REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

Similar documents
High-Performance VAV Systems

Dehumidifying with Dedicated Outdoor Air

Agenda and Objectives

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

Do All DOAS Configurations Provide the Same Benefits?

Zoned Rooftop Systems. Light commercial packaged rooftop systems from Trane

Agenda and Objectives

b.) Technical Information:

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Energy Recovery Ventilation

ASHRAE JOURNAL ON REHEAT

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Trane Engineers Newsletter Live

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Digital Precise Air Control - DPAC

Agenda and Objectives

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Trane CDQ Desiccant Dehumidification

ENGINEERING. Edition No. 13 October 2002

Benefits Offered by Passive Dehumidification Wheel Speed Control

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

Relative Humidity in Schools Jim Cummings and Chuck Withers

BAS Point Trend Data Guidance

SERVICE ASSISTANT OVERVIEW FDSI Online Training

Mechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

DIGI-VAV APPLICATIONS

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Air Conditioning Clinic

MicroTech Rooftop/RMC

CHAPTER 4. HVAC DELIVERY SYSTEMS

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Redesign of Bennett Hall HVAC System

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

EarthWise System Seminar

Verasys System Operation Overview Technical Bulletin

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

HEAT COOL. Meets Commercial California Title 24

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

ANSI/AHRI Standard 911 (SI) 2014 Standard for Performance Rating of Indoor Pool Dehumidifiers

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Active desiccant integration with packaged rooftop HVAC equipment

OWNER S MANUAL Venstar Inc. 08/07

Intelligent Variable Air. An EarthWise System from Trane for chilled-water applications

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

By MIKE WEST, PHD, PE Advantek Consulting Inc. Melbourne, Fla.

Modular Active. Chilled. Beams

Continuous Commissioning Report

High Performance Air Systems. An AMCA International White Paper. December, 2015

Optimizing Electric Humidifier Operation with an Air Side Economizer

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

Analyzing Air Handling Unit Efficiency. Michael Rosenberg, PE, CEM

IAQ: Re-tuning Commercial Buildings

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

Job Name Control Systems Description Date

Supply air temperature reset

Selected Laboratory Energy Efficiency Measures

Fan Selection. and Energy Savings

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

Adding More Fan Power Can Be a Good Thing

DADANCO Technical Paper

Computing Services Center

4. OVERVIEW OF MECHANICAL SYSTEM

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

ASHRAE/IESNA Standard

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

COMcheck Software Version Mechanical Compliance Certificate

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

COMcheck Software Version Mechanical Compliance Certificate

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Are uncontrollable humidity problems costing you a bundle?

Inspection Phase Three. Mechanical, Electrical & Plumbing Section 503

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

Mechanical Compliance Certificate

HEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative

To Keep Docs Cool, Dry and Happy

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks

Comfort and health-indoor air quality

Dehumidification in HVAC Systems

Executive Summary. OA/person (cfm/p) Private and open offices, Classrooms, Building as designed

Managing HVAC in High Performance Buildings

Transcription:

Energy-Savings Strategies for Rooftop VAV Systems Occupied set-point temperature Unoccupied set-point temperature Rooftop variable-air-volume (VAV) s are used to provide comfort in a wide range of building types and climates. 1 This kind of consists of a packaged rooftop air conditioner that serves several individually controlled zones. Each zone has a VAV terminal unit that is controlled by a temperature sensor. This article will discuss HVAC control strategies that can be used to save energy in rooftop VAV s. Optimal Start/Stop In some buildings, a simple time clock or System on Optimal start Occupied hours Zone temperature Starts s as late as possible Control strategies can help turn energy savings into operating-cost savings and earn LEED credits Optimal stop By JOHN MURPHY, LEED AP Trane LaCrosse, Wis. System off Allows 2 F drift below set point Midnight 6 a.m. Noon 6 p.m. Midnight FIGURE 1. With an optimal-start strategy, a building-automation waits as long as possible before starting so each zone s temperature can reach the occupied set point just in time for occupancy. time-of-day schedule is used to start and stop the HVAC. When a building is expected to be unoccupied, the is shut off and the temperature allowed to drift away from the occupied set point. The time at which the is to restart typically is set to ensure that the indoor temperature reaches the desired occupied set point prior to occupancy on either the coldest or warmest morning of the year. As a result, for most days, the starts much earlier than needed. In turn, this increases the number of operating hours and energy use. An alternative approach is a strategy called optimal start. This strategy utilizes a building-automation (BAS) to determine the length of time required to bring each zone from its current temperature to the occupied set-point temperature. The waits as long as possible before start- An applications engineer for Trane, John Murphy, LEED AP, aids engineers in the proper design and application of HVAC s. He is a member of several American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) technical committees and a contributing author of ASHRAE s recently published Advanced Energy Design Guide for K-12 School Buildings. 2 May 2008 HPAC Engineering

ing, so the temperature in each zone can reach the occupied set point just in time for occupancy (Figure 1). This optimal starting time is determined using the difference between the actual zone temperature and occupied set point. It compares this difference with the historical performance of the zone warming up or cooling down. The optimal-start strategy reduces the number of operating hours and saves energy by avoiding the need to maintain the indoor temperature at the occupied set point even though the building is unoccupied. A related strategy is called optimal stop. As mentioned previously, at the end of an occupied period, the HVAC is shut off and the temperature allowed to drift away from the occupied set point. However, the building occupants may not mind if the indoor temperature drifts just a few degrees before they leave for the day. Optimal stop uses a BAS to determine how early heating and cooling can be shut off for each zone so that the indoor temperature drifts only a few degrees from the occupied set point (Figure 1). In this case, only cooling and heating are shut off. The supply fan continues to operate, and the outdoorair damper remains open to continue ventilating the building. The optimal-stop strategy also reduces the number of operating hours, saving energy by allowing indoor temperatures to drift early. Supply fan Static-pressure sensor Communicating building-automation more static pressure at part load than necessary. When communicating controllers are used on VAV terminals, it is possible to optimize this staticpressure control function to minimize duct pressure and save fan energy. Each VAV-unit controller knows the current position of its air-modulation damper. The BAS continually polls these individual controllers, looking for the VAV terminal with the damper that is open the widest (Figure 2). The Variable-air-volume terminals FIGURE 2. The building-automation looks for the VAV terminal with the damper that is open the widest. Surge supply fan s set point then is reset to provide just enough pressure so that at least one damper is nearly wide open. This results in the supply fan generating only enough static pressure to push the required quantity of air through this critical VAV-terminal unit. This control strategy, which sometimes is called fan-pressure optimization, has several benefits: Reduced supply-fan energy use. At part-load conditions, the supply fan is able to operate at a lower static pressure Fan-Pressure Optimization As cooling loads change, VAV terminals modulate to vary airflow supplied to the zones. This causes the pressure inside the supply ductwork to change. In many s, a pressure sensor is located approximately two-thirds of the distance along the main supply duct. The rooftop unit varies the capacity of the supply fan to maintain the static pressure in this location at a constant set point. With this approach, however, the usually generates Static pressure Duct static-pressure control Fan-pressure optimization Potential energy savings Airflow 800 rpm 900 rpm 1,000 rpm FIGURE 3. Fan-pressure optimization. At part-load condidtions, the supply fan is able to operate at a lower static pressure and consume less energy. HPAC Engineering May 2008 3

Conditions that favor using supply-air-temperature reset: Mild climates that have many hours when outdoor dry-bulb temperature is below 60 F. Systems with variable-air-volume (VAV) terminals that have minimum airflow settings higher than 30 percent of design airflow. Efficient air-distribution design. Systems with interior zones that have varying cooling loads. Conditions that reduce the potential to save energy with supply-air-temperature reset: Hot climates that have relatively few hours when the outdoor dry-bulb temperature is below 60 F. Systems with efficient part-load fan modulation. Inefficient air-distribution design. Systems with interior zones that have varying cooling loads. TABLE 1. Guidance concerning supply-air-temperature reset. and consume less energy (Figure 3). Lower sound levels. The supply fan does not generate as much static pressure and typically generates less noise. In addition, with lower pressures in the supply duct, the dampers in the VAV terminals open wider, resulting in less regenerated noise. Reduced risk of fan surge. With the fan operating at a lower pressure when delivering reduced airflow, the fan operating point is kept farther away from the surge region (Figure 3). Flexibility of sensor location. Because this strategy uses the position of VAV dampers to reset the pressure set point, the static-pressure sensor can be located anywhere in the supply duct. It even can be located at the fan s discharge, allowing it to be installed Comments In this type of climate, the economizer-related benefits typically outweigh the impact on increased supply-fan energy. Higher minimum airflow settings increase the likelihood that reheat will be needed to avoid overcooling the zones. Low pressure losses result in less of a fan-energy penalty for the higher airflows that result from raising supply-air temperature. The variable loads might allow these zones to still be satisfied with a warmer supply-air temperature. Comments In this type of climate, the economizer-related benefits are minimal. Using a variable-frequency drive on the supply fan and/or the fan-pressure-optimization control strategy may make it more advantageous to reduce supply airflow to save fan energy, rather than increase airflow and save compressor energy. High pressure losses result in a significant fan-energy penalty for the higher airflow that accompanies a warmer supply-air temperature. These zones will require near-design airflow during all occupied hours, limiting the ability to raise supply-air temperature. Investigate using a separate to serve these zones. inside the rooftop unit and tested at a factory. In this location, it also can serve as a duct high-pressure sensor, protecting ductwork from damage in the event that a fire damper closes. Supply-Air-Temperature Reset In a VAV, it is tempting to raise the supply-air temperature at part-load conditions to save compressor and/or reheat energy. Increasing supply-air temperature reduces compressor energy because it allows a compressor to operate at a warmer suction temperature. The corresponding higher suction pressure reduces compressor lift, reducing the power required. An air-side economizer is more beneficial when supply-air temperature is reset. When outdoor air is cooler than the supply-air-temperature set point, compressors are shut off and outdoorand return-air dampers modulate to deliver the desired supply-air temperature. A warmer supply-air-temperature set point allows the compressors to be shut off sooner and increases the number of hours in which the economizer is able to provide all of the necessary cooling. When supply airflow has been reduced to a VAV terminal s minimum setting, raising supply-air temperature decreases the use of reheat in those zones that have very low cooling loads. However, because the supply air is warmer, zones that require cooling will need more air to satisfy the cooling load. This increases supply-fan energy. Finally, in non-arid climates, warmer supply air means less dehumidification at coils and higher humidity levels in zones. If dehumidification is a concern, use caution when implementing this strategy. Table 1 contains some general guidance on determining when this strategy can provide the most benefit. 2 Supply-air-temperature reset should be implemented so that it minimizes overall energy use. This requires consideration of the tradeoff among compressor, reheat, and fan energy, as well as the impact on space humidity levels. These competing issues often are balanced by first reducing supply airflow, taking advantage of the significant energy savings that come from unloading the fan. Once fan airflow has been reduced, the supply-air temperature can be raised to minimize reheat energy and enhance the benefit of the air-side economizer. Figure 4 is an example of a supplyair-temperature-reset strategy that is based on a changing outdoor drybulb temperature. When the outdoor temperature is warmer than 70 F, no reset takes place, and the supply-airtemperature set point remains at the design value of 55 F. When it is that warm outside, outdoor air provides 4 May 2008 HPAC Engineering

little or no cooling benefit for economizing. In most zones, the cooling load is likely high enough that reheat is not required to prevent overcooling. In addition, the colder (and drier) supply air allows the HVAC to provide sufficiently dry air to the zones, improving part-load dehumidification. When the outdoor temperature is between 60 F and 70 F, the supplyair-temperature set point is reset at a 2-1 ratio. That is, for every 2 F change in outdoor temperature, the set point is reset 1 F. In this range, supply-airtemperature reset enhances the benefit provided by the economizer and it is likely that some zone-level reheat can be avoided. Finally, when the outdoor temperature is colder than 60 F, no further reset occurs, and the supply-airtemperature set point remains at 60 F. Limiting the amount of reset to 60 F Supply-air-temperature set point, degrees Fahrenheit 61 60 59 58 57 56 55 50 55 60 65 70 75 80 allows the to satisfy the cooling loads in interior zones without needing Outdoor dry-bulb temperature, degrees Fahrenheit FIGURE 4. A supply-air-temperature-reset strategy based on a changing outdoor dry-bulb temperature. to substantially oversize VAV terminals and ductwork. Circle 000 HPAC Engineering May 2008 5

Time-of-day schedule Communicating building-automation Occupancy sensor Lounge Restroom Mechanical room Storage Office Vestibule Corridor Reception area Elevators Office Conference room Computer room Occupancy sensor FIGURE 5. Zone-level demand-controlled-ventilation strategies. Alternatively, some s reset the supply-air-temperature set point based on the temperature in the critical zone. (This is the zone at greatest risk Unoccupied Humidity Control VAV typically dehumidifies effectively over a wide range of operating A conditions because it continues to deliver cold, dry air at part-load conditions. As long as supply-air-temperature reset is used with caution and reheat is available for those VAV terminals that have high minimum-airflow settings or experience low cooling loads, a VAV typically will provide supply air at a dew point that is low enough to prevent elevated indoor humidity levels during occupied periods. However, controlling humidity levels always is a priority, not just when a building is occupied. When indoor humidity rises too high during unoccupied times, one option is to turn on the rooftop unit and dehumidify the recirculated air to about 55 F. However, there typically is little sensible load in the zones during these periods, so delivering cold air will result in overcooling. Reheat coils in the VAV terminals, and possibly a boiler and hot-water pumps, will need to be activated. An energy-saving alternative is to equip the rooftop unit with hot-gas reheat. When after-hours dehumidification is needed, the rooftop unit turns on and diverts hot refrigerant vapor from the compressor through a refrigerant-to-air heat exchanger located in the air stream following the evaporator coil. Sensible heat is transferred from the hot refrigerant to reheat the dehumidified air leaving the evaporator. This strategy uses heat recovered from refrigeration circuits to reheat centrally and saves energy by avoiding the use of new energy to reheat remotely at VAV terminals. of overcooling, which would require activating local reheat.) In these s, a BAS monitors the temperature in all zones, finding the critical zone that is closest to the heating set point. A rooftop unit then resets the supply-air-temperature set point to prevent the critical zone from needing to activate reheat. When considering using supply-airtemperature reset in a rooftop VAV, first analyze the to determine if the savings in compressor and reheat energy will outweigh the increase in fan energy. If higher space humidity levels are a concern, consider disabling the reset function when it is humid outside or provide a humidity sensor in one or more zones to override the reset function whenever indoor humidity exceeds some maximum limit. For interior zones with near-constant cooling loads during occupied periods, design airflows should be calculated based on the warmer, reset supply-air temperature (60 F in the example from 6 May 2008 HPAC Engineering

Outside air Rooftop unit with controls Reset outdoor airflow Supply air Return air Occupancy sensor Communicating building-automation New outside-air set point Occupancy sensor Direct-digital controls/ variable-air-volume terminals Required ventilation Actual primary airflow FIGURE 6. System-level ventilation-reset strategy. Figure 4). While this may require larger VAV terminals and ductwork, it allows the use of supply-air-temperature reset during cooler weather, while still providing the necessary cooling to weather-independent interior zones. It also is best to design a rooftop VAV s air-distribution for low-pressure losses and use the fan-pressure-optimization strategy to minimize the fan-energy penalty that accompanies a warmer supply-air temperature. Ventilation Optimization In a typical VAV, the rooftop unit delivers fresh outdoor air to several individually controlled zones. Demand-controlled ventilation (DCV) involves resetting intake airflow in response to variations in zone population. One approach to optimizing ventilation in a multiple-zone VAV is to combine the various DCV strategies at the zone level (using each where it fits best) with ventilation reset at the level. Ventilation reset involves resetting intake airflow based on variations in ventilation efficiency. For this approach, carbon-dioxide ( ) sensors are installed only in zones that are densely occupied and experience widely varying patterns of occupancy. For the example building in Figure 5, sensors are installed only in the conference room and lounge. These zones are the best candidates for sensors and provide the biggest bang for the buck. These sensors reset the ventilation requirement for their respective zones based on measured. While DCV strategies commonly employ sensors, occupancy sensors or time-of-day (TOD) schedules also can be used. Zones that are less densely occupied or have a population that varies only a little (such as private offices, open-plan office spaces, or many classrooms) probably are better suited for occupancy sensors. In Figure 5, each of the private offices has an occupancy sensor to indicate when the occupant is present. When unoccupied, the controller lowers the ventilation requirement for the zone. Occupancy sensors are relatively inexpensive, do not need to be calibrated, and already are used in many zones to control lights. Finally, zones that are sparsely occupied or have predictable occupancy patterns can be controlled efficiently through the use of a TOD schedule. The schedule can indicate when the zone normally will be occupied/unoccupied or be used to vary the zone ventilation requirement based on anticipated population. These various zone-level DCV strategies can be used to reset the ventilation requirement for their respective zones for any given hour. The zone-level control then is tied together using ventilation reset at the level (Figure 6). In addition to resetting a zone s ventilation requirement, the controller on each VAV terminal continuously HPAC Engineering May 2008 7

HVAC energy consumption, percentage of base 100 80 60 40 20 0 Atlanta Base Los Angeles Optimized controls FIGURE 7. HVAC energy savings from optimized controls. There is a real potential to save energy in rooftop VAV s through optimized -control strategies. Minneapolis monitors the primary airflow being delivered to the zone. A BAS periodically gathers this data from all of the VAV terminals and solves the ventilation-reset equations (prescribed by ANSI/ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air Quality) to determine how much outdoor air must be brought in at the rooftop unit to satisfy all of the zones served. Finally, the BAS sends this outdoor-airflow set point to the rooftop unit, which modulates a flowmeasuring outdoor-air damper to maintain the new set point. In a direct-digital-control/vav, this strategy is fairly easy to implement because the necessary realtime information already is available digitally. Combining DCV at the zone level with ventilation reset at the level has many benefits, including: Ensuring that zones are ventilated properly without requiring a sensor in each. sensors are used only in the zones in which they can have the most benefit. This minimizes installation costs and avoids the periodic calibration and cleaning required to ensure proper sensor operation. For the other zones, occupancy sensors and TOD schedules can be used to reduce ventilation. Enabling documentation of actual ventilation- performance. The VAV controllers communicate each zone s ventilation airflow to the BAS, even for the zones that do not have sensors. The BAS can be used to generate reports showing ventilation airflow in every zone, hour by hour. Using -level ventilationreset equations that are defined in an industrywide standard. Using equations from ASHRAE Standard 62 improves the ability to defend the control strategy s use. Conclusion The impact of any energy-saving strategy on the operating costs of a specific building depends on climate, building usage, and utility costs. Building-analysis tools can be used to analyze these strategies and convert energy savings to operating-cost savings and help make financial decisions. Figure 7 shows the potential energy savings of using these various strategies in an office building with a typical rooftop VAV. The optimized uses the optimal-start, supplyair-temperature-reset, and ventilationoptimization strategies discussed in this article. In addition, the supply fan is controlled based on fan-pressure optimization, rather than a constant set point in the ductwork. The optimized rooftop VAV would reduce HVAC energy use by about 30 percent if the building were located in Atlanta and Los Angeles and by 33 percent if it were located in Minneapolis. There is a real potential to save energy in rooftop VAV s through optimized -control strategies. This savings can reduce a building owner s operating costs and help earn points toward Leadership in Energy and Environmental Design certification. REFERENCE 1) Murphy, J. (2007). Rooftop VAV s applications engineering manual (SYS-APM007-EN). La Crosse, WI: Trane. 2) California Energy Commission. (2003). Advanced variable air volume design guide. Sacramento, CA: California Energy Commission. For past HPAC Engineering feature articles, visit www.hpac.com. 8 May 2008 HPAC Engineering