of refrigerant will be by certified refrigeration technicians, approved by the U.S. EPA. PART 1 GENERAL 1.01 COMPLIANCE A. Specify that the contractor shall comply with Colorado Department of Health Regulation 15 and all applicable EPA rules and regulations regarding the purchase, disposal and handling of refrigerants. 1.02 SUBMITTALS A. Product Data: 1. Component and accessories list. a) Include mounting information. 2. Ratings and nameplate information. a) Include unit capacity, entering and leaving water temperatures, ambient air temperature, electrical connection requirements, clearances, unit weight. B. Quality Assurance Data: 15650 Page 1 of 8

1. Certified production test reports or mill test reports. 2. Test reports for previous design, and documentation showing previous design ratings and configurations. C. Project Record Documents: 1. Shop Drawings: a) Certified elevation and outline drawings with dimensions. b) Certified plan view drawings with dimensions. c) Wiring and termination drawings. D. Operation and Maintenance Data: 1. Operating and maintenance procedures. 2. Complete set of manufacturers drawings. 3. Complete documentation of inspections and tests performed, including any logs, curves, and certificates. Documentation shall note any replacement of equipment or components that failed during testing. 4. Spare parts lists. 5. Data sheets updated to reflect field installation conditions. 1.03 WARRANTY A. Provide compressor warranty information. 1.04 COMMISSIONING A. Require that a factory representative be employed for start-up of chiller. 1.05 COMPRESSOR REQUIREMENTS A. Compressors Over 100 ton Capacity: 1. Motors and Starters: a) Dual winding, wye-delta design with matching two-step, closed transition, time-delay starting switchgear is preferred. (An auxiliary timer in the starting circuit is required.) b) Specify that timer be set to limit starts to a minimum of 30 minutes apart, or greater as recommended by the manufacturer. c) An auto-transformer with reduced voltage start is an acceptable alternate starter. d) All motors shall have heat sensors in the windings for thermal protection. 2. Full-running Protection: a) Specify compressors equipped with high- and low-pressure safety cutouts, external overload protection, inherent thermal protection, and low oil pressure. b) Manual reset-type safeties which cause an electrical lock-out of the starting circuit when it has tripped, with an indication of which safety device has operated. 3. Gauges and Lubrication: a) Compressor package to include gauges indicating high side, low side and oil pressures. Not required if unit is equipped with microprocessor control that shows pressure at control panel. b) Forced-feed lubrication system with filter, cooler and visual inspection port in the oil reservoir. 4. Heaters: a) Specify crankcase heaters wired on a separate electrical circuit. b) Specify oil pump starter wired on a separate electrical circuit. 15650 Page 2 of 8

5. Refrigerant Transfer: a) Unit should have provisions for pump out/down into unit-mounted receiver if application warrants it. (DPS Project Manager authorization is required for exception). 6. Pressure Relief: a) Show on drawings safety valve pressure relief piping vented to outdoors in accordance with ANSI/ASHRAE Standard 15-78. Pressure relief valves shall be self-closing, resealing type. 7. Hail Guards: a) Specify hail guards to protect exposed coils in unit (DPS Project Manager authorization required for exception). B. Compressors of 60 to 100 ton Capacity: 1. Semi-hermetic, reciprocating-type, helical rotor or scroll. 2. Full running protection as described for larger compressors. 3. Suction, discharge and oil pressure gauges. 4. Crankcase heaters. 5. Oil reservoir sight glass. 6. Replaceable refrigerant filter dryers in liquid line. 7. Hydraulic capacity control by cylinder unloading for adjustments to load fluctuations. 8. Positive unloaded start. 9. An adequate discharge muffler. 10. Internal vibration isolation to provide minimum vibration transmission. 11. Closed-transition starting switchgear, determined by the electrical requirements for the particular sizes of motors. Part-winding start is acceptable. 12. As described on larger air-cooled units, specify a receiver on the condenser and provisions for pumping the full refrigerant charge into the receiver. If condenser will hold the full charge, this is an acceptable alternative. 13. Extended five (5) year warranty on compressor(s). C. Compressors under 60 but over 15 ton Capacity: 1. Hermetic or semi-hermetic reciprocating, scroll or helical rotor. 2. Inherent thermal overload protection for motors. 3. Suction, discharge and oil pressure gauges. 4. Crankcase heaters. 5. Oil reservoir sight glass. 6. Replaceable refrigerant filter-dryers. 7. Hydraulic capacity control by cylinder unloading or staging of multiple compressors. 8. Positive unloaded start. 9. Adequate discharge muffler. 10. Internal vibration isolation. 11. Closed-transition starting switchgear determined by the electrical requirements for the particular sizes of motors. 12. A receiver on the condensers and provisions for pumping the full refrigerant charge into the receiver. If condenser will hold the full charge, this is an acceptable alternative. 15650 Page 3 of 8

13. Extended five (5) year warranty on compressor(s). D. Compressors between 7-½ and 15 ton Capacity: 1. Same requirements as 15 to 60 ton compressors, except that cylinder unloading and unloaded start features are not required on these units. E. Compressors below 7-½ tons Capacity: 1. Same requirements as 7-½ to 15 ton compressors, except that gauges are not required. PART 2 PRODUCTS 2.01 RECIPROCATING COMPRESSORS (HERMETIC) 1. Bohn 2. Bristol 3. Carrier 4. Copeland 5. Tecumseh 6. Trane 7. York B. Unit performance certified in accordance with latest edition of ARI Standard 520. C. Unit construction in accordance with ANSI B9.1 Safety Code. 2.02 RECIPROCATING COMPRESSORS (OPEN DRIVE) 1. Bohn 2. Carrier 3. Trane 4. York 2.03 WATER-COOLED CONDENSING PACKAGED UNITS A. Acceptable Manufacturers 1. Bohn 2. Carrier 3. McQuay 4. Trane 5. York B. Unit performance certified in accordance with latest edition of ARI Standard 520. C. Unit construction in accordance with ANSI B9.1 Safety Code and ASME Code. 2.04 AIR-COOLED CONDENSING UNITS 15650 Page 4 of 8

1. Submit recommendation. B. Unit performance certified in accordance with latest edition of ARI Standards 210 and 270. C. Unit construction in accordance with ANSI B9.1 Safety Code and ASME Code. 2.05 WATER-COOLED RECIPROCATING CHILLER (REMOTE CONDENSER) 1. Submit recommendations. B. Unit performance certified in accordance with latest edition of ARI Standard 590. C. Unit construction in accordance with ANSI B9.1 Safety Code and ASME Code. F. Units UL-listed and CSA certified. 2.06 WATER-COOLED CONDENSERS A. Acceptable Manufacturers 1. Bohn 2. Carrier 3. Refrigeration Services 4. Trane 5. York B. Unit performance certified in accordance with latest edition of ARI Standard 450. C. Unit construction in accordance with ANSI B9.1 Safety Code and ASME Code. 2.07 AIR-COOLED CONDENSERS 1. Submit recommendations. B. Unit performance certified in accordance with latest edition ARI Standard 460. C. Unit construction in accordance with ANSI B9.1 Safety Code. F. Units UL-listed and CSA certified. G. In units with multiple fans, isolate each fan section. 2.08 CENTRIFUGAL OR ROTARY-SCREW WATER CHILLER 1. Carrier 15650 Page 5 of 8

2. McQuay (with sound abatement kit) 3. Trane 4. York B. Chiller performance rated in accordance with latest edition of ARI Standard 550. C. Factory-wired control panel in accordance with NEC. D. Connect to Integrated Building Automation System. Refer to Section 15975 Integrated Building 2.09 COOLING TOWER (INDUCED DRAFT, VERTICAL DISCHARGE) 1. Tower-Tech 2. Baltimore Aircoil 3. Evapco 4. Marley 5. CCT B. Capacity rating in accordance with CTI Standards. Include altitude effects. C. Cooling Towers: 1. Specify the following for induced-draft towers: a) Fiberglass-reinforced polyester (or equivalent) or galvanized steel throughout. b) A propeller-type fan, on which blade pitch can be adjusted. c) A gear reducer drive for anything beyond 10 HP, if applicable. d) Motors situated outside the tower's humid airstream. e) Fill manufactured of fire-retardant PVC material (minimum 15 mil. thickness). f) Hot return water basin covers. g) Safety railings and ladder to fan deck. h) Safety cage on ladder. i) Oversized sump outlet for gravity flow to inside remote sump. j) Extended lube and oil fill lines with sight glass or dipstick. k) Stainless steel hardware, and brass or stainless steel fittings, within wet area. l) Vibration switch. 2.10 COOLING TOWERS (FORCED DRAFT) 1. Tower-Tech 2. Baltimore Aircoil 3. Evapco 4. Marley 5. CCT B. Provide the following for forced-draft towers: 1. "Baltibond" (Baltimore Air Coil trademark) or equivalent coating. 2. Galvinized steel sump with blow-through prevention kit. 15650 Page 6 of 8

C. If installed indoors, relief dampers shall have stainless steel knuckles. 2.11 REMOTE SUMP TANK A. Furnish and install welded stainless steel or fiberglass sump tank of size and capacity shown on Drawings. B. Remote sump tank. Incorporate the following requirements in sump tank design: 1. Allow minimum water level of four (4) feet of suction head under operating conditions, or greater if required to meet NPSH of pump. And provide redundant (stand-by) condenser water pump. 2. Provide a minimum of 150 percent of drain down storage capacity in addition to the above operating level. 3. Drain down capacity to consist of volume of cooling tower water retention plus all piping exposed to freeze conditions. 4. Design vortex breaker and screen at suction outlet. 5. Provide taps on tank for sump filtration cleaning system. 6. Include inspection ladder on tank to monitor water conditions. C. Provide adequate ventilation in sump room to control humidity. 2.12 COOLING TOWER SUMP FILTRATION SYSTEM 1. Submit recommendations. 2. For sand-type filtration, consider PEP Model SMF-24. B. Description: pumped recirculation of water from cooling tower sump or drain down sump through filter and back to sump as shown on drawings. Include use of distribution piping to sweep floor of tower sump towards the outlet. C. Cooling Tower Sump Filtration System: 1. To improve and maintain good water conditions in condenser water, specify and show on drawings a pumped system to re-circulate water from sump through a filter and back to sump. 2. Sand filters or cyclone filters are preferred, sized to filter entire system volume each hour or at 10 percent of tower flow rate, whichever is greater. Verify that floor drain can handle flow rate of backwash. PART 3 EXECUTION 3.01 INSTALLATION A. Chillers: 1. Install water chillers on concrete base. Concrete materials and installation requirements are specified in Division 3. 2. Vibration Isolation: Mount water chiller on vibration isolation equipment base as specified in Specification Section 15240 Mechanical Sound and Vibration Control. 3. Maintain manufacturer's recommended clearances for service and maintenance. 4. Charge water chiller with refrigerant if not factory charged. 5. Install separate devices furnished by manufacturer. B. Condensers: 15650 Page 7 of 8

1. Select air-cooled condensers with sufficient capacity to compensate for altitude deration of 5,400 feet and 105 F inlet air temperature. 2. Vertical blow-type condenser fans shall not be specified for systems that are operated during winter. 3. A horizontal blow with a weather-protecting shroud designed to prevent possible blade icing and unbalance during cold weather is required. 4. Orient fans to discharge eastward where practicable. C. Cooling Towers: 1. Install cooling towers on concrete base. 2. Vibration Isolation: Mount water cooling towers on a vibration isolation equipment base as specified in Specification Section 15240 Mechanical Sound and Vibration Control. 3. Maintain manufacturer's recommended clearances for service and maintenance. D. Loose Components: Install electrical components, devices, and accessories that are not factory mounted. E. Engage a factory-authorized service representative to perform startup service. 3.02 STARTUP SERVICE A. Engage a factory-authorized service representative to perform startup service. B. Inspect field-assembled components, equipment installation, and piping and electrical connections for proper assemblies, installations, and connections. C. Complete installation and startup checks according to manufacturer's written instructions and perform the following: a) Verify that refrigerant charge is sufficient and water chiller has been leak tested. b) Verify that pumps are installed and functional. c) Verify that thermometers and gages are installed. d) Operate water chiller for run-in period according to manufacturer's written instructions. e) Check bearing lubrication and oil levels. f) Verify that refrigerant pressure relief is vented outside (for water-cooled water chillers). g) Verify proper motor rotation. h) Verify static deflection of vibration isolators, including deflection during water chiller startup and shutdown. i) Verify and record performance of water chiller protection devices. j) Test and adjust controls and safeties. Replace damaged or malfunctioning controls and equipment. D. Prepare a written startup report that records results of tests and inspections. E. Occupancy Adjustments: when requested within 12 months of date of Substantial Completion, provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to two visits to site outside normal occupancy hours for this purpose. 3.03 DEMONSTRATION A. Engage a factory-authorized service representative to train owner's maintenance personnel to adjust, operate, and maintain cooling towers. Refer to Division 1 Section Demonstration and Training. END OF SECTION 15650 15650 Page 8 of 8