Application Note. Using XPoint Wireless Devices with Emergency Lighting. 1 of 16

Similar documents
HIGH BAY APPLICATIONS

TSLED STAIRWELL INSTALLATION INSTRUCTIONS

SERVICE BY QUALIFIED PERSONNEL ONLY

GTD20A Installation Instructions BRANCH CIRCUIT TRANSFER SWITCH/LIGHTING CONTROL DEVICE

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

Remote Chexit Module (RCM) System. General Information

XET-20 Series 20 Amp Emergency Lighting Control Device

MODEL RLY-DIM-D INSTALLATION INSTRUCTIONS

Dual Technology Wall Mounted Occupancy Sensor. Manual & Specification

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

DE5300 Delayed Egress System. General Information

I-320 SERIES AC EMERGENCY LIGHTING EQUIPMENT

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

AL800ULADA. NAC Power Extender. Installation Guide

Public Safety DAS Annunciator Panel

SETION EMERGENCY LIGHTING NATIONAL FIRE PROTECTION ASSOCIATION (NEPA) (2006) Life Safety Code, 2006 Edition

ILB-CP TBTS A MOUNTING DESIGN EMERGENCY LIGHTING EQUIPMENT FOR LED

AL600ULADA. NAC Power Extender. Installation Guide

F series. Complete Room Controller. echoflex Powered by ETC. Product Overview ERDRC-FC

INSTRUCTION MANUAL IMPORTANT SAFEGUARDS. When using electrical equipment, basic safety precautions should always be followed, including the following:

Product Guide. Ceiling PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs.

High bay PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Vive PowPak Fixture Controls

SECTION AUTOMATIC TRANSFER SWITCHES

Ceiling PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. PIR Sensor.

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

ILB-CP TBTS B MOUNTING DESIGN EMERGENCY LIGHTING EQUIPMENT FOR LED Patented. See iotaengineering.com/patents for more details

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

F series. echoflex. Slim Line Dimming Controller. Product Overview ER1S-FC

MEGA WAY LCD 4-CHANNEL MOTORCYCLE ALARM SECURITY SYSTEM. Operation Manual MEGATRONIX CALIFORNIA, U.S.A. MEGA 3100 OPERATE 1

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

600 Watt Dimmer Install Guide

Product Guide. Ceiling PIR HS presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs.

Installation, Operating and Maintenance Manual

ILB-CP TBTS A MOUNTING DESIGN EMERGENCY LIGHTING EQUIPMENT FOR LED

Application Note #106 Revision D June Emergency Lighting. Overview

EBDHS-DD-LT30. Ceiling PIR HS presence detector DALI / DSI, low temperature. Product Guide. Overview. Features

Product Guide. Ceiling microwave presence detector DALI / DSI. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs.

Model 4880 Status Output Display Module Manual

ETSA380MF SHOWN WARNING. shall be used ONLY on approved vehicles. It is the sole responsibility of the user of these devices to ensure compliance.

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx:

Related Sections: TBD. Effective Date: January 1, 2016

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.

Series. Access Power Controllers. Installation Guide

MODEL LUT-ATS-D (EPC-D-F-ATS) INSTALLATION ! IMPORTANT SAFEGUARDS!

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

Installation Guide for models:

Instructions Dual Spectrum Infrared Flame Detector PM-5MPX. 4.1 Rev: 8/

Installation Guide for models:

Wireless High Bay Sensor (WHS100) Installation Instructions

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

Bdl60u Fluorescent Emergency Ballast

EMERGENCY POWERHUBB NODE INSTALLATION AND OPERATION GUIDE

SENSA MRE DDM MR

CHAPTER 20 SERVICE EQUIPMENT

/ How To Order

SP-1000X. Panic Device Power Controller Installation Guide. Rev

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

Emergency TLED Lighting Retrofit 101. December 6 th 2017

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SOFTWARE VERSION 2.20 CONTROL PANEL RESET:

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

PSC-BL-I-FM-DC0(-BLE) Bi-level Dimming PIR Sensor

M2500 Engine Controller Installation Manual

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

SECTION LIGHTING CONTROLS

Ceiling Microwave presence detector - DALI / DSI 12-24V AC/DC. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs.

LUCE 1 TL. specifications: internal. specifications: external. ordering logic. builder. Job/Location:

LOCK INTO THE ACSI ADVANTAGE LOCK INTO THE ACSI ADVANTAGE

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Applied Lighting Controls

tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Integrated PIR detectors

, ,

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR

MODEL EPC-D-F-ATS INSTALLATION INSTRUCTIONS ! IMPORTANT SAFEGUARDS!

Crypto-Lock. Model CC-8521B Updated 7/17. Access Control System. MONITEQ, Inc. INSTRUCTION MANUAL

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

DS160/161 Request To Exit PIR sensors Installation Instructions

Heat Pump Defrost Board Replacement Kit

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

FHSAC1-UNV-40L INSTALLATION INSTRUCTIONS

DS160/DS161 Request To Exit PIR sensors Installation Instructions

RAZOR RZR SERIES DIE CAST ALUMINUM LED EXIT SIGNS INSTALLATION AND OPERATING INSTRUCTIONS IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS

WARNING Important Safety Information

Transcription:

Using XPoint Wireless Devices with Emergency Lighting 1 of 16

Table of Contents Introduction...3 Application Summary...3 UL924 Standard Summary...4 ER Option - Normal Power Sensing Leads...4 ER Intended Applications...4 ER Available Device Models and Wiring...4 ER Testing Note...4 ER Egress Mode Sequence of Operations...4 EM Option - Power Interruption Detection...6 EM Intended Applications...6 EM Available Devices Models and Wiring...6 EM Light Controllers with Relay...6 EM Light Controllers without Relay...7 EM Testing Note...8 EM Egress Mode Sequence of Operations...8 Emergency Driver with Standard XPoint Wireless Controller...9 Intended Applications...9 Wiring Instructions...9 Testing Note...10 Sequence of Operation...10 Generator Transfer Device (GTD) with Standard XPoint Wireless Controller...11 Intended Applications...11 Wiring Instructions...11 Testing Note...12 Sequence of Operation...12 AC Micro-Inverter with Standard XPoint Wireless Controller...13 Intended Applications...13 Wiring Instructions...13 Testing Note...13 Sequence of Operation...14 Emergency Bypass Relay with Standard XPoint Wireless Controller...15 Intended Applications...15 Wiring Instructions...15 Testing Note...16 Sequence of Operations...16 2 of 16

Introduction This application note reviews the theory of operation and proper applications of XPoint Wireless lighting control devices when used with various emergency lighting strategies. This note includes guidance regarding the use of UL924-listed ER and EM options of XPoint Wireless lighting control devices that provide energy saving operation (such as shutoff or dimming) during normal power conditions and automatic full illumination override during typical loss of power scenarios. This note also discusses the use of standard XPoint Wireless lighting control devices with separately listed (by others) UL924-type devices, such as emergency battery drivers, generator transfer devices, emergency bypass relays, and AC micro-inverters. Application Summary Table 1 provides a summary of the recommended specification option for use with a given emergency lighting strategy. Each individual application is discussed in depth in the following sections. Table 1 - Recommended Controller Specification Option for Emergency Lighting Strategy Emergency Lighting Strategy Diesel genset emergency backup supply Slow transfer inverter (> 30 ms) emergency backup supply Recommended Control Device Option EM Option UL924 Listed. Utilizes Power Interruption Detection to initiate lighting control override during loss of normal power scenarios. Requires power interruption > 30 ms to luminaire during transfer to emergency backup supply. Fast Transfer (FT) inverter emergency backup supply Uninterruptible Power System (UPS) emergency backup supply ER Option (UL 924 Listed) UL924 Listed. Utilizes dedicated Normal Power sensing leads to initiate lighting control override during loss of normal power scenarios. Requires connections to both emergency and normal power circuits. Luminaire-integral Battery Pack (BP) and emergency driver Luminaire-integral AC micro-inverter Generator Transfer Device (GTD) Emergency Bypass Relay (separate from integral control device) Standard Option Not specifically listed for emergency use. Wired such that a separately listed emergency device provides emergency lighting power and/or control during loss of normal power scenarios. 3 of 16

UL924 Standard Summary The UL 924 standard applies to emergency lighting and power equipment for use in unclassified locations (meaning locations which are not specifically covered by other defined egress lighting requirements) and intended for connection to branch circuits of 600 volts or less. Such equipment is intended to automatically supply illumination or power or both to critical areas and equipment in the event of failure of the normal supply, in accordance with Article 700 or 701 of the National Electrical Code, NFPA 70; the Life Safety Code, NFPA 101; the Fire Code, NFPA 1; the International Building Code, IBC; and the International Fire Code, IFC. ER Option - Normal Power Sensing Leads ER Intended Applications The XPoint Wireless ER models with normal power circuit sensing leads are intended to be powered by an emergency circuit and have an isolated AC power detection circuit that is intended to be connected to a normal power circuit. The ER model controller provides a flexible control solution for central emergency lighting power, suitable for traditional emergency power sources in addition to fast-transfer (FT) inverters or uninterruptible power systems (UPS). ER Available Device Models and Wiring XPoint Wireless light controllers and sensor/controllers are available in the following UL924 listed models that use normal power circuit sensing leads for override of lighting control: XPA RP20 D ER Externally mounted wireless controller, attached to luminaire or junction box. # indicates dimming option. XPA RP20 D/DSL ER Normal} XPA RP20 D ER or XPA RP20 DSL ER EMERGENCY 0-10 VDC Ballast or LED Driver Emergency } 120 V - 277 V Legend RED 120-277VAC Emergency Hot WHT/RED Emergency Neutral BLK Unswitched Normal Hot WHT Normal Neutral BLU Switched Output VIO 0-10V Dimming (+) GRY 0-10V Common (-) GRN Ground Normally Closed Test Switch (Optional, by others) Figure 1 - Example Wiring Diagram: XPA RP20 D ER ER Testing Note The ER light controller may be tested by opening normal circuit breaker or through an optional test switch, provided by others. Test switch should be of type normally-closed with contacts and rated for line voltage. In the case of ER controllers, the test switch will only carry a small amount of current (less than 0.1A), as it is used only to interrupt AC line voltage to the ER controller s normal power circuit sensing leads. 4 of 16

ER Egress Mode Sequence of Operations The UL924 XPoint Wireless ER Light Controllers are designed to drive the controlled luminaires to full light output (relay closed, dimming output at maximum trim setting) if there is no line voltage detected on the normal power circuit sensing leads. This operation is referred to as Egress Mode, during which the control device ignores both manual and automatic dimming/occupancy/daylight control signals. The ER Egress Mode Sequence of Operations is as follows: Normal Condition: o AC line voltage is detected across normal hot and normal neutral (controller black and white wires) o Controller can dim and turn off the load as normal, in response to automatic and manual control. Emergency Condition: o Whether due to failure of utility power or opening of normal hot circuit breaker, the ER controller detects loss of AC voltage on the normal power circuit sensing leads. o ER controller ignores all automatic and manual control commands and controls the driver or ballast to its fully tuned light output: the relay is closed and the 0-10V dimming signal is set at the maximum trim level (default 9.3 VDC, user programmable). Restoration of Normal Power: o ER controller resumes normally programmed manual and automatic control sequences when AC voltage is restored to the normal power circuit sensing leads. 5 of 16

EM Option - Power Interruption Detection EM Intended Applications The XPoint Wireless EM models with power interruption detection are intended for use on central emergency power systems that interrupt AC voltage when transferring to the backup power source, such as diesel generators. The EM model controller provides a simple installation, not requiring a wiring connection to normal hot power. This model can be used on central emergency lighting power operating from diesel generators or other equipment with power interruption transfer times greater than 30 milliseconds. The power interruption requirement is necessary for the XPoint Wireless controllers to activate the Egress Mode functionality (see next section, Sequence of Operations ). EM Available Devices Models and Wiring There are two styles of XPoint Wireless EM power interruption detection devices available, those with relay and those without relay. EM Light Controllers with Relay Most applications are best served with Relay models, so that the lights may be completely turned off during normal power conditions. For example, California s Title 24 energy code indicates that luminaires in daylight zones of parking garages should be completely turned off when adequate daylight is available. If this daylight zone is powered by an emergency lighting circuit, a UL924 solution allows the luminaire and circuit design to be compliant with both the energy code and relevant life safety code. The part numbers for XPoint Wireless UL924 power interruption detection controllers with relays are: XPA RL1 DSI EM Internally mounted wireless controller, integral to luminaire. XPA SBOR# EM Externally mounted wireless controller and sensor, attached to luminaire or junction box. # indicates occupancy sensor lens type. XPA CMRB# EM Externally mounted wireless controller and sensor, attached to luminaire or junction box. # indicates occupancy sensor lens type. XPA RP20 D# EM Externally mounted wireless controller, attached to luminaire or junction box. # indicates dimming option. 4-pin connector CLASS 1 BLACK WHITE BLUE XPA RL1 DSI EM CLASS 2 VIO GRY 0-10V RET 120/277 VAC NEUTRAL BLACK WHITE H N DRIVER (0-10VDC DIMMING) Figure 2 - Example EM Wiring Diagram: XPA RL1 DSI EM 6 of 16

EM Light Controllers without Relay Applications where constantly powered luminaires are desired (applications in which the lights should never turn completely off) may consider using the XPoint Wireless controllers without relays. These are essentially dimmingonly control devices with an internal shunt (in place of the relay) that passes uninterrupted line voltage directly to the LED drivers. While exact condition of the device cannot be guaranteed under all possible controller malfunction scenarios, this version of the controller is designed to open the dimming control signal (full light output) and pass uninterrupted line voltage to the LED driver under most typical controller malfunction scenarios (see Table 2 for additional details regarding controller malfunction scenarios). Non-relay models have a red wire that monitors the load current for power measurement purposes. The part numbers for XPoint Wireless UL924 power interruption detection controllers without relays are: XPA RL0 DSI EM Internally mounted wireless controller, integral to luminaire, dimming only (no relay). XPA SBON# EM Externally mounted wireless controller and sensor, attached to luminaire or junction box, dimming only (no relay). # indicates occupancy sensor lens type. XPA CMNB# EM Externally mounted wireless controller and sensor, attached to luminaire or junction box, dimming only (no relay). # indicates occupancy sensor lens type. 4-pin connector CLASS 1 BLACK WHITE RED XPA RL0 DSI EM CLASS 2 VIO GRY 0-10V RET 120/277 VAC NEUTRAL BLACK WHITE H N DRIVER (0-10VDC DIMMING) Figure 3 - Example EM Wiring Diagram: XPA RL0 DSI EM Controller Model RL1 CMRB, SBOR RL0, CMNB, SBON Relay Type Electrically held normally open (N.O.) relay Latching relay, no failure bias There is no relay Table 2 - Electrical Comparison of Relay vs. No-Relay Models Typical Condition under Controller Hardware Malfunction Relay Open (Lamp OFF); Dimming Circuit Open Relay in Last State (Lamp can be ON if driver still functional, or OFF); Dimming Circuit Open (full light output, if relay is closed) Pass-through of line voltage (Lamp can be ON if driver still functional); Dimming Circuit Open (full light output) 7 of 16

EM Testing Note The EM light controller is typically tested by opening and then closing the emergency circuit breaker to simulate a transfer scenario. An optional test switch (by others) may be used; in this case a line voltage normally closed test switch, rated to carry the full load of the AC drivers in the luminaire, may be wired in series with the light controller unswitched hot input. Momentarily opening, then releasing the test switch, shall activate the controller Egress mode. EM Egress Mode Sequence of Operations The UL924 XPoint Wireless EM Light Controllers are designed to drive the controlled luminaires to full light output (relay closed, dimming output at maximum trim setting) for 90 minutes following AC power interruption. This operation is referred to as Egress Mode, during which the control device ignores both manual and automatic dimming/occupancy/daylight control signals. Note that the sequence of operation described below applies following any interruption of AC input voltage greater than 30 ms, which may possibly include scenarios such as initial power-on, recovery to normal power conditions, and intermittent voltage conditions, in addition to a typical loss of power scenario. The EM Egress Mode Sequence of Operations is as follows: Normal Condition: o Controller can dim and turn off* the load as normal, in response to automatic and manual control. Emergency Condition: o Utility power fails, and controller loses power. o Backup power source activates, transfer switch moves the emergency circuit powering the controller onto the backup source, and controller regains power. o The EM Controller detects voltage interruption > 30ms on its line voltage input wire. o EM controller ignores all automatic and manual commands and controls the driver or ballast to its fully tuned light output for 90 minutes: the relay is closed and the 0-10V dimming signal is set at the maximum trim level (default 9.3 VDC, user programmable). o EM controller resumes normally programmed manual and automatic control sequences after 90 minutes, regardless of whether normal utility power has been restored. Restoration of Normal Power: o Utility power recovers, transfer switch moves the emergency circuit powering the controller onto the normal source. o If the recovery transfer interruption is less than 30 ms then the 90-minute Egress Mode timer will continue from the time of initial backup power transfer. o If the recovery transfer interruption is greater than 30 ms then the 90-minute Egress Mode timer shall restart. o After the 90-minute Egress Mode timer expires the normally programmed control sequences shall continue. * requires relay-equipped models (e.g., XPA RL1, XPA CMRB, XPA SBOR); Models without a relay can only dim the load to minimum (e.g., XPA RL0, XPA CMNB, XPA SBON) 8 of 16

Emergency Driver with Standard XPoint Wireless Controller Intended Applications This application typically involves the following characteristics: The luminaire is fed by a normal power circuit unswitched hot line feed. When normal power fails, a battery-powered emergency driver is intended to supply DC power directly the light engine. Wiring Instructions Wiring instructions for this use case will vary with the specific model of battery driver but the following are general guidelines for how an emergency driver is typically connected. The installation instructions and wiring diagram supplied with the specific emergency driver being used should be followed. Controller line voltage input wire (black) should be connected in parallel with emergency driver or battery unswitched hot input wire. Controller switched relay output (blue) should be connected to line voltage input of standard AC LED driver(s) only. Controller 0-10V dimming wires (violet and gray) should be connected to 0-10V input of all LED drivers. Figure 4: Example Wiring Diagram - Power Sentry PS30250 battery powered emergency driver with XPoint Wireless Controller Figure 5: Example Wiring Diagram - Power Sentry PS1050 battery powered emergency driver with XPoint Wireless Controller 9 of 16

Testing Note Follow the emergency driver manufacturer s instructions for installation and wiring of test switches. Some emergency drivers use low voltage test switches and others use line voltage test switches. Where a line voltage normally closed test switch is supplied that is also intended (and rated) to carry the full load of the AC drivers in the luminaire, it is recommended to wire the unswitched hot connections of both controller and battery pack on the output side of this type of test switch, so that use of the switch has the following simultaneous effects: controller along with normal AC drivers are disabled, battery driver is enabled. Sequence of Operations Normal Condition: o Controller operates the standard AC LED driver(s) under normal power conditions and otherwise does not interfere with the unswitched hot connection to the emergency driver. Emergency Condition: o Controller and standard AC LED drivers are de-energized by loss of normal power. o Emergency driver detects the loss of normal power on the unswitched hot input, and provides power to the connected light engines to provide illumination. Restoration of Normal Power: o Emergency driver detects the presence of line voltage on the normal power unswitched hot input, disables power to the connected light engines, and resumes charging. o XPoint Wireless controller becomes re-energized and follows its normal default power-on sequence: relay is closed to switch on the AC driver(s) and dimming output is at maximum trim voltage (default 9.3VDC, user configurable) until further instructions are received by automatic or manual control measures. 10 of 16

Generator Transfer Device (GTD) with Standard XPoint Wireless Controller Intended Applications This application typically involves the following characteristics: The GTD is fed by both a normal power circuit and by an emergency power circuit. o Confirm that the GTD being evaluated/installed is approved for use as a transfer device (and not a bypass device) featuring normal power switched hot & neutral inputs that are fully isolated from emergency power unswitched hot & neutral inputs. o The normal power and emergency power circuits have both been sized to carry the load of this luminaire. Note: if the normal power circuit has not been sized for this lighting load and is only intended to be used as a normal power unswitched hot sensing line, then a bypass relay should be used; see Emergency Bypass Relay section lower down for more details. GTD provides AC output power for emergency luminaire(s) or emergency driver(s). When normal power fails, the GTD transfers the emergency lighting load from the normal circuit (typically a controlled/switched hot and neutral pair) to the emergency circuit (unswitched hot and neutral pair). Wiring Instructions Wiring instructions for this use case will vary with the specific model of GTD but the following general guidelines for wiring a standard controller can be followed: Controller line voltage input wire (black) should be connected in parallel with GTD s normal power unswitched hot input wire. o Do not connect standard model controller to emergency power unswitched hot when used with a transfer device. This is important to ensure that emergency AC drivers are not dimmed by the controller during loss of normal power. Controller switched relay output (blue) should be connected to switched hot line voltage input of GTD. Emergency AC driver(s) to be powered during emergency power conditions line voltage & neutral inputs should only be connected to line voltage & neutral driver output of GTD: there should be no direct line voltage connections between the XPoint Wireless controller and the emergency AC driver(s). Controller 0-10V dimming wires (violet and gray): o If GTD does not provide 0-10V interrupt, controller 0-10V output should be connected to 0-10V input of all LED drivers. o If the GTD unit offers a 0-10V interrupting capability, then controller 0-10V output may be wired to GTD. 11 of 16

Figure 6: Example Wiring Diagram - GTD with XPoint Wireless Controller Testing Note The GTD may be tested by opening normal circuit breaker or through an optional test switch. Follow the GTD manufacturer s instructions for specification, installation and wiring of test switches. Note that if the GTD s test switch mechanism does not de-power the XPoint Wireless controller or interrupt the controller s 0-10V output, it may be possible for the controller to maintain dimming control of the LED driver during a test. If this is the case, then opening of normal circuit breaker is the recommended testing procedure. Sequence of Operations Normal Condition: o Controller operates the standard AC LED driver(s) under normal power conditions and controller switched output does not impact on the status of the GTD. Emergency Condition: o GTD detects loss of normal power unswitched hot and transfers emergency power unswitched hot and neutral directly to emergency AC drivers. o Loss of normal power results in XPoint Wireless controller s dimming output opening (becomes uncontrolled). o Emergency AC drivers operate at full uncontrolled output. Restoration of Normal Power: o GTD detects presence of line voltage on normal power unswitched hot and transfers normal power switched hot and neutral to emergency AC drivers. o XPoint Wireless controller becomes re-energized and follows its normal default power-on sequence: relay is closed to switch on the AC driver(s) and dimming output is at maximum trim voltage (default 9.3VDC, user configurable) until further instructions are received by automatic or manual control measures. 12 of 16

AC Micro-Inverter with Standard XPoint Wireless Controller Intended Applications This application typically involves the following characteristics: The AC inverter is fed by a normal power circuit unswitched hot line feed. When normal power fails, a battery pack and inverter are intended to supply unswitched AC power to the emergency AC drivers. Wiring Instructions Wiring instructions for this use case will vary with the specific model of AC inverter but the following general guidelines for wiring a standard controller can be followed: Controller line voltage input wire (black) should be connected in parallel with AC inverter s unswitched hot input wire. Controller switched relay output (blue) should be connected to switched hot line voltage input of AC inverter. Emergency AC driver(s) to be powered during emergency power conditions line voltage & neutral inputs should only be connected to line voltage & neutral driver output of AC inverter: there should be no direct line voltage connections between the XPoint Wireless controller and the emergency AC driver(s). Controller 0-10V dimming wires (violet and gray): o If AC inverter does not provide 0-10V interrupt, controller 0-10V output should be connected to 0-10V input of all LED drivers. o If the AC inverter offers a 0-10V interrupting capability, then controller 0-10V output may be wired to AC inverter. Figure 7: Example Wiring Diagram - Backup Micro Inverter with XPoint Wireless Controller Testing Note Follow the AC inverter manufacturer s instructions for installation and wiring of test switches. Some inverters use low voltage test switches and others use line voltage test switches. Where a line voltage normally closed test switch is supplied, confirm whether the switch is rated to carry the full load of the AC drivers in the luminaire. If so, then it is recommended to wire the unswitched hot connections of both controller and battery pack on the output side of this type of test switch, so that use of the switch has the following simultaneous effects: controller along with normal AC drivers are disabled, battery driver is enabled. 13 of 16

Note that if the AC inverter s test switch mechanism does not de-power the XPoint Wireless controller or interrupt the controller s 0-10V output, it may be possible for the controller to maintain dimming control of the LED driver during a test. If this is the case, then opening of normal circuit breaker is the recommended testing procedure. Sequence of Operation Normal Condition: o Controller operates emergency AC LED driver(s) under normal power conditions and otherwise does not interfere with unswitched hot connection to AC inverter. Emergency Condition: o AC inverter detects loss of normal power unswitched hot and provides unswitched AC power to emergency AC drivers. o Loss of normal power results in XPoint Wireless controller s dimming output opening (becomes uncontrolled). o Emergency AC drivers operate at full uncontrolled output. Restoration of Normal Power: o AC inverter detects presence of line voltage on normal power unswitched hot and provides normal power switched hot and neutral to emergency AC drivers. o XPoint Wireless controller becomes re-energized and follows its normal default power-on sequence: relay is closed to switch on the AC driver(s) and dimming output is at maximum trim voltage (default 9.3VDC, user configurable) until further instructions are received by automatic or manual control measures. 14 of 16

Emergency Bypass Relay with Standard XPoint Wireless Controller Intended Applications This application typically involves the following characteristics: The emergency bypass relay is fed by both a normal power circuit and by an emergency power circuit. o The emergency power circuit is intended to carry the load of this luminaire. o The normal power circuit is only intended to be used as a normal power unswitched hot sensing line. When normal power fails, the emergency bypass relay provides a path for AC voltage to reach the emergency AC drivers, regardless of whether the controller s relay is open or closed. Because XPoint Wireless controllers are typically used with 0-10V dimming, it is important to select an emergency bypass relay that can perform at least one of the following functions that will result in disabling/ opening of the dimming control: o Normally open dry contact intended for use as 0-10V interrupt; This will break the positive leg of the 0-10V control signal (violet). o Double-throw Form C contact (combination NO and NC line voltage bypass relay); This will simultaneously open unswitched emergency hot power input to control device while closing the emergency hot bypass to the lighting load, thereby disabling 0-10V dimming output. Intended Applications Wiring instructions for this use case will vary with the specific model of emergency bypass but the following general guidelines for wiring a standard controller can be followed: Controller line voltage input wire (black) should be connected as follows: o Double-throw Form C contact available: connect controller line voltage input to emergency bypass relay Normally Open contact o Single-throw Normally Closed contact: connect controller line voltage input to emergency power circuit unswitched hot (note that 0-10V interrupt must be used) Controller switched relay output (blue) should be connected in parallel to emergency bypass relay Normally Closed bypass relay contact and emergency AC drivers line voltage input wires. Controller 0-10V output (violet): o If emergency bypass relay provides 0-10V interrupting capability, controller 0-10V output should be connected to normally open dry contact. o If emergency bypass relay does not provide 0-10V interrupting capability, then controller 0-10V output may be wired directly to LED drivers (note that double-throw Form C contact must be used). 15 of 16

Figure 8: Example Wiring Diagram - Emergency Bypass Relay (Form C) with XPoint Wireless Controller Figure 9: Example Wiring Diagram - Emergency Bypass Relay (0-10V Interrupt) with XPoint Wireless Controller Testing Note Follow the emergency bypass relay manufacturer s instructions for installation and wiring of test switches. Some emergency bypass relays use low voltage test switches and others use line voltage test switches. A typical line voltage test switch would consist of a normally-closed switch wired in series with the normal power unswitched hot connection to the bypass relay; opening the test switch would trigger the bypass relay to momentarily override the light controller. Sequence of Operations Normal Power Conditions: o Controller operates all standard and emergency AC LED driver(s) together under normal power conditions and controller switched output does not impact on the status of the Emergency Bypass Relay. Emergency Power Conditions o Loss of power, or use of test switch, completely disables both the controller and standard AC drivers. o Emergency Bypass Relay detects loss of normal power unswitched hot, or use of test switch, and provides emergency AC power to emergency AC drivers. o Emergency AC drivers are at full uncontrolled output because XPoint Wireless Controller dimming wires are open (either due to de-powering of XPoint Controller by Form C contact, or due to interruption of dimming wire by N.O. relay). 16 of 16