Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Similar documents
Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump

Low GWP Refrigerants for Air Conditioning Applications

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Study of R161 Refrigerant for Residential Airconditioning

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Performance Measurement of R32 Vapor Injection Heat Pump System

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Evaluation of HCFC Alternative Refrigerants

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE


R32 Compressor for Air conditioning and Refrigeration applications in China

Low GWP Refrigerants for Air Conditioning and Chiller Applications

HFO-1234yf Performance in a Beverage Cooler

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor- Compression Equipment

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Transcritical CO2 Bottle Cooler Development

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Modelling the Performance of a Diffusion Absorption Refrigeration System

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

Compression of Fins pipe and simple Heat pipe Using CFD

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

System Modeling of Gas Engine Driven Heat Pump

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

MINIMISING THE RISK OF WATER HAMMER AND OTHER PROBLEMS AT THE BEGINNING OF STAGNATION OF SOLAR THERMAL PLANTS- A THEORETICAL APPROACH

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Global Journal of Engineering Science and Research Management

POTENTIAL OF NON - AZEOTROPIC REFRIGERANT MIXTURE AS WORKING REFRIGERANT IN HOT WATER HEAT PUMPS. FJ Smit and JP Meyer

Investigation of Evaporator Performance with and without Liquid Overfeeding

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

A Comparison Between Refrigerants Used In Air Conditioning

Transcritical Carbon Dioxide Microchannel Heat Pump Water Heaters: Part II - System Simulation and Optimization

Performance of an Improved Household Refrigerator/Freezer

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

ZERO ZONE USER GUIDE TO THE 2017 EPA RETAIL FOOD REFRIGERATION REGULATIONS

Alternative Refrigerants For Household Refrigerators

Hot Reservoir Stainless-Methanol Variable Conductance Heat Pipes for Constant Evaporator Temperature in Varying Ambient Conditions

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Evaluation of a Virtual Refrigerant Charge Sensor

AIR CONDITIONER PERFORMANCE RATING

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

S.A. Klein and G.F. Nellis Cambridge University Press, 2011 = 90 F. compressor. condenser. 5 evaporator 1. evap

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

A fair comparison of CO2 and propane used in light commercial applications featuring natural refrigerants

EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEAT EXCHANGER

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Numerical Simulation of a New Cooling System for Commercial Aircrafts

(Refer Slide Time: 00:00:40 min)

Dynamic Simulation of Liquid Chillers

STUDY, ANALYSIS AND DESIGN OF AUTOMOBILE RADIATOR (HEAT EXCHANGER) PROPOSED WITH CAD DRAWINGS AND GEOMETRICAL MODEL OF THE FAN

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Heat Pump Clothes Dryer Model Development

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Chapter 10. Refrigeration and Heat Pump Systems

Transcription:

2597, Page 1 Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump Ian H. BELL 1 *, James E. BRAUN 2 1 Bell Thermal Consultants ian.h.bell@gmail.com 2 Purdue University, Mechanical Engineering Department, Herrick Labs West Lafayette, IN, USA jbraun@purdue.edu * Corresponding Author ABSTRACT In residential heat pump systems, the motivation for secondary loop systems is to allow for the use of flammable or toxic refrigerants with lower global warming potentials than the currently employed HFC refrigerants. The addition of radiant panels as integral building components (embedded in concrete at construction) is becoming more common. Combining the large surface area of the radiant panel and an efficient primary loop, the hydronic secondary loop heat pump system can greatly outperform the conventional air-to-air heat pump. The improvement in coefficient of performance is as much as 38% over the conventional air-to-air heat pump when the secondary loop hydronic system is employed. Due to the large area of the radiant panel, the condensing temperature of the primary loop for the hydronic secondary loop heat pump can be reduced by as much as 5 C at high ambient temperatures. 1. INTRODUCTION Radiant heating and cooling systems are becoming more and more popular around the world. As of 2002, radiant heating and cooling were employed as many of 90% of new constructions in Korea, and 30-50% in Germany (Olesen, 2002). Many of these systems employ electric water heaters as the heat source, which while easy to implement, is not the most efficient solution. The conventional air-to-air heat pump is quite ubiquitous. 1.8 million split-type air-source heat pumps were produced by U.S. manufacturers in 2011, and 20 million units between 1992 and 2011 (AHRI, 2012). Many of the modern heat pump units operate with the refrigerant R410A which has a global warming potential (GWP) of 2100, versus a GWP for propane of 20 (Calm, 2007). Regulatory pressure in Europe and elsewhere is pushing towards systems that do not use HFC refrigerants like R410A, and regulatory bodies are reconsidering the use of flammable refrigerants like propane. Radiant heating systems are employed not just for their performance benefits. They can also improve occupant comfort due to a more even temperature profile in the occupied space (Olesen, 2002). In addition, it has been suggested that the air temperature setpoint can be reduced due to the use of radiant heat, although that effect has not been investigated here. In principle, the hydronic heating system could also be coupled with a solar collector and use the solar energy as the heat source for the heat pump.

2597, Page 2 2. SYSTEM DESCRIPTIONS 2.1 Systems Under Consideration In this study, two different types of systems are under consideration for the heating of a residential structure. These systems are a conventional air-to-air heat pump that operates with an HFC-based working fluid (here refrigerant R410A) and a secondary loop heat pump system that employs radiant panels for heating of the occupied space. The secondary loop system can use flammable working fluids like propane that would not be acceptable for direct expansion systems. Figure 1a shows a schematic of the air-to-air direct expansion heat pump system. In the direct expansion system, refrigerant exits the evaporator (the outdoor heat exchanger) at state point 1. The compressor then compresses the refrigerant from state point 1 to state point 2. The refrigerant is heated against the ambient air up to state point 3 as it passes through the vapor line on its way to the condenser. In the condenser, heat is delivered to the heated space by the condensation of the refrigerant, and the refrigerant condenses from state point 3 to state point 4. In general, the refrigerant is subcooled at the outlet of the condenser. At the outlet of the condenser, the refrigerant passes through the liquid line from state point 4 to state point 5. The refrigerant next passes through the expansion device which throttles the refrigerant to state point 6, the inlet to the evaporator. Then the refrigerant re-enters the evaporator and the cycle continues. (a) DX R410A System (b) Hydronic Loop System Figure 1: Schematics of DX and Secondary Loop systems In the secondary loop heat pump system considered here, there are a few modifications to the conventional air-to-air heat pump. Figure 1b shows a schematic of the secondary loop system. The primary refrigerant loop (state points 1 to 4) is essentially the same, except that the refrigerant delivers its heat into a secondary loop in the plate heat exchanger as it condenses, and there is are no vapor or liquid lines since the whole compressor-expansion deviceplate heat exchanger loop can be close-coupled, decreasing greatly the piping pressure losses and the refrigerant charge. In the secondary loop, a secondary working fluid is heated from state point 5 to state point 6 in the plate heat exchanger against the condensing refrigerant. The warmed secondary working fluid then passes through a pump which is required to overcome the pressure drops from the heat exchangers and the lines. The secondary working fluid passes through the supply pipe and is then delivered to the radiant panels. In the radiant panels, the secondary working fluid is cooled and delivers its heat to the heated space. The cooled secondary working fluid is then returned to the plate heat exchanger through the return pipe. For the secondary loop system, there are a number of options for the secondary working fluid, but water is the most obvious choice. It has the highest mass specific heat of any liquid, and one of the highest densities of any liquid. In

2597, Page 3 addition, its low viscosity results in low pressure drops. For radiant systems applied to heating applications, water would be the secondary working fluid. 2.2 Air-Conditioning Heat Pump Model (ACHP) A specialized model has been developed to analyze direct-expansion and secondary loop heat pump and airconditioning systems (ACHP) that is freely available online, including source code. The details of the ACHP model are provided in the documentation available online 1. In ACHP, each of the heat exchanger models are based on moving boundary formulations. Essentially, the moving boundary heat exchanger model is based on using a numerical solver to find the locations where the refrigerant changes phase, and then solve each of the portions of the heat exchanger separately. The addition of partiallywet/partially-dry air-side surfaces analysis is also included in the evaporator. The compressor model is based on 10-coefficient compressor performance map with appropriate correction for compressor inlet superheat. Models are also available for the plate heat exchanger, line sets and other components. The refrigerant and humid air properties are based on a reference-quality property database developed in parallel with ACHP 2. Coupling all the component models together, a multi-dimensional numerical solver is used to find the evaporation and condensation saturation temperatures for the refrigerant loop and enforce a few energy balances. Either charge or refrigerant subcooling can be imposed, though subcooling was imposed for all the work carried out here. The expansion device is an idealized device that can achieve a given evaporator outlet superheat. In the case of the secondary loop, the solver is also used to find a secondary loop temperature. 2.3 Radiant Panel Model The radiant panel is formed of a number of tubes with inlet and outlet manifolds. In practice, the tubes may be bent to fit the contours of the space it is installed in, but for the purposes here, the tubes are assumed to all be straight. The radiant panel is then sized based on the area available for the panel. If the total area available for the panel is given by A panel, then the length of the tubes can be obtained from A panel Ltube (1) wtube tube Ntubes where w tube-tube and N tube are the tube-to-tube centerline distance (in meters) and the number of tubes forming the panel respectively. For instance, the average floor space of American homes in 2010 was 222 m 2 [2,392 ft 2 ] 3. If 80% of the available area is used for the radiant paneling and there are 10 tubes with 0.254 m [10 inch] tube-to-tube centerline distance, then the tubes would need to be 69.9 meters long. 1 ACHP 1.3: http://achp.sf.net 2 CoolProp: Fluid properties for the masses. http://coolprop.sf.net/ 3 http://www.census.gov/const/c25ann/sftotalmedavgsqft.pdf

2597, Page 4 If the spreading heat conduction thermal resistance in the radiant panel is neglected, there are two thermal resistances that govern the heat transfer from the radiant panel to the surroundings. The overall heat transfer conductance can therefore be given by 1 1 UA (2) hair Apanel hwater Ntubes Di, tubel tube which includes the convective thermal resistance in the tubes as well as the combined radiant and convective air-side thermal resistance. The overall air-side heat transfer coefficient is usually on the order of 10 W/m 2 /K. With the value for UA known, the water outlet temperature can then be obtained from (Bergman, 2011) T T wo, UA exp (3) T T w, i mwater c p and the heat transfer rate is then given by Q m c ( T T ) (4) water p w, i w, o The pressure drop in the radiant panel is governed by the internal flow pressure drop relations as described in the ACHP documentation. 2.2 Air-To-Air Heat Pump System Analysis The required model parameters for the R410A air-to-air heat pump system are summarized in Table 1 (heat exchangers) and Table 2 (other parameters). The heat exchanger parameters were obtained from the analysis of Shen (2006). This system is a nominal 3-ton cooling capacity system. Table 1: Heat Exchangers for R410A system based on Bo Shen Evaporator Condenser Tubes per bank [-] 41 32 Number of bank [-] 1 3 Number of circuits [-] 5 6 Length of tube [m] 2.286 0.452 Tube OD [m] 0.007 0.009525 Tube ID [m] 0.0063904 0.0089154 Longitudinal tube pitch [m] 0.0191 0.0254 Transverse tube pitch [m] 0.0222 0.0219964 Fin Type Wavy Lanced Wavy Lanced Fins/inch [1/in] 25 14.5 Twice fin amplitude [m] 0.001 0.001 ½ period of fin waviness [m] 0.001 0.001 Fin thickness [m] 0.00011 0.00011 Fin conductivity [W/m/K] 237 237 Humid air volume flow rate [m 3 /s] 1.7934 0.5663 Atmospheric pressure [kpa] 101.3 101.3 Relative humidity [-] 0.51 0.51 Fan power [W] 160 438 1 Table 2: Other parameters for R410A system Parameter Value Refrigerant R410A Condenser outlet subcooling [K] 7.0 Evaporator outlet superheat [K] 5.0 Line set length [m] 7.6

2597, Page 5 2.3 R410A Heat Pump Performance Results ANSI/AHRI Standard 210/240 governs the rating of unitary heat pump units, and provides a few rating points for which heat pump manufacturers must provide performance data. The ASHRAE standard rating point H1 is used in this study as the conventional rating point. The H1 rating point employs an 8.33 C [47 F] air inlet temperature to the evaporator, and a 21.1 C [70 F] air inlet temperature to the condenser. Standard 210/240 provides rating points as low as -8.33 C [17 F] air inlet temperature to the evaporator (rating point H3). Table 3 summarizes the results for the three rating points. Both COSP and Capacity are very nearly linear with evaporator air inlet temperature. Table 3: Modeling Results for the R410A Heat Pump Rating Condenser Air Evaporator Air COSP Capacity Point Inlet Temp. Inlet Temp. H1 21.1 C [70 F] 21.1 C [47 F] 3.44 10000 W H2 21.1 C [70 F] 1.66 C [35 F] 2.96 8341 W H3 21.1 C [70 F] -8.33 C [17 F] 2.29 6242 W 2.4 Secondary Loop System In order to provide a fair comparison between the two systems, the same operating conditions have been used for both systems. In the secondary loop system, the condenser is replaced with a plate heat exchanger described by the geometry in Table 4. Table 4: Geometry of Plate Heat Exchanger for Secondary Loop System Parameter Value Number of plates [-] 46 B p [m] 0.117 L p [m] 0.300 Plate Amplitude [m] 0.001 Plate Thickness [m] 0.0003 Plate Conductivity [W/m/K] 15 Plate Wavelength [m] 0.0628 Inclination Angle [deg] 60 The saturation pressure of propane at 0 C (474 kpa) is quite a bit lower than that of R410A (800 kpa). As a result, the number of circuits in the evaporator must be increased in order to have a well-controlled pressure drop in the evaporator. The number of circuits in the evaporator was increased to 12, otherwise all the parameters of the secondary loop evaporator are the same as the evaporator in Table 1. The water flow-rate through the secondary loop system was set at 0.38 kg/s. Furthermore, the compressor displacement of the propane secondary loop system was scaled slightly in order to yield the same capacity as the R410A system at the H1 rating point. The propane compressor displacement (and therefore mass flow rate and electrical power) was decreased by 5.3% when the scaling parameter was introduced.

2597, Page 6 Figure 2: COSP of the systems as a function of the air inlet temperature to the evaporator Figure 3: Condensing temperature of the systems as a function of the air inlet temperature to the evaporator Figure 4: Heating capacity of the systems as a function of the air inlet temperature to the evaporator Figure 5: Compressor overall isentropic efficiency for the systems as a function of the air inlet temperature to the evaporator As can be seen from Figure 2 to Figure 5, by every important performance metric, the performance of the propane secondary-loop system is better than that of the R410A air-to-air heat pump. Figure 2 shows the COSP for both the secondary loop heat pump and the direct expansion heat pump. These results show that for all the evaporator air inlet temperatures, the COSP of the secondary loop system is better than that of the direct expansion system. There a number of factors contributing to the improved performance with the secondary loop system. For one, in the secondary loop system, the fan power required for the condenser (which is quite significant) is removed. In addition, the condensing temperature of the secondary loop system can be reduced, further improving the compressor electrical power input. Figure 3 shows the condensing temperature of the systems. Figure 4 shows the heating capacity of the system as a function of the air inlet temperature to the evaporator. For all temperatures investigated here, the capacity of the secondary loop system is better than the direct expansion system. Although the compressor for the secondary loop system was not specifically selected in order to match the lower condensing temperatures, the compressor map predicts a higher overall isentropic efficiency, as seen in Figure 5.

2597, Page 7 Figure 6: COSP of secondary loop systems as a function of water mass flow rate Figure 6 shows the COSP of the secondary loop systems for a range of water mass flow rates and evaporator air inlet temperatures. The system COSP is not very sensitive to the mass flow rate of water; as a result, a fixed mass flow rate of water can be used over the full operating envelope with very little decrease in system efficiency. All other parameters were unchanged from the comparisons above. Further optimization of the mass flow rate of the secondary loop can be achieved by determining the optimal mass flow rate for a selection of evaporator air inlet temperatures (shown with the circular markers in Figure 6) and then conducting a linear fit of the optimal mass flow rate versus the evaporator air inlet temperature. The optimal mass flow rate for this particular system as a function of evaporator air inlet temperature can therefore be given by m 0.004146 T + 0.3064 (5) where T i,evap is in C and m water, opt is in kg/s. water, opt i, evap Figure 7 shows that as long as the water flow rate is high enough, there is very little impact on the heat pump capacity. As a matter of fact, the use of the optimal water flow rate from Equation (5) would yield a good solution for the water flow rate, and would allow for a simple control strategy if the secondary loop pump speed were controllable. Figure 7: Capacity as a function of secondary loop water flow rate and air inlet temperature to evaporator

Part Sizing Energy Flows 2597, Page 8 3. SYSTEM COMPARISONS It is useful to consider the energy flows and other system parameters for the rating point H1 in order to clarify the differences between the secondary loop options. Table 5: Summary of system parameters for operation at rating point H1 Air-Source DX Secondary Loop Compressor Power [W] 2311 1820 Evaporator Fan Power [W] 160 160 Condenser Fan Power [W] 438 - Pump Power [W] - 27 Net Power [W] 2909 2007 System Capacity [W] 10000 10000 Compressor pumped vol. rate [m 3 /s] 4 6.121 10.29 Evaporator air-side area [m 2 ] 105.34 105.34 Condenser air-side area [m 2 ] 36.8 - Radiant panel area [m 2 ] - 132 With the use of the secondary loop system, the relatively high condenser fan power of the DX system is traded for a much lower secondary loop pump power, which reduces the energy consumption by 411 W. The decreased condensing temperature of the secondary loop system results in a further 491 W reduction in compressor input power. The compressor pumped volumetric rate for the secondary loop system is 68% larger than that of the R410A compressor, due to the fact that the density of the propane is lower than that of R410A. Thus, at the same evaporation temperature, and for the same heating capacity, a larger volumetric flow rate is required for the propane compressor. The cause of the lower condensing temperature for the secondary loop system can be clearly seen from a comparison of the condenser air-side area of the DX system and the radiant panel dimensions of the secondary loop system. The available area for heat transfer of the radiant panel is 3.6 times greater than that of the condenser installed in the ductwork. 3.1 Other considerations The use of a secondary loop system is a natural first step to a multi-zoned heating system. Robust zone temperature control can therefore be achieved through the use of variable water flow rates to the zones, each zone getting a radiant panel. Since water is used as the fluid flowing to the zones (rather than a refrigerant), the pressure drop can be well-controlled for long line sets The secondary loop system could also be used in cooling mode, though that is not considered here. The performance of the secondary loop systems in cooling mode have been shown to be competitive with, if not better than, the performance of direct expansion R410A systems. CONCLUSIONS The benefits to system efficiency through the use of a secondary-loop hydronic heat pump are quite significant. This suggests that it should be straightforward to design a hydronic heat pump that can easily achieve the same seasonal performance as a conventional HFC-based air-source heat pump. Furthermore, this technology would be easily adapted for cooling mode operation or multi-zone systems. 4 Based on the compressor map; pumped mass flow rate divided by density at compressor inlet. Includes the volumetric efficiency implicitly since the volumetric efficiency is built into the compressor map

2597, Page 9 NOMENCLATURE Parameter Units Description A panel m 2 Area of panel c p J/kg/K Mass specific heat D i,tube m Inner diameter of tube h W/m 2 /K Air mean heat transfer coefficient air h water W/m 2 /K Water mean heat transfer coefficient L tube m Length of panel m kg/s Water mass flow rate water m kg/s Optimal water mass flow rate water, opt N tubes - Number of tubes T i,evap K Evaporator air inlet temperature T cond K Condensing temperature T w,i K Water inlet temperature T w,o K Water outlet temperature T K Ambient temperature w tube-tube m Tube-tube centerline distance UA W/K Overall heat transfer conductance REFERENCES AHRI, 2012: Central Air Conditioners and Air-Source Heat Pumps Historical Data, http://www.ahrinet.org/central+air+conditioners+and+air_source+heat+pumps+historical+data.aspx Bergman, T.; Lavine, A.; Incropera, F.; Dewitt, D.; Fundamentals of Heat and Mass Transfer 7 th Edition, Wiley Calm, J. M. & Hourahan, G. C. 2007, Refrigerant Data Update, HPAC Engineering v. 79, 50-64. Gong, X.; Claridge, D.; 2002, Impact of the Position of the Radiators on Energy Consumption and Thermal Comfort in a Mixed Radiant and Convective Heating System, ASHRAE Transactions. Olesen, B., 2002, Radiant Floor Heating In Theory and Practice, ASHRAE Journal, July 2002 Shen, B., 2006, Improvement and Validation of Unitary Air Conditioner and Heat Pump Simulation Models at Off- Design Conditions ASHRAE Final Report 1173-RP, http://rp.ashrae.biz/page/rp-1173.pdf