Performance Analysis of Solar Assisted Cascade Refrigeration System of Cold Storage System

Similar documents
Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

Chapter 11. Refrigeration Cycles. Study Guide in PowerPoint

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Week 9. Refrigeration Cycles I. GENESYS Laboratory

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Chapter 11 REFRIGERATION CYCLES

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Refrigerator and Heat Pump Objectives

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

International Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 1-5

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Study of solar-thermal collector assisted hybrid split air conditioner

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Chapter 11 REFRIGERATION CYCLES

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance investigation of Air-conditioning system using ejector as expansion device

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

REFRIGERATION AND AIR CONDITIONING

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

REVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Thermodynamics II Chapter 5 Refrigeration

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Modified Air Cooler with Split Cooling Unit

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Chapter 10. Refrigeration and Heat Pump Systems

Thermodynamics I. Refrigeration and Heat Pump Cycles

Chapter 9. Refrigeration and Liquefaction

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Design and Fabrication of Water Refrigeration System by Creating Vacuum

Chapter 11 REFRIGERATION CYCLES. Department of Mechanical Engineering

ISSN Vol.08,Issue.21, November-2016, Pages:

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Experimental Investigation of Hot water Fired R134A-DMAC VARS System at Various Heat Source Temperatures

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Enhancement of COP in Vapour Compression Refrigeration System

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Design & Fabrication of Hybrid Cooler

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Design and development of vapor absorption refrigeration system for rural dwellers. Adekeye, T. Oyedepo, S.O and Oyebanji, J.A

Adsorption refrigeration system using waste heat

COMPRESSOR LESS SOLAR REFRIGERATOR

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

International Journal of Informative & Futuristic Research ISSN (Online):

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Chapter 10 VAPOR AND COMBINED POWER CYCLES

(Refer Slide Time: 00:00:40 min)

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Modelling the Performance of a Diffusion Absorption Refrigeration System

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

LECTURE-18 Vapour Absorption Refrigeration System

PERFORMANCE OF REFRIGERATOR USING R-600A AS REFRIGERANT

Performance Assessment of Water Cooled Condenser Refrigeration System

Refrigeration and Air Conditioning

Thermodynamic Analysis of Combined Vapor Compression and Vapor Absorption Refrigeration System ABSTRACT

Fabrication of Hot and Cold Water Dispenser

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

ADVANCES in NATURAL and APPLIED SCIENCES

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Carnot. 2. (a) Discuss the advantages of the dense air refrigeration system over an open air refrigeration system?

A Review Paper on Extracting Waste Heat from the Engine Exhaust and Reutilizing in Car Air Conditioning

A Comparison Between Refrigerants Used In Air Conditioning

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

SIMULATION OF A NEW TYPE GAS-FIRED AIR-COOLED AIR-CONDITIONER. Lin Wang, Xing Xu, Aihua Ma, Yonghui Guo and Xiwen Zhou

CH2351 Chemical Engineering Thermodynamics II Unit V Refrigeration. Dr. M. Subramanian

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

Design of solar powered vapour absorption refrigeration system

EXPERIMENTAL INVESTIGATION OF VAPOUR ABSORPTION SYSTEM

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

STUDY OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING DOUBLE PIPE HEAT EXCHANGER

Analysis of Coefficient of Performance & Heat Transfer Coefficient on Sterling Cycle Refrigeration system.

ADVANCES in NATURAL and APPLIED SCIENCES

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Energy and Exergy Analysis of an Ejector-Absorption Refrigeration Cycle with Using NH3-H2O as the Working Fluids

Refrigeration Cycles. Refrigerators, Air-conditioners & Heat Pumps. Refrigeration Capacity/Performance. Dr. Md. Zahurul Haq

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

Transcription:

Performance Analysis of Solar Assisted Cascade Refrigeration System of Cold Storage System Dr. Nimai Mukhopadhyay 1, ER. Someshwar Chowdhury 2 Assistant Professor, Dept. of M. E., Jalpaiguri Government Engineering College,Jalpaiguri,West Bengal, India 1 M.Tech Scholar, Dept. of M. E., Jalpaiguri Government Engineering College,Jalpaiguri,West Bengal, India 2 ABSTRACT: By preserving food products in the cold storage, good quality of food can be supplied throughout the year, minimizing the damage and enhancing the agricultural economy. Huge amount of electric energy is required to run a cold storage. Minimizing the use of electrical energy or proper utilization of electrical energy and thus by enhancing the COP would definitely be the major factor for sustainability of the cold storage and the decrease of the price of preserving the food in it. Theoretical modeling of solar-assisted cascade refrigeration system in cold storage is studied in this work. The system consists of electricity-driven vapor compression refrigeration system and solar-driven vapor absorption refrigeration system. The vapor compression refrigeration system is connected in series with vapor absorption refrigeration system. The results shows higher COP as compared with the conventional vapor compression refrigeration system. COP of this type refrigeration system increases as sunlight becomes intense. Keywords: coefficient of performance (COP),Cold storage, solar-assisted cascaded refrigeration, vapor absorption refrigeration system,vapour compression refrigeration system. I.INTRODUCTION A. History of refrigeration: I. Murthy et al. (1991) tested different ejector dimensions at the cooling capacity about 0.5 kw. R12 was used as the refrigerant. A COP in the range of 0.08-0.33 was obtained. II. Bejan et al. (1995) designed a single-stage solar-driven ejector system with 3.5 kw of refrigeration capacity at an evaporating temperature of 4 C and a generating temperature of 90-105 C with R114. III. A solar assisted ejector-vapor compression cascade system was proposed by Göktun (2000). The inter-cooler was installed serving as a condenser for the vapor compression system and an evaporator for the ejector system. IV. Sözen and Özalp (2005) proposed a solar-driven ejector absorption system. The main focus of this study is to investigate the possibility of using this system in Turkey. As a result of the analysis, using the ejector, the COP improved by about 20%. V. Performance variations of a solar-powered ejector cooling system (SECS) using an evacuated-tube collector has been presented by Ersoy et al. (2007) in different cities in Turkey. VI. Varga et al. (2009) carried out theoretical study to assess system and refrigeration efficiencies of a solarassisted ejector cycle using water as the operating fluid. The results indicated that in order to achieve an acceptable coefficient of performance, generator temperatures should not fall below 90 C. Evaporator temperatures below 10 C and condenser temperatures over 35 C. II. VAPOR COMPRESSION REFRIGERATION CYCLE In vapor compression refrigeration cycle (shown in Figure 1) the refrigerant is vaporized completely before it is compressed and the turbine is replaced with a throttling device. Path description is given in Table 1 Table 1: VCRS path description Path Processes 1 2 isentropic compression in a compressor 2 3 constant pressure heat rejection in a condenser 3 4 throttling in an expansion device 4 1 constant pressure heat absorption in an evaporator Copyright to IJAREEIE www.ijareeie.com 1248

COP R = Characteristics of VARS: q L 1. HIGHER ENERGY CONSUMPTION. 2. MODERATE COP. 3. LOWER INITIAL INVESTMENT. 4. EMITS GREEN-HOUSE GAS. Figure 1: vapor compression refrigeration cycle w net,in = 1 4 2 1..(i) II. ABSORPTION REFRIGERATION SYSTEMS There is a source of inexpensive thermal energy at a temperature of 100 to 200 C is absorption refrigeration. Characteristics of AVRS:- 1. A liquid is compressed instead of a vapor and as a result the work input is very small. 2. The unit cost of thermal energy is low and is projected to remain low relative to electricity. 3. The COP of actual absorption refrigeration systems is usually less than unity. Desired output COP absorption = Required output = Q L Q L Q gen + W punp,in Q gen. (ii) Copyright to IJAREEIE www.ijareeie.com 1249

Figure 2: Absorption refrigeration system process cycle III. PROPOSED SYSTEM FOR FUTURE USE A major application area of thermodynamics is refrigeration, which is the transfer of heat from a lower temperature region to a higher temperature one. Devices that produce refrigeration are called refrigerators, and the cycles on which they operate are called refrigeration cycles. The reversed Carnot cycle is the most efficient refrigeration cycle operating between TL and TH... (iii) Where, T H = condenser temperature T L = evaporator temperature Our main objective of this project is to increase the efficiency of refrigeration cycle. So we can increase the COPs as the difference between the two temperatures decreases, that is, as T L rises or T H falls. But there is a certain limit to increase the evaporator temperature due to refrigerant limitation. So there is a possibility to increase the COP of refrigeration cycle by decreasing the condenser temperature. This can be done by using a vapour compression refrigeration system is connected in series with vapor absorption refrigeration system. Solar-driven vapour absorption refrigeration has advantages in energy conservation and environmental protection.however, conventional solar-driven vapour compression refrigeration has many disadvantages, such as 1. Low efficiency 2. Intermittent operation 3. Too large unit cost 4. High capital cost Besides, the popularity and application of electricity-powered vapour compression refrigeration have been one of the main reasons of summer and winter electricity demand peak in recent years. In particular, 60% of the total electricity capacity is generated by coal. Not only does it exacerbate the depletion of fossil fuel, but also it can produce dangerous gases such as carbon dioxide, nitrogen oxides and sulphur oxides, which cause the greenhouse effect and deteriorate the global environment. In order to solve the above problems in the conventional electricity-powered vapour compression refrigeration system and solar-driven one, a solar assisted cascade refrigeration system is analysed. Copyright to IJAREEIE www.ijareeie.com 1250

The main objective of this paper is to design, fabricate and evaluate a new solar-assisted cascaded refrigeration system which was the combination of both vapour absorption refrigeration system and vapour compression refrigeration system. IV. MODEL DEVELOPMENT Characteristics features of SACR cycle:- Figure 3: Line diagram of Solar Assisted Cascaded Refrigeration Cycle 1. It is very efficient and environmental friendly. 2. Power consumption is reduced greatly. 3. Coefficient of performance is nearly 25-30 % greater than VCRS. 4. It uses environment friendly energy resources. COP = Q H W compressor + Q generator + W pump. (iv) The cycle can be broken into different flows, one comprising of the ammonia-water mixture and the other comprising of the R-134a alone. Points (1-4) are the cycle of the R-134a, and the rest of the points constitute the ammonia vapor cycle. In the bottom cycle R-134a taking heat vaporizes in the evaporator (1) then the it is compressed by the compressor (2) and goes to the condenser (the evaporative condenser heat exchanger) at point (3) and then expanded in the expansion valve (4) and comes back to the evaporator again. Now in the top cycle has solution rich in refrigerant at point (7) is pumped to higher pressure through the solution heat exchanger (5) into the generator where heat is added and an ammonia-water vapor mixture is sent to the rectifier, and the solution poor refrigerant is sent back through the solution heat exchanger to the absorber. The ammonia-water vapor is purified in the rectifier by condensing the water vapor in the mixture into liquid. The pure ammonia vapor is sent to the condenser and the water liquid is sent back to the generator. The ammonia vapor loses heat to the surrounding by convection as it goes through the condenser and is cooled into liquid ammonia. The ammonia liquid is passed through a flow restrictor where it experiences a sudden drop in pressure and evaporates because this new pressure is less than its saturation pressure. The ammonia is now a saturated vapor at a temperature that corresponds to this new pressure. This temperature is always lower than the desired compartment temperature. The saturated ammonia vapor is sent to the evaporator where heat from the condenser of bottom cycle is absorbed. The ammonia vapor then absorbs heat before returning to the absorberwhere it is absorbed into the water and the process repeats again. Now, from energy balance equation: Copyright to IJAREEIE www.ijareeie.com 1251

m a 2 + m b 5 = m a 3 + m b 6 m a 2 3 = m b ( 6 5 ) m a = 6 5 m b 2 3 Now, cooling effect COP = = Q H. (v) net work input W compressor + Q generator + W pump 2 [For reversible device, W 1 2 = vdp, here pump is a reversible device and working fluid is in liquid phase, so 1 v is very small and hence W pump is negligible] From the top cycle, using the first law δq δw = 0 Q generator + Q c = Q absorber + Q k [AsδW = W pump 0] Q generator = Q absorber + Q k Q c Now, Q u = m b ( 15 14 ) Q absorber = m c p (t in t out ) Q c = m b ( 6 5 ) Q generator = m c p t in t out + m b 15 14 m b 6 5 m a ( 1 4 ) COP = m a 2 1 + m c p t in t out + m b ( 15 + 5 6 14 ) V. RESULTS AND DISCUSSIONS Data obtained experimentally m a = 0.28 kg/s m b = 0.023 kg/s t absorber out = 40.6 t generator out = 95 Q l = m b 1 4 = 0.023 239.16 55.16 = 4.232 kj/kg W compressor = m b 2 1 = 0.023 255.93 239.16 = 0.389 kj/kg Q generator = m a c p t generator out t absorber out = 0.28 0.037 95 40.6 = 0.457 Q l 4.232 COP = = W compressor + Q generator 0.3857 + 0.457 = 5.022 Here COP increases by 5.022 3.97 3.97 = 26. 49 % Copyright to IJAREEIE www.ijareeie.com 1252

Graphical plot of cop: VI.FIGURES AND TABLES Figure 4: Variation of COP with respect to evaporator temperature Figure 5: Variation of COP with respect to condenser temperature Copyright to IJAREEIE www.ijareeie.com 1253

V. CONCLUSION The solar-assisted cascade refrigeration system includes the solar-driven vapour absorption refrigeration unit and electricity-powered vapour compression refrigeration unit. COP of the solar cascade refrigeration system is up to 6.1 with the solar intensity of 700W/m2, outdoor air temperature of 35 and chilled water supply temperature of 7. Power consumption of the cascade refrigeration system is 50% lower than that of the conventional vapour compression refrigeration (CVCS) in the cooling mode. The COP of the new vapour compression refrigeration system (VCRS) increases as sunlight becomes intense. COP of the cascade refrigeration system is up to the maximum when COP of the conventional vapour compression refrigeration system is minimal. REFERENCES [1]. Thermodynamics, an engineering approach; Yunus A Cengel, Michael A Boles.Journal paper: [2]. S. Rosiek, F.J. Batlles, Integration of the solar thermal energy in the construction: Analysis of the solar-assisted air conditioning system installed in CIESOL building, Renewable Energy, vol.34, 2009, pp1423-1431pp2820-2832. [3]. R.J. Romero, W. Rivera, R. Best, Comparison of the theoretical performance of a solar air conditioning system operating with water/lithium bromide and an queousternary hydroxide, Solar Energy Materials & Solar Cells, vol.63, 2000,pp387-399 [4]. Lin Wang, Aihua Ma, Xiwen Zhou, Yingying Tan, Xiaona Yan and Wang Yu, Environment and energy challenge of airconditioner in China, The proceedings of the International Conference of Environmental Pollution and Public Health, China, vol.2,no. 5, 2008, pp4413-4416. [5]. B.J. Huang, J.M. Chang, V.A. Petrenko, K. B. Zhuk, A solar ejector cooling system using refrigeration R141b, SolarEnergy, vol.64, No.4-6, 1998, pp223-226. BIOGRAPHY Dr. NimaiMukhopadhyay, Assistant Professor, Department of Mechanical Engineering,, Jalpaiguri Government Engineering College, Jalpaiguri,WB-735102,BE (Mechanical ) from N.I.T., Durgapur; MBA from Jadavpur University; Ph.D Engineering from Jadavpur University; 4 National Journals 5 International Journals. ER. SomeshwarChowdhury, B.Tech in Mechanical Engineering.in 2011 from West Bengal University Of Technology, West Bengal; Pursuing M.Tech from Jalpaiguri Government Engineering College, West Bengal University Of Technology, West Bengal; Specialization: Production Technology and Management; Certified Graduate Engineer for Planning & Designing of Cold Chain Infrastructure from National Horticulture Board, INDIA. Copyright to IJAREEIE www.ijareeie.com 1254