White Paper. Monitoring Corrosion in Water Based Fire Sprinkler Systems (July 2013) By Jeffrey Kochelek V.1.0.0

Similar documents
White Paper. Chemical Corrosion Inhibitors - Six Reasons Why They Should Not Be Used in Water Based Fire Sprinkler Systems (June 2011)

White Paper. Six Reasons Why Chemical Corrosion Inhibitors Should NOT be Used in Water Based Fire Sprinkler Systems (June 2011)

Predictive Maintenance for Fire Sprinkler Systems. Jeffrey D. Gentry Sonic Inspection Corporation

ECS Protector Dry SMART Vent - PSV-D (PSV-DE) Specifications

ECS Protector Nitrogen Generator PGEN-40FK/PGEN-50FK/PGEN-60FK PGEN-40M/PGEN-50M/PGEN-60M

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-10/(PGEN-10E)

ECS Protector Dry SMART Vent - PSV-D (PSV-DE) Specifications

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950

ECS Protector Nitrogen Generator. ECS Protector Nitrogen Generator PGEN-30. Specifications

Comprehensive corrosion solutions backed by over 115 years of fire sprinkler monitoring. POTTER CORROSION SOLUTIONS

Corrosion in Fire Sprinkler Systems Increasing Your Liability, Increasing Your Costs, and Shortening System Life

Design Criteria. Installation

STEP 1: SELECT A NITROGEN GENERATOR STEP 2: SELECT A VENT STEP 3: SELECT MONITORING EQUIPMENT STEP 4: CONTACT ECS

POTTER CORROSION SOLUTIONS

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-3/(PGEN-3E) PGEN-5/(PGEN-5E)

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

CO Guardian LLC Document: E. AIRPORT DRIVE Date: 11/15/05 OWNERS MANUAL

1. The Nature of Soils and Soil Fertility

Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General Description

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

Instruction Manual. AcuRite Atlas Outdoor Device model 06059

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

TECHNICAL DATA OBSOLETE

OWNERS MANUAL. CARBON MONOXIDE DETECTOR MODELS Panel Mount & Remote Detectors (R) Guardian Avionics 1951 E. AIRPORT DRIVE TUCSON, AZ.

Which RO/DI Water Heater is Right For Your Application? By: Caitlin Carrier

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

Users Manual. LAURUS Systems, Inc. - Ph: Fax:

DESIGNED BY FIRE FIGHTERS FOR FIRE FIGHTERS.

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

SERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK

TOTALPAC2 Integrated Fire Protection System

Installation Manual February Opticom Infrared System. Model 575 Confirmation Light Kit

Manufacturing safety solutions

Series TY-B & TY-FRB, 10 mm Orifice, ISO 7/1-R3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General Description

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA OBSOLETE

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

OWNERS MANUAL MODEL 451 (-101 & -201)

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

RK/ RK Oxygen Detector Operator s Manual

Inline Heater for Solvent or Gas. Installation and Operation Manual

Monitoring Flammable Vapors and Gases in Industrial Processes

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

TL-105 COLUMN HEATER

Model gffoz Process Ozone Sensor (In-Line)

Installation, Operation, and Maintenance Manual

The Series LFII (TY3596) Residential

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

SOTTOSTAZIONI PER TELERISCALDAMENTO DISTRICT HEATING SUBSTATIONS

Independent Study Shows Sludge Build-up Significantly Affects Hydronic Heating System Performance

USER S INFORMATION MANUAL Model: HSE 125 N/P, HSE 145 N/P Gas-fired, Condensing Boiler and Instantaneous Water Heater

NEMA Applications Guide

Commercial product range

THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Document No

CRU-S Series Stainless Steel Condensate Recovery Unit

IMPORTANT. Questions? Contact Customer Support at (877) or visit 5-in-1 PRO+ Weather Sensor model

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

Gas Detection in Process Industry The Practical Approach

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

Cold weather regions where temperatures can fall below freezing present a threat to any building housing water-filled systems.

Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number:

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

KS-D1 Op ManualQ7.qxp:Layout 1 4/14/11 9:25 AM Page 2. Model KS-D1. owner s manual WHEN ACCURACY IS THE POINT.

WITH OMRON E5CC CONTROL

HOW COMMERCIAL FIRE PROTECTION SPRINKLER SYSTEMS REALLY OPERATE

INSTALLATION AND OPERATING INSTRUCTIONS

1 (800)

RK-02 Multi Point Detector Operator s Manual

NTC THERMISTOR SENSOR PERFORMANCE

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

THE TENNESSEE VEGETABLE GARDEN

Ambient Weather WS-2063 Indoor Temperature and Humidity Monitor with Backlight User Manual

ToThePOINT. Best Practices. Best Practice No. 1: Have your boiler inspected regularly by an authorized inspection agency. LOSS CONTROL SERVICES

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

AE R4 July 2015 Guide for the Use of R-290 Refrigerant in Copeland Refrigeration Compressors

Series LFII Residential Pendent Sprinklers 4.9 K-factor General Description

3M Benchtop Air Ionizer 963E. User s Guide

Healthcare Emergency Power Supply Systems. Maintenance and Testing

Transcription:

White Paper Monitoring Corrosion in Water Based Fire Sprinkler Systems (July 2013) By Jeffrey Kochelek V.1.0.0

Copyright 2013 Engineered Corrosion Solutions, LLC. All rights reserved. This white paper is provided for educational and informational purposes only. It should not be used as a substitute for the advice of a qualified and/or licensed professional concerning the particular circumstances of a situation. Although the authors have taken reasonable steps to ensure the accuracy of the information in this document as of the date of publication, it is possible that some information may be inaccurate or incomplete. Engineered Corrosion Solutions has no duty to update or correct this document in light of new information or changing circumstances. Engineered Corrosion Solutions shall not be liable for any loss or harm, whether direct, indirect, incidental or consequential, that arises from the use or misuse of the information herein. This document is provided as is and without warranty of any kind, whether express or implied. Engineered Corrosion Solutions may have patents, patent applications, trademarks, copyrights or other intellectual property rights covering the subject matter of this document. The furnishing of this document does not grant a license or any other rights to any patents, trademarks, copyrights or other intellectual property. Engineered Corrosion Solutions, LLC 11336 Lackland Road St. Louis, MO 63146 314 432 1377 2 Monitoring Corrosion in Water Based Fire Sprinkler Systems

Corrosion can be defined as the deterioration of metal through chemical interaction with the surrounding environment. In the simplest chemical expression, the subject metal gives up electrons to form a metal ion that generally precipitates as an oxide by product. In the case of fire sprinkler systems, black steel or galvanized steel piping reacts with dissolved oxygen in the fire supply water to form iron or zinc hydroxide. The net effect is metal loss from the pipe wall (pit) and insoluble debris in the piping. Anodic Reactions: Fe o Fe +2 + 2e iron becomes a water soluble ion Zn o Zn +2 + 2e zinc becomes a water soluble ion Cathodic Reaction: ½O 2 + H 2 O + 2e 2OH oxygen creates demand for e Electrochemical Reaction: Fe o + ½O 2 + H 2 O Fe(OH) 2 iron hydroxide precipitate Zn o + ½O 2 + H 2 O Zn(OH) 2 zinc hydroxide precipitate Corrosive degradation of fire sprinkler piping used in water based fire sprinkler systems is well documented 1,2,3,4. Empirical evidence from the field indicates that fire sprinkler piping is particularly vulnerable to weld seam corrosion 5. From a life safety and fire loss standpoint, risk increases when insoluble byproduct from the corrosion reaction accumulates within the fire sprinkler piping. Not only can the corrosion debris affect the hydraulic performance of the system design, it can also plug drops and sprinklers. However, the problems caused by water damage due to pin hole leaks that result from oxygen corrosion may pose the most immediate financial risk for a property owner. Fire Sprinkler System Corrosion Risks Plugging of sprinkler piping Plugging of sprinklers Reduced hydraulic performance Water leaks Reduced service life Repair costs Business interruption 3 Monitoring Corrosion in Water Based Fire Sprinkler Systems

One of the systemic problems with corrosion in fire sprinkler systems is that the systems themselves tend to fall into the category of out of sight, out of mind. After they are installed, property owners, business managers and fire personnel alike hope that they will never be needed or deployed. Unfortunately, corrosion continues within the fire sprinkler system piping even though the external manifestations of the corrosion activity may remain hidden for years. Every time an air compressor operates to maintain the pressure in a dry pipe sprinkler system warm, moist oxygen is added to the internal piping environment. Similarly, every time a wet pipe system is drained and filled, fresh oxygen in the air is added and trapped somewhere within the piping network to reignite the corrosion reaction. Given the nature of corrosion in these systems and the insidious damage that is being done, waiting for the inevitable first leak may be the most risky approach. The first leak may create a very significant financial loss. Corrosion Management Strategy Developing a strategy for managing corrosion in any industrial application involves the following five steps: 1. Root cause determination what is the active corrosion mechanism? 2. Assessment of corrosion damage remediation, repair or replacement of damaged equipment (location and severity of corrosion) 3. Implementation of corrosion management plan installation of corrosion control equipment and monitoring devices 4. Equipment inspection and maintenance routine inspection of corrosion control equipment and preventative maintenance 5. Ongoing monitoring of corrosion in situ early warning system to detect elevated corrosion rates If a plan is to be implemented to reduce corrosion related risk, it follows that there must be a mechanism to gauge the effectiveness of the plan that has been deployed. The more significant the corrosion related risk, the more important the corrosion monitoring. It would not be prudent to implement a corrosion control plan without an accurate early warning system to verify that everything is under control. The discussion presented here will concern itself specifically with monitoring corrosion within the fire sprinkler system piping. It should be noted that there are settings where the risks associated with a corrosion related failure in the fire sprinkler piping are much higher than other settings. For example, monitoring corrosion in a preaction sprinkler system protecting a mission critical data center would certainly be more important than monitoring corrosion in a dry pipe sprinkler system in a parking structure. But the bottom line is that corrosion related leaks in fire sprinkler piping create 4 Monitoring Corrosion in Water Based Fire Sprinkler Systems

financial risk whether they are in a wet pipe sprinkler system protecting a pharmaceutical warehouse or in a retail setting at a home improvement center. Monitoring Corrosion Corrosion monitoring is a very important element in a comprehensive corrosion management strategy for water based fire sprinkler systems. An effective corrosion monitoring program should provide evidence that the corrosion control program is working to prevent metal degradation. It should also provide early warning for elevated corrosion activity so that steps can be taken to return the system to a state of corrosion control before damage occurs and a failure results. In any corrosive environment physical degradation of the metal can occur in two different ways. General thinning of the metal across broad areas which leads to gradual loss of the wall thickness and pitting attack which results in highly localized loss of the metal at specific points on the pipe surface. Pitting attack is particularly troublesome because it can lead to premature breaches in the pipe wall in an otherwise moderately damaged surface. Most leaks in fire sprinkler system piping occur because of pitting corrosion. There are three direct effects of the corrosion process that can be measured to provide an indication of the corrosion rate: 1. Electrons flow out from the metal that is being corroded 2. A void (pit) is created at the metal surface where the corrosion event has occurred 3. A metal by product (oxide salt) is produced from the corrosion event Corrosion monitoring methodologies take advantage of one or more of these corrosion effects: 1. Measure and record the electron flow (current) 2. Measure the damage that has occurred at the metal surface (pitting and wall thinning) 3. Measure the accumulation of corrosion by product Corrosion monitoring can be instantaneous or time averaged: Instantaneous corrosion monitoring generally measures current flow for a sample of the subject metal within the exposed corrosive environment. Measuring the presence or absence of the corrosive gas within the system is also an instantaneous method. The benefit of instantaneous corrosion monitoring is that it can provide real time data regarding the actual corrosion conditions at any point in time. If corrosion rates vary with operating conditions, instantaneous monitoring can identify time intervals when corrosion rates are at maximum and minimum levels. Time averaged corrosion monitoring exposes a sample of the subject metal and measures the metal loss over a given exposure period. Time averaged corrosion monitoring can also analyze damage that has occurred in the piping itself over time. The weakness of time averaged 5 Monitoring Corrosion in Water Based Fire Sprinkler Systems

corrosion monitoring is that it cannot differentiate time intervals (events) when the corrosion rate is elevated. Corrosion monitoring can be direct or indirect: Direct corrosion monitoring measures the direct impact of corrosion on the subject metal in situ as it is exposed to the actual corrosive environment. Indirect corrosion monitoring measures the production of corrosion byproduct (e.g. hydrogen gas, metal ions or by product) and uses the results to provide some correlation to the corrosion activity within the system. Corrosion Monitoring in Fire Sprinkler Systems One complicating factor associated with the corrosion reaction in fire sprinkler systems is that corrosion rates vary greatly throughout the piping system. For example, in wet pipe sprinkler systems the corrosion rate will be greatest at the point that is proximate to any trapped air within the system piping. As oxygen in the air dissolves into the water it immediately reacts with the first steel it contacts to form iron oxide. So the air/water interface represents the most active corrosion site within these systems. At fluid packed points within the piping system that are more removed from the trapped air corrosion rates will be quite low. In general, the rate of corrosion is directly proportional to the amount of oxygen that is introduced and available. In dry pipe sprinkler systems the corrosion rates will be highest at locations where water has pooled within the piping. In dry pipe systems there is an excess of oxygen for the small amount of pipe surfaced that is covered with trapped water. In areas within the dry pipe network that remain dry, the corrosion rates will be essentially zero. Other factors that increase the rate of corrosion include temperature, solids and operating pressure. Given the localized nature of oxygen corrosion in fire sprinkler systems, placement of corrosion monitoring device is very important. Improper placement may lead to readings that do not reflect the highest risk for corrosion failure within the system. In general, the closer the monitoring device can be placed to the highly active corroding sites, the better. NFPA 13 Corrosion Monitoring Requirements The 2013 edition of the NFPA 13 Standard for the Installation of Sprinkler Systems discusses the use of corrosion monitoring in conjunction with the following sections: 24.1.5.1 Where conditions are found that contribute to MIC, the owner(s) shall notify the sprinkler system installer and a plan shall be developed to treat the system using one of the following methods: 6 Monitoring Corrosion in Water Based Fire Sprinkler Systems

1. Install a water pipe that will not be affected by the MIC microbes 2. Treat all water that enters the system using an approved biocide 3. Implement an approved plan for monitoring the interior condition of the pipe at established time intervals and locations 4. Install corrosion monitoring station and monitor at established intervals 24.1.5.2 Where conditions are found that contribute to unusual corrosive properties, the owner(s) shall notify the sprinkler system installer and a plan shall be developed to treat the system using one of the following methods: 1. Install a water pipe that is corrosion resistant 2. Treat all water that enters the system using an approved corrosion inhibitor 3. Implement an approved plan for monitoring the interior condition of the pipe at established time intervals and locations 4. Install corrosion monitoring station and monitor at established intervals Riser Mounted Corrosion Monitoring Station The most common type of time averaged, direct corrosion monitoring is the use of corrosion coupons. In this technique, preweighed samples of the subject metal are inserted into the corrosive environment and exposed for a measured period of time. The weight loss relative to the initial weight is used to determine the level of corrosion activity. In order to accurately reflect the corrosion within the system, it is very important that the metal coupons match the piping material and that they be installed at a location where corrosion is most active. In many industrial process applications it is common to insert removable corrosion coupons at a point within the system piping where they can be easily removed for inspection. Coupon placement within fire sprinkler system piping is restricted because the coupons within the path of water flow can create an obstruction. As a result, within the fire sprinkler industry corrosion monitoring stations have been installed on the fire sprinkler riser to mimic the conditions within the fire sprinkler system piping. To simulate wet pipe sprinkler systems a trapped air pocket is created within the station. To simulate dry pipe sprinkler systems a pool of trapped water is created within the station. Corrosion coupons are installed in the stations to measure the effect of oxygen corrosion on the subject metal. Additionally, a thin walled probe can be used to provide an early warning signal through the use of an attached pressure switch. Although the approach has limitations, to this point it has been the most common corrosion monitoring technique in the fire sprinkler industry. 7 Monitoring Corrosion in Water Based Fire Sprinkler Systems

Concerns: Corrosion monitoring station may not see the same environment as the actual fire sprinkler system piping temperature, solids, water flow during testing of the system The volume of oxygen per exposed unit of metal within the system piping may be significantly higher than the amount that is present within the corrosion monitoring station Corrosion coupons are not completely representative of the interior surfaces of the fire sprinkler system piping itself lack of weld seam, solids build up Coupons do not provide an early warning signal data regarding the corrosion rate is only available when the coupons are pulled and inspected Gas Analyzer Gas analyzers can be used as instantaneous, indirect measure of the level of corrosive gas within the fire sprinkler system piping. With the advent of nitrogen inerting in dry pipe fire sprinkler systems, this technique is very useful because it measures the amount of oxygen and assumes that there is a direct correlation between the amount of oxygen gas that is available and the instantaneous corrosion rate. Concerns: Oxygen sensor may require frequent calibration if subject to drift Unless the gas from the system piping is monitored continuously, the gas reading only provides instantaneous measure of oxygen concentration at that point in time Does not provide actual corrosion (metal loss) data indirect correlation In Line Corrosion Monitor The ideal corrosion monitoring device for a fire sprinkler system would have the following attributes: Can be sized to be installed in line directly within the fire sprinkler system piping network at the point where oxygen corrosion is expected to be the most severe: o Where air is trapped within the piping in wet pipe sprinkler systems o Where water is pooled within the piping in dry (preaction) sprinkler systems Does not create an obstruction risk to the water flow within the fire sprinkler system piping Can provide a 360 o interior pipe surface that is identical to the fire sprinkler system piping Can be composed of the same metallurgy as the fire sprinkler system piping black steel or galvanized steel 8 Monitoring Corrosion in Water Based Fire Sprinkler Systems

As an in line device it can be exposed to all of the environmental factors that the system piping sees flow tests, solids, temperature fluctuations Provides an early warning failure signal to indicate that the corrosion rate is at an unacceptable level Can be easily installed and removed for inspection post mortem in the event of a failure signal The in line corrosion monitor should be comprised of the following: 1. The core component is a piece of fire sprinkler pipe that matches the system that will be monitored in size, schedule and composition (figure 1). 2. A portion of the pipe is milled down from the outside to create a thinwalled section at the center of the pipe (figure 2). 3. A secondary housing is welded over the thin walled section of the pipe to create a pressure chamber (figure 3). 4. A pressure switch is attached to the pressure chamber to provide a detection response in the event that the thin walled section is breached by the action of corrosion (figure 4). 5. The ends of the pipe section are roll grooved for easy installation into the fire sprinkler system piping network. 6. The pressure switch signal is connected to the building management system or to the fire alarm panel as a supervisory signal. Figure 1 Figure 2 Figure 3 Figure 4 Measuring the effectiveness of any corrosion control program through ongoing monitoring of the protected system is essential. The unique attributes of wet pipe and dry pipe fire sprinkler systems means that the corrosion monitoring program must provide early warning and not affect the effective operation of the fire sprinkler system itself. The in line corrosion monitor design described above meets those criteria. 9 Monitoring Corrosion in Water Based Fire Sprinkler Systems

References 1 Under Deposit Corrosion at Weld Seams in Carbon Steel Piping, Andrew G. Howell, NACE International Corrosion 97. 2 MIC is NOT the Primary Cause of Corrosion In Fire Sprinkler Systems, Jeffrey T. Kochelek, Sprinkler Age Magazine, October 2009 3 Galvanized Steel Piping in Dry and Preaction Systems Six Reasons Why it Should NOT Be Used, Lucas Kirn and Jeffrey T. Kochelek, Sprinkler Age Magazine, May June 2011 4 Steel Piping Material Corrosion Dry and Pre Action Fire Protection Systems, Paul Su and David B. Fuller, Sprinkler Age Magazine, February 2013 5 Evidence from Failed Sprinkler Pipe Analysis done by St. Louis Testing Laboratories on field samples from operating fire sprinkler systems source Engineered Corrosion Solutions, LLC 10 Monitoring Corrosion in Water Based Fire Sprinkler Systems

Engineered Corrosion Solutions, LLC is a corrosion management consulting firm that offers fire sprinkler system assessment and analysis coupled with design services and a full suite of corrosion management strategies that include equipment and integrated devices for controlling corrosion in water based wet, dry, and preaction fire sprinkler systems. We understand the science of corrosion in fire sprinkler systems in a complete variety of different settings from parking structures to warehouses to clean rooms to data centers. Engineered Corrosion Solutions, LLC offers proprietary dry pipe nitrogen inerting technology (DPNI) and wet pipe nitrogen inerting technology (WPNI), which includes the ECS Protector Nitrogen Generator, Pre Engineered Skid Mounted Nitrogen Generator, Gas Analyzers, SMART Dry Vent, Two (2) Wet Pipe Nitrogen Inerting Vents and the industry s first real time in situ corrosion monitoring device the ECS In Line Corrosion Detector. Finally, we offer the first comprehensive remote corrosion monitoring system that provides live validation of the corrosion control strategy that is in place within your facility. For complete information about the entire line of corrosion management products and services and the complete list of downloads of White Papers, FAQs, installation schematics and product spec sheets please visit the Engineered Corrosion Solutions website at or contact us at (314) 432 1377 and one of our engineers will assist in personally answering any of your questions. 11 Monitoring Corrosion in Water Based Fire Sprinkler Systems