Energy Efficiency of Air-to-Air Mini Heat Pump

Similar documents
Performance Comparison Of Round Tubes Finned Heat Exchangers And Macro Micro-Channel Heat Exchangers In A Low Capacity Heat Pump

HSPF Calculation of a System Allowing Switching Between a Single-Stage to a Two-Stage Compression System

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

High Efficiency Heat Pump for Domestic Hot Water Generation

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Low GWP Refrigerants for Air Conditioning Applications

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Sub-Critical Operation of the CO2 Expander/ Compressor

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Low Global Warming Refrigerants For Commercial Refrigeration Systems

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Modeling and Design of an Indirect Air Conditioning System Operating With Low GWP Zeotropic Mixtures

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

Performance of CO2 Cycles with a Two-Stage Compressor

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

System Modeling of Gas Engine Driven Heat Pump

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Comparison of Energy Efficiencies of Commercial Refrigeration Direct and Indirect Systems

Purdue e-pubs. Purdue University

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Study of R161 Refrigerant for Residential Airconditioning

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Green Roofs Impact on Buildings Cooling Load

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance Measurement of R32 Vapor Injection Heat Pump System

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

R32 Compressor for Air conditioning and Refrigeration applications in China

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Dynamic Simulation of Liquid Chillers

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Investigation of Evaporator Performance with and without Liquid Overfeeding

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Optimization of Compressors used in Air Conditioning Units

Efficiency of Non-Azeotropic Refrigerant Cycle

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Performance Testing of Unitary Split-System Heat Pump with an Energy Recovery Expansion Device

An Experimental-Numerical Procedure to Characterize Compressor Performance under Cycling Operating Conditions of Refrigerators

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Air-Cooled Heat Exchanger Performance for R410A

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Energy Consequences of Non-optimal Heat Pump Parameterization

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

The Use Of Attic Space For Cooling and Dehumidification

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 21 Energy Efficiency of Air-to-Air Mini Heat Pump Sorina Mortada Center for Energy & Process/ EDF R&D Assaad Zoughaib Center for Energy & Process/ EDF R&D Christine Arzano-Daurelle Center for Energy & Process/ EDF R&D Denis Clodic Center for Energy & Process/ EDF R&D Follow this and additional works at: http://docslibpurdueedu/iracc Mortada, Sorina; Zoughaib, Assaad; Arzano-Daurelle, Christine; and Clodic, Denis, "Energy Efficiency of Air-to-Air Mini Heat Pump" (21) International Refrigeration and Air Conditioning Conference Paper 178 http://docslibpurdueedu/iracc/178 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries Please contact epubs@purdueedu for additional information Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W Herrick Laboratories at https://engineeringpurdueedu/ Herrick/Events/orderlithtml

2277, Page1 ENERGY EFFICIENCY OF AIR-TO-AIR MINI HEAT PUMP Sorina MORTADA 1*, Assaad ZOUGHAIB 2, Christine ARZANO-DAURELLE 3, Denis CLODIC 4 1, 2, 4 Center of Energy and Processes, Ecole des Mines de Paris, 5 Rue Leon Blum 9112 Palaiseau, France 1, 3 EDF R&D Avenue des Renardières Ecuelles 77818 MORET-SUR-LOING, France 1 Phone: +33-1-69194233, Fax: +33-1-6919451 Email address: sorinamortada@mines-paristechfr 2 Phone: +33-1-69194518, Fax: +33-1-6919451 Email address: assaadzoughaib@mines-paristechfr 3 Phone: +33-1-6737181, Fax: +33-1-673656 Email address: christinearzano-daurelle@edffr 4 Phone: +33-1-6919452, Fax: +33-1-6919451 Email address: denisclodic@mines-paristechfr ABSTRACT Mini-channel heat exchangers (MCHE) are used in automobile applications due to their low weight and high compactness Those MCHEs have just gained interest in stationary applications and they have a great potential for low heating capacity heat pumps to be installed in passive houses where the heating demand is 3 to 5 times lower than the current new individual houses built in European countries This paper compares performance and efficiency of a low-capacity heat pump (< 2 kw) with mini-channels as evaporator and condenser (mini-heat pump MHP) and an existing heat pump (EHP) This MHP is based on a third heat exchanger that will ensure an important part of a passive house heating demand A numerical model of a heat pump is presented in order to achieve this comparison 1 INTRODUCTION Climate change affecting the world pushed the governments to take actions to reduce greenhouse gases and air pollution Global emissions of greenhouse gases should be divided by 2 before 25 At the European level, the energy-climate package is a plan 3 x 2% by 22 This plan is based on: 2% energy saving, 2% renewable energy, and 2% reduction of green house gases emissions To reduce energy consumption, standards are reinforced in the building sector because it represents 47% of the energy consumption in France (industry, agriculture 28%, transportation 25%) A low-energy consumption building, as defined in the RT 25, is a new building that consumes less than 5 kwh/m²yr of primary energy (for heating, hot water, ventilation, lightening and cooling) The greenhouse gases (GHGs) emitted by those buildings are less than 5 kg CO 2 m²/yr For these buildings, the heating needs are estimated at 15 kwh/m²yr Air-to-air heat pumps are installed in apartment buildings and individual houses They were introduced in the 9s for heating buildings and have benefited from their introduction of significant improvements in performance; some of them are equipped with variable speed compressor Existing air-to-air heat pumps have a high heating capacity compared to the heating needs of a low energy building Heating systems adapted to the low demand of low energy buildings are under development and MCHE seems to be a solution for low heating capacity heat pumps The purpose of this study is to describe a model of a low heating capacity heat pump (MHP) adapted for low energy buildings 2 SYSTEM DESCRIPTION 21 Mini-heat pump An air-to-air heat pump extracts heat from the outside air and transfers it to the air inside the house via a refrigeration loop Air-to-air heat pumps (EHP system) are usually in Europe split systems

2277, Page2 A new type of HP is developed in Europe, installed in the air supply exhaust system, allowing the recovery from a recovery heat exchanger (RHX); see Figure 1(a) This additional heat exchanger transfers the heat between the exhaust air and the fresh air Both sensible and latent heats may be transferred Latent heat is transferred when moisture in the exhaust air condensates in the RHX The power recovered may reach 3% of the heating demand when it is a high demand and sometimes 1% if the outside temperature exceeds 9 C The integrated MHP is used to complement the heating demand Depending on this demand, a variable speed fan is regulated to provide variable airflow rates On the other hand, the exhaust air passing through the RHX is mixed with complementary fresh airflow before passing on the evaporator This complementary fresh air is also regulated by a variable speed fan To adapt to the needs, compressors will be variable-speed compressors The condenser and the evaporator are mini-channel heat exchangers (MCHE) They are light, compact, and more efficient than conventional heat exchangers For the same temperature, the MCHE presents a capacity higher by about 3% than the conventional heat exchanger and a lower pressure drop of about 33 % (Mortada 21) Figure 1 shows a schematic description of the studied systems (a) (b) Figure 1: Schematic description of mini-heat pump (MHP) 22 Performance and control The COP level of the studied MHP is directly affected by the RHX performance and the control system Based on the French standards, the ventilation must be permanent The minimum fresh airflow rate is defined depending on the building type and the occupancy This airflow rate is capable of covering the heating demand of a low energy building by passing it through a high efficiency recovery heat exchanger The control parameters are the airflow rate related to the fan speed and the temperature of the air supply related to a comfort temperature inside the house The temperature of the supply air affects the condensation temperature A higher supply air temperature involves a higher condensation temperature The COP is then reduced due to the increase in the condensing pressure, which is due to: A greater compression ratio, the isentropic efficiency decreases A higher discharge temperature Degradation of the COP cycle then degradation of the COP system On the other hand, choosing a low condensing temperature leads to higher airflow rates then to higher fan electric consumption This results in the degradation of the COP system For optimizing COP system, the control system has to find an agreement between the air supply temperature and the airflow rate In this study, the importance of the additional heat exchanger and the control system are presented via a model developed with an equation-based object-oriented modeling language Modelica 3 MODEL Dymola /Modelica is a solver able to solve numerical systems in a dynamic way It supports hierarchical model composition, libraries components, connectors, and composite acausal connections 31 Description Each MHP component is integrated as a model in a package named PAC Connectors are created to make the links between these components Two types of connectors exist in this model, the air connector and the refrigerant connector Moist air thermodynamic properties are integrated as equations in a single package called HumidAir A model is developed in PAC package dedicated to call HumidAir every time needed to calculate the air properties in the RHX, the condenser, and the evaporator This model takes in consideration the air state (dry or wet) in the RHX and the evaporator It calculates the latent and the sensible heats, and the condensed water amount The thermodynamic properties of the fluid (temperature, enthalpy, pressure, and vapor quality) are calculated using Refprop 8, which is interfaced with Dymola

2277, Page3 Figure 2: MHP system diagram Outlet air properties in the RHX are calculated by the effectiveness-ntu method The overall thermal conductance of the heat exchanger is experimentally determined Heat exchangers have been tested and a database of their global thermal conductance has been built Equations (1) to (5) are used in this model NTU ( UA) C (1) min 1 22 78 1exp * NTU exp Cr * NTU 1 C r (2) Q * Cmin *( T inexhaustair T infreshair ) (3) Q mair*( hout hin ) (4) Q Q Q (5) ExhaustAir FreshAir The recovery heat exchanger model calculates the mass flow of condensate water on the heat exchanger surface The surface temperature is calculated and compared to the air dew point When that surface is cooler than the dew point temperature, the condensation is observed In this case, Q is calculated by Equation (6) Q * Cmin *( T inexhaustair T infreshair ) + Condensate*Lv (6) The air mixer model is used in the MHP twice; it calculates the air properties of the air entering the evaporator and the condenser Equations of energy and mass conservation are used (7) m m m Air1 Air2 Airmix Air1 Air1 Air2 Air2 Airmix Airmix m h m h m h Air1 Air1 Air2 Air2 Airmix Airmix m w m w m w Depending on the heating demand, the compressor speed is controlled Using the manufacturer database, the isentropic and volumetric efficiencies are computed as functions of the compression ratio and the compressor (8) (9)

2277, Page4 speed The compressor determines the refrigerant mass flow rate circulating in the system Equations (11) to (15) are used to model the compressor behavior 4 3 2 is F4* F3* F2* F1* F (11) 4 3 2 vol G4* G3* G2* G1* G (12) vol N (13) mref * *D* ref 1 6 hout, is h (14) in is h h out compressor ref out h in in Q m h : compression ration; F4,F3,F2,F1,F,G4,G3,G2,G1,G are functions of N (the compressor speed); D: displacement (m 3 ) For the condenser and the evaporator the Log Mean Temperature Difference (LMTD) method is used Their UA (global conductance) is calculated with a detailed model called Air-Hex developed at the Center for Energy and Processes (Bigot 21) Air-Hex is developed to perform numerical simulations of various types of heat exchangers Having chosen the type of heat exchanger, different elements are described in a (txt) file: working fluids and their mass flow rates, geometric description, number of rows and tubes, entry conditions, adapted correlations as well as the circuit The resolution method is iterative: evaporation pressure varies until the air conditions (temperature and humidity) are constant Conservation of mass and energy and momentum equations are solved under a tube-by-tube calculation scheme Based on Air_Hex simulations, UA is defined for the condenser and the evaporator They are integrated as a parameter in Dymola The evaporation and the condensation temperatures are considered constant in the heat exchanger The LMTD method is used to define these temperatures (15) Q UA* LMTD (16) ref refout ref in Q m h h (17) Q m *( h h ) (18) Air Air out Air in An iterative calculation takes place to fix the condensation and evaporation pressures depending on the compressor behavior The air moisture condensation is also taken into account in the evaporator model The model of the expansion valve is based on one equation h h (19) refout ref in 32 Control scenario The control system depends on the house heating demand Therefore, a controller model is created In the simulated scenario, fans are at constant speed The variable speed fans will be considered for future simulations The controller compares the load to the sum of the condenser and the air to air heat exchanger capacities Three inputs are needed for the controller model, the outdoor temperature, the condenser capacity, and the air-to-air heat exchanger capacity An output signal is sent to a first order controller controlling the variable speed compressor 4 RESULTS 41 Model parameters The air source variables used in this model are defined in Table 1 UA of heat exchangers needed for the problem resolution and the compressor parameters for both cases MHP and EHP are shown in Table 2 Table 1: Air source parameters Temperature ( C) Relative humidity % Flow rate (m 3 /h) Fresh air [-7;14] 5 15 CFA [-7;14] 5 3 Exhaust air 2 6 15 Recycled air 2 6 3

2277, Page5 Table 2: Calculation parameters RHX Evaporator Condenser Compressor UA (W/K) Maximal Swept volume (m 3 /s) Refrigerant MHP 55 82 92 122 R-134a EHP 111 124 1788 R-134a 42 Results 421 Recovery heat exchanger (RHX) Heating demand was previously calculated using the building simulation software COMFIE Simulations have been done in different French regions and for the whole year The maximal heating demand is 2 kw for a 112 m² house in the Trappes region (continental climate) This heating demand is compared to the heating capacity recovered by the RHX simulated in Dymola Figure 3 shows the heating capacity recovered by the RHX for an outdoor temperature higher than 5 C RHX can ensure the total heating demand 43% of the time all over the heating season In these conditions, the electrical consumption is restricted to the fans consumption Heat Capacity (W) 16 14 12 1 8 6 4 2 Heating demand Capacity RHX 5 7 9 11 13 Outdoor Temperature ( C) Figure 3: Heating demand and RHX as functions of the outdoor temperature 422 System When the RHX cannot ensure the total heating demand, the heat pump is used to cover the load In this case, the compressor and the recycling ventilators are running In order to compare the MHP (Mini heat pump) and the EHP (existing heat pump) the COP Thermodynamic and the COP System are calculated COP COP Ther mod ynamic System _ MHP COP System _ EHP Q P Q Condenser (2) PCompressor Q Condenser recoveryhx P Compressor Q Compressor P Condenser P Three outdoor temperatures were chosen for this comparison: -7 C an extreme case, -5 C and 5 C a mid case The COP Thermodynamic is degraded when the outdoor temperature decreases This is due to a lower evaporation temperature then a higher compression ratio Increasing the low pressure implies a reduction of the compressor input power For 5 C outdoor temperature, it is obvious that HEP COP Thermodynamic is lower than that of the MHP This is related to the UA of the heat exchangers in the EHP that becomes limiting (21) (22)

2277, Page6 6 5 4 3 2 1 MHP EHP COP thermodynamic (a) 4 35 3 25 2 15 1 5 COP system MHP EHP Figure 4: COP Thermodynamic (a) and (b) COP System as functions of the outdoor temperature (b) The MHP COP System is higher than that of the EHP (see Figure 4 (b)) This is related to the heat capacity recovered by the RHX It is also important to note that the COP System is degraded when the outdoor temperature increases due to the use of a constant air flow rate In fact, a higher outdoor temperature implies lower heating demand, then lower compressor speed and lower air flow rate may be used, which is not the case in the simulated scenario French standards impose permanent ventilation with a minimum air flow rate Therefore, minimum consumption of electrical fans is imposed Figure 5 (a) shows that the electrical consumption of fans can be higher than that of compressors In this case, the control of the variable speed fans according to the heating demand will permit the consumption reduction of fans and then improve the COP System P *1 % Pconsumed (23) % 1 9 8 7 6 5 4 3 2 1 MHP (a) Compressors 1 9 8 7 6 5 4 3 2 1 EHP Figure 5: % of power consumed by the fans (MHP (a) & EHP (b)) QRHX *1 (24) % RHX Heatingdemand The RHX ensures about 35% of the heating demand for the extreme case -7 C as outdoor temperature (see Figure 6) Its presence is necessary for a higher COP System The energy recovered decreases for a high outdoor temperature but it can be sometimes sufficient for covering the total heating demand % 4 35 3 25 2 15 1 5 %RHX (b) Compressors Figure 6: % of capacity generated by the recovery heat exchanger in MHP

2277, Page7 5 CONCLUSIONS AND PERSPECTIVES A detailed model of a heat pump with an integrated third heat exchanger was presented The MHP presented a higher COP System even with a non-optimized control This is due to the essential role of the RHX that can ensure about 3% of the heating demand in the extreme climate conditions and 1% of the heating demand for 43% of the time during the heating season The electrical consumption of fans affects remarkably the COP System The improved version of this model will include the control of the variable speed fans and the study of frost formation on the evaporator and the air to air heat exchanger NOMENCLATURE C min minimum heat capacity W K -1 D displacement m 3 Q capacity W h enthalpy kj kg -1 Lv latent heat of vaporization kj kg -1 m mass flow rate kg s -1 N compressor speed RPM P pressure bar power W RH relative humidity % T temperature K UA overall conductance for heat transfer W K -1 Greek letters density kg m -3 effectiveness efficiency compression ratio Subscripts CFA complementary fresh air comp compressor COP coefficient of performance EHP existing heat pump is isentropic min minimal MHP mini heat pump ref refrigerant RHX recovery heat exchanger vol volumetric REFERENCES 1 ASHRAE Handbook, 25,Fundamentals,Chapter 6: Psychometrics, 2 Bigot G, 21, Étude et conception de systèmes air/air inversables utilisant des mélanges à glissement de temperature, Center for Energy and Processes,Paris 3 COMFIE, Center for Energy and Processes, France http://wwwizubafr/logiciel/pleiadescomfie 4 Dynasim AB Dymoladynamic modeling laboratory Lund, Sweden http://wwwdynasimse/dymolahtm 5 Incropera F, Dewitt D, 1996, Fundamentals of Heat and Mass Transfer, Wiley, 886 p 6 Mortada S, 21, Heat transfer performance of a mini-channel evaporator for heat pump application, Sustainable Refrigeration and Heat Pump Technology, KTH Stockholm, Sweden 7 RT 25, Décret relatif aux caractéristiques thermiques et à la performance des constructions, (Order of 8 may 27) 8 Slim, R et al, 28,Modeling of a solar and heat pump sludge drying system, Int J Refrig, doi:1116/jijrefrig2833 9 The Modelica Asssociation Modelica A unified object-oriented language for physical systems modelinglanguage Specification Version 31, 29 wwwmodelicaorg